Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

1361A Multi-Conductor - Databus® Isa/Sp-50 Foundation Fieldbus or Profibus Cable

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Detailed Specifications & Technical Data

METRIC MEASUREMENT VERSION

1361A Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable

For more Information


please call

1-800-Belden1

General Description:
2 pair, 16 AWG stranded (7x24) tinned copper conductors, polyolefin insulation, individual & overall
Beldfoil® shield (100% coverage), tinned copper drain wire, oil-resistant PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material Dia. (mm)
2 16 7x24 TC - Tinned Copper 1.499

Total Number of Conductors: 4

Insulation
Insulation Material:
Insulation Material
PO - Polyolefin

Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100

Inner Shield Drain Wire AWG:


AWG
20

Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100

Outer Shield Drain Wire AWG:


AWG Stranding Drain Wire Conductor Material
16 7x24 TC - Tinned Copper

Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride

Overall Cable
Overall Nominal Diameter: 14.732 mm

Pair
Pair Color Code Chart:
Number Color
1 Blue & Orange Numbered 1
2 Blue & Orange Numbered 2

Pair Lay Length & Direction:


Lay Length (mm) Twists (twist/m)
63.500 16.405

Page 1 of 3 11-08-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION

1361A Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable

Mechanical Characteristics (Overall)


Operating Temperature Range: -40°C To +105°C

UL Temperature Rating: 105°C

Bulk Cable Weight: 193.466 Kg/Km

Max. Recommended Pulling Tension: 636.093 N

Min. Bend Radius/Minor Axis: 147.320 mm

Applicable Specifications and Agency Compliance (Overall)


Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMG, CMX-Outdoor, ITC, PLTC-ER

CEC/C(UL) Specification: CMG

EU Directive 2011/65/EU (ROHS II): Yes

EU CE Mark: Yes

EU Directive 2000/53/EC (ELV): Yes

EU Directive 2002/95/EC (RoHS): Yes

EU RoHS Compliance Date (mm/dd/yyyy): 09/01/2006

EU Directive 2002/96/EC (WEEE): Yes

EU Directive 2003/11/EC (BFR): Yes

CA Prop 65 (CJ for Wire & Cable): Yes

MII Order #39 (China RoHS): Yes

Flame Test
UL Flame Test: UL1685 FT4 Loading

IEC Flame Test: 60332-3-24 (Category C)

IEEE Flame Test: 1202

Suitability
Suitability - Indoor: Yes

Suitability - Outdoor: Yes

Sunlight Resistance: Yes

Plenum/Non-Plenum
Plenum (Y/N): No

Electrical Characteristics (Overall)


Unaveraged Impedance:
Description Freq. (MHz) Start Freq. (MHz) Stop Freq. (MHz) Impedance (Ohm)
.03125 100

Nom. Inductance:
Inductance (µH/m)
0.62339

Nom. Capacitance Conductor to Shield:


Capacitance (pF/m)
147.645

Nom. Mutual Capacitance:


Capacitance (pF/m)
78.744

Maximum Capacitance Unbalance:


Capacitance (pF/m)

Page 2 of 3 11-08-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION

1361A Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus or PROFIBUS Cable

3.9372

Nominal Velocity of Propagation:


VP (%)
66

Nom. Conductor DC Resistance:


DCR @ 20°C (Ohm/km)
13.780

Nominal Outer Shield DC Resistance:


DCR @ 20°C (Ohm/km)
16.0769

Ind. Pair Nominal Shield DC Resistance @ 20 24.608 Ohm/km


Deg. C:
Nom. Attenuation:
Description Freq. (MHz) Start Freq. (MHz) Stop Freq. (MHz) Attenuation (dB/100m)
.039 0.26248

Max. Attenuation:
() Freq. (MHz) Attenuation (dB/100m)
0.298571 0.039 0.299

Max. Operating Voltage - UL:


Voltage
300 V RMS

Max. Recommended Current:


Description Current
Per Conductor 5.2 Amps

Other Electrical Characteristic 1: Max Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft

Other Electrical Characteristic 2: 31.25 KBits/sec

Put Ups and Colors:


Item # Putup Ship Weight Color Notes Item Desc
1361A 0031000 1,000 FT 143.000 LB ORANGE 2 FS PR #16 PO FS FRPVC

Revision Number: 0 Revision Date: 04-27-2012

© 2019 Belden, Inc


All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.

All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

Page 3 of 3 11-08-2019