Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

5322FM

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Detailed Specifications & Technical Data

ENGLISH MEASUREMENT VERSION

5322FM Multi-Conductor - Commercial Applications

For more Information


please call

1-800-Belden1

General Description:
Circuit Integrity Fire Alarm, Rated-FPLR-CI, 4-18 AWG solid bare copper conductors with silicone
insulation, Beldfoil® shield, LSZH jacket
Usage (Overall)
Suitable Applications: Survivability, Survivability from Attach by Fire, Fire Alarm Circuit Integrity, CI,
Survivability by NFPA72, Sim to MI, Similar to Mineral Insulated, FPLR-CI,
Emergency Circuits, Notification Devises, Fire Pumps, 2 hour fire rating

Physical Characteristics (Overall)


Conductor
AWG:
# Conductors AWG Stranding Conductor Material
4 18 Solid BC - Bare Copper

Total Number of Conductors: 4

Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
Silicone Rubber .034

Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Polyester Tape-Aluminum Foil 100

Outer Shield Drain Wire AWG:


AWG Stranding Drain Wire Conductor Material
20 7x28 TC - Tinned Copper

Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (in.)
FRPE - Flame Retardant Polyethylene .045

Overall Cable
Overall Cabling Color Code Chart:
Number Color
1 Black#1
2 Black#2
3 Black#3
4 Black#4

Overall Nominal Diameter: 0.358 in.

Mechanical Characteristics (Overall)


Operating Temperature Range: -20°C To +105°C

UL Temperature Rating: 105°C

Bulk Cable Weight: 70 lbs/1000 ft.

Max. Recommended Pulling Tension: 78.400 lbs.

Page 1 of 3 11-08-2019
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION

5322FM Multi-Conductor - Commercial Applications

Max. Recommended Pulling Tension: 78.400 lbs.

Min. Bend Radius/Minor Axis: 3.750 in.

Applicable Specifications and Agency Compliance (Overall)


Applicable Standards & Environmental Programs
NEC/(UL) Specification: FPLR-CI

NEC Articles: 760

EU Directive 2011/65/EU (ROHS II): Yes

EU CE Mark: Yes

EU Directive 2000/53/EC (ELV): Yes

EU Directive 2002/95/EC (RoHS): Yes

EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2005

EU Directive 2002/96/EC (WEEE): Yes

EU Directive 2003/11/EC (BFR): Yes

CA Prop 65 (CJ for Wire & Cable): Yes

MII Order #39 (China RoHS): Yes

Flame Test
UL Flame Test: UL1666 Riser, UL2196 Two Hour Circuit Integrity

Plenum/Non-Plenum
Plenum (Y/N): No

Electrical Characteristics (Overall)


Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
27

Nom. Conductor DC Resistance:


DCR @ 20°C (Ohm/1000 ft)
5.86

Nominal Outer Shield DC Resistance:


DCR @ 20°C (Ohm/1000 ft)
9

Max. Operating Voltage - UL:


Voltage Description
300 V RMS FPLR only applications
41 V RMS CI applications

Put Ups and Colors:


Item # Putup Ship Weight Color Notes Item Desc

Revision Number: 2 Revision Date: 03-11-2013

© 2019 Belden, Inc


All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.

All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and

Page 2 of 3 11-08-2019
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION

5322FM Multi-Conductor - Commercial Applications

the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

Page 3 of 3 11-08-2019