General Description:
Circuit Integrity Fire Alarm, Rated-FPLR-CI, 4-18 AWG solid bare copper conductors with silicone
insulation, Beldfoil® shield, LSZH jacket
Usage (Overall)
Suitable Applications: Survivability, Survivability from Attach by Fire, Fire Alarm Circuit Integrity, CI,
Survivability by NFPA72, Sim to MI, Similar to Mineral Insulated, FPLR-CI,
Emergency Circuits, Notification Devises, Fire Pumps, 2 hour fire rating
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
Silicone Rubber .034
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Polyester Tape-Aluminum Foil 100
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (in.)
FRPE - Flame Retardant Polyethylene .045
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1 Black#1
2 Black#2
3 Black#3
4 Black#4
Page 1 of 3 11-08-2019
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
EU CE Mark: Yes
Flame Test
UL Flame Test: UL1666 Riser, UL2196 Two Hour Circuit Integrity
Plenum/Non-Plenum
Plenum (Y/N): No
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
Page 2 of 3 11-08-2019
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 3 of 3 11-08-2019