General Description:
18 AWG pairs stranded (7x26) bare copper conductors, twisted pairs, PVC insulation, overall Beldfoil®
shield (100% coverage), PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
1 18 7x26 BC - Bare Copper

Total Number of Conductors: 2

Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.406

Insulation Color Code Chart:


Number Color
1 Black & White

Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100

Outer Shield Drain Wire AWG:


AWG Stranding Drain Wire Conductor Material
20 7x28 TC - Tinned Copper

Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.9398

Outer Jacket Ripcord: Yes

Overall Cable
Overall Nominal Diameter: 5.918 mm

Mechanical Characteristics (Overall)


Operating Temperature Range: -30°C To +105°C

Bulk Cable Weight: 48.367 Kg/Km

Max. Recommended Pulling Tension: 115.653 N

Min. Bend Radius/Minor Axis: 58.420 mm

Applicable Specifications and Agency Compliance (Overall)


Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMG, ITC, PLTC

CEC/C(UL) Specification: CMG

AWM Specification: UL Style 2464 (300 V 80°C)

EU Directive 2011/65/EU (ROHS II): Yes

EU CE Mark: Yes

EU Directive 2000/53/EC (ELV): Yes

EU Directive 2002/95/EC (RoHS): Yes

EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005

EU Directive 2002/96/EC (WEEE): Yes

Page 1 of 3 10-30-2014
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION

1032A Multi-Conductor - 300V Power-Limited Tray Cable

EU Directive 2003/11/EC (BFR): Yes

CA Prop 65 (CJ for Wire & Cable): Yes

MII Order #39 (China RoHS): Yes

Flame Test
UL Flame Test: UL1685 UL Loading

CSA Flame Test: FT4

IEEE Flame Test: 1202

Suitability
Suitability - Burial: No

Sunlight Resistance: Yes

Plenum/Non-Plenum
Plenum (Y/N): No

Surface Printing (Overall)


Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.62339

Nom. Capacitance Conductor to Conductor:


Capacitance (pF/m)
167.331

Nom. Capacitance Cond. to Other Conductor & Shield:


Capacitance (pF/m)
311.695

Nom. Conductor DC Resistance:


DCR @ 20°C (Ohm/km)
19.2267

Nominal Outer Shield DC Resistance:


DCR @ 20°C (Ohm/km)
16.6347

Max. Operating Voltage - UL:


Voltage Description
300 V RMS PLTC, CMG
150 V RMS ITC

Max. Recommended Current:


Current
8 Amps per conductor @ 25°C

Notes (Overall)
Notes: Alternate color coding available upon request.

Put Ups and Colors:

Item # Putup Ship Weight Color Notes Item Desc


1032A 0061000 305 MT 14.515 KG BLUE, LIGHT C 2 #18 PVC FS PVC
1032A 00610000 3,048 MT 158.758 KG BLUE, LIGHT C 2 #18 PVC FS PVC
1032A 0065000 1,524 MT 72.575 KG BLUE, LIGHT CZ 2 #18 PVC FS PVC
1032A 0101000 305 MT 14.515 KG BLACK C 2 #18 PVC FS PVC
1032A 01010000 3,048 MT 176.902 KG BLACK CZ 2 #18 PVC FS PVC

Notes:
C = CRATE REEL PUT-UP.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Revision Number: 3 Revision Date: 07-30-2013

© 2014 Belden, Inc


All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is

Page 2 of 3 10-30-2014
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION

1032A Multi-Conductor - 300V Power-Limited Tray Cable

correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.

Page 3 of 3 10-30-2014

You might also like