Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

For More Information Please Call 1-800-Belden1: Description

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Detailed Specifications & Technical Data

ENGLISH MEASUREMENT VERSION

5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled

For more Information


please call

1-800-Belden1

Description:
18 AWG bare copper conductors, PP insulation, conductors cabled together, PVC jacket with ripcord,
sequential footage marking every two feet.
Usage (Overall)
Suitable Applications: Fire Protections, Alarm, Signal, Monitor/Detection, Audio Circuits, Control
Circuits, Initiating Circuits, Notification Circuits

Physical Characteristics (Overall)


Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2 18 Solid BC - Bare Copper

Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
PP - Polypropylene 0.007

Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded

Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.017

Outer Jacket Ripcord: Yes

Overall Cabling
Overall Cabling Lay Length & Direction:
Length (in.) Twists (ft.)
3 4

Overall Cabling Color Code Chart:


Number Color
1 Black
2 Red

Overall Nominal Diameter: 0.143 in.

Mechanical Characteristics (Overall)


Operating Temperature Range: -20°C To +75°C

UL Temperature Rating: 75°C

Bulk Cable Weight: 15.900 lbs/1000 ft.

Max. Recommended Pulling Tension: 39.200 lbs.

Min. Bend Radius (Install)/Minor Axis: 1.500 in.

Page 1 of 3 03-31-2011
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION

5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled

Applicable Specifications and Agency Compliance (Overall)


Applicable Standards & Environmental Programs
NEC/(UL) Specification: FPLR

NEC Articles: 760

EU CE Mark: Yes

EU Directive 2000/53/EC (ELV): Yes

EU Directive 2002/95/EC (RoHS): Yes

EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005

EU Directive 2002/96/EC (WEEE): Yes

EU Directive 2003/11/EC (BFR): Yes

CA Prop 65 (CJ for Wire & Cable): Yes

MII Order #39 (China RoHS): Yes

Other Specification: California State Fire Marshall

Flame Test
UL Flame Test: UL1666 Vertical Shaft

CSA Flame Test: FT4

Plenum/Non-Plenum
Plenum (Y/N): No

Plenum Number: 6320UL

Electrical Characteristics (Overall)


Nom. Inductance:
Inductance (µH/ft)
.16

Nom. Capacitance Conductor to Conductor:


Capacitance (pF/ft)
29

Nom. Conductor DC Resistance:


DCR @ 20°C (Ohm/1000 ft)
6.4

Max. Operating Voltage - UL:


Voltage
300 V RMS

Max. Recommended Current:


Current
5 Amps per conductor @ 25°C

Put Ups and Colors:


Item # Putup Ship Weight Color Notes Item Desc
5320UL D15C500 500 FT 7.000 LB BLUE 2 #18 PP FRPVC
5320UL D151000 1,000 FT 16.000 LB BLUE C 2 #18 PP FRPVC
5320UL 001U1000 1,000 FT 16.000 LB BROWN 2 #18 PP FRPVC
5320UL 002U1000 1,000 FT 16.000 LB RED 2 #18 PP FRPVC
5320UL 002U500 500 FT 8.500 LB RED 2 #18 PP FRPVC
5320UL 0021000 1,000 FT 16.000 LB RED C 2 #18 PP FRPVC
5320UL 010U1000 1,000 FT 16.000 LB BLACK 2 #18 PP FRPVC
5320UL 0101000 1,000 FT 16.000 LB BLACK 2 #18 PP FRPVC

Notes:
C = CRATE REEL PUT-UP.

Page 2 of 3 03-31-2011
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION

5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled

Revision Number: 3 Revision Date: 07-24-2009

© 2011 Belden, Inc


All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.

All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.

Page 3 of 3 03-31-2011

You might also like