LRFD Pedestrian Bridge Example Rev
LRFD Pedestrian Bridge Example Rev
LRFD Pedestrian Bridge Example Rev
C
C
h
o
r
d
s
4
'
-
6
"
L L
10'-0" Deck Width
L
L
Floorbeam
End Posts:
Section: 6 x 3 x 5/16" structural tubing
A = 4.98 in
2
w = 16.96 plf
Vertical Posts:
Section: 5 x 3 x 5/16" structural tubing
A = 4.36 in
2
w = 14.83 plf
I
x
= I
c
= 13.2
in
4
Diagonals:
Section: 4 x 3 x 1/4" structural tubing
A = 3.09 in
2
w = 10.51 plf
FLOORBEAMS:
Section: W8x10
I
x
= I
b
= 30.8
in
4
S
x
= 7.81
in
3
Spacing = 6 ft. at each panel point
DEAD LOAD:
Weight of each truss = 60 plf per truss
Assumed deck loading = 25 psf
Weight of deck & floor system = 25 psf x 10.50 ft. / 2
= 132 plf per truss
Total dead load = 60 plf + 132 plf
= 192 plf Use 200 plf
PEDESTRIAN LIVE LOAD: (Specification, Article 3.1)
MAIN MEMBERS: Trusses
- Use 90 psf without impact.
Live load per truss = pedestrian loading x deck width / 2
= 90 psf x 10.0 ft. / 2
= 450 plf
SECONDARY MEMBERS: Deck, Stringers, Floorbeams
- Use 90 psf without impact.
VEHICLE LOAD: (Specification, Article 3.2)
- Use Table 3.2-1 for Minimum Axle Loads and Spacings.
Use the following vehicle for a clear deck width between 7 ft. and 10 ft.
Front axle = 2 k
Rear axle = 8 k
Axle spacing = 14 ft.
Wheel spacing = 6 ft.
Note:
WIND LOAD: (Specification, Article 3.4)
- Assume 100 mph design wind.
- The design life shall be taken as 50 years for the purpose of calculating the wind loading.
- The deck area may be used to compute design pedestrian live load for all main member components
(truss members). The deck area is the non-zero influence surface for all such components.
- Vehicular access is not prevented by fixed physical methods, therefore, the pedestrian bridge should be
designed for an occassional single maintenance vehicle load.
- The vehicular load shall not be placed in combination with the pedestrian load. Consideration of impact
is not included with this vehicular loading.
- Neglect wind load on the live load vehicle.
For this example, the pedestrian load controls for the truss design; however, the
vehicle load will control for the floor system design.
- Use wind load as specified in the AASHTO Signs , Articles 3.8 and 3.9.
Horizontal Wind Loading
- Apply the design horizontal wind pressure on the truss components.
P
z
= design wind pressure on superstructure using AASHTO Signs, Eq. 3-1 or Table 3-7, psf
= 0.00256K
z
GV
2
I
r
C
d
(AASHTO Signs, Eq. 3-1)
where:
K
z
= height and exposure factor from AASHTO Signs, Eq. C3-1 or Table 3-5
= 1.00 (conservatively taken from Table 3-5 for a height of 32.8 ft.)
G = gust effect factor
= 1.14 (minimum)
V = basic wind velocity
= 100 mph
I
r
= wind importance factor from AASHTO Signs, Table 3-2
= 1.00
C
d
= wind drag coefficient from AASHTO Signs, Table 3-6
= 2.00
P
z
= 58.4 psf
Projected vertical area per linear foot:
Chords: 2 @ 3 in./ 12 x 6 ft. / 6 ft. 0.50 SF/ft.
Verticals: 3 in./ 12 x 4.75 ft. long / 6 ft. 0.20 SF/ft.
Diagonals: 3 in. x 7.81 ft. long / 6 ft. 0.33 SF/ft.
Total per Truss: 1.03 SF/ft.
Deck + Stringers: 10" / 12 0.83 SF/ft.
WS
H
= total horizontal wind on superstructure, plf
= (2 trusses x 1.03 SF/ft. + 0.83 SF/ft.) x 58.4 psf
= 169 plf
Note:
(Alternatively, AASHTO Signs, Table 3-7 may be used
with a C
d
value of 2.0 applied)
The full lateral wind loads must be resisted by the entire superstructure.
Appropriate portions of the design wind loads must also be distributed to the truss
top chord for design lateral forces on the truss verticals.
Vertical Wind Loading
WS
V
=
= P
v
*w
deck
where:
P
v
= vertical wind loading on superstructure, ksf
= 0.020 ksf
w
deck
= total deck width, ft.
= 10.0 ft.
Therefore,
WS
V
= 0.020 ksf x 1000 x 10.00 ft.
= 200 plf
Vertical load on leeward truss = 200 plf x (7.5 ft. + (0.5 in. + 2.5 in.) / 12) / 10.50 ft.
= 147.6 plf
Vertical load on windward truss = 200 plf x (2.5 ft. + (0.5 in. + 2.5 in.) / 12) / 10.50 ft.
= 52.4 plf (uplift)
TOTAL VERTICAL LOADS PER TRUSS: (Specification, Article 3.7)
DEAD LOAD (DC1+DC2): 200 plf
LIVE LOAD (Pedestrian, PL): 450 plf
WIND (Overturning, WS): 148 plf
Load Factors (AASHTO LRFD Table 3.4.1-1)
Limit
State
DC1 & DC2 PL WS
Str I 1.25 1.75 0
Str III 1.25 0 1.40
Ser I 1.00 1.00 0.30
STRENGTH I LIMIT STATE (
DC1+DC2
*(DC1+DC2) +
PL
*PL)
= 1,038 plf
STRENGTH III LIMIT STATE (
DC1+DC2
*(DC1+DC2) +
WS
*WS
V
)
= 457 plf
SERVICE I LIMIT STATE (
DC1+DC2
*(DC1+DC2) +
PL
*PL +
WS
*WS
V
)
= 694 plf
vertical wind load on the full projected area of the superstructure applied at the
windward quarter point, plf
- Apply a vertical pressure of 0.020 ksf over the full deck width concurrently with the horizontal loading.
This loading shall be applied at the windward quarter point of the deck width.
TRUSS MEMBER DESIGN LOADS:
Panel point load from controlling load comb. = 1.038 klf x 6.0 ft. panel = 6.23 k/panel
Maximum Truss Member Axial Loads (from separate truss analysis):
Chord (U05-U06) 134.57 k (compression)
End Post (U00-L00) 34.27 k (compression)
Diagonal (U00-L01) 53.52 k (tension)
Vertical (U01-L01) 28.04 k (compression)
TRUSS TOP CHORD LATERAL SUPPORT: (Specification, Article 7.1)
- Lateral support is provided by a transverse U-frame consisting of the floorbeam and truss verticals.
Compute CL/P
c
for use in the Table.
where:
C = P/A
= 2.917 k/in. (from a separate 2D analysis)
L =
= 72 in.
P
c
=
= 178.9781 k
CL/P
c
= 1.17
n = number of panels
= 12
Therefore,
1/K = 0.688 (Specification, by interpolation of Table 7.1.2-1)
K = 1.45
- Assume the truss verticals are adequate to resist the lateral force per Specification, Article 7.1.1 (Must
verify assumption; see section titled "LATERAL FORCE TO BE RESISTED BY VERTICALS")
unbraced length of the chord in compression (i.e. length between panel
points), in.
desired critical buckling load (i.e. factored compressive force) multiplied by 1.33, k
(Specification, Article 7.1.2)
Determine the design effective length factor, K, for the individual top chord members supported between
the truss verticals using Specification, Table 7.1.2-1.
TOP CHORD COMPRESSIVE RESISTANCE: (AASHTO LRFD, Article 6.9.2)
Check the slenderness ratio against the limiting value.
For main members: KL/r s 120
For bracing members: KL/r s 140
Section: 6 x 3 x 5/16" Structural Tube
A = 4.98 in
2
r
x
= radius of gyration about the x-axis, in.
= 2.06 in.
r
y
= radius of gyration about the y-axis, in.
= 1.18 in.
K = 1.45
L = 72 in.
KL/r
x
= (1.45 x 72 in.) / 2.06 in.
= 50.8 < 120 OK
KL/r
y
= (1.00 x 72 in.) / 1.18 in.
= 61.0 < 120 OK
P
r
= factored resistance of components in compression, k
= |
c
P
n
(AASHTO LRFD, Eq. 6.9.2.1-1)
where:
|
c
= resistance factor for compressive per AASHTO LRFD, Article 6.5.4.2
= 0.9
P
n
= nominal compressive resistance per AASHTO LRFD, Article 6.9.4, k
Determine the nominal compressive resistance, P
n
If s 2.25, then:
P
n
= 0.66
F
y
A
s
(AASHTO LRFD, Eq. 6.9.4.1-1)
If > 2.25, then:
P
n
= (AASHTO LRFD, Eq. 6.9.4.1-2)
y s
0.88F A