Accesorios Media Tension Elastimold

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88
At a glance
Powered by AI
The document provides an overview of cable accessories from Elastimold including separable elbow connectors, cable joints, terminations and other components for underground power distribution systems ranging from 5kV to 35kV.

The document describes separable elbow connectors available in 200A loadbreak, 200A deadbreak and 600A deadbreak styles. It also mentions cable joints, terminations, molded multi-point junctions, PCJ power cable joints and other accessories.

Some of the ratings and specifications provided for the molded vacuum recloser include nominal system voltage, rated maximum voltage, nominal frequency, phase spacing, BIL, power frequency withstand ratings, continuous and overload currents, interrupting and making currents, creepage distances, insulation medium, mechanical operations range and operating temperatures.

In this catalogue...

Power and High Voltage


Elastimold / Fisher Pierce Cable Accessories ......Section A Homac / Blackburn Overhead Connectors ..........Section B Homac Underground Distribution ..........................Section C Boreal Flexible Braids.............................................Section D Russellstoll Electrical Interconnection Systems .....Section E Alphanumerical Index ...............................................Section F

Elastimold Fisher Pierce

Cable Accessories

Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A2 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A3A4 Standard Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A5 200 A Loadbreak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A6A9 200 A Deadbreak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A10A11 600 Series Deadbreak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A12A15 600 Series Deadbreak Cam-Op, Link-Op . . . . . . . . . . . . .A16A17 600 Series Deadbreak Stick-Op, Window-Op . . . . . . . . . .A18A19 600 Series Deadbreak Cable Joints . . . . . . . . . . . . . . . . . . .A20A21 Molded Multi-Point Junctions . . . . . . . . . . . . . . . . . . . . . . . . .A22A23 PCJ Power Cable Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . .A24A25 Cable Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A26A29 Shield Adapters, Sealing and Grounding . . . . . . . . . . . . . . . . .A30A31 Equipment Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A32 How to Specify Size-Sensitive Products . . . . . . . . . . . . . . . . . .A33A34 AEIC and ICEA Cable Insulation Diameter . . . . . . . . . . . . . . . . .A35A38 WX Size Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A39A41 Shrink-Fit Cable Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A42A43 Ranger2 Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A44A49 Faulted Circuit Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A50A57 Underground Distribution Switchgear . . . . . . . . . . . . . . . . . . .A58A69 Molded Fuse Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A70A79 Surge Arresters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A80A85 Molded Vacuum Recloser . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A86A87

w w w. tnb.c a

A1

Elastimold

Cable Accessories

Introduction
This section provides an easy-to-use, comprehensive listing of Elastimold products for 5 kV thru 35 kV underground power distribution systems. Included are separable elbow connectors, cable joints, terminations and other cable accessory components. This catalogue incorporates information relative to product application, ratings and selection. The Thomas & Betts Elastimold brand is recognized as the leading producer of premolded cable accessory components worldwide. Utilizing specially formulated materials with 100% peroxide-cured insulation and shielding, Elastimold products represent the state-of-the-art in premolded process technology. Durable, quality construction and non-degrading, high-reliability, maintenance-free performance is assured when specifying Elastimold products. Elastimolds broad line of premolded products offers signicant advantages over eld-fabricated and other alternatives, including: 100% factory assurance testing prior to delivery and installation; simplied, single-piece construction with built-in insulating, shielding and sealing surfaces; ease of installation with no special skills or tools required; and compact, lightweight, durable designs for easy handling and application.

Separable Elbow Connectors and their related accessories are available in 200 A loadbreak, 200 A deadbreak and 600 A deadbreak styles. Rated for padmount, subsurface, vault, indoor, outdoor and other applications, units feature interchangeable interfaces which can be easily engaged or separated to provide a convenient method to connect or disconnect cable and equipment in a distribution system.

Cable Joints are available in permanently crimped or bolted (separable) connector styles. Permanently crimped units are rated the same as the cable they are connecting and are available for all applications including direct buried.

Cable Terminations are available in single-piece or modular designs. Rated for indoor, outdoor or padmount applications, units allow connection and transition from shielded underground cables to bare overhead conductors and live-front equipment. Elastimold Special Component Services Group provides custom products tailored to specic application requirements. Please contact the factory for further information regarding this service. For Surge Arresters see pages A80 to A85 and Fused Elbows, see pages A70 to A79.

A2

w w w. tnb.c a

Elastimold

Cable Accessories

Ratings
Certied Tests and Performance
Elastimold Separable Connectors, Cable Joints, Cable Terminators and other cable accessory products have been designed and tested per applicable portions of IEEE, ANSI and other industry standards including: IEEE 386 Standard For Separable Connectors IEEE 404 Standard For Cable Joints and Splices IEEE 48 Standard For Cable Terminations IEEE 592 Standard For Exposed Semiconducting Shields ANSI C119.4 Standard For Copper and Aluminum Conductor Connectors AEIC CS8 Standards For XLP and EPR Insulated Cables ICEA S-94-649-2004 and S-97-682-2000 Standard for Cables Rated 5,000 46,000 V

Cable Joints and Terminations Ratings Refer to the pages listed below for rating information: PCJ Cable Joints, page A24 Separable Connector Ratings Table 1 shows voltage and current ratings which apply to all Separable Connectors including 200 A Loadbreak, 200 A Deadbreak and 600 Series Deadbreak products. Table 2 shows switching and fault close ratings which only apply to 200 A Loadbreak Connectors. Cable Terminations, page A26 to A29

w w w. tnb.c a

A3

Elastimold

Cable Accessories

Ratings
Certied Tests and Performance (contd)
Table 1
OPERATING VOLTAGE Maximum line-to-ground (See Application Info Note 1) BIL Impulse withstand 1.2 x 50 microsecond wave WITHSTAND VOLTAGE AC One Minute DC Fifteen Minute CORONA EXTINCTION LEVEL @ 3pC Sensitivity 200 A Products Continuous Current: Symmetrical Momentary Current: 600 Series Products Continuous Current: Symmetrical Momentary Current:

15 kV Class Ratings

25 kV Class Ratings

35 kV Class Ratings

8.3 kV

15.2 kV

21.1 kV

95 kV 34 kV 53 kV 11 kV 200 A* 10 kA sym, 10 cycle duration 600 and 900 A* 25 kA sym, 10 cycle duration

125 kV 40 kV 78 kV 19 kV

150 kV 50 kV 103 kV 26 kV

* Designed for 90C maximum continuous operating temperature

Table 2 15 kV Class Ratings

Loadmake/Loadbreak Switching
1 and 3 circuits 8.3 kV line to ground, 14.4 kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power factor.

Fault Close
1 fault close operation at 8.3 kV or 14.4 kV; 10,000 A, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asym factor applies to new or used mating parts (up to maximum designated switching operations.) 1 fault close operation at 15.2 kV or 26.3 kV; 10,000 A, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asym factor applies to new or used mating parts (up to maximum designated switching operations.) 1 fault close operation at 21.1 kV or 36.6 kV; 10,000 A, rms, sym. 10 cycles (0.17 sec.) 1.3 max. asym factor applies to new or used mating parts (up to maximum designated switching operations.)

25 kV Class Ratings

1 and 3 circuits 15.2 kV line to ground, 26.3 kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power factor.

35 kV Class Ratings

1 and 3 circuits 21.1 kV line to ground, 36.6 kV max. across open contacts. 10 loadmake/break operations at 200 A max. with 70 to 80% lagging power factor.

Application Information: 1. Loadbreak connectors are designed and rated for use on grounded WYE systems. For application on ungrounded WYE or delta systems, the next higher voltage class product is recommended. Examples: 5 kV ungrounded: use 15 kV class products; 15 kV ungrounded: use 25 kV class products; 25 kV ungrounded: use 35 kV class products. 2. Products are designed and constructed for all applications including padmount, subsurface, vault, indoor, outdoor, direct sunlight, direct buried and continuously submerged in water. 3. Products are designed and rated for ambient temperatures of -40C to +65C. It is recommended that loadbreak connectors be hotstick operated at -20C to +65C ambient temperature range and at altitudes not exceeding 6000 ft.

A4

w w w. tnb.c a

Elastimold

Cable Accessories

Standard Interfaces
Standard Interfaces for Separable Connectors, Components and Equipment Bushings
ANSI/IEEE Standard 386 denes the specic interface dimensions that 200 A and 600 Series elbows, inserts, junctions, equipment bushings and any mating components must conform to insure interchangeability. The table below provides information concerning the types of interfaces supplied by Elastimold for various applications and is useful to assure proper matching of components.

Bushing Interface
200 A DEEPWELL EQUIPMENT BUSHING

Voltage Class

Interface Description

Standard No. Figure No

A
200 A LOADBREAK INSERT

15 kV, 25 kV and 35 kV

200 A Bushing Well Interface 8.3 kV, 15.2 kV, 21.1 kV

A
IEEE 386-2001 Fig. 3

B
200 A LOADBREAK INSERT

15 kV

200 A Loadbreak 8.3 kV and 8.3 kV/14.4 kV

IEEE 386-2001 Fig. 5

C
200 A LOADBREAK INSERT

25 kV

200 A Loadbreak 15.2 kV and 15.2 kV/26.3 kV

IEEE 386-2001 Fig. 7, Note 1

D
200 A DEADBREAK INSERT

35 kV

200 A Loadbreak Interface No. 2 21.1 kV and 21.1 kV/36.6 kV

IEEE 386-2001 Fig. 7, Note 1

E
600 SERIES EQUIPMENT BUSHING

15 kV and 25 kV

200 A Deadbreak 8.3 kV and 15.2 kV

IEEE 386-2001 Fig. 4

F
600 SERIES EQUIPMENT BUSHING

15 kV and 25 kV

600 A Deadbreak Interface No.1 8.3 kV and 15.2 kV

IEEE 386-2001 Fig. 11

35 kV

600 A Deadbreak Interface No.1 21.1 kV

IEEE 386-2001 Fig. 13

1. Elastimold uses Fig. 7 interface for both 25 and 35 kV applications.

w w w. tnb.c a

A5

Elastimold

Cable Accessories

200 A Loadbreak

200 A loadbreak connectors and accessories provide a convenient method to connect/disconnect cable and equipment on power distribution systems. Loadbreak elbows include provisions for energized operation using standard hotstick tools, allowing loadmake/break operation and a visible disconnect. Components can be isolated with insulated caps, plugs and parking bushings. Optional accessories allow system grounding, testing, bypass, lightning surge protection and current limiting fusing. Additional connecting points and taps can be provided by use of junctions or feed-thrus.

Ratings Overview
See page A3A4 for complete information including switching and fault close ratings. Current Ratings 200 A Continuous 10 kA sym., 10 Cycles Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 14.4 kV Phase-to-Phase 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 15.2 kV Phase-to-Ground 26.3 kV Phase-to-Phase 125 kV BIL 40 kV AC Withstand 78 kV DC Withstand 19 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction

200 A LOADBREAK SEPARABLE CONNECTOR COMPONENTS


CABLE TO EQUIPMENT CONNECTIONS BUSHING WELL LOADBREAK BUSHING INSERT EXTENDED BUSHING INSERT LOADBREAK ELBOW CONNECTOR WITH OR WITHOUT TEST POINT

BUSHING WELL PLUG

LOADBREAK FEED-THRU INSERT BOLTED ELBOW W/TAP

REPLACEMENT ELBOW REPAIR ELBOW GROUNDING ELBOW

OPERATING ACCESSORIES

INSULATED PARKING BUSHING

PARKING STAND

GROUNDING PLUG INSULATED CAP FEED THRU INSULATED CAP WITH GROUND

FUSED ELBOW

ASSEMBLY TOOL

SEE PAGES A80 TO A85 FOR SURGE ARRESTER APPLICATIONS

A6

w w w. tnb.c a

Elastimold

Cable Accessories

200 A Loadbreak
Illustration (not to scale) Description Voltage ELASTIMOLD Class Cat. No.
15 kV Elbow Connector 25 kV 35 kV 15 kV Elbow Connector w/ Test Point 25 kV 35 kV Jacket Seal Elbow Connector Jacket Seal Elbow Connector w/ Test Point Repair Elbow Connector 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 25 kV 15 kV 15 kV 25 kV 35 kV 35 kV 15 kV 25 kV 15 kV 25 kV 35 kV 15 kV 15 kV 15 kV 25 kV 35 kV

Notes
N2, 3, 4, 5 N2, 3, 4, 5 N2, 3, 5 N2, 3, 4, 5, 24 N2, 3, 4, 5, 24 N2, 3, 5, 24 N2, 19 N2, 19 N2, 19, 24 N2, 19, 24 N5, 10, 18 N5, 10, 18 N5, 10, 18, 24 N5, 10, 18, 24 N5, 11, 13 N5, 11, 13 N5, 11, 13, 24 N5, 11, 13, 24 N2, 5, 22 N2, 5, 22 N5, 10, 18, 22 N5, 10, 18, 22 N5, 10, 18, 22, 24 N5, 10, 18, 22, 24

Illustration (not to scale)

Description
Insulated Cap w/ Ground and Test Point Grounding Plug (1/0 AWG x 6 Ground Lead) Grounding Elbow (1/0 AWG x 6 Ground Lead)

Voltage ELASTIMOLD Class Cat. No.


15 kV 25 kV 35 kV 15 kV 25 kV 15 kV

Notes
N7 N7 N7

165LR-W5X
Use Tables W1 and X1

275LR-W5X
Use Tables W16 and X1

375LR-W5X
Use Tables W3 and X2

166LR-W5X
Use Tables W1 and X1

168DRG 274DRG 376DRG 161GP 272GP 160GLR

25/35 kV 370GLR 15 kV 25 kV 35 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV

N12

276LR-W5X
Use Tables W16 and X1

376LR-W5X
Use Tables W3 and X2

Feed-Thru

165LRJS-W5X
Use Tables W1 and X1

275LRJS-W5X
Use Tables W16 and X1

Feed-Thru Vertical Adjustable Bracket 2-point Feed-Thru Adjustable Bracket 3-point Feed-Thru Adjustable Bracket 4-point Feed-Thru Feed-Thru Well Feed-Thru Well Vertical

166LRJS-W5X
Use Tables W1 and X1

276LRJS-W5X
Use Tables W16 and X1

167ELR-W5X
Use Tables W5 and X1

273ELR-W5X
Use Tables W5 and X1

Repair Elbow Connector w/ Test Point

168ELR-W5X
Use Tables W5 and X1

164FT 274FT 371FT 373FT 164FTV 274FTV 373FTV 164FT2-AB 274FT2-AB 373FT2-AB 164FT3-AB 274FT3-AB 373FT3-AB 164FT4-AB 274FT4-AB 373FT4-AB

N16

N23 N23 N23 N23 N23 N23 N23 N23 N23

274ELR-W5X
Use Tables W5 and X1

15/25 kV K1601WFT 15/25 kV K1601WFTV 15 kV 25 kV 35 kV 15 kV 25 kV ALL 15/25 kV 35 kV ALL

167RLR-W5X
Use Tables W4 and X1

Replacement Elbow

273RLR-W5X
Use Tables W2 and X1

Replacement Elbow w/ Test Point Direct Test Elbow Connector Direct Test Repair Elbow Connector Direct Test Repair Elbow Connector w/ Test Point Fused Elbow (Full Range Current Limiting) Bolted Elbow w/ Tap Bushing Insert Extended Bushing Insert Feed-Thru Insert Insulated Cap Insulated Cap w/ Ground

168RLR-W5X
Use Tables W4 and X1

Insulated Parking Bushing

274RLR-W5X
Use Tables W2 and X1

167DLR-W5X
Use Tables W4 and X1

Test Rod Bushing Well Plug Assembly Tool

273DLR-W5X
Use Tables W2 and X1

161SOP 272SOP 372SOP 164SOP 274SOP 370TR 276BWP M276BWP 200AT

N20 N20 N21 N20, 23 N20, 23

N8

167DELR-W5X
Use Tables W5 and X1

273DELR-W5X
Use Tables W5 and X1

168DELR-W5X
Use Tables W5 and X1

274DELR-W5X
Use Tables W5 and X1

168FLR H-W0X 274FLR H-W0X


See Product Guide PG-PC-H

167LRT-W5X
Use Tables W4 and X1

N17 N4, 8, 20 N4, 8, 20 N6, 21 N8, 21 N8, 20 N8, 20 N16 N16 N6, 16 N9 N9 N7, 9 N7, 9 N7, 9

1601A4 2701A4 3701A4 3701A3 1601EA4 2701EA4 1602A3R 2702A1 3702A1 160DR 160DRG 167DRG 273DRG 375DRG

N1. Copper lug for use on COPPER CONDUCTOR ONLY. N2. W5X indicates that the Cat. No. includes 02500X long bi-metal compression lug as standard. For an all-copper lug, replace W5X with W2X in Table X1 to specify the all-copper 02702X lug. N3. Also available as housing only. Specify: 165BLR-W; 275BLR-W; 375BLR-W; 166BLR-W; 276BLR-W; 376BLR-W. N4. Also available as elbow/insert combination. Specify: 165A4-WX; 275A4-WX; 166A4-WX; 276A4-WX. N5. Also available with 200ECS jacket seal included. Add - S sufx to Cat. No. N6. Rated for single-phase applications only. N7. Equipped with insulated cuff. N8. Includes internal torquing feature using 200AT Assembly Tool. N9. Also available without probe. Specify A sufx Example: 273DRGA. N10.Repair elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 in. length. N11.Replacement elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 in. length.

N12.Rated for 25 kV thru 35 kV applications. N13.Includes long bi-metal contact 00400X. N14.160CA Cable Size Adapter can only be used with elbow Cat. No. 165LR/166LR C size only. N16.Fully rotatable for 360 positioning. Includes bail assembly to secure feed-thru insert to bushing well. N17.Includes 02800X bi-metal contact. N18.Includes 02509X long bi-metal contact. N19.Includes built-in jacket seal. Also available as housing only specify: 165BLRJS-W, 166BLRJS-W, 275BLRJS-W or 276LRJS-W. Also available as elbow/insert combination specify: 165JSA4-W5X, 166JSA4-W5X, 275JSA4-W5X or 276JSA4-W5X. N20. Includes a yellow seating indicator and vent ring. N21. Includes a black vent ring. N22. Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated voltage meter and Hot-line Stick provides a means for direct conductor voltage testing. N23. With stainless steel bracket. N24.Test Point Cap Cat# 156-7

CONTACTS, PROBES, PLUGS, CABLE ADAPTERS AND JUNCTIONS CONTINUED ON PAGE A9.

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. tnb.c a

A7

Elastimold

Cable Accessories

200 A Loadbreak
Ratings Overview
See page A3A4 for complete information including switching and fault close ratings. Current Ratings 200 A Continuous 10 kA sym., 10 Cycles Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 14.4 kV Phase-to-Phase 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 15.2 kV Phase-to-Ground 26.3 kV Phase-to-Phase 125 kV BIL 40 kV AC Withstand 78 kV DC Withstand 19 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction

200 A LOADBREAK SEPARABLE CONNECTOR COMPONENTS

CABLE TO CABLE CONNECTIONS 4-POINT

3-POINT 2-POINT JUNCTION JUNCTION JUNCTION

SEE PAGES A70 TO A 79 FOR FUSED ELBOW SELECTION

2 POINT WELL JUNCTION

LOADBREAK BUSHING INSERT

SEE PAGES A80 TO A 85 FOR SURGE ARRESTER APPLICATIONS

3 POINT WELL LOADBREAK JUNCTION BUSHING INSERT

4 POINT WELL JUNCTION

LOADBREAK BUSHING INSERT

A8

w w w. tnb.c a

Elastimold

Cable Accessories

200 A Loadbreak
Illustration (not to scale) Description Voltage ELASTIMOLD Class Cat. No. Notes Illustration (not to scale) Description
2-Point Junction with/Stainless Steel bracket N1 N2 N3 2-Point Junction w/U-straps 3-Point Junction with/Stainless Steel bracket Elbow Probe 15 kV 25 kV 35 kV

Voltage ELASTIMOLD Class Cat. No.


15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV

Notes
N7 N7 N7 N5, 8 N5, 11 N5, 11 N7 N7 N7 N5, 9 N5, 12 N5, 12 N7 N7 N7 N5, 10 N5, 13 N5, 13

Contacts:
Long Bi-Metal ELR Bi-Metal Copper LRT Contact RLR Contact

ALL 15/25 kV 02702X 02800X 15/25 kV

Use Table X1

164J2 274J2 373J2 164J2-5 274J2-5 373J2-5 164J3 274J3 373J3 164J3-5 274J3-5 373J3-5 164J4 274J4 373J4 164J4-5 274J4-5 373J4-5

02500X 02509X 02702X 02800X 00400X

166LRF 274LRF 375LRF 10EPW


Use Table W6

3-Point Junction w/U-straps 4-Point Junction with/Stainless Steel bracket N4 4-Point Junction w/U-straps N14
N1. N2. N3. N4. N5. N6. N7.

Elbow Cable Entrance Insulating Plug Cable Size Adapter Direct Voltage Test Meter Adapter for: HD Electric Meters Ross Meters Chance Meters 2-Way Well Junction w/ s.s. Bracket 2-Way Well Junction w/ U Straps 3-Way Well Junction w/ s.s. Bracket 3-Way Well Junction w/ U Straps 4-Way Well Junction w/ s.s. Bracket 4-Way Well Junction w/ U Straps

ALL

160CA-W
15 kV Use Table W6 EB-FA Only

200TC-1 200TC-2 200TC-4


15/25 kV K1601WJ2

ALL

N14 N14

N6

15/25 kV K1601WJ2-5

N5, 6, 11

15/25 kV K1601WJ3

N6

Repair elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 in. length. Copper lug for use on COPPER CONDUCTOR ONLY. Replacement elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 in.length. 160CA Cable Size Adapter can only be used with elbow part numbers 165LR/166LR C size only. Also available as rubber only, without straps. Specify sufx -4 in place of -5 in the Cat. No. Supplied with replaceable stud. Replacement stud available separately. Specify 1000-150. Hardware packages, consisting of brackets and straps only, may be ordered separately by specifying -6 in the Cat. No. Example 164J4-6 N8. Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 1601US-J2. N9. Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 1601US-J3. N10.Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 1601US-J4. N11.Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 271-68. N12.Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 271-61. N13.Hardware package, consists of U-straps and back plate only, may be ordered separately by specifying 271-70. N14.For use with Direct Test Connectors.

15/25 kV K1601WJ3-5

N5, 6, 12

15/25 kV K1601WJ4

N6

15/25 kV K1601WJ4-5

N5, 6, 13

w w w. tnb.c a

A9

Elastimold

Cable Accessories

200 A Deadbreak

200 A deadbreak connectors and accessories provide a quick disconnect feature for cable and equipment connections on power distribution systems. All deadbreak connectors must be DE-ENERGIZED before operating and must be mechanically secured with bails when connected. Components can be isolated with insulated caps, plugs and parking bushings. All deadbreak elbows are equipped with test points as standard. Optional accessories allow system grounding, bypass and lightning surge protection. Additional connecting points and taps can be provided by use of junctions or feed-thrus.

Ratings Overview
See page A3A4 for complete information including switching and fault close ratings. Current Ratings 200 A Continuous 10 kA sym., 10 Cycles Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 14.4 kV Phase-to-Phase 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 15.2 kV Phase-to-Ground 26.3 kV Phase-to-Phase 125 kV BIL 40 kV AC Withstand 78 kV DC Withstand 19 kV Corona Extinction

200 A DEADBREAK SEPARABLE CONNECTOR COMPONENTS


CABLE TO EQUIPMENT BUSHING PLUG WELL BUSHING WELL BUSHING INSERT

INSULATED CAP DEADBREAK FEED-THRU INSERT INTEGRAL BUSHING OPERATING ACCESSORIES PARKING STAND STAND-OFF PLUG BELOW CONNECTOR GROUNDING PLUG STRAIGHT RECEPTACLE

CABLE TO CABLE CONNECTIONS LOCKING AND REPAIR SPLICE LOCKING Y SPLICE

FEED THRU

INSULATED PLUG STRAIGHT PLUG IN-LINE JUNCTION

EXCEPT FOR LOCKING SPLICES ALL 200 DEADBREAK PRODUCTS MUST BE MECHANICALLY SECURED WITH A BAIL WHEN CONNECTED

TEE SPLICE 3-POINT JUNCTION 4-POINT JUNCTION 2-POINT JUNCTION

SEE PAGES A80 TO A 85 FOR SURGE ARRESTER APPLICATIONS

A10

w w w. tnb.c a

Elastimold

Cable Accessories

200 A Deadbreak
Illustration (not to scale) Description
Elbow Connector w/ Test Point Direct Test Elbow Connector Bail Assembly for 156LR Elbow Bushing Insert

Voltage ELASTIMOLD Class Cat. No.


15/25 kV 156LR-W5X Use Tables W4 and X1 15/25 kV 156DLR-W5X Use Tables W4 and X1 15/25 kV 150BA N1, 2

Notes

Illustration (not to scale) Description


BAIL

Voltage ELASTIMOLD Class Cat. No.


15/25 kV

Notes
N5

150TB4 150TB5 02500X 02702X 10EP-W


Use Table W6

N1, 2, 22

BAIL Contacts: Long Bi-Metal Copper Elbow Cable Entrance Insulating Plug Cable Entrance Insulating Plug Cable Size Adapter

15/25 kV 15/25 kV 15/25 kV 15/25 kV

N5

N7

15/25 kV

BK1501A1 K1502A1 K150DP K150DR K151SOP 151GP K1501FT K1501J2-U K1501J3-U K1501J4-U 156LRF

N3

N10

Feed-thru Insert

15/25 kV

N3, 4

15/25 kV

152EA-W
Use Table W6

N11

160CA-W
15/25 KV
Use Table W6 EB-FA Only

Insulated Plug

15/25 kV

N3

N14

Insulated Cap Insulated Parking Bushing Grounding Plug

15/25 kV

N3 N3

15/25 kV

15/25 kV

N3

Feed-Thru

15/25 kV

N3, 6

2-Point Junction

15/25 kV

N3, 6

3-Point Junction

15/25 kV

N3, 6

4-Point Junction

15/25 kV

N3, 6

Elbow Probe Straight Receptacle Straight Plug

15/25 kV

15/25 kV K151SR-W0X Use Tables W1 and X1 15/25 kV K151SP-W0X Use Tables W1 and X1 15/25 kV K150T

N3, 12, 13, 17, 18

N3, 12, 13, 19

Tee Splice

N3

In-Line Junction Locking Splice/ Repair Splice Locking Y Splice BAIL

15/25 kV K150S 15/25 kV K151LS-W0X Use Tables W1A and X1 15/25 kV K151LY-W0X Use Tables W1A and X1 15/25 kV 150TB1

N3 N8, 9, 13, 15, 16, 17, 20, 23 N8, 9, 13, 15, 17, 21

N1. Includes bail assembly. N2. W5X indicates that the Cat. No. includes a 02500X bi-metal compression lug, which is rated for either aluminum or copper conductor, as standard. For an all-copper lug, replace W5X with W2X in Table X1 to specify the all-copper 02702X lug. N3. Bails are required but not included. Order separately. Consult factory for bails not listed for a specic application. N4. Fully rotatable for 360 positioning. Includes bail assembly to secure feed-thru insert to bushing well. Elbows bail assemblies are required but not included with the feed-thru insert. N5. Refer to factory for application details. N6. Center-to-center spacing equals 4 in. N7. Copper lug for copper cable only. N8. To order cable legs for different cable sizes, list each leg size W and X. Example: K151LY-A1240-A1240-B1220. See Tables W1 and X1 for sizes. N9. To order locking contacts for K151LS and K151LY, order 01401X (Al) or 01402X (Cu) for plug contact. Order 01301X (Al) or 01302X (Cu) for receptacle. See Table X1 for sizes. N10.For use with 156LR elbows. N11.For use with K151SR, K151SP, K151LS, K151LY receptacles, plugs and splices. N12.Also available as housing only. Specify K151BSP-W or K151BSR-W. N13.Also available in EB-FA sizes per table W6 by using 160CA cable adapter with C size plugs and receptacles. N14.160CA cable adapter can only be used with C size plugs and receptacles. N15.Bails are not required for locking splices. N16.When used as a repair splice, the assembled length allows 4 in. for cable replacement/repair. N17.Straight receptacles are also available with test point. Specify K152SR-W0X Cat. No. N18.W0X indicates that the Cat. No. includes a 01500X universal aluminum compression lug, which is rated for either aluminum or copper, as standard. For an all-copper lug, replace W0X with W2X in Table X1 to specify the all-copper 01502X lug. N19.W0X indicates that the Cat. No. includes a 01600X universal aluminum compression lug, which is rated for ei ther aluminum or copper, as standard. For an all-copper lug, replace W0X with W2X in Table X1 to specify the all-copper 01602X lug. N20.W0X indicates that the Cat. No. includes a 01400X universal aluminum compression lug, which is rated for ei ther aluminum or copper, as standard. For an all-copper lug, replace W0X with W2X in Table X1 to specify the all-copper 01402X lug. N21.W0X indicates that the Cat. No. includes a 01300X universal aluminum compression lug, which is rated for ei ther aluminum or copper, as standard. For an all-copper lug, replace W0X with W2X in Table X1 to specify the all-copper 01302X lug. N22.Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated voltage meter and Hot-line Stick provides a means for direct conductor voltage testing. See page A13 for meter adapters. N23.Gains approximately 4 in. of repair length.

N5 Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

BAIL

15/25 kV 150TB2

N5

BAIL

15/25 kV 150TB3

N5

w w w. t n b. c a

A11

Elastimold

Cable Accessories

600 Series Deadbreak

600 Series deadbreak elbows, straight receptacles, junctions, vault stretchers and accessories are used to connect equipment and cable on primary feeder and network circuits. Designs accommodate large conductors and feature bolted connections and deadfront modular construction for maximum reliability, performance and versatility. DE-ENERGIZED connectors can be quickly and easily connected and disconnected using standard hand tools and equipment in accordance with accepted operating practices. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arresters and circuit protection. Hotstick operable and separable joint systems are shown on pages A16 thru A21.

Ratings Overview
See page A3A4 for complete information. Current Ratings (Prexes: 650, K650, K655, K656, 750, 755, 756 and 03700) 600 A Continuous 25 kA sym., 10 cycles (Prexes 675, K675, K676, 775, 776 and 03702) 900 A Continuous 25 kA sym., 10 cycles
Note: 900 A ratings require copper cable and copper current-carrying components.

SEPARABLE CONNECTORS 600 SERIES DEADBREAK


SEE PAGES A80 TO A 85 FOR SURGE ARRESTERS APPLICATIONS
CABLE TO EQUIPMENT ELBOW CONNECTOR
INSULATING PLUG STRAIGHT RECEPTACLE BOLT & ADAPTER WASHERS

STRAIGHT RECEPTACLE
RETAINING RING

STRAIGHT COMPRESSION CABLE ADAPTER LUG RECEPTACLE HOUSING VOLTAGE DETECTION CAP

200A TAPS
200A DEADBREAK SEE PAGES A10 & A11

INTEGRAL BUSHING

THREADED BUSHING CONNECTING STUD COMPRESSION EXTENDER PLUG LUG

THREADED STUD 600 SERIES ELBOW

600 SERIES CONNECTING TAPS


PLUG

DEADBREAK REDUCING TAP PLUG REDUCING TAP WELL

SPANNER WRENCH 200 A DEADBREAK SEE PAGES A6 & A7 WINDOW-OP SEE PAGES A18 & A19

CABLE TO CABLE (UTILIZING JUNCTION) SEE PAGES A22 AND A23 FOR ADDITIONAL JUNCTIONS
4 PT JUNCTION

CABLE ADAPTER 2 PT JUNCTION 3 PT JUNCTION BUSHING EXTENDER

LOADBREAK ELBOW TAP PLUG

VOLTAGE RATINGS 15/25 kV Class (5 kV thru 28 kV) 16.2 kV Phase-to-Ground 28 kV Phase-to Phase 140 kV BIL 45 kV AC Withstand 84 kV DC Withstand 21.5 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction
Note: Elastimold has increased the IEEE Standard Production and Design Test levels for 25 kV Class products to include 27 kV and 28 kV systems.

L-4 THREADED STUD L-3 INSULATED CAP WITH TEST POINT L-2

OPERATING ACCESSORIES
GROUNDING PLUG INSULATED PARKING BUSHING

CABLE ADAPTER

CABLE TO CABLE UTILIZING-KITS


SEE PAGE A14 & A15 L-1

HOTSTICK OPERABLE 600 SERIES CONNECTORS SEE PAGES A16-A19

STICK-OP SEE PAGES. A18 & A19

COMPRESSION LUG VAULT STRETCHER CONNECTOR VAULT STRETCHER COMPRESSION LUG CABLE ADAPTER

STICK-OP LOADBREAK REDUCING TAP PLUG THREADED COMPRESSION LUG

VS2

LINK-OP SEE PAGES A16 & A17

THREADED STUD LINK-OP LINK CONNECTOR RETAINER LINK-OP SLEEVES CAM-OP RETAINER SLEEVES CAM-OP SEE PAGES A16 & A17 CAM-OP LINK CONNECTOR

CABLE TO CABLE UTILIZING VAULT STRETCHERS


SEE PAGE A14 & A15

VS3

VS4

A12

w w w. tnb.c a

Elastimold

Cable Accessories

600 Series Deadbreak


Illustration (not to scale) Voltage ELASTIMOLD Class Cat. No. 15/25 kV K655LR-W0X
35 kV

Description
600 Series Elbow (w/ Insul. Plug, Cap, Stud, Lug and Cable Adapter) 600 Series Direct Test Elbow (w/ Insul. Plug, Cap, Stud Lug and Cable Adapter) 600 Series Elbow w/ Test Point (w/ Insul. Plug, Cap, Stud Lug and Cable Adapter) 600 Series Direct Test Elbow w/Test Point (w/ Insul. Plug, Cap, Stud, Lug and Cable Adapter) 600 Series Elbow Housing only (w/ Stud) 600 Series Elbow w/ Test Point Housing only (w/ Stud) 600 Series Replacement Elbow Housing only w/o Test Point 600 Series Replacement Elbow Housing only w/o Test Point 600 Series Straight Receptacle (w/ Cable Adapter, Lug and Retaining Ring) 600 Series Direct Test Straight Receptacle Elbow 600 Series Straight Receptacle Housing (Lug and Cable Adapter not included) Straight Receptacle Adapter 600 Series Vault Stretcher (Housing only Cable Size Adapter

Notes
N1, 2, 12 N1, 2, 12 N1, 2, 12, 14 N1, 2, 12, 14 N1, 2, 12 N1, 2, 12 N1, 2, 12, 14 N1, 2, 12, 14 N1, 3 N1, 3 N1, 3 N1, 3

Illustration (not to scale)

Description
600 Series Straight Receptacle Size Sensitive Kit (Cable Adapter, Retaining Ring and Lug) Bushing Extender (w/ Stud) Insulated Cap w/ Test Point (w/ Stud) Insulated Cap w/ Test Point (w/ Stud and Ground) Insulating Plug (w/ Cap) Grounding Plug (Ground Lead 2/0 AWG x 30 in.) Insulated Parking Bushing Connecting Plug Deadbreak Reducing Tap Plug Reducing Tap Well Loadbreak Elbow Tap Plug Vault Stretcher Threaded Stud 600 Series Elbow Threaded Stud Assembly Tool (Window-Op)

Voltage ELASTIMOLD Class Cat. No.


15/25 kV 655CK-W0X-ARR Use Tables W7 and X6

Notes

Use Tables W7 and X6

755LR-W0X
Use Tables W9 and X6

N2

15/25 kV K655DLR-W0X 35 kV

755DLR-W0X

15/25 kV K655BE 35 kV 755BE 15/25 kV K656DR 15/25 kV K656DRG 15/25 kV K650BIP 35 kV 750BIP 15/25 kV 650GP 35 kV 750GP 15/25 kV K650SOP 35 kV 750SOP 15/25 kV K650CP 15/25 kV K651CP 35 kV 750CP 15/25 kV K650RTP 15/25 kV K650RTW 15 kV 25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV ALL ALL

N1, 3 N1, 3 N3, 7 N3, 7 N1, 7, 8 N1, 7, 8 N1, 7, 8 N1, 7, 8 N7, 8 N7, 8 N1, 7, 8, 9, 13 N1, 7, 8, 10 N1, 7, 8, 10 N1, 7, 8, 9 N1, 7, 8, 9 N1, 7, 8, 10, 12 N1, 7, 8, 10, 12 N1, 7, 8, 10, 12 N1 N1 N1 N1 N12 N9 N14 N14 N14

15/25 kV K656LR-W0X Use Tables W7 and X6 35 kV

756LR-W0X
Use Tables W9 and X6

15/25 kV K656DLR-W0X Use Tables W7 and X6 35 kV

756DLR-W0X
Use Tables W9 and X6

15/25 kV K655BLR 35 kV 755BLR 15/25 kV K656BLR 35 kV 756BLR

15/25 kV K655BRLR

N16

15/25 kV K656BRLR

N16

15/25 kV K655SR-W0X Use Tables W7 and X6

N1 ,2, 11

650ETP K650ETP 750ETP 650VSA 750VSA 650SA 750SA 600ATM 600SW 200TC-1

15/25 kV K655DSR-W0X Use Tables W7 and X6

N1, 2, 11, 14

Spanner Wrench Direct Voltage Test Meter Adapter for: HD Electric Meters Ross Meters Chance Meters

15/25 kV K655BSR

N1, 11

ALL

200TC-2 200TC-4

15/25 kV K650SRA 15/25 kV K655BVS

N1, 4 N1, 9 N1, 9

755BVS 15/25 kV 655CA-W


35 kV 35 kV ALL ALL

Use Table W7

755CA-W
Use Table W9

03700X
Use Table X6

Compression Lug 600 Series Elbow and Vault Stretcher Size Sensitive Kit (Cable Adapter and Lug) Adapter Retaining Ring

N5 N6

03702X
Use Table X6

15/25 kV 655CK-W0X Use Tables W7 and X6 35 kV

N2 N2

755CK-W0X
Use Tables W9 and X6

ALL

650ARR-X
Use Table X6

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

N1. For 900 A ratings, substitute 675 for 650 and 655; 676 for 656; K671 for K651; K675 for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756 and 2X for 0X in the Cat. No. The 900 A rating requires copper current-carrying connector components and copper conductor cable. N2. Add sufx symbol from page A29 to include cable shield grounding kit and/or cable jacket sealing kit. N3. Available without the stud by adding N to the Cat. No. N4. Straight Receptacle Adapter is used to connect Straight Receptacles K655YBSR and K655YSR-W0X (Page A19) to equipment bushings. N5. Aluminum lug for use on aluminum or copper conductors. DO NOT substitute threaded 03600X lug. N6. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOT substitute threaded 03602X lug. N7. Available with the stud factory-assembled by adding SP to the Cat. No. 675ETP, K675ETP and 775ETP are available as -SP only. The stud is not eld removable. N8. Available with a loose stud by adding sufx S to the Cat. No. N9. 600SW spanner wrench is recommended for installation of K650CP connecting plug, deadbreak reducing tap plugs and reducing tap wells. N10.Use 600ATM Assembly Tool. N11.600 Series Elbows and Straight Receptacles with IEEE Std. 386 capacitive test points are available by substituting 656 for 655; K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775 in the Cat. No. N12.See page A17 for Window-Op Connector Kit. N13.Superseded by K651CP. N14.Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated voltage meter and Hot-line Stick; provides a means for direct conductor voltage testing. N15.With stainless steel bracket. N16.Replacement Elbow includes an I-Adapter, and Straight Receptacle, resulting in a net gain of 20 in.

w w w. tnb.c a

A13

Elastimold

Cable Accessories

600 Series Deadbreak

600 Series deadbreak elbows, straight receptacles, junctions, vault stretchers and accessories are used to connect equipment and cable on primary feeder and network circuits. Designs accommodate large conductors and feature bolted connections and deadfront modular construction for maximum reliability, performance and versatility. DE-ENERGIZED connectors can be quickly and easily connected and disconnected using standard hand tools and equipment in accordance with accepted operating practices. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arresters and circuit protection. Hotstick operable and separable joint systems are shown on pages A16 thru A21.

Ratings Overview
See page A3A4 for complete information. Current Ratings (Prexes: 650, K650, K655, K656, 750, 755, 756 and 03700) 600 A Continuous 25 kA sym., 10 cycles (Prexes 675, K675, K676, 775, 776 and 03702) 900 A Continuous 25 kA sym., 10 cycles
NOTE: 900 A ratings require copper cable and copper current-carrying components.
4 PT JUNCTION

SEPARABLE CONNECTORS 600 SERIES DEADBREAK


SEE PAGES A 80 TO A 85 FOR SURGE ARRESTERS APPLICATIONS
STRAIGHT RECEPTACLE
STRAIGHT RECEPTACLE BOLT & ADAPTER WASHERS STRAIGHT RECEPTACLE HOUSING RETAINING RING COMPRESSION CABLE ADAPTER LUG

CABLE TO EQUIPMENT

ELBOW CONNECTOR
THREADED STUD 600 SERIES ELBOW VOLTAGE INSULATING DETECTION CAP PLUG CONNECTING PLUG

200A TAPS

200A DEADBREAK SEE PAGES 8 & 9

INTEGRAL BUSHING

CABLE TO CABLE (UTILIZING JUNCTION)

THREADED BUSHING CONNECTING STUD COMPRESSION EXTENDER PLUG LUG CABLE ADAPTER

600 SERIES TAPS

DEADBREAK REDUCING TAP PLUG REDUCING TAP WELL LOADBREAK ELBOW TAP PLUG

SPANNER WRENCH

200A DEADBREAK SEE PAGES 4 & 5 WINDOW-OP SEE PAGES 16 & 17

2 PT JUNCTION

3 PT JUNCTION THREADED STUD BUSHING EXTENDER

L-4

Voltage Ratings 15/25 kV Class (5 kV thru 28 kV) 16.2 kV Phase-to-Ground 28 kV Phase-to-Phase 140 kV BIL 45 kV AC Withstand 84 kV DC Withstand 21.5 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction
Note: Elastimold has increased the IEEE Standard Production and Design Test levels for 25 kV Class products to include 27 kV and 28 kV systems.

OPERATING ACCESSORIES
GROUNDING PLUG

L-3 INSULATED CAP WITH TEST POINT

L-2

INSULATED PARKING BUSHING

CABLE ADAPTER COMPRESSION LUG

CABLE TO CABLE UTILIZING-KITS

L-1

HOTSTICK OPERABLE 600 SERIES STICK-OP CONNECTORS SEE PAGES 14 - 17 SEE PAGES 16 & 17
THREADED COMPRESSION LUG STICK-OP LOADBREAK REDUCING TAP PLUG

VAULT STRETCHER CONNECTOR

VS2

LINK-OP THREADED STUD SEE PAGES 14 & 15 LINK-OP LINK CONNECTOR RETAINER LINK-OP SLEEVES CAM-OP SEE PAGES 14 & 15 CAM-OP RETAINER SLEEVES CAM-OP LINK CONNECTOR

VAULT STRETCHER COMPRESSION LUG

VS3

CABLE TO CABLE UTILIZING VAULT STRETCHERS

VS4

CABLE ADAPTER

A14

w w w. tnb.c a

Elastimold

Cable Accessories

600 Series Deadbreak


Illustration (not to scale) Voltage ELASTIMOLD Class Cat. No.
15/25 kV K650J2 35 kV 750J2 15/25 kV K650J3 35 kV 750J3
N1. For 900 A ratings, substitute 675 for 650 and 655; 676 for 656; K675 for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756 and 2X for 0X in the Cat. No. The 900 A rating requires copper current-carrying connector components and copper conductor cable. N2. 600SW spanner wrench is recommended for installation of K650CP connecting plug, deadbreak reducing tap plugs and reducing tap wells. N3. L-Kits and VS-Kits do not include cable adapters or compression lugs. These items must be ordered separately. N4. 600 Series Elbows and Straight Receptacles with IEEE Std. 386 capacitive test points are available by substituting 656 for 655; K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775 in the Cat. No. N5. 600ATM is recommended for installing K651CP and 750CP. N6. Can be used as a repair joint. (Gains 3-1/2 in. of repair length) N7. Can be used as a reducing joint for different size cables. N8. See page A17 for Window-Op Connector Kit. N9. Rubber junction with stainless steel mounting plate and back plate. Add -U for rubber junction with stainless steel mounting plate, back plate and adjustable mounting bracket. Add -4 for rubber junction only. Add -5 for rubber junction, stainless steel U-straps and back plate. N10.Two - six-position multi-point junctions shown on pages A20 and A21.

Description
2-Point Junction

Notes
N1, 9, 10 N1, 9, 10 N1, 9, 10 N1, 9, 10

3-Point Junction

4-Point Junction

15/25 kV K650J4 35 kV 750J4

N1, 9, 10 N1, 9, 10

1-way L-Kit 2-way L-Kit 2-way VS-Kit

15/25 kV K655L1 35 kV 755L1 15/25 kV K655L2 35 kV 755L2 15/25 kV K655VSL2 35 kV

N1, 2, 3, 4 N1, 2, 3, 4 N1, 2, 3, 4, 5, 6, 7 N1, 2, 3, 4, 5, 6, 7 N1, 2, 3 N1, 2, 3 N1, 2, 3, 4, 5 N1, 2, 3, 4, 5 N1, 2, 3, 5, 6, 7 N1, 2, 3, 5, 6, 7

755VSL2

3-way L-Kit

15/25 kV K655L3 35 kV

755L3

3-Way VS Kit

15/25 kV K655VSL3 35 kV

755VSL3

4-Way L-Kit

15/25 kV K655L4 35 kV 755L4 15/25 kV K655VSL4 35 kV ALL ALL

N1, 2, 3, 4, 5 N1, 2, 3, 4, 5 N1, 2, 3, 5 N1, 2, 3, 5 N8 N2

4-Way VS-Kit Assembly Tool (Window-Op) Spanner Wrench

755VSL4 600ATM 600SW

VAULT STRETCHER Provides an alternate method of splicing and joining various types and styles of cables using standard 600 Series components.
Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. tnb.c a

A15

Elastimold

Cable Accessories

600 Series Deadbreak Cam-Op, Link-Op

Elastimold 600 Series Cam-Op, and Link-Op deadbreak connector systems incorporate provisions for hotstick operation of DE-ENERGIZED primary feeder or network circuits. Congurations allow external visible break, testing, grounding and isolation. Retrot kits allow upgrading existing equipment. Cam-Op systems utilize pin and socket connectors. Link-Op connectors are bolted and installed using torque controlled tools. Either system can be retrotted to existing equipment. The Cam-Op and Link-Op connectors are unique, allowing all hotstick operations to be completed without moving the cable, an important consideration when large, stiff cables prohibit movement. The Cam-Op connector is easily installed or removed by hotstick operation of the cam action disconnect lever. Ratings Overview
See page A3A4 for complete information. Current Ratings 600 and 900 A Continuous 25 kA sym., 10 cycles
NOTE: 900 A ratings require copper cable and copper current-carrying components.

CAM-OP and LINK-OP SYSTEM 600 SERIES DEADBREAK


CAM-OP OR EQUIPMENT BUSHING ALIGNMENT BRACKET RETROFIT COMPONENTS FOR EXISTING EQUIPMENT W/O PROVISIONS FOR MOUNTABLE INSULATED BUSHING

CABLE TO EQUIPMENT
EQUIPMENT BUSHING

INSULATED LINK-OP PARKING BUSHING BUSHING EXTENDER CAM-OP RETAINER SLEEVES OR OR INSULATED CAP

CAM-OP OR ALIGNMENT BRACKET

Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 14.4 kV Phase-to-Phase 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 15.2 kV Phase-to-Ground 26.3 kV Phase-to-Phase 125 kV BIL 40 kV AC Withstand 78 kV DC Withstand 19 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction

LINK CONNECTOR

LOADBREAK ELBOW CONNECTOR

MOUNTABLE INSULATED PARKING BUSHING

LINK-OP

600 SERIES ELBOW

LINK-OP

LOADBREAK ELBOW CONNECTOR INSULATED CAP ELBOW ARRESTER COMPRESSION LUG CABLE ADAPTER ELBOW ARRESTER

LINK CONNECTOR LINK-OP LOADBREAK OR ELBOW TAP LUG CAM-OP LINK-OP CAM-OP OR RETAINER SLEEVES OR 600 SERIES 600 SERIES ELBOW ELBOW

OPERATING TOOL

GROUNDING ELBOW TEST ROD

CABLE ADAPTER

CABLE ADAPTER

COMPRESSION LUG

COMPRESSION LUG OR 2-POINT NSULATED BUSHINGS

CABLE TO CABLE CONNECTION

SEE PAGES A 80 TO A 85 FOR SURGE ARRESTER APPLICATIONS


LINK-OP

CAM-OP

A16

w w w. tnb.c a

Elastimold

Cable Accessories

600 Series Deadbreak Cam-Op, Link-Op

Illustration Voltage ELASTIMOLD (not to scale) Description Class Cat. No.


15 kV CAM-OP CONNECTOR KIT 25 kV 35 kV 15 kV LINK-OP CONNECTOR KIT Mountable Insulated Bushing RETROFIT CAM-OP CONNECTOR KIT 25 kV 35 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 25 kV 35 kV 15 kV 25 kV 35 kV ALL ALL ALL ALL

Notes
N1, 3, 11, 13, 14, 18 N1, 3, 11, 13, 14, 18 N1, 3, 11, 13, 14, 18 N2, 3, 11, 12 13, 14, 18 N2, 3, 11, 13, 14, 18 N2, 3, 11, 13, 14, 18 N3 N3 N5, 11, 13 14, 18 N5, 11, 13 14, 18 N5, 11, 13 14, 18 N6, 11, 12, 13, 14, 18| N6, 11, 12, 13, 14, 18 N6, 11, 12, 13, 14, 18 N4 N4

Illustration Voltage ELASTIMOLD (not to scale) Description Class Cat. No.


CAM-OP Loadbreak Reducing Tap Plugs (Visi-Break) CAM-OP LINK LINK-OP Loadbreak Reducing Tap Plug Grounding Elbow (1/0 AWG x 6 Ground Lead) Test Rod Assembly Tool Cam-Op Operating Kit Link-Op Operating Kit 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV ALL ALL 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV

Notes

655LINK-C-LR-W0X-B-DRG
Use Tables W7 and X6

K655LINK-C-LR-W0X-B-DRG
Use Tables W7 and X6

755LINK-C-LR-W0X-B-DRG
Use Tables W9 and X6

650LK-C-VB K650LK-C-VB 750LK-C-VB 650LK-C K650LK-C 750LK-C 650LT-B K650LT-B 750LT-B 160GLR 370GLR 370GLR 370TR 600AT 650CAM-OK K650CAM-OK 750CAM-OK 650LINK-OK K650LINK-OK 750LINK-OK
N11 N16 N16 N16 N17 N17 N17 N11

655LINK-B-LR-W0X-B-DRG
Use Tables W7 and X6

K655LINK-B-LR-W0X-B-DRG
Use Tables W7 and X6

755LINK-B-LR-W0X-B-DRG
Use Tables W9 and X6

K650LBM-3 750LBM-3 655LINK-C-LR-W0X-A-DRG


Use Tables W7 and X6

N19 N19

K655LINK-C-LR-W0X-A-DRG
Use Tables W7 and X6

755LINK-C-LR-W0X-A-DRG
Use Tables W9 and X6

655LINK-B-LR-W0X-A-DRG
Use Tables W7 and X6

RETROFIT LINK-OP CONNECTOR KIT Insulating Plug CAM-OP Alignment Bracket

K655LINK-B-LR-W0X-A-DRG
Use Tables W7 and X6

755LINK-B-LR-W0X-A-DRG
Use Tables W9 and X6

K650LB 750LB 650CAB K650CAB 750CAB 650AB 650ABV 03700X


Use Table X6

AB

ABV

LINK-OP Alignment Bracket (Retrofit LINK-OP Only) Compression Lug CAM-OP and LINK-OP Size Sensitive Kit (Cable Adapter and Lug) CAM-OP Retaining Sleeve LINK-OP Retaining Sleeve CAM-OP CABLE JOINT KIT

N15 N15

N7 N8

03702X
Use Table X6

15/25 kV 655CK-W0X Use Tables W7 and X6 35 kV ALL ALL 15 kV 25 kV 35 kV 15 kV

N13 N13

755CK-W0X
Use Tables W9 and X6

650RSC 650RS 655BI-LINK-C-LR-WOX-DRG


Use Tables W7 and X6

N11 N11 N9, 11, 13 14, 18 N9, 11, 13 14, 18 N9, 11, 13 14, 18 N10, 11, 12, 13, 14, 18 N10, 11, 12, 13, 14, 18 N10, 11, 12, 13, 14, 18

K655BI-LINK-C-LR-WOX-DRG
Use Tables W7 and X6

755BI-LINK-C-LR-WOX-DRG
Use Tables W9 and X6

655BI-LINK-B-LR-WOX-DRG
Use Tables W7 and X6

LINK-OP CABLE JOINT KIT

25 kV 35 kV

K655BI-LINK-B-LR-WOX-DRG
Use Tables W7 and X6

755BI-LINK-B-LR-WOX-DRG
Use Tables W9 and X6

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

N1. Cam-Op connector kit includes: 1- Cam-Op link; 1- elbow housing; 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves; 1- insulated cap; 1- mountable insulated bushing and 1- alignment bracket. N2. Link-Op connector kit includes: 1- Link-Op link; 1- elbow housing; 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves; 2- insulated caps; and 1- mountable insulated bushing. N3. Mountable insulated bushing included with Cam-Op and Link-Op connector kit. Requires 3 threaded studs on equipment faceplate for installation. N4. Use with the Retrot Cam-Op and Retrot Link-Op connector kit. N5. Retrot Cam-Op connector kit includes: 1- link; 1- elbow housing; 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves; 1- insulated cap; 1- insulating plug; and 1- alignment bracket. N6. Retrot Link-Op connector kit includes: 1- link; 1- elbow housing; 1- cable adapter; 1-0370 style lug; 1- bushing extender; 2- retainer sleeves; 2- insulated caps; 1- insulating plug; and 1- alignment bracket. N7. Aluminum lug for use on aluminum or copper conductors. DO NOT substitute threaded 03600X lug N8. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOT substitute 03602X threaded lug. N9. Cam-Op Cable Joint Kit includes: 1- Cam-Op link; 1- Cam-Op BI-SOP; 2- elbow housings; 2- cable adapters; 20370 style lugs; 2- retainer sleeves; 1- insulated cap. N10.Link-Op Cable Joint Kit includes: 1- Link-Op link; 1- Link-Op BI-SOP; 2- elbow housings; 2- cable adapters; 2- 0370 style lugs; 2- retainer sleeves; 2- insulated caps. N11.600AT assembly tool required for operation and/or installation of Link-Op. 600ATM is recommended for installing Link-Op/Cam-Op retaining sleeves. N12.For 900 A ratings, substitute 675 for 650 and 655; 676 for 656; K675 for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756 and 2X for 0X in the Cat. No. The 900 A rating requires copper current-carrying connector components and copper conductor cable. N13.Add sufx symbol from page A29 to include cable shield grounding kit and/or cable jacket sealing kit. N14.To add elbows or arresters instead of insulating caps, replace the DRG with LR-WX for elbows (with test point) or ESA for elbow arresters. N15.The 650ABV is required when the bushing horizontal spacing on the equipment or junctions is less than 5". N16.Cam-Op operating kit includes accessories that enable visible break, testing, isolation and grounding functions to be performed. Kit includes: 3- Cam-Op loadbreak reducing tap plugs; 3- grounding elbows; 1- assembly tool; 1- test rod; 1- carry case; 1- lubricant; 1- instructions. N17.Link-Op operating kit includes accessories that enable visible break, testing, isolation and grounding functions to be performed. Kit includes: 6- Link-Op loadbreak reducing tap plugs; 3- grounding elbows; 1- assembly tool; 1- test rod; 1- carry case; 1- lubricant; 1- instructions. N18.600 Series Elbows and Straight Receptacles with IEEE Std. 386 capacitive test points are available by substituting 656 for 655; K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775 in the Cat. No. N19. Rated for both 25 kV and 35 kV applications.

w w w. tnb.c a

A17

Elastimold

Cable Accessories

600 Series Deadbreak Stick-Op, Window-Op


Elastimold 600 Series Window-Op and Stick-Op deadbreak connector systems incorporate provisions for hotstick operation of DE-ENERGIZED primary feeder or network circuits. The Window-Op and Stick-Op connectors allow direct testing and grounding with no required cable movement. Window-Op is ideal for equipment applications which include viewing windows to provide an internal visible break that does not require hotstick removal of the elbows. Stick-Op provides an external visible break by hotstick removal of the elbow. Window-Op and Stick-Op connectors are bolted and installed using torque controlled tools. Ratings Overview
See page A3A4 for complete information. Current Ratings 600 and 900 A Continuous 25 kA sym., 10 cycles
NOTE: 900 A ratings require copper cable and copper current-carrying components.

INSULATED CAP

LOADBREAK REDUCING TAP PLUG

BOLTED CONNECTION

STICK-OP and WINDOW-OP SYSTEM 600 SERIES DEADBREAK


SEE PAGES A80 TO A 85 FOR SURGE ARRESTER APPLICATIONS
STICK-OP LRTP LOADBREAK TAP PLUG

INTEGRAL BUSHING 600 SERIES ELBOW WINDOW-OP ETP ELBOW TAP PLUG THREADED COMPRESSION LUG STICK-OP OR COMPRESSION LUG WINDOW-OP CABLE ADAPTER INSULATED CAP

Continuous Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 14.4 kV Phase-to-Phase 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 15.2 kV Phase-to-Ground 26.3 kV Phase-to-Phase 125 kV BIL 40 kV AC Withstand 78 kV DC Withstand 19 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 36.6 kV Phase-to-Phase 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction

TEST ROD STAND-OFF PLUG ASSEMBLY TOOL (WINDOW-OP) ASSEMBLY TOOL (STICK-OP) GROUNDING ELBOW STICK-OP 600BD/200LB BUSHING/ELBOW ADAPTER

GROUNDING PLUG

OPERATING ACCESSORIES

A18

w w w. tnb.c a

Elastimold

Cable Accessories

600 Series Deadbreak Stick-Op, Window-Op


Illustration Voltage ELASTIMOLD (not to scale) Description Class Cat. No.
15 kV WINDOW-OP Connector Kit 25 kV 35 kV WINDOW-OP Replacement Connector Kit 15 kV 25 kV 15 kV STICK-OP Connector Kit 25 kV 35 kV STICK-OP Replacement Connector Kit WINDOW-OP Loadbreak Elbow Tap Plug STICK-OP Loadbreak Reducing Tap Plug STICK-OP Bushing Adapter Compression Lug WINDOW-OP Threaded Compression Lug STICK-OP 15 kV 25 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV ALL ALL ALL ALL

Notes

655ETP-W0X-DRG
Use Tables W7 and X6

K655ETP-W0X-DRG
Use Tables W7 and X6

N1, 4, 5, 6 13, 15

755ETP-W0X-DRG
Use Tables W9 and X6

655RETP K655RETP 655LRTP-W0X-DRG


Use Tables W7 and X6

N4, 5, 6 8, 13

K655LRTP-W0X-DRG
Use Tables W7 and X6

N2 ,3, 4, 5, 8, 13

755LRTP-W0X-DRG
Use Tables W9 and X6

655RLRTP K655RLRTP 650ETP K650ETP 750ETP 650LRTPA3 K650LRTPA2 750LRTPA2 655BEA3 K655BEA2 755BEA2 03700X
Use Tables X6

N3, 4, 5 8, 13, 16 N4, 15 N4, 15 N4, 15

N3,4

N1. Window-Op Kit includes: insulated cap; Window-Op reducing tap plug; 600 Series elbow housing; cable adapter; and 0370 style compression lug. N2. Stick-Op Kit includes insulated cap; Stick-Op Loadbreak reducing tap plug; 600 A Elbow Housing; cable adapter; and threaded 0360 style compression lug. N3. 600AT assembly tool required for operation and/or installation of Stick-Op. N4. For 900 A ratings, substitute 675 for 650 and 655; 676 for 656; K675 for K650 and K655; K676 for K656; 775 for 750 and 755; 776 for 756 and 2X for 0X in the Cat. No. The 900 A rating requires copper current-carrying connector components and copper conductor cable. N5. Add sufx symbol from page A29 to include cable shield grounding kit and/or cable jacket sealing kit. N6. Aluminum lug for use on aluminum or copper conductors. DO NOT substitute threaded 03600X lug. N7. Copper lug for use on COPPER CONDUCTOR ONLY. DO NOT substitute 03602X threaded lug. N8. Threaded aluminum lug (Stick-Op only) for use on copper or aluminum conductors. DO NOT substitute unthreaded 03700X lugs. DO NOT use with 675, 676, K675, K676, 775 or 776 Cat. Nos N9. Threaded copper lug (Stick-Op only) for use on copper conductors only. DO NOT substitute unthreaded 03702X lugs. N10.Required to disassemble Stick-Op loadbreak reducing tap plug from the threaded compression lug and 600 Series elbow after the shear-pin is broken during assembly. N11.Stick-Op Operating Kit includes accessories that enable visible break direct testing, isolation, and grounding functions to be performed. Kit includes: 3-insulated parking bushings; 3-grounding elbows; 3-600DB/200LB bushing/elbow adapters; 1-assembly tool; 1-test rod; 1-carry case; 1-lubricant; 1-instructions. N12.Window-Op Operating Kit includes accessories that enable visible grounding and direct testing functions to be performed. Kit includes: 3-grounding elbows; 1-test rod; 1-carry case;1-lubricant; 1-instructions. N13.600 Series Elbows and Straight Receptacles with IEEE Std. 386 capacitive test points are available by substituting 656 for 655; K656 for K655; K676 for K675; 756 for 755; 676 for 675; K676 for K675 and 776 for 775 in the Cat. Nos. N14.Rated for both 25 kV and 35 kV applications. N15.600ATM assembly tool required for Window-Op assembly. 50 60 ft./lb. torque wrench required but not included. N16.Replacement Elbow includes: insulated cap; reducing tap plug; 600 series elbow housing; I-Adapter; straight receptacle, resulting in a net gain of 20 in. length vs. a standard elbow kit. Compression lugs and cable adapters are ordered separately.

N3,4 N6 N7 N8 N9 N5 N5 N5 N5 N10

03702X
Use Tables X6

03600X
Use Tables X6

03602X
Use Tables X6

WINDOW-OP 15/25 kV Size Sensitive Kit (Cable Adapter 35 kV and Lug) STICK-OP 15/25 kV Size Sensitive Kit (Cable Adapter 35 kV and Threaded Lug) Extraction Tool Grounding Elbow (1/0 AWG x 6 Ground Lead) Test Rod Assembly Tool (Stick-Op) Assembly Tool (Window-Op) STICK-Op Operating Kit WINDOW-Op Operating Kit ALL 15 kV 25 kV 35 kV ALL ALL ALL 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV

655CK-W0X
Use Tables W7 and X6

755CK-W0X
Use Tables W9 and X6

655TCK-W0X
Use Tables W7 and X6

755TCK-W0X
Use Tables W9 and X6

650ET 160GLR 370GLR 370GLR 370TR 600AT 600ATM 650STICK-OK K650STICK-OK 750STICK-OK 650WINDOW-OK K650WINDOW-OK 750WINDOW-OK

N14 N14

N3 N15 N11 N11 N11 N12 N12 N12

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. tnb.c a

A19

Elastimold

Cable Accessories

600 Series Deadbreak Cable Joints

600 Series Separable Cable Joints are available in 2, 3 and 4-way versions and include a capacitive test point as standard. Units are interchangeable, featuring bolted connections. Designs are compact and ideally suited for small vaults and manholes. DE-ENERGIZED joints can be quickly and easily connected and disconnected using standard hand tools and equipment in accordance with accepted operating practices. Bus bars can be changed to add or remove cables from the joint. Optional accessories include insulating and grounding caps and plugs which allow visible external separation, by-pass, isolation, dead-ending, grounding and testing.

Ratings Overview
See page A3A4 for complete information. Current Ratings (Prexes: 650, K650, K655, K656 and 03700) 600 A Continuous 25 kA sym., 10 cycles Voltage Ratings 15/25 kV Class (5 kV thru 28 kV) 16.2 kV Phase-to-Ground 28 kV Phase-to-Phase 140 kV BIL 45 kV AC Withstand 84 kV DC Withstand 21.5 kV Corona Extinction
Note: Elastimold has increased the IEEE Standard Production and Design Test levels for 25 kV Class products to include 27 kV and 28 kV systems.
C

SEPARABLE CABLE JOINTS 600 SERIES DEADBREAK


B

SEPARABLE H-JOINT (4-WAY)


4-WAY INSULATED BUS BAR W/TEST POINT

SEPARABLE WYE-JOINT (3-WAY)


3-WAY INSULATED BUS BAR W/TEST POINT RETAINING RING D BOLT AND WASHERS

STRAIGHT RECEPTACLE HOUSING

CABLE ADAPTER COMPRESSION LUG 2-WAY INSULATED BUS BAR W/TEST POINT

SEPARABLE STRAIGHT-JOINT (2-WAY)

OPERATING ACCESSORIES

INSULATED PLUG W/TEST POINT AND CAP INSULATED CAP WITH BAIL

Note: The separable cable joints shown here use a special Y interace that may not be interchangeable with other 600 Series interfaces.

Dimension
GROUNDING CAP

(in.)
4-1/4 37-1/8 8-1/8 3-7/8

A B C D

GROUNDING PLUG

A20

w w w. tnb.c a

Elastimold

Cable Accessories

600 Series Deadbreak Cable Joints


Illustration (not to scale) Voltage ELASTIMOLD Class Cat. No.
15/25 kV K656I-W0X Use Tables W7 and X6 N1, 8

Description
Separable Straight Joint Pkg. (2-way) w/ Test Point Basic Housing Pkg. Straight Joint w/ Test Point Separable Wye Joint Pkg. (3-Way) w/ Test Point Basic Housing Pkg. Wye Joint w/ Test point Separable H Joint Pkg. (4-Way) w/ Test Point Basic Housing Pkg. H Joint w/ Test Point 2-Way Insulated Bus Bar w/Test Point 3-Way Insulated Bus Bar w/Test Point

Notes

Illustration (not to scale)

Description
600 Series Straight Receptacle Size Sensitive (Cable Adapter, Retaining Ring and Lug) Insulating Plug w/ Test Point and Cap

Voltage ELASTIMOLD Class Cat. No.

Notes

15/25 kV 655CK-W0X-ARR Use Tables W7 and X6

N8

15/25 kV K656I-HP N2

N2

15/25 kV K650YBIP

15/25 kV K656CY-W0X Use Tables W7 and X6

N1, 8

Grounding Plug (4/0 AWG x 6 Ground Lead) Grounding Cap (4/0 AWG x 6 Ground Lead) Stainless Steel Bolt and Washers

15/25 kV 650YGP

15/25 kV K656CY-HP N2

N2

15/25 kV 650GYDR

15/25 kV K656CH-W0X Use Tables W7 and X6

N1, 8 15/25 kV 650BAW

15/25 kV K656CH-HP

N2

Assembly Disassembly Tool Assembly Disassembly Tool

ALL

600YADT-1 N6

N6

15/25 kV K656I-BUS

N3 ALL

600RR T N6

N6

15/25 kV K656CY-BUS

N3

4-Way Insulated Bus Bar w/Test Point

15/25 kV K656CH-BUS

N3

Straight Receptacle

15/25 kV K655YSR-W0X Use Tables W7 and X6

N4, 8

Direct Test Straight Receptacle Elbow Direct Test Straight Receptacle Elbow w/ Test Point Straight Receptacle Housing Only Insulated Ca w/ Bail Bail Only

15/25 kV K655YDSR-W0X Use Tables W7 and X6

N4, 8, 11

K656YDSR-W0X
15/25 kV Use Tables W7 and X6 N4, 8, 11

N1. Complete Joint Packages consisting of: insulated bus bar; straight receptacle housings, retaining rings, cable size adapters, lugs, bolts and washers. N2. Housing Packages consisting of the following non-size sensitive components of the joint: insulated bus bar, straight receptacle housings, bolts and washers. N3. Insulated bus bar only. N4. Straight Receptacle consisting of: straight receptacle housing, retaining ring, cable adapter, lug, bolt and washers. N5. Straight receptacle housing consisting of: straight receptacle housing, bolt and washers. N6. Recommended for ease of assembly/disassembly of receptacles to Bus. 600 YADT is lever drive and 600RRT is screw drive. N7. Aluminum lug for use on aluminum or copper conductors. DO NOT substitute threaded 03600X lug. N8. Add sufx symbol from page A29 to include cable shield grounding kit and/or cable jacket sealing kit. N9. Copper lug for use with COPPER CONDUCTOR ONLY. DO NOT substitute threaded 03602X lug. N10.Available without the bolt and washers by adding N to the Cat. No. N11.Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated voltage meter and Hot-line Stick; provides a means for direct conductor voltage testing. See page A13 for meter adapters.

15/25 kV K655YBSR

N5, 10

15/25 kV K655YDR

15/25 kV 650BA 15/25 kV 655CA-W Use Table W7 15/25 kV 650ARR -X Use Table X6 15/25 kV 03700X N7 15/25 kV 03702X N9 Use Table X6 N7 N9 Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

Cable Adapter Adapter Retaining Ring Compression Lug

w w w. tnb.c a

A21

Elastimold

Cable Accessories

Molded Multi-Point Junctions


Elastimold multi-point junctions are available in 2, 3, 4, 5 or 6 point congurations with 15, 25 or 35 kV ratings. Units feature modular design exibility, allowing selection of any combination of 200 A deepwell or 600 A bushing interfaces located on standard 4 in. or optional 6 1/2 in. centers. The 6 1/2 in. center spacing is especially well suited for Distributed Switchgear applications including fused elbow, MVI fault interrupter, MVS switch, etc. Designs incorporate lightweight, damage resistant, EPDM molded rubber construction and corrosion resistant 304 stainless steel mounting brackets. Junctions are maintenance-free, fully shielded, deadfront and submersible. Units are ideally suited for subsurface, padmount, indoor and outdoor vault applications. Elastimold multi-point junctions provide a convenient method for connecting, looping and tapping of 200 and 600 A elbows and other accessories at a common location where utilization of space, cable training, exibility and operability are important. Ratings Overview
See page A3A4 for complete information. Current Ratings 600 A Continuous 25 kA sym., 10 cycles or with 200 A Bushing Well versions 200 A Continuous 10 kA sym., 10 cycles
C

J6-622226-25

J6-662266-25-SV

DIMENSIONAL INFORMATION
FIGURE 1: MULTIPOINT JUNCTIONS WITH 4 IN. INTERFACE SPACINGS.
A

FIGURE 2: MULTIPOINT JUNCTIONS WITH 6-1/2 IN. INTERFACE SPACINGS.

5-1/2 IN.

B 6-3/4 IN. 5-1/2 IN. 6-3/4 IN.

9/16 IN. X 1 IN. MOUNTING HOLES 4 IN. TYP 1-1/2 IN. 5-1/4 IN. C 9/16 IN. X 1 IN. MOUNTING HOLES 6-1/2 IN. TYP

Voltage Ratings 15 kV Class 8.3 kV Phase-to-Ground 95 kV BIL 34 kV AC Withstand 53 kV DC Withstand 11 kV Corona Extinction 25 kV Class 16.2 kV Phase-to-Ground 140 kV BIL 45 kV AC Withstand 84 kV DC Withstand 21.5 kV Corona Extinction 35 kV Class 21.1 kV Phase-to-Ground 150 kV BIL 50 kV AC Withstand 103 kV DC Withstand 26 kV Corona Extinction

5-1/4 IN. NAME PLATE GROUND LUG

NAME PLATE

GROUND LUG

Figure 1 Type of Junction A


15 19 24 27 31

Figure 2 Number of mounting holes


6 6 6 6 8

B
7-1/2 11-1/2 15-1/2 19-1/2 23-1/2

C
6 8 10 12 9-3/8

A
19-1/2 26 32-1/2 39 45-1/2

B
10 10 23 10 36

C
8-1/4 11-1/2 9-1/4 12 8-1/4

Number of mounting holes


6 6 8 8 10
15 TO 60 ADJUSTABLE ANGLE

J2 J3 J4 J5 J6

Optional Tilt Mounting Adapter.

A22

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Multi-Point Junctions


Elastimold multi-point junctions feature modular design exibility that permits the specier to determine the positions of the bushing interfaces and bushing well positions. Base Catalogue Numbers
Installation (not to scale) Description Voltage Class

Elastimold Cat. No. Notes 4 in. Spacing


J2 - __ __ - 15 J2 - __ __ - 25 J2 - __ __ - 35 J3 - __ __ __ - 15 J3 - __ __ __ - 25 J3 - __ __ __ - 35 J4 - __ __ __ __ - 15 J4 - __ __ __ __ - 25 J4 - __ __ __ __ - 35 J5 - __ __ __ __ __ - 15 J5 - __ __ __ __ __ - 25 J5 - __ __ __ __ __ - 35 J6 - __ __ __ __ __ __ - 15 J6 - __ __ __ __ __ __ - 25 J6 - __ __ __ __ __ __ - 35

6-1/2 in. Spacing


J2 - __ __ - 15-SV J2 - __ __ - 25-SV J2 - __ __ - 35-SV J3 - __ __ __ - 15-SV J3 - __ __ __ - 25-SV J3 - __ __ __ - 35-SV J4 - __ __ __ __ - 15-SV J4 - __ __ __ __ - 25-SV J4 - __ __ __ __ - 35-SV J5 - __ __ __ __ __ - 15-SV J5 - __ __ __ __ __ - 25-SV J5 - __ __ __ __ __ - 35-SV J6 - __ __ __ __ __ __ - 15-SV J6 - __ __ __ __ __ __ - 25-SV J6 - __ __ __ __ __ __ - 35-SV N1, 2

2- point Junction (J2-26-15 shown) 3- point Junction (J3-626-35 shown) 4- point Junction (J4-6226-15 shown) 5- point Junction (J5-62226-15 shown) 6- point Junction (J6-622226-15 shown)

15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV

N1, 2

N1, 2

N1, 2

N1, 2

ORDERING INFORMATION To specify and order Elastimold Multi-Point Junctions: 1. Use Table 1 to construct a catalogue number describing the required junction. Table 1. Catalogue Number Construction

J
Multi-Point Junction

Number of Points
2 3 4 5 6 2 Points 3 Points 4 Points 5 Points 6 Points 2 6 B

Voltage Class
15 25 35 15 kV 25 kV 35 kV

Interface Spacing Options


Blank No tilt mounting bracket Tilt Mounting Adapter. Bolts to the bottom of the standard mounting to provide 15, 30, 45 or 60 TMA bracket degree adjustable angle mounting. (Two Tilt Mounting Adapters are required for each installation.) L R Left parking stand only Right parking stand only No parking stand

Interface Identification * and Positioning


200 A Deepwell Interface 600 A Bushing Interface Blank Position

Blank SV

Standard spacing 4 in. centers Optional 6-1/2 in.centers

*When there is a 200 A Interface on one side of the junction and a 600 Series Interface on the other side, always start with the 200 A side.

Ordering Example A To order a 4-point, 15 kV junction with 4 in. spacings and 600 Series interfaces on the outside ways and 200 A wells on the inside ways specify: Catalogue Number J4-6226-15 Ordering Example B To order a 6-point, 25 kV junction with 6-1/2 in. spacings and 600 Series interfaces on the ways 1, 3, 4, 6 and 200 A wells on the ways 2 and 5 speciy: Catalogue Number J6-626626-25-SV
N1. The 6-1/2 in.wide spacing is necessary if the junction is to be used to connect with a single-phase MVS Molded Vacuum Switch or MVI Molded Vacuum Interrupter. N2. Also available with a shorter bracket by reducing the number of parking stands, see R, L, N above.

w w w. tnb.c a

A23

Elastimold

Cable Accessories

PCJ Power Cable Joints

PCJ Power Cable Joints utilize permanently crimped connectors. PCJ Housings are fully insulated, shielded and sealed for direct buried, vault, submersible and other severe service applications. Units have been designed and tested per IEEE Standard 404 to assure system matched performance and ratings equal to the cable to which the splice will be installed. PCJ Power Cable Joints are available in 2 styles: Style 1 uses a single piece housing that is sized to accommodate a specic range of cable. Style 1 units are ideally suited for straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable.

ELECTRICAL RATINGS SUMMARY


The following ratings summary is based on IEEE Std. 404 and applies to all Elastimold PCJ Power Cable Joints. Voltage A. 15 kV Class (8.7 kV Phase-to-Ground) B. 25 kV Class (14.4 kV Phase-to-Ground) C. 35 kV Class (20.2 kV Phase-to-Ground) Impulse Withstand: A=110 kV, B=150 kV, C=200 kV BIL,1.2 x 50 microsecond wave Corona Extinction Voltage: A=13 kV, B=22 kV, C=30 kV minimum, 3pC sensitivity DC Withstand: During installation: A=56 kV, B=80 kV, C=100 kV DC Withstand: After installation and in service for the rst 5 years: A=18 kV, B=25 kV, C=31 kV for XLPE Insulated Cables and A=45 kV, B=64 kV, C=80 kV for EPR Insulated Cables (Reference AEIC CS6 and CS8, Section L.2.) Current Continuous rating equal to the rating of the cable Short-Time rating equal to the rating of the cable up to 35 kA Shield Design Meets IEEE standard 592 for Exposed Semiconducting Shields on Premolded High Voltage Cable Joints and Separable Insulated Connectors

Production tests include 100% tests of the premolded joints to assure: Corona Extinction Voltage: A=13 kV, B=22 kV, C=30 kV minimum, 3pC sensitivity AC Withstand: A=35 kV, B=52 kV, C=69 kV, 60 Hz, 1 minute Design tests on production joints demonstrate compliance with IEEE 404 including: Corona Extinction Voltage: A=13.0 kV, B=22.0 kV, C=30.0 kV minimum, 3pC sensitivity AC Withstand: A=35 kV, B=52 kV, C=69 kV, 60 Hz 1 minute. DC Withstand: A=70 kV, B=100 kV, C=125 kV negative polarity, 15 minutes Impulse Withstand (BIL): A=110 kV, B=150 kV, C=200 kV, 10 positive and 10 negative, 1.2 x 50 microsecond wave, at conductor temperatures of 20 and 130C, nominal Short-Time Current: magnitude equal to cable up to 35 kA Cyclic Aging: 30 days at: A=26.1 kV, B=43.2 kV, C=60.6 kV AC continuous, load current for 8 hours per day, providing 130 conductor temperature. Joints then subjected to: A=31 kV, B=50 kV, C=71 kV for 5 hours followed by: A=39 kV, B=65 kV, C=91 kV for 5 min. Load Cycle: Connectors meet requirements of ANSI C119.4, Class A and Class 3 ratings

A24

w w w. tnb.c a

Elastimold

Cable Accessories

PCJ Power Cable Joints


PCJ Style 1 with single-piece housing

ORDERING INFORMATION

1 5 P C J 1 W 1 X
PCJ Style 2 with universal housing and separate cable adapters that can be varied with the cable application.
Conductor Conductor Size Code Notes
N1 N2 N1 N2 N1 N2 N1 N2 N1 N2 N1 N2

1 - Style 1 2 - Style 2

Insulation Diameter

Voltage Class

Power

Cable

Joint

Style

1 - Aluminum 2 - Copper

W SIZING INFORMATION AND SELECTION Use Table W8 for 15PCJ Use Table W9 for 25PCJ Use Table W10 for 35PCJ
DIMENSION B OUTSIDE DIA.

X SIZING INFORMATION AND SELECTION Use Table X7 for 15PCJ, 25PCJ and 35PCJ
DIMENSION A OVERALL LENGTH

DIMENSIONAL DATA
Style 1 Cat. No. 15PCJ1FX 15PCJ1GX 25PCJ1GX 15/25/35PCJ1HX 15/25/35PCJ1JX 15/25/35PCJ1KX 15/25/35PCJ1LX 15/25PCJ1LMX 15/25/35PCJ1MX 15/25/35PCJ1NX 15/25/35PCJ1PX 15/25/35PCJ1QX Style 2 Cat. No. 15PCJ2FX 15/25PCJ2GX 15/25/35PCJ2HX 15/25/35PCJ2JX 15/25/35PCJ2KX 15/25/35PCJ2LX 15/25/35PCJ2MX 15/25/35PCJ2NX 15/25/35PCJ2PX 15/25/35PCJ2QX A (in.)
10-1/4 10-1/4 14-3/8 14-3/8 14-3/8 14-3/8 14-3/8 14-3/8 14-3/8 15-3/4 15-3/4 15-3/4

B (in.)
1-3/4 1-3/4 2-7/16 2-7/16 2-7/16 2-25/32 2-25/32 2-25/32 2-25/32 3-3/16 3-3/16 3-3/16 Power Cable Joint Style 2 Power Cable Joint Style 1

Description

Voltage Class

ELASTIMOLD Cat. No.

15 kV 15 kV 25 kV 25 kV 35 kV 35 kV

15PCJ1W1X 15PCJ1W2X 25PCJ1W1X 25PCJ1W2X 35PCJ1W1X 35PCJ1W2X

15 kV 15 kV 25 kV 25 kV 35 kV 35 kV

15PCJ2W1X 15PCJ2W2X 25PCJ2W1X 25PCJ2W2X 35PCJ2W1X 35PCJ2W2X

A (in.)
16-3/8 16-3/8 16-3/8 16-3/8 21 21 21 21 21 21

B (in.)
2-25/32 2-25/32 2-25/32 2-25/32 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4 3-3/4

N1. Kit includes aluminum compression connector suitable for splicing aluminum conductor to aluminum conductor or aluminum conductor to copper conductor. An all-copper connector is required for copper-to-copper connections. N2. Kit includes copper compression connector suitable for splicing copper conductors to copper conductor only. DO NOT use copper connectors on aluminum conductors.

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. tnb.c a

A25

Elastimold

Cable Accessories

Cable Terminations

Elastimold cable terminations are available in single piece or modular designs. Terminators allow connection and transition from shielded, underground cable to bare overhead conductors and live-front equipment. Units are designed and rated per IEEE Standard 48 for riser pole, padmount, indoor and outdoor applications. PCT1, PCT2, 16THG and 35MTG terminators provide sufcient creep, strike and weather sealing for class 1 outdoor service. PCT1 and PCT2 also include an integral cable jacket seal. The 35MTGI terminators and 35MSC stress cones are rated for class 2 and class 3 indoor service respectively. Optional mounting brackets, aerial lugs and equipment connectors are available as required.

Electrical Ratings Summary


The following ratings summary is based on IEEE Std. 48 and applies to all the terminations on pages A26 thru A29. Elastimold terminations are designed for use on three-phase systems, either 3-wire or 4-wire and the single-phase laterals of these systems. Voltage Ratings 15 kV Class 9.5 kV Phase-to-Ground 110 kV BIL 1.2 x 50 microsecond wave AC Withstand: 50 kV 1 min. dry 35 kV 6 hr. dry 45 kV 10 sec. wet 13 kV Corona Extinction 25 kV Class 16 kV Phase-to-Ground 150 kV BIL 1.2 x 50 microsecond wave AC Withstand: 65 kV 1 min. dry 55 kV 6 hr. dry 60 kV 10 sec. wet 21.5 kV Corona Extinction 35 kV Class 22 kV Phase-to-Ground 200 kV BIL 1.2 x 50 microsecond wave AC Withstand: 90 kV 1 min. dry 75 kV 6 hr. dry 80 kV 10 sec. wet 30 kV Corona Extinction

TERMINATIONS
SINGLE PIECE TERMINATORS STRESS CONE MODULAR TERMINATORS

PCT-1

PCT-2

16THG

16THGS

35MSC

35MSCI

35MTGI

35MTG

BRACKETS

PB-1

16TB2

35MTB

1535AFB

A26

w w w. tnb.c a

Elastimold

Cable Accessories

Cable Terminations

Illustration Voltage (not to scale) Description Class


Single-Piece Terminator (Class 1) Housing only Single-Piece Terminator (Class 1) Housing only Single-Piece Terminator for solid conductor only (Class 1) Stress Cone (Class 3) Stress Cone w/Grd. Strap Modules only Modular Terminator (Class 1) 15 kV 25 kV 15 kV 25 kV

ELASTIMOLD Cat. No. PCT1-1X-4


Use Table X9

Notes N12, 14, 15, 22 N12, 14, N15, 23 N13,22 N13,23 N2, 14 15

PCT2-1X-4
Use Table X9

PCT1-4 PCT2-4

15/25 kV 16THG-W0X-4 Use Tables W12 and X8 15/25 kV 16THGH-W Use Table W12 15/25 kV 16THGS-WX Use Tables W12 and X4

N3

ALL ALL ALL 15 kV 25 kV 35 kV

35MSC-W
Use Table W11

N17 N17 N11, 16 N2, 11 N2, 5, 11 N2, 6, 11 N11 N11 N7, 11 N1, 14, 15 N2, 8 N3, 9 N2, 10, 11 18, 25 N2, 10, 11 19, 25 N4, 10, 11 20, 25 N1 N1 N2, 10, 11 21, 25

35MSCI-W
Use Table W11

35MG-W
Use Table W13

N1. Use with PCT1 or PCT2 Terminators. N2. Includes contact rod, ground strap and rain cap. N3. Includes crimp ring, ground strap and rain cap. N4. Includes spade contact, ground strap and rain cap. N5. For KA thru PB sizes use 35MTG-WX-6-CA. N6. For KA thru PB sizes use 35MTG-WX-8-CA. N7. For KA thru PB sizes use 35MTGI-W-6. N8. Use with 16THG Terminators. N9. Use with 16THGS Terminators. N10.Use with 35MTG Terminators. N11.Refer to page A26 for detailed ordering instructions. N12.Includes rod contact as standard. Specify sufx -3 in place of -4 for two-hole spade lug. Specify sufx -5 in place of -4 for one-hole spade lug. N13.Specify sufx -3 or -5 in place of -4 for two-hole spade lug housing or one- hole spade style housing. N14.Use 1X for an aluminum rod contact for aluminum conductors only. N15.Substitute 0X for 1X for a universal aluminum rod contact for aluminum or copper conductors. N16.Available in sizes from GA thru PB and are supplied qty. 2 per package. N17.Available in sizes EB thru PB. N18.For conductors from 1/0 thru 350 kcmil. N19.For conductors from 400 kcmil thru 1000 kcmil. N20.For conductors from #2 to 1000 kcmil. N21.For conductors from #6 thru 4/0. N22.Use for insulation dia. range from .640 in. thru 1.070 in. N23.Use for insulation dia. range from .830 in. thru 1.180 in. N24.Select symbol for A from aerial lug ordering information on page A28. N25.W13 Table provides sizing for rain cap. X10 Table provides sizing for connectors.

35MTG-WX-4-CA
Use Tables W13 and X3

35MTG-WX-8-CA
Use Tables W13 and X3

35MTG-WX-10-CA
Use Tables W13 and X3

Modular Terminator (Class 2) w/o Rain Cap Rod Contact for PCT Rod Contact for 16THG Solid Conductor Package for 16THGS 3/4 in.-16 Threaded Rod for MTG 1 in.-14 Threaded Rod for MTG Two-Hole Spade for MTG Two-Hole Spade for PCT One-Hole Spade for PCT Universal Rod for MTG Aerial Lugs for MTG Threaded Rod (Two-hole spade or bare wire)

15 kV 25 kV 35 kV

35MTGI-W-4
Use Table W13

35MTGI-W-6
Use Table W13

35MTGI-W-8
Use Table W13

15/25 kV 00700X Use Table X9 15/25 kV 16TCA-X Use Table X8 15/25 kV 16CAS-X Use Table X4 ALL ALL ALL ALL ALL ALL

35MTGA-WX-1
Use Tables W13 and X3

35MTGA-WX-2
Use Tables W13 and X3A

35MTGA-WX-3
Use Tables W13 and X3

01000X
Use Table X9

01100X
Use Table X9

35MTGA-WX-4
Use Tables W13 and X3

ALL

35AL-A

N10, 24

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. t n b. c a

A27

Elastimold

Cable Accessories

Cable Terminations

ORDERING INSTRUCTIONS FOR MODULAR TERMINATORS

35MTG - W X - N - C A
I - Indoor Blank = Outdoor Use Table W13, below Connector Style Selection Chart Use Table X3 or Table X3A
NOTE: Applicable table and available sizes depend upon connector style. Reference Connector Style Selection Chart and notes A through D.

Description Available for Symbol Notes Conductor Sizes


3/4 in.-16 Threaded Rod 1/0 thru 350 kcmil 400 thru 1000 kcmil #2 thru 1000 kcmil #6 thru 4/0 -1 A

Aerial Lugs for Threaded Rod Connectors Only Type


Bare Wire 2-Hole Spade Bare Wire

Connector Symbol
3/4 in.-16 Rod 3/4 in.-16 Rod 1 in-14 Rod 1 in-14 Rod -11 -12 -21 -22

Recommended Number of Modules GA-JB


15 kV 25 kV 35 kV 4 8 10

KA-PB
4 8 10

1 in.-14 Threaded Rod 2-Hole Spade Universal Rod

-2

-3

C 2-Hole Spade

NOTES:
A. B. C. D. Available for 1/0 through 350 conductor sizes only. Use Table X3 for size selection. Available for 400 through 1000 conductor sizes only. Use Table X3A for size selection. Available for #2 through 1000 conductor sizes only. Use Table X3 for size selection. Available for #6 through 4/0 conductor sizes only. Use Table X3 for size selection.

-4

Table W13
USE FOR FOLLOWING PRODUCTS

Cable insulation Diameter in (in.) Min.


0.775 0.825 0.875 0.930 0.980 1.040 1.095 1.160 1.220 1.285 1.355 1.485 1.530 1.575 1.665 1.755

Table X3 Symbol for W


GA GAB GB GH HA HAB HB HJ JA JAB JB KA KAB KB PA PB USE FOR FOLLOWING PRODUCTS

Max.
0.885 0.935 0.985 1.040 1.115 1.175 1.240 1.305 1.375 1.395 1.520 1.595 1.640 1.685 1.785 1.875

Symbol for X Conductor SIZE AWG Strand./ Compt./ or kcmil Compr. Solid
#6 #5 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 5 4 3 2 1 0 10 20 30 40 250 300 350 400 450 500 550 600 650 750 750 800 900 1000 5 4 3 2 1 0 10 20 30 40 250 300 350 400 450 500 550 600 650 750 800 900

Table X3A
USE FOR FOLLOWING PRODUCTS

Symbol for X Conductor SIZE AWG Strand./ Compt./ or kcmil Compr. Solid
400 400 450 500 550 600 650 750 750 1000 400 450 500 500 550 600 650

35MTG 35MTGI

35MTG
FOR USE WITH STYLE-1,-3, and -4 CONNECTORS ONLY. SEE NOTES A, C, and D FOR APPLICATION INFORMATION

35MTG
FOR USE WITH STYLE-2 CONNECTORS ONLY. SEE NOTES B FOR APPLICATION INFORMATION 450 500 550 600 650-700 750 800 1000

A28

w w w. tnb.c a

Elastimold

Cable Accessories

Cable Terminations

TERMINATIONS
Illustration Voltage (not to scale) Description Class
PCT Positioning Bracket 16THG Bracket Bracket for crossarm 16THG Bracket for riser pole mounting 16THG Bracket for tri-mounting 16THG KELLUMS GRIP Bracket KELLUMS Bracket for crossarm mounting Bracket (for riser pole mounting) KELLUMS Bracket for tri-mounting ALUMA FORM Bracket ALUMA FORM Bracket for Crossarm mounting ALUMA FORM Bracket for riser-pole mounting ALUMA FORM Bracket for tri-mounting ALL ALL

ELASTIMOLD Cat. No. PB-1 16TB-2

Notes
N1, 12 N6

ALL

16TB-3

N6

N1. Use with PCT-1 or PCT-2 Terminators. N2. Fits overall cable O.D. from 1.195 in. to 1.625 in. N3. Fits overall cable O.D. from 0.925 in. to 1.335 in. N4. Fits overall cable O.D. from 0.890 in. to 1.185 in. N5. Fits overall cable O.D. from 1.500 in. to 2.000 in. N6. Use with 16THG and 16THGS Terminators. N7. Use with MTG, MTG1 and MSC Terminators. N8. For conductors from 1/0 thru 350 kcmil. N9. For conductors from 400 kcmil thru 1000 kcmil. N10.For conductors from #2 to 1000 kcmil. N11.For conductors from #6 thru 4/0. N12.Fits overall cable O.D. from 0.750 in. to 1.625 in. N13.Fits overall cable O.D. from 0.750 in. to 2.000 in.

ALL

16TB-4

N6

ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL ALL

16TB-5 35MTB1-A 35MTB1-B 35MTB1-C 35MTB1-D 35MTB3-A 35MTB3-B 35MTB3-C 35MTB3-D 35MTB4-A 35MTB4-B 35MTB4-C 35MTB4-D 35MTB5-A 35MTB5-B 35MTB5-C 35MTB5-D 1535AFB-1

N6 N1, 2, 6, 7 N1, 3, 6, 7 N1, 4, 6, 7 N1, 5, 6, 7 N1, 2, 6, 7 N1, 3, 6, 7 N1, 4, 6, 7 N1, 5, 6, 7 N1, 2, 6, 7 N1, 3, 6, 7 N1, 4, 6, 7 N1, 5, 6, 7 N1, 2, 6, 7 N1, 3, 6, 7 N1, 4, 6, 7 N1, 5, 6, 7 N1, 6 ,7, 13

ALL

1535AFB-3

N1, 6, 7, 13

ALL

1535AFB-4

N1, 6, 7, 13

ALL

1535AFB-5

N1, 6, 7, 13

Refer to the W and X tables on pages A39 to A41 for sizing to cable insulation diameter and conductor size. For cable shield adapters and jacket seals, see page A30.

w w w. tnb.c a

A29

Elastimold

Cable Accessories

Shield Adapters, Sealing and Grounding


Elastimold cable terminations are available in single piece or modular designs. Terminators allow connection and transition from shielded, underground cable to bare overhead conductors and live-front equipment. Units are designed and rated per IEEE Standard 48 for riser pole, padmount, indoor and outdoor applications. PCT1, PCT2, 16THG and 35MTG terminators provide sufcient creep, strike and weather sealing for class 1 outdoor service. PCT1 and PCT2 also include an integral cable jacket seal. The 35MTGI terminators and 35MSC stress cones are rated for class 2 and class 3 indoor service respectively. Optional mounting brackets, aerial lugs and equipment connectors are available as required.
600/200 ECS 600/200 ECSG1-2 600/200 ECSG2-2 600/200 ECSG3

CABLE ENTRANCE DETAIL INSULATION EPDM RUBBER MOLDED SHIELD CONDUCTIVE EPDM RUBBER

21MA

20MA

10 TL

10 TL

NONE REQUIRED

CONDUCTOR INSULATION EXTRUDED SHIELD CONCENTRIC NEUTRAL WIRES

CONDUCTOR INSULATION EXTRUDED SHIELD CONCENTRIC NEUTRAL WIRES

CONDUCTOR INSULATION EXTRUDED SHIELD

CONDUCTOR INSULATION EXTRUDED SHIELD

CONDUCTOR INSULATION EXTRUDED SHIELD

CONDUCTOR INSULATION EXTRUDED CONDUCTIVE JACKET

DRAIN WIRES OUTER JACKET

COPPER SHIELD OUTER JACKET OUTER JACKET DRAIN WIRES

OUTER JACKET

CABLE SHIELD TYPES

JACKETED CONCENTRIC NEUTRAL CABLE


10TL

CONCENTRIC NEUTRAL CABLE


20MA

DRAIN WIRE SHIELDED CABLE


21MA

COPPER TAPE SHIELDED CABLE

LEAD JACKETED CABLE

UNSHIELD CABLE

ECS

CABLE SHIELD ADAPTERS Cable Insulation Dia.


min. max.

JACKET SEALS 21MA (in.)


0.530 1.780

10TL (in.)
0.495 1.875

20MA (in.)
0.530 1.780

Jacket O.D.
min. max.

200ECS (in.)
0.80 1.50

600ECS (in.)
1.28 2.30

A30

w w w. tnb.c a

Elastimold

Cable Accessories

Shield Adapters, Sealing and Grounding

Illustration (not to scale)

Description
Cold Shrinkable Jacket Seal Cold Shrinkable Jacket Seal Metallic Tape Shield Adapter Wire Shield Adapter Shield Adapter Cold Shrinkable Seal w/ Copper Rod and Crimp Connector Cold Shrinkable Seal w/ Copper Rod and Crimp Connector Cold Shrinkable Seal w/ Copper Rod and Constant Force Spring Cold Shrinkable Seal w/ Copper Rod and Constant Force Spring Cold Shrinkable Seal w/ Copper Braid and Constant Force Spring Cold Shrinkable Seal w/ Copper Braid and Constant Force Spring

ELASTIMOLD Cat. No. 200ECS 600ECS 20MA-W


Use Table W14 for sizing -S -S

Suffix

Notes
N1, 3 N1, 4 N1, 2, 5, 6

-0MA

21MA-W
Use Table W14 for sizing -1MA N1, 2, 5, 6

N1. To order the kits as separate items, use the Cat. Nos shown in the table. Example: To order a cold shrinkable tube as a separate item, use the Cat. No. 200ECS. To order the kits as components of other items, add the sufx to the end of the Cat. No. Example: To order a cold shrinkable jacket seal as a component of an elbow kit, use the Cat. No. 166LR-A5200-S. N2. Only use this sufx with Cat. Nos that designate a W housing size. Sizing the main component will also size the sufx adapter. N3. Size range 0.80 in. to 1.50 in. jacket diameters. Maximum installed diameter is approx. 02 in. N4. Size range 1.28 in. to 2.30 in. jacket diameters. Maximum installed diameter is approx. 2.75 in. N5. Voltage rating equal to Elastimold product being used. N6. Copper rod size is no. 6 for sizes FA thru HA and no. 2 for sizes HAB thru JB. N7. Braid is equivalent to no. 6 copper rod for sizes FA thru HA and no. 2 copper rod for sizes HAB thru JB.

10TL-W
Use Table W15 for sizing -TL N1, 2

200ECSG1-2 600ECSG1-2

-SG1

N1 ,3 ,5, 6

-SG1

N1, 4, 5, 6

200ECSG2-2

-SG2

N1, 3, 5, 6

600ECSG2-2

-SG2

N1, 4, 5, 6

200ECSG3

-SG3

N1, 3, 5, 7

Table W15
USE FOR

Insulation (in.) Min.


0.495 0.525 0.575 0.625 0.675 0.725 0.775 0.825 0.875 0.930

600ECSG3

-SG3

N1, 4, 5, 7

10TL

Max.
0.585 0.635 0.585 0.735 0.785 0.835 0.885 0.935 0.985 1.040 1.115 1.175 1.240 1.305 1.375 1.395 1.520 1.595 1.640 1.685 1.875

Symbol for W
EB EF FA FAB FB FG GA GAB GB GH HA HAB HB HJ JA JAB JB KA KAB KB PB

Table W14
USE FOR

Insulation (in.) Min.


0.530 0.640 0.760 0.850 0.980 1.090 1.180 1.370 1.515

20MA 21MA

Max.
0.680 0.820 0.950 1.050 1.180 1.310 1.465 1.630 1.780

Symbol for W
E F G H J K L M N

0.980 1.040 1.095 1.160 1.220 1.285 1.355 1.485 1.530 1.575 1.755

w w w. tnb.c a

A31

Elastimold

Cable Accessories

Equipment Bushings
A complete line of Elastimold 200 A deepwell and 600 Series apparatus bushings are available for use on transformers, switchgear and other equipment applications. The bushings incorporate IEEE 386 standard interfaces (shown on page A5) and are constructed of molded epoxy with stainless steel anges for mounting by welding or gasketed clamp. K1601PCC Series bushings are provided with a molded epoxy ange for gasketed clamp mounting only. Bushings are available for use on AIR, OIL or SF6 insulated equipment. Units are rated for submersible, padmount, indoor, outdoor and other applications. Options include hold-down bail tabs and replaceable studs for 200 A deepwell bushings.

Illustration (not to scale)

Description
Short Shank Well with bail tabs and non-replaceable well stud Short Shank Well with bail tabs and with replaceable well stud Short Shank Well without bail tabs and non-replaceable well stud Short Shank Well without bail tabs and with replaceable well stud Long Shank Well with bail tabs and non-replaceable well stud Long Shank Well with bail tabs and with replaceable well stud Long Shank Well without bail tabs and non-replaceable well stud Long Shank Well without bail tabs and with replaceable well stud Epoxy Flange Well with replaceable well stud Well w/Insert (K1601PCC-R and 1601A4) Well w/Insert (K1601PCC-R and 2701A4) 200 A Deadbreak Bushing 200 A Deadbreak Bushing 200 A Deadbreak Bushing 600 A Short Shank Bushing w.o./stud 600 A Short Shank Bushing w.o./stud 600 A Cu Short Shank Bushing w.o./stud 600 A Long Shank Bushing w.o./stud 600 A Cu Long Shank Bushing w.o./stud 600 A Long Shank Bushing w.o./stud 600 A 12 in. Long Shank Bushing w.o./stud 600 A In-Air Long Shank Bushing w.o./stu 600 A Cu In-Air Long Shank Bush. w/stud Boot and Collars for K600T1 to use in air

Voltage Class
15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 35 kV 15/25 kV 15 kV 25 kV 15/25 kV 15/25 kV 15/25 kV 15/25 kV 35 kV 15/25 kV 15/25 kV 15/25 kV 35 kV 35 kV 15/25 kV 15/25 kV 15/25 kV

ELASTIMOLD Cat. No. K1601PC-S1 L1601PC-S1 K1601PC-S1-R L1601PC-S1-R K1601PC-S2 L1601PC-S2 K1601PC-S2-R L1601PC-S2-R K1601PC-T1 L1601PC-T1 K1601PC-T1-R L1601PC-T1-R K1601PC-T2 L1601PC-T2 K1601PC-T2-R L1601PC-T2-R K1601PCC-R 1601CABA4R 2701CABA4R K180S4 K180T4 K180C4 K650S1 750S1 K675S1 K650T1 K675T1 750T1 750L12 K650TBC K675TBC 600BC

Bushing Shank Length


2-3/4 in. 2-3/4 in. 2-3/4 in. 2-3/4 in. 9-1/4 in. 9-1/4 in. 9-1/4 in. 9-1/4 in.

Notes
N3, 7, 14 N1, 3, 7, 14 N3, 7, 14 N1, 3, 7, 14 N3, 7, 14 N1, 3, 7, 14 N3, 7, 14 N1, 3, 7, 14 N1,3, 7, 14 N1, 3, 8, 14 N1, 3, 9, 14 N3 ,10 ,13 N2, 5, 11, 14, 15 N2, 5, 12, 14, 16 N3, 5, 11, 14, 15 N2, 5, 11, 14, 15 N3, 5, 11, 14, 15 N2, 5, 12, 14, 16 N2, 5, 12, 14, 16 N2, 4, 11, 6, 14 N3, 5, 11, 6, 14 N6

2-3/4 in. 2-9/16 in. 7-11/32 in. 9-1/4 in. 2-15/16 in. 8-9/16 in. 8-9/16 in. 8-9/16 in. 12 in. 8-9/16 in.

N1. N2. N3. N4. N5. N6. N7. N8. N9.

Replacement stud available separately. Specify 1601RS. Equipped with standard aluminum conductor rod. Equipped with copper conductor rod. Includes 5/8-11 threaded stud at elbow end. Includes 5/8-11 threaded hole at elbow end. Provides increased creep and strike. Includes 1601PPC1 shipping cap. Includes 1601APC1 shipping cap. Includes 2701-41 shipping cap.

N10.Includes 180PPC shipping cap. N11.Includes 650PPC shipping cap. N12.Includes 750PPC1 shipping cap. N13.Parking stands for 200 A deadbreak applications are available as separate items. Specify 151PS. N14.Parking stands for 200 A loadbreak and 600 A deadbreak applications are available as separate items. Specify 160PS. N15.Aluminum stud available separately. Specify 650SA. N16.Aluminum stud available separately. Specify 750SA.

A32

w w w. tnb.c a

Elastimold

Cable Accessories

How to Specify Size-Sensitive Products

PN -WX-
Determines Size of Molded Rubber Part
W INSULATION DIAMETER

W
CABLE INSULATION DIAMETER

INSULATION DIAMETER SELECTION GUIDE Elastimold Elbows, cable joints and terminations are designed for application on XLP, EPR and other solid dielectric insulated power cables. These components are constructed of molded elastomer and rely on an interference t with the cable insulation diameter in order to maintain proper dielectric strength, creep path integrity and a water seal. Elastimold components are available in a wide range of sizes in order to accommodate a variety of cable insulation diameters. Selection of size-sensitive components requires determining the cable insulation diameter. This can be done in several ways: A. Refer to the cable manufacturers spec sheet for dimensions. B. Measure the cable. C. If the cable conforms to AEIC or ICEA standards and is: 1. 15 kV, 175 mil wall thickness, use the table on page A35. 2. 15 kV, 220 mil wall thickness, use the table on page A36. 3. 25 kV, 260 mil wall thickness, use the table on page A36. 4. 35 kV, 345 mil wall thickness, use the table on page A37. After the cable insulation diameter minimum and maximum has been determined: 1. Locate the W table indicated in the Cat. No. selection chart. 2. Complete the ordering information by selecting and inserting the symbol (given in the W table) into the Cat. No. Ordering Examples AEIC To complete the information required to order a K655LR-W0X elbow for use on standard AEIC 1000 kcmil compressed stranding aluminum 25 kV cable with .260 inch thick insulation wall: A. Determine that the insulation diameter (for AEIC cable in the table on pages A35-A37) is 1.645 1.770 in. B. For this elbow, the Cat. No. selection chart on page A13 indicates to use table W7 for elbow sizing and table X6 for connector sizing. C. From table W7 the symbol for W is N. D. From table X6 the symbol for X is 410. E. The completed Cat. No. therefore is K655LR-N0410.

ICEA To complete the information required to order a K655LR-W0X elbow for use on standard ICEA 1000 kcmil compressed stranding aluminum 25 kV cable with .260 inch thick insulation wall: A. Determine that the insulation diameter (for ICEA cable in the table on pages A35-A37) is 1.645 1.740 in. B. For this elbow, the Cat. No. selection chart on page A13 indicates to use table W7 for elbow sizing and table X6 for connector sizing. C. From table W7 the symbol for W is N. D. From table X6 the symbol for X is 410. E. The completed Cat. No. therefore is K655LR-N0410.

w w w. tnb.c a

A33

Elastimold

Cable Accessories

How to Specify Size-Sensitive Products

PN -WX-
Determines Crimp Connector Size
X CABLE CONDUCTOR

PN -WX-
SUFFIX CABLE SHIELD AND JACKET

X
CABLE CONDUCTOR

Determines Required Accessories (if any)


Cable Shield Adaptors Cable Grounding Kits Cable Jacket Seal

CONNECTOR SELECTION GUIDE Elastimold elbows, cable joints and terminations are furnished with crimp style cable connectors. As standard, these connectors are constructed with a tin-plated aluminum barrel lled with an oxide inhibitor. Most aluminum barrel connectors are universal and are designed for use on either aluminum or copper conductor cable. When specied, all copper crimp style connectors can be furnished. These connectors are only for use on copper conductor cable and are not for use with aluminum conductor cables. Bi-metallic connectors are constructed with a copper top and an aluminum barrel. Bi-metal connectors can be used on either aluminum or copper conductor cable and are furnished as standard with 200 A Loadbreak Elbows, 200 A Deadbreak Elbows, and PCT, 16 THG or MTG terminators with rod connectors. Aluminum connectors used in PCJ Cable Joints are rated as follows: Aluminum conductor to aluminum conductor, cable rated Aluminum conductor to copper conductor, cable rated equal to the aluminum cable Copper connectors used in PCJ Cable Joints are rated as follows: Copper conductor to copper conductor, cable rated Selection and ordering the proper crimp connector requires determining information relative to the cable conductor as follows: A. Conductor size in AWG or kcmil B. Conductor type (stranded, compressed, compact or solid) C. Conductor material (aluminum or copper) After the cable conductor information has been determined: 1. Locate the X table indicated in the Cat. No. selection chart. 2. Complete the ordering information by selecting and inserting the symbol (given in the X table) into the Cat. No. See the Ordering Example on page A33 for further information.
Reference Pages A30 and A31 for application, selection and ordering information.

A34

w w w. tnb.c a

Elastimold

Cable Accessories

AEIC and ICEA Cable Insulation Diameter


15 kV 100% 175 mil Insulation (0.175 in.) 15 kV 133% 220 mil Insulation (0.220 in.) 25 kV 100% 260 mil Insulation (0.260 in.) 35 kV 100% 345 mil Insulation (0.345 in.) AEIC CS8-06 Specication for Extruded Dielectric, Shielded Power Cable Rated 5 - 46 kV AEIC-Calulated Diameters - Solid and Compressed Stranding from Tables C-4 and C-6 and Compact Stranding from Tables C-5 and C-7
WALL

ANSI/ICEA S-94-649-2004 and S-97-682-2000 Standard for Concentric Neutral Cables and Utility Shielded Power Cables Rated 5 - 46 kV ICEA-Concentric Stranding Table C-3, Compressed Stranding Table C-4, Compact Stranding Table C-5 ICEA Abbreviated, for additional cables please refer to the standard.

W = Insulation Diameter (Conductor + 2 X Conductor Shield + 2 X wall)

15 kV Cable (100% level, 175 mil)


Aluminum and Copper Conductor Size Solid Conductor Industry Standard Diameter (in.) Over Insulation Min. #2 #1 1/0 2/0 3/0 4/0 250 350 500 750 1000
AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA 0.610 0.610 0.645 0.645 0.680 0.680

Stranded Conductor Diameter (in.) Over Insulation Min.


0.645 0.685 0.725 0.775 0.825 0.880 0.935 1.045 1.175 1.370 1.520

Compressed Conductor Diameter (in.) Over Insulation Min.


0.635 0.635 0.675 0.675 0.715 0.715 0.760 0.760 0.810 0.810 0.865 0.865 0.920 1.025 1.025 1.150 1.150 1.340 1.340 1.485 1.485

Compact Conductor Diameter (in.) Over Insulation Min.


0.620 0.620 0.655 0.655 0.690 0.690 0.730 0.730 0.775 0.775 0.830 0.830 0.880 0.980 0.980 1.100 1.100 1.280 1.280 1.430 1.430

Max.
0.700 0.695 0.730 0.725 0.770 0.760

Max.
0.730 0.770 0.810 0.855 0.905 0.965 1.020 1.130 1.260 1.455 1.610

Max.
0.725 0.720 0.765 0.760 0.805 0.800 0.850 0.845 0.900 0.895 0.955 0.950 1.005 1.115 1.110 1.245 1.235 1.440 1.425 1.590 1.575

Max.
0.710 0.705 0.740 0.735 0.775 0.775 0.815 0.815 0.865 0.860 0.915 0.910 0.965 1.065 1.065 1.185 1.185 1.370 1.365 1.520 1.515

ICEA NOTE: Diameters specied in the above table are different than specied by AEIC CS8-00. Consult your Regional Sales Ofce for proper selection of accessories. Diameters to be measured in accordance with 9.6.

w w w. tnb.c a

A35

Elastimold

Cable Accessories

AEIC and ICEA Cable Insulation Diameter


15 kV Cable (133% level, 220 mil)
Aluminum and Copper Conductor Size #2 #1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Industry Standard Solid Conductor Diameter (in.) Over Insulation Min.
AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA 0.700 0.700 0.735 0.735 0.770 0.770

Stranded Conductor Diameter (in.) Over Insulation Min.


0.735 0.775 0.815 0.865 0.915 0.970 1.025 1.135 1.265 1.460 1.610

Compressed Conductor Diameter (in.) Over Insulation Min.


0.725 0.725 0.765 0.765 0.805 0.805 0.850 0.850 0.900 0.900 0.955 0.955 1.010 1.115 1.115 1.240 1.240 1.430 1.430 1.575 1.575

Compact Conductor Diameter (in.) Over Insulation Min.


0.710 0.710 0.745 0.745 0.780 0.780 0.820 0.820 0.865 0.865 0.920 0.920 0.970 1.070 1.070 1.190 1.190 1.370 1.370 1.520 1.520

Max.
0.790 0.790 0.820 0.820 0.860 0.855

Max.
0.825 0.865 0.905 0.950 1.000 1.060 1.115 1.220 1.355 1.550 1.705

Max.
0.815 0.815 0.855 0.855 0.895 0.895 0.940 0.935 0.990 0.985 1.045 1.045 1.100 1.205 1.200 1.335 1.330 1.530 1.520 1.680 1.670

Max.
0.800 0.800 0.830 0.830 0.865 0.865 0.905 0.905 0.955 0.955 1.005 1.005 1.060 1.155 1.155 1.275 1.275 1.460 1.460 1.610 1.610

25 kV Cable (100% level, 260 mil)


Aluminum and Copper Conductor Size #1 1/0 2/0 3/0 4/0 250 350 500 750 1000 Industry Standard Solid Conductor Diameter (in.) Over Insulation Min.
AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA 0.805 0.805 0.840 0.840

Stranded Conductor Diameter (in.) Over Insulation Min.


0.845 0.885 0.935 0.985 1.040 1.095 1.205 1.335 1.530 1.680

Compressed Conductor Diameter (in.) Over Insulation Min.


0.835 0.835 0.875 0.875 0.920 0.920 0.970 0.970 1.025 1.025 1.080 1.185 1.185 1.310 1.310 1.500 1.500 1.645 1.645

Compact Conductor Diameter (in.) Over Insulation Min.


0.815 0.815 0.850 0.850 0.890 0.890 0.935 0.935 0.990 0.990 1.040 1.140 1.140 1.260 1.260 1.440 1.440 1.590 1.590

Max.
0.900 0.895 0.940 0.930

Max.
0.935 0.980 1.025 1.075 1.135 1.190 1.295 1.430 1.625 1.775

Max.
0.935 0.925 0.975 0.965 1.020 1.010 1.070 1.060 1.125 1.115 1.175 1.295 1.275 1.425 1.405 1.620 1.595 1.770 1.740

Max.
0.910 0.905 0.945 0.940 0.985 0.980 1.035 1.030 1.085 1.080 1.135 1.245 1.230 1.365 1.350 1.550 1.535 1.700 1.685

ICEA NOTE: Diameters specied in the above table are different than specied by AEIC CS8-00. Consult your Regional Sales Ofce for proper selection of accessories. Diameters to be measured in accordance with 9.6.

A36

w w w. tnb.c a

Elastimold

Cable Accessories

AEIC and ICEA Cable Insulation Diameter


35 kV Cable (100% level, 345 mil)
Solid Conductor Aluminum and Copper Conductor Size 1/0 2/0 3/0 4/0 250 350 500 750 1000 Diameter (in.) Over Insulation Min.
1.010 1.010

Stranded Conductor Diameter (in.) Over Insulation Min.


1.055 1.105 1.155 1.210 1.265 1.375 1.505 1.700

Compressed Conductor Diameter (in.) Over Insulation Min.


1.045 1.045 1.090 1.090 1.140 1.140 1.195 1.195 1.250 1.355 1.355 1.480 1.480 1.670 1.670 1.815 1.815

Compact Conductor Diameter (in.) Over Insulation Min.


1.020 1.020 1.060 1.060 1.105 1.105 1.160 1.160 1.210 1.310 1.310 1.430 1.430 1.610 1.610 1.760 1.760

Industry Standard
AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC ICEA AEIC

Max.
1.110 1.110

Max.
1.155 1.200 1.255 1.310 1.370 1.475 1.605 1.800 1.955

Max.
1.145 1.145 1.190 1.190 1.240 1.240 1.295 1.295 1.350 1.470 1.455 1.600 1.580 1.795 1.770 1.945 1.920

Max.
1.115 1.120 1.155 1.160 1.205 1.205 1.255 1.260 1.315 1.420 1.410 1.540 1.530 1.725 1.710 1.875 1.865

ICEA 1.850 ICEA NOTE: Diameters specied in the above table are different than specied by AEIC CS8-00. Consult your Regional Sales Ofce for proper selection of accessories. Diameters to be measured in accordance with 9.6.

w w w. tnb.c a

A37

Elastimold

Cable Accessories

AEIC and ICEA Cable Insulation Diameter

Conductor Diameters for Copper and Aluminum (Class B) Stranded, Compressed, Compact and Solid Cables

CABLE CONDUCTOR

Conductor Size AWG of kcmil

No. of Strands and their Nom. Strand Dia. (in.)


7 x 0.0242

Cross-sectional Area Square (in.)


0.0032 0.0051 0.0082 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.1054 0.1318 0.1662 0.1964 0.2749 0.3924 0.4712 0.5498 0.5890 0.6283 0.7069 0.7854 0.8639 0.9425 0.9818 1.021 1.100 1.178 1.257 1.335 1.374 1.414 1.492 1.571

mm2 Conversion
2.08 3.31 5.26 8.37 13.30 21.15 33.62 42.41 53.49 67.43 85.01 107.2 127 177 253 304 355 380 405 456 507 557 608 633 659 709 760 811 861 887 912 963 1010

Stranded Conductors (in.)


0.073 0.092 0.116 0.146 0.184 0.232 0.292 0.332 0.373 0.418 0.470 0.528 0.575 0.681 0.813 0.893 0.964 0.998 1.031 1.094 1.152 1.209 1.263 1.289 1.315 1.364 1.412 1.459 1.504 1.526 1.548 1.590 1.632

Compressed Conductors (in.)


0.283 0.322 0.362 0.405 0.456 0.512 0.558 0.661 0.789 0.866 0.935 0.968 1.000 1.061 1.117 1.173 1.225 1.250 1.276 1.323 1.370 1.415 1.459 1.480 1.502 1.542 1.583

Compact Conductors (in.)


0.268 0.299 0.336 0.376 0.423 0.475 0.520 0.616 0.736 0.813 0.877 0.908 0.938 0.999 1.060

Solid Conductors (in.)


0.064 0.081 0.102 0.129 0.162 0.204 0.258 0.289 0.325

14 12 10 8 6 4 2

7 x 0.0305 7 x 0.0385 7 x 0.0486 7 x 0.0612 7 x 0.0772 7 x 0.0974 19 x 0.0664 19 x 0.0745 19 x 0.0837 19 x 0.0940 19 x 0.1055 37 x 0.0822 37 x 0.0973 37 x 0.1162 61 x 0.0992 61 x 0.1071 61 x 0.1109 61 x 0.1145 61 x 0.1215 61 x 0.1280 91 x 0.1099

1 1/0 2/0 3/0 4/0

250 350 500 600 700 750 800 900 1000

1100 1200 1250 1300 1400 1500

91 x 0.1148 91 x 0.1172 91 x 0.1195 91 x 0.1240 91 x 0.1284 127 x 0.1122

1600 1700 1750 1800 1900 2000

127 x 0.1157 127 x 0.1174 127 x 0.1191 127 x 0.1223 127 x 0.1225

A38

w w w. tnb.c a

Elastimold

Cable Accessories

WX Size Tables
Table W1
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.575 0.635 0.805 0.890

Table W7 Symbol for W


A B C D USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.640 0.760 0.850 0.980 1.090 1.180 1.280 1.370 1.515 1.725

Max.
0.740 0.905 1.060 1.220

Max.
0.820 0.950 1.050 1.180 1.310 1.465 1.430 1.630 1.780 1.935

Symbol for W
F G H J K L LM M N P

151SP/SR 151LS/LY 165/166LR 165/166LRJS

Table W2
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.760 0.850 0.980 1.090

Max.
0.950 1.050 1.180 1.310

Symbol for W
G H J K

273RLR 274RLR

K656I/CY/CH K655/656LR K655/656SR 655/656LINK K655/656LINK 655/656ETP K655/656ETP 655/656RTP K655/656LRTP 655/656BI-LINK K655/656BI-LINK 655CA/CK/TCK

Table W8
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.640 0.760 0.850 0.980 1.090 1.180 1.280

Table W3
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.850 0.980 1.090 1.235

Max.
0.820 0.950 1.050 1.180 1.310 1.465 1.430 1.630 1.780 1.935 2.120

Symbol for W
F G H J K L LM M N P Q

Max.
1.050 1.180 1.310 1.465

Symbol for W
H J K L

375RLR 376RLR

15PCJ-1 15PCJ-2

Table W4
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.640 0.760 0.850 0.980 1.090

Symbol for W
F G H J K

1.370 1.515 1.725 1.900

Max.
0.820 0.950 1.050 1.180 1.310

156LR 167/168RLR 167LRT

Table W9
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min. Max.

Symbol for W

Table W5
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.665 0.740 0.880 1.090

Max.
0.895 0.950 1.100 1.310

Symbol for W
6689 7495 88110 K

167/168ELR 273/274ELR

25PCJ-1 25PCJ-2 755/756LR 755/756LINK 755/756ETP 755/756LRTP 755/756BI-LINK 755CA/CK/TCK

0.760
0.850 0.980 1.090 1.180 1.280 1.370 1.515 1.725

.950
1.050 1.180 1.310 1.465 1.430 1.630 1.780 1.935 2.120

G
H J K L LM M N P Q

Table W6
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.495 0.525 0.575 0.625 0.675 0.725 0.775 0.825 0.875

Max.
0.585 0.635 0.685 0.735 0.785 0.835 0.885 0.935 0.985

Symbol for W
EB EF FA FAB FB FG GA GAB GB

1.900

10EP 152EA 160CA*


(*EB-FA Only)

Please see page A28for Table W13 and page A31 for Tables W14 and W15.

w w w. tnb.c a

A39

Elastimold

Cable Accessories

WX Size Tables
Table W10
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.850 0.980 1.090 1.180 1.280 1.370 1.515 1.725 1.900

Max.
1.050 1.180 1.310 1.465 1.430 1.630 1.780 1.935 2.120

Symbol for W
H J K L LM M N P Q

Table X1
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


#4 #3 #2 #1 1/0 2/0 3/0 4/0 250

Symbol for X Strand./ Compr.


200 210 220 230 240 250 260 270

Compt./ Solid.
190 200 210 220 230 240 250 260 270

35PCJ-1 35PCJ-2

Table W11
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.495 0.525 0.575 0.625 0.675 0.725 0.775 0.825 0.875 0.930 0.980 1.040 1.095 1.160 1.220 1.285 1.355 1.485 1.530 1.575 1.665 1.755

Max.
0.585 0.635 0.685 0.735 0.785 0.835 0.885 0.935 0.985 1.040 1.115 1.175 1.240 1.305 1.375 1.395 1.520 1.595 1.640 1.685 1.785 1.875

Symbol for W
EB EF FA FAB FB FG GA GAB GB GH HA HAB HB HJ JA JAB JB KA KAB KB PA PB

35MSC 35MSCI

167/168ELR 273/274ELR 156LR 165/166LR 275/276LR 167LRT 167/168RLR 273/274RLR 00400 02500 02509 02702 02800 K151SP/SR K151LS/LY Table X2
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


1/0 2/0 3/0 4/0

Symbol for X Strand./ Compr.


240 250 260 270

Compt./ Solid.
230 240 250 260

375/376LR

Table X3
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


#6 #5 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 550 600 650 700 750 800 900 1000

Symbol for X Strand./ Compr.


5 4 3 2 1 0 10 20 30 40 250 300 350 400 450 500 550 600 650 750 750 800 900 1000

Compt./ Solid.
5 4 3 2 1 0 10 20 30 40 250 300 350 400 450 500 550 600 650 750 800 900

35MTG
NOTE: SEE PAGE A24 FOR DETAILED APPLICATION INFORMATION

Table W12
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.495 0.525 0.575 0.625 0.675 0.725 0.775 0.825 0.875 0.930 0.980

Max.
0.585 0.635 0.685 0.735 0.785 0.835 0.885 0.935 0.985 1.040 1.115

Symbol for W
EB EF FA FAB FB FG GA GAB GB GH HA

16THG 16THGS 16THGH

Table W16
USE FOR FOLLOWING PRODUCTS

Cable Insulation Diameter (in.) Min.


0.635 0.800 0.940 1.090

Max.
0.905 1.060 1.170 1.310

Symbol for W
B CC DD E

275/276LR 275/276LRS

A40

w w w. tnb.c a

Elastimold

Cable Accessories

WX Size Tables
Table X3A
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


400 450 500 550 600 650-700 750 800 1000

Symbol for X Strand./ Compr.


400 450 500 550 600 650 750 750 1000

Table X7
USE FOR FOLLOWING PRODUCTS

Compt./ Solid.
400 450 500 500 550 600 650

Conductor Size AWG or kcmil


#6 #5 #4 #3 #2 #1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1250

Symbol for X Strand./ Compr.


180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 380 380 390 400 410 440

Compt./ Solid.
180 190 200 210 220 230 240 250 260 270 280 290 300 310 310 320 330 340 350 360 380 380 400 420

35MTG
NOTE: SEE PAGE A24 FOR DETAILED APPLICATION INFORMATION

15PCJ1 25PCJ1 35PCJ1 15PCJ2 25PCJ2 35PCJ2

Table X4
USE FOR FOLLOWING PRODUCTS

Riser Conductor Size AWG Solid


#2 #1 1/0 2/0 3/0 4/0

Symbol for X
2 2 10 20 30 30

16THGS 16CAS

Table X6
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


#2 #1 1/0 2/0 3/0 4/0 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1250

Symbol for X Strand./ Compr.


220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 380 380 390 400 410 440

Compt./ Solid.
210 220 230 240 250 260 270 280 290 300 310 320 320 330 340 350 360 360 380 400 420

655/656LRTP K655/656LRTP 755/756LRTP K656I/Y/H K655/656LR 755/756LR K655/656SR 655/656LINK K655/656LINK 755/756LINK 655/656ETP K655/656ETP 755/756ETP 655/656BI-LINK K655/656BI-LINK 755BI-LINK 655CK 755CK 655TCK 03600 03602 03700 03702

Table X8
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


#6 #5 #4 #3 #2 #1 1/0 2/0 3/0 4/0

Symbol for X Strand./ Compr.


180 190 200 210 220 230 240 250 260 270

Compt./ Solid.
180 190 200 210 220 230 240 250 260

16THG 16TCA

Table X9
USE FOR FOLLOWING PRODUCTS

Conductor Size AWG or kcmil


#2 #1 1/0 2/0 3/0 4/0

Symbol for X Strand./ Compr.


220 230 240 250 260 270

Compt./ Solid.
210 220 230 240 250 260

PCT1 PCT2 01000 01010

w w w. tnb.c a

A41

Elastimold

Cable Accessories

Shrink-Fit Cable Joints


The Faster, Easier Way to Splice Medium-Voltage Cables in Direct-Burial, Underground or Overhead Applications.
Features Automatic core removal without ripcords or heat required for installation High-quality molded EPDM elastomer housing withstands the elements in harsh direct-burial, vault, manhole and overhead applications Four sizes support a wide range of cable and conductor sizes IEEE 404 rated shrink-t cable joint For over 50 years, the Elastimold brand has been associated with reliable, high-quality, pre-molded power cable splices that are designed to stand the rigors of the toughest utility applications. These products provide a cost-effective method to splice medium voltage cables using a push-on motion, and allowing cable neutrals to be solidly connected across the body of the splice without the use of any external braids. For those who prefer a more range-taking solution without the use of any physical force to install, the only options available have been cumbersome heat-shrink products that require multiple steps and the use of an open ame that may not result in uniform cable coverage, or over-designed cold-shrink products that either use awkward, entangling ripcords or expensive braid/jacket combinations that do not offer the ability to solidly connect neutrals across the splice. Now theres a faster and easier way to splice medium-voltage cables one that combines all of the convenience and exibility of a pre-molded splice, with the range-taking ease of installation offered in a cold- or heat-shrink product, but without the use of ripcords, heat or excessive force. Introducing, the NEW Elastimold Shrink-Fit Cable Joints from Thomas & Betts! The Shrink-Fit Cable Joints are made of the same molded EPDM elastomer as our other Elastimold cable accessories. This high-performance material offers more durability than silicone for direct burial. The joints feature a four-piece plastic support core, which is placed over the cable for installation of the splice. The support core is then easily removed with the supplied tool, allowing the elastomer joint to contour over the spliced cable for a uniform seal every time. Each Elastimold Shrink-Fit Cable Joint covers a wide range of cable sizes, features an insulated, semi-conductive shield and can be used with either a standard aluminum or optional copper compression splice. Optional kits are available for neutral, shielding and jacket restoration.

SFJ115
Shrink-Fit Cable Joint

SFJ415
Shrink-Fit Cable Joint

Disposable four-piece plastic support core

Typical Applications Direct Burial Handhole/Pullbox Manhole Vault Overhead

A42

w w w. tnb.c a

Elastimold

Cable Accessories

Shrink-Fit Cable Joints


Installation Sequence

Place Elastimold Shrink-Fit Joint in position.

Install connector.

Cut fastening straps.

Automatic core detachment begins.

Core pushes itself towards the ends of the Shrink-Fit Joint.

Core automatically detaches from second end.

Last core piece detaches.

Crimp grounding wires.

Ratings
Volt Class
Max. Phase-to-Ground Operating Voltage BIL Impulse Withstand (1.2 x 50sec. wave) Corona Extinction Level @ 3.0 pC Sensitivity DC Withstand during Installation DC Withstand up to 5 yrs.* XLPE Insulation DC Withstand up to 5 yrs.* EPR Insulation AC Withstand at 60 Hz for 60 sec. Continuous Current Short-Term Current *Reference: AEC CS6 and CS8, section L.2.

15 kV
8.7 kV 110 kV 13 kV 56 kV 18 kV 45 kV 35 kV

25/28 kV
14.4 kV 150 kV 22 kV 80 kV 25 kV 64 kV 52 kV

35 kV
20.2 kV 200 kV 30 kV 100 kV 31 kV 80 kV 69 kV

Dimensions
Cable Joint Size
1 2 3 4

Insulation Range
L (in.)
11 16 18 18

D (in.)
1.85 2.12 2.4 2.6

Cable Joint Size


1 2 3 4

Min. (in.)
0.620 0.815 0.935 1.210

Max. (in.)
0.780 0.920 1.190 1.760

Min. (mm)
15.75 20.70 23.75 30.73

Max. (mm)
19.81 23.37 30.23 44.70

Equal to that of cable Equal to that of cable up to 35 kA

How to construct a catalogue number for an Elastimold Shrink-Fit Cable Joint:


S F J

Size Code 15 kV 1 2 3 4 1 2 3 4 25/28 kV 2 3 4 35 kV 3 4

Cable Joint Size Wall Min. Max. Thickness Conductor Conductor (mils) Size* Size*
#2 AWG 4/0 AWG 350 kcmil 700 kcmil #2 AWG 2/0 AWG 250 kcmil 600 kcmil #1 AWG 3/0 AWG 500 kcmil 1/0 AWG 250 kcmil 3/0 AWG 250 kcmil 600 kcmil 1000 kcmil 1/0 AWG 4/0 AWG 500 kcmil 1000 kcmil 2/0 AWG 350 kcmil 1000 kcmil 4/0 AWG 1000 kcmil

Voltage Rating 15 25 35
11 kV 25/28 kV 35 kV

Connector Type C
Crimp

Conductor 1 2
Aluminum Copper

X Code 210 220 230 240 250 260 270 280 290 300 310 330 360 380 400 410

Connector Size Conductor Size (AWG or Kcmil) Stranded/ Solid/ Compressed Compact
#2 AWG #1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 650 kcmil 750 kcmil 900 kcmil 1000 kcmil #2 AWG #1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 650 kcmil 750 kcmil 900 kcmil 1000 kcmil

175

220

260

345

* Based on the minimum compact AEIC and ICEA cable insulation diameters. Note: Each kit contains shrink-t housing on removable core, splice connector, lubricant, installation instructions and crimp chart. For ordering information on optional neutral, shielding and jacket restoration kits, please contact your Regional Sales Ofce.

w w w. tnb.c a

A43

Elastimold

Cable Accessories

Ranger2 Terminations
Overview
Elastimold Ranger2TM Terminations are specically designed for use on 15 thru 35 kV, XLP or EPR insulated, underground power distribution cable systems. Units allow proper transition and connection of the underground cable system to bare overhead conductors and live front equipment. Applications include indoor, outdoor, riser pole, padmounted and other live front or weather exposed installations. Designs use advanced silicone rubber insulating materials to provide necessary creep, strike, weather sealing and contamination resistance, assuring proper performance in the most severe conditions. The grey color blends in with outdoor environments. Ranger2 Terminations support a wide application range with only three sizes required to cover #2 AWG through 1250 kcmil cables. The single-piece 15 kV and 25 kV shrink-t design makes installation effortless, and the two-piece 35 kV design facilitates easier core removal. Simply position the terminator on the prepared cable and remove the center core. Units are compact and lightweight, allowing installation in restricted spaces and free-hanging applications. Silicone Polymer Housings The R2T and R2IT terminations are manufactured using an optimized weather-resistant silicone formulation. The housing offers superior cable sealing and voltage withstand characteristics. Elastimold terminations meet or exceed all requirements of IEEE Standard 48 for Class 1 outdoor or Class 2 indoor terminations. Unit tests include voltage withstand wet and dry, before and after load cycling on units installed on maximum conductor sized cable. Stress Relief The R2T and R2IT terminations provide electric stress control for the cable by means of a exible tube with a high permittivity dielectric constant. The stress-relief tube is preassembled on the core under the polymer housing. As the core is removed, the stress-relief tube and housing shrink onto the cable at the same time, in exactly the right position. No secondary operations are required during installation. The electrical elds are refracted through the high dielectric constant tube and housing as shown. Installation Standard cable preparation techniques are used for all R2T, Elastimold Ranger2 Outdoor Terminations, and R2IT, Elastimold Ranger2 Indoor Terminations. The Elastimold shrink-t terminations are assembled on a removable core. After the termination is placed onto the prepared cable, the core is removed by pulling on the end. The housing then collapses onto the prepared cable. Memory of the material provides the interface solid dielectric and sealing properties required to meet the electrical ratings and prevent the ingress of moisture. Kit Contents Every R2T and R2IT comes complete with housing and stress tube preassembled on the core, ready for installation. Easy-to-read installation instructions will take you from cable preparation through installation. All kits include a tube of silicone grease, two plastic gloves and one strip of self-fusing silicone tape. Outdoor kits also include mastic for sealing. Metallic Tape (M) kits include a grounding adapter for Tape Shield, Wire Shield and UniShield cables. LC Shield (L) kits include a high ampacity grounding adapter for Longitudinally Corrugated Shield, Tape Shield and Wire over Tape Shield cables. Stress Relief Voltage Stress

1 2 4
Terminal Housing Cable Insulation

1 2

Terminal Stress Relief 3 Conductor

Cable Semi-Conductor

A44

w w w. tnb.c a

Elastimold

Cable Accessories

Ranger2 Terminations
Overview
Grey Molded Silicone Insulator Connector Built-In Cable Entrance Seal Cable Jacket

Silicone Tape Seal

Cable Insulation

Cable Shield Hi-K Voltage Stress-Control Tube

Mastic Concentric Neutral Wires

Typical Installation on Jacketed Concentric Neutral (JCN) Cable


Features
Silicone Polymer Housing Shrink-Fit Housing Three Different Shed Designs for Superior Weathering Wide Range Integral Hi-K Voltage Stress-Control Tube Pull-Down Tabs for Easy Installation of Built-In Jacket Seal Lightweight, Compact Design Dark Grey Molded Silicone Insulator Optional Connectors Optional Cable and Support Bracket

Benefits/Descriptions
Superior memory and weathering characteristics Uses common installation procedures and cable preparation dimensions. Field-removable center core allows for easy installation. Four sheds for 15 kV outdoor model Six sheds for 25/28 kV outdoor model Eight sheds for 35 kV outdoor model Three sizes cover entire cable range from #2 AWG to 1250 kcmil. Units accommodate popular XLP and EPR cable types and shield constructions. Provides uniform voltage grading over the length of the termination. Eliminates damaging voltage stress concentrations at the cable insulation shield edge. Thick wall construction securely maintains critical interface pressure for consistent long term reliability and performance. Accommodates CN, JCN, Tape, Wire or LC shielded cable construction Installs in restricted spaces. Permits application where free hanging is desired. Blends well into outdoor environments. Utilizes specially formulated silicone materials with improved UV stability, track, erosion and weather resistance. Outdoor styles feature large diameter, multi-shed profile with extra creep and strike for enhanced performance under the worst environmental conditions. Connector with copper stem, one-hole and two-hole spade connector Three sizes, ranging from 0.80 in. 1.95 in. O.D.

Certied
Elastimold Ranger2 Terminations have been designed and tested per applicable portions of ANSI, IEEE, AEIC, ICEA and other industry standards.
IEEE 48 ANSI C119.4 AEIC CS8-06 and ANSI/ICEA S-94-649-2004 and S-97-682-2000 Standard for indoor and outdoor cable terminations Standard for cable connectors for aluminum and copper conductors Standards for XLP and EPR insulated cables

Application Information
IEEE 48 Classification Ambient Temperature Range Power System Frequency Altitude Range Mounting Outdoor = Class 1A, Indoor = Class 2 -30C to 65C 48 to 62 Hz 3 300 ft. max. Free hanging or optional bracket

Ratings
Ratings
Termination Catalogue Series Sizes Available* Voltage Rating (kV) Max. Design Voltage to Ground (kV) Corona Extinction Voltage (kV) (3 p.c.) (Partial Discharge)

Indoor
R2IT15 1, 2, 4 15 9.5 13 110 50 36 75

Outdoor
R2T15 1, 2, 4 15 9.5 13 110 45 50 35 75

Outdoor
R2T28 2, 4 25/28 16 22 150 60 65 55 105

Outdoor
R2T35 2, 4 35 22 30 200 80 90 75 140

Dimensions
Dimensions Indoor Outdoor
R2T15 1, 2, 4 15 4 11.6 (295) 15.0 (381)

Outdoor
R2T28 2, 4 25/28 6 14.5 (368) 22.8 (579)

Outdoor
R2T35 2, 4 35 8 16.8 (427) 30.0 (762)

Insulation Withstand Voltage:


Lightning Impulse (BIL Dry 110 Withstand) (kV Crest) 10 Sec. Wet (60 Hz) (kV) 1 Minute Dry (60 Hz) (kV) 5 Hour Dry (60 Hz) (kV) DC Withstand 15 Min. Dry (kV) * See page A46 for cable insulation diameter ranges.

Termination Catalogue Series R2IT15 1, 2, 4 Sizes Available* 15 Voltage Rating (kV) 0 Number of Sheds Minimum Strike Distance in. (mm) 8.4 (213) Creepage Distance in. (mm) * See page A46 for cable insulation diameter ranges.

w w w. tnb.c a

A45

Elastimold

Cable Accessories

Ranger2 Terminations Base Catalogue Numbers


The R2T and R2IT termination design couples shrink-t technology and Elastimolds pull-down jacket seal feature to provide a termination line that covers the widest range of applications with the fewest number of models. Three sizes cover 0.64 in. (16 mm) to 2.10 in. (53 mm) insulation diameter cables (#2 AWG through 1250 kcmil). The R2T housings are designed for maximum performance in all eld conditions with superior creepage and strike distances for longterm service. Insulating silicone sleeves are also available when more creepage is required or when wildlife protection is needed to insulate the connectors. Contact your Thomas & Betts Sales Representative for further information.
Cable Range (Insulation Diameter) (in.)
0.64 to 1.12 15 Indoor 0.84 to 1.38 1.30 to 2.10 0.64 to 1.12 15 Outdoor 0.84 to 1.38 1.30 to 2.10 0.84 to 1.38 25/28 Outdoor 1.30 to 2.10 33.0 to 53.3

TM

Cat. No. Concentric Neutral and Jacketed Concentric Neutral Cable R2IT15J1 R2IT15J2 R2IT15J4 R2T15J1 R2T15J2 R2T15J4 Tape Shield, Wire Shield and UniShield Cable R2IT15M1 R2IT15M2 R2IT15M4 R2T15M1 R2T15M2 R2T15M4 LC Shield, Wire over Tape Shield and Tape Shield Cable R2IT15L1 R2IT15L2 R2IT15L4 R2T15L1 R2T15L2 R2T15L4

kV Class

Type

mm
16.3 to 28.4 21.3 to 35.1 33.0 to 53.3 16.3 to 28.4 21.3 to 35.1 33.0 to 53.3 20.3 to 35.1

R2T28J2

R2T28M2

R2T28L2

R2T28J4

R2T28M4

R2T28L4

0.84 to 1.38 35 Outdoor 1.30 to 2.10

20.3 to 35.1

R2T35J2

R2T35M2

R2T35L2

33.0 to 53.3

R2T35J4

R2T35M4

R2T35L4

A46

w w w. tnb.c a

Elastimold

Cable Accessories

Ranger2 Terminations Accessories Connector Options


Type Material Conductor Conductor Size Connector Prefix*

TM

Aluminum or Copper Stem Compression Connector Aluminum Aluminum Only #2 through 4/0 (34107 mm2)

T0

T1

One-Hole Spade Connector

Tinned Aluminum

Aluminum or Copper

#2 through 500 kcmil (34253 mm2)

H0

Two-Hole Spade Connector

Tinned Aluminum

Aluminum or Copper

#2 through 1250 kcmil (34633 mm2)

N0

* See page A48 for conductor code.

Cable Support Bracket Options


Ranger2 Terminations are compact, lightweight and frequently allow use of free-hanging mounting methods. Optional cable support brackets are available if required. Optional Cable Support Brackets
Type Cable Range (in.) (Overall O.D.) Cat. No. Suffix No.

Single Clamp

0.801.25 (2032 mm)

JB-1

B1

Single Clamp

1.101.50 (2838 mm)

JB-2

B2

Double Clamp

1.451.95 (3750 mm)

JB-3

B3

w w w. tnb.c a

A47

Elastimold

Cable Accessories

Ranger2 Terminations Ordering Information


How to construct a catalogue number for Ranger2 Terminations:
Housing Only

TM

Add a connector

Add a cable support bracket

XXX
Step 1. Select the Termination Housing: A. Select Outdoor or Indoor housing style B. Select applicable voltage class C. Select neutral/ shield type D. Select the size based on the cable insulation diameter*
Type Outdoor Indoor

XX

XX XXX

XX
Cable Mounting Bracket

R2T R2IT

B1 B2 B2

0.801.25 (2032) 1.101.50 (2838) 1.451.95 (3750)

kV Code 15 kV 25/28 kV 35 kV
15 28 35

Conductor Code 210 220 230 240 250 260 270 280 290 300 310 330 360 380 400 410 440

Stranded or Compressed
#2 #1 1/0 2/0 3/0 4/0 250 300 350 400 500 650 750 900 1000 1250

Compact or Solid
#2 #1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 750 900 1000

Cable Type J
Concentric Neutral/Jacketed Concentric Neutral Tape Shield/Wire Shield/ UniShield LC Shield Tape Shield/Wire Over Tape Shield

Connector Option
Step 2. Select the Connector: E. Select desired connector F. Select connector code based on conductor size and conductor type

M L

Insulation Range 1 2 4
0.64 in.1.12 in. (16 mm28 mm) (15 kV only) 0.84 in.1.38 (21 mm35 mm) (15 kV, 25 kV, 35 kV) 1.30 in.2.10 in. (33 mm53 mm) 15 kV, 25 kV, 35 kV)

Cable Support Bracket Option


Step 3. Select the Cable Support Bracket: G. Select cable support bracket based on the overall O.D. of the cable
T0 T1 H0 N0

Connector Type
Universal Aluminum Barrel for AL or CU conductor w/Copper Wire Lead #24/0 Aluminum Barrel for AL conductor only w/Copper Wire Lead #24/0 Aluminum 1-Hole Spade #2750 kcmil Aluminum 2-Hole Spade #21250 kcmil

Connector only
* To help in selecting the proper terminator, ICEA and AEIC standard dimensions for XLP and EPR cables are shown in pages A35 to A37.

A48

w w w. tnb.c a

Elastimold

Cable Accessories

Ranger2 Terminations Installation


Typical Installation of Elastimold Shrink-Fit Terminations (R2T Outdoor and R2IT Indoor)

TM

1
1.

5
5. Apply a liberal bead of silicone lubricant to the semi-conshield step.

6
6. Pull the loose end of the core cord until the core is even with the end of the termination housing.

7
7. Position the terminator onto the cable.

Train the cable into position and cut to length. Using standard practices, cut back the cable jacket, metallic shield, semi-conductive shield and cable insulation, exposing the conductor. Finish preparing the metallic shield. For concentric neutral or jacketed concentric neutral cables, bend back the neutral wires and seal with mastic strips and vinyl tape. For metallic tape, drain wire, UniShield or LC Shield cables: install the ground braid using the constant force spring and seal with mastic strips and vinyl tape.

2.

3.

Clean the exposed conductor, install and crimp the connector. Use mastic and vinyl tape to ll any gap or step between the connector and the cable insulation. Clean the cable.

4.

8
8. Shrink into place by unwinding the removable core.

9
9. Apply silicone lubricant to skirt and mastic area.

10
10.Fold down the skirt over the mastic to seal the cable entrance.

11
11.Seal the top of the terminator at the connector area with silicone tape.

12
12.Attach the neutral wires or optional ground braid to the system ground per local code. Install the optional cable support bracket if required.

w w w. tnb.c a

A49

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Series 1548 Overhead FCIs
Reliable fault indication for single-phase overhead applications
FCIs with Radio Transmitters

Series 1548 radio FCIs can signal faults to handheld receivers, radio receivers and the SmartLink Series 5000 cellular remote terminal unit (RTU) systems integrated with SCADA and web-based reporting systems. Status, alarms and other event notications can be integrated into SCADA systems, as well as sent to customer-designated personnel via e-mail, pager or text message. Having precise fault information reduces outage duration, improves system reliability and lowers operation costs.
Trip Logic Adaptive or xed current trip with inrush restraint logic. Adaptive trip logic eliminates the need for trip-rating selection or revision with changing load. Reset Logic Automatic reset with return of load current and/or time reset of permanent fault indication. Automatic time reset for temporary fault indication. Manual trip test and reset capabilities using hotstick-mountable trip/reset tool. Fault Indication Visual indication choices of LED, 5-LED Array, Flag or Strobe Light. Highly viewable 360 indication (Strobe or LED). Radio fault reporting capability also available. Mounting Hotstick mounting with automatic torque limiting. Replaceable Lithium Battery Offers 10-year, maintenance-free service life. (Note that Flag model has non-replaceable battery). Supports a Wide Range of Conductors Mounts on conductors with diameters from 0.14 in. to 1.20 in. (3.56 mm to 30.48 mm). Optional Features Available Options include temporary/permanent fault indication, instantaneous recloser coordination feature and backfeed restraint using a delay-trip scheme (requires protective device to pass two cycles minimum of fault current before closing).
Swipe Here

Technical Specications Fault Registration: Red, high-intensity LED with choice of hard-wired or fiber optic cable remote mounting or audible intermittent beeper signal Trip current: Factory preset to customer specifications within range of 50 A and 100 A to 1,500 A in 100 A increments Trip Current Accuracy: 10% of trip rating (calibrated using 1 in. dia. cable for 400 A trip or less or 2.0 in. dia. cable for greater than 400 A trip) Trip Response Speed: Consult trip curves (coordinated to properly applied link, expulsion, power and current-limiting fuses) Reset Time: 4 hrs., 2 hrs., 1 hr., manual trip/reset standard Overload Capacity: Capable of withstanding 25,000 A for 10 cycles Continuous Load Current: Rated at 1,000 A max. Temperature Range: -40C to 85C Submersibility: Tested to 30 ft. Operating Battery Life: 800 hrs. for LED indication, 160 hrs. for audible indication, both with 10-yr. life at 20C Battery: Long-life lithium cell Cable Ranges: 0.63 in. (16 mm) to 1.58 in. (40 mm); 1.58 in. (40 mm) to 2.36 in. (60 mm); 2.36 in. (60 mm) to 3.55 in. (90 mm) Remote Fiber Optic Options: Permanent or removable (10 ft. standard, 30 ft. max.) Certifications: Complies with ANSI/IEEEE 495-1986

Trip/Reset Tool AT2186-10 Manual trip/reset test for both permanent and temporary fault indication using hotstick-mountable reset tool.

A50

w w w. tnb.c a

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Underground/Padmount Faulted Circuit Indicators Series 1541/42/43 Automatic Time Reset FCIs
The following diagram shows how to construct a catalogue number for Series 1541/1542/1543 FCIs. Not all combinations are possible; consult your Regional Sales Ofce for ordering assistance. Indicates eld that must be lled in to complete order.
NOTE: Availability of selected conguration will be veried at quotation time.

Basic Model Cable Clamp Size 1541 1542 1543


Single-Phase Two-Phase Three-Phase

S M L

Small 0.63 in.1.58 in. cable dia. Medium 1.58 in.2.36 in. cable dia. Large 2.36 in.3.55 in. cable dia.

Inrush Restraint F N
Inrush time overcurrent (dual curve) standard Non-inrush delay

Display Options R Indication/Battery Options H R A


LED, non-replaceable battery, hotstick mounted LED, replaceable battery, hotstick mounted Audible alarm indication, replaceable battery, hotstick mounted Remote LED Integral LED or audible alarm (always selected with code A or H under Indication/Battery Options) Remote LED, fiber optic cable Remote LED, removable fiber optic cable

T E F

Length of Remote LED Cable N Trip Point 0.5 0.6 1 2 3 4 4.5 5 6 8 10 12 15


50 A 60 A 100 A 200 A 300 A 400 A 450 A 500 A 600 A 800 A 1000 A 1200 A 1500 A Not applicable when code T is selected under Display Options Remote LED, removable fiber optic cable

10

Reset Time Delay After Fault Occurrence A B C


4-hr. automatic reset time delay 2-hr. automatic reset time delay 1-hr. automatic reset time delay

w w w. tnb.c a

A51

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Test Point Fault Indicators TPM Series
Mount directly to any IEEE 386 standard capacitive test point. Test Point Mounted Fault Indicators consist of a solid-state current sensor connected to a faulted-circuit display, providing a clear visual means for quickly locating faulted cables and equipment on underground distribution systems. Designs incorporate advanced circuit logic and monitoring system protection operation to prevent the indicator from tripping unless an overcurrent condition is followed by a loss of system voltage. Trip and reset operations are automatic, and for versatility and convenience, the same indicator may be used for 5 kV thru 35 kV applications.

AccQTrip Logic Circuitry Prevents false indications in voltage-reset units due to inrush currents, cold load pickup and overloading. High/Low Trip-Setting Selection Requires no minimum load current and no load surveys. Internal Magnetic Shielding Prevents adjacent phase effects. 1 msec. Trip Response Coordinates with current-limiting fuses, as well as other protection devices. Magnetically Latched Flag Prevents ag indication from changing state due to shock or vibration. Test Point Mounting Mounts directly to 200 and 600 A elbows, splices and other cable accessories equipped with IEEE 386 standard capacitive test points. Built-In Pulling Eye Enables safe, easy hotstick installation and removal from test points. Durable Construction Enclosed in a rugged, yet lightweight and compact, sealed, impact- and corrosion resistant Lexan housing with EPDM molded-rubber test point mounting boot.

Time/current Curve for TPMVF, VL, VOL,TL

Trip Point VS. Cable Diameter

Basic Operation A faulted circuit produces an associated magnetic eld, which closes a reed switch in the indicator, resulting in a tripped display. Trip response occurs in .001 seconds (1 msec.), allowing the fault indicator to properly coordinate with all types of circuit-protection schemes, including current limiting fuses. To eliminate confusing false trips, voltage-reset indicators are equipped with inrush, backfeed, overload and cold-load pick-up restraint circuitry. Current sensors feature internal shielding to prevent inadvertent tripping when located in close proximity to adjacent phases, such as in junction-mounted applications.

A52

w w w. tnb.c a

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Test Point Fault Indicators TPM Series
Test Point

Pulling Eye for Hotstick Installation and Removal Faulted Circuit Display

3-7/8 (98) 1-1/8 (29) 1-3/8 (35)

2-1/4 (57)

3-1/4 (83)

Test Point Mounting Plug

(all dimensions (in.) with millimeter equivalents in parentheses)

Cat. No. TPMTL-[ _ ] TPMVF-[ _ ] TPMVL-[ _ ] TPMVOL-[ _ ] Cat. No. Suffix -LT -HT

Description
Time Reset with LED Display (auto-resets to normal after 4 hrs.; may also be manually reset using an FTT test tool) Voltage Reset with Flag Display (auto-resets to normal after system voltage restoration; reset requires 5 kV min. voltage with time required for reset proportional to system voltage) Voltage Reset with LED Display (auto-resets to normal after system voltage restoration; reset requires 5 kV min. voltage with time required for reset proportional to system voltage) Voltage Operated, Time Reset, LED Display (auto-resets after 4 hrs.; longer time resets available upon request)

Description
For 200 A. All fused taps use LOW trip rating. For URD applications, use LOW trip rating. For 600 A. For URD applications, use HIGH trip rating.

NOTE: For overhead bulk feeder applications, use HIGH or LOW trip ratings (whichever is greater than the minimum pickup setting of the related protection device). AccQTrip and AccQClamp are trademarks of Quality Indications, Inc.

w w w. tnb.c a

A53

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Overhead Line Fault Indicators OLM Series
Locate faulted circuits and equipment on overhead distribution systems Self-powered Fisher Pierce Series OLM Overhead Line Fault Indicators consist of a solid-state current sensor connected to a faulted circuit display. Advanced circuit logic monitors system protection operation and prevents indicator tripping unless an overcurrent condition is followed by a loss of system voltage. Trip and reset operations are automatic, and the same indicator may be used for 5 kV thru 35 kV line-to-ground applications. These compact, sealed and corrosion-resistant units are designed for direct installation to an overhead line using a spring-loaded, over-center toggle clamp. Equipped with retainer pads to prevent slip and twist, the clamp positions the conductor at a constant distance from the current sensor, maintaining trip accuracy over the entire conductor diameter range of .4 in. to 2.2 in. Basic Operation A faulted circuit produces a magnetic eld, which closes a reed switch in the indicator and causes a tripped display. A trip response time of .001 seconds enables the indicator to properly coordinate with all circuit-protection schemes, including current-limiting fuses. To eliminate confusing false trips, indicators feature inrush, overload and cold-load pickup restraint circuitry as standard. Internal shielding of current sensors prevents inadvertent tripping when in close proximity to adjacent phases.
3-7/8 (98) 1-1/8 (29) 1-1/8 (29)

AccQTrip Logic Circuitry In voltage reset units prevents false indications due to inrush currents, cold load pickup and overloading. AccQClamp Mounting Provision Universal one-size-tsall design automatically adjusts. High/Low Trip Setting Selection No minimum load current requirement and no load surveys needed.

4-1/4 (108)

4-1/4 (108) Open 2-1/4 (57)

Trip Response of .001 Seconds Coordinates with currentlimiting fuses, as well as other protection devices. Internal Magnetic Shielding Prevents adjacent phase effects.
5-5/8 (143) open

Magnetically Latched Flag Indication Flag indication will not change states due to shock or vibration. Lightweight Enclosure Compact and sealed.

2-3/8 (60) Open

Time/current Curve for OLMVF, VL, VOL,TL

Trip Point VS. Cable Diameter

A54

w w w. tnb.c a

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Overhead Line Fault Indicators OLM Series
Cat. No. OLMTL OLMVF OLMVL OLMVOL Cat. No. Suffix LT HT Description
Time Reset with LED Display Voltage Reset with Flag Display Voltage Reset with LED Display Voltage Operated, Time Reset, LED Display

Reset Operation
Indicator auto-resets to normal after a four hour time duration. indicator may also be manually reset using an FTT test tool. Indicator auto-resets to normal after system voltage restoration. Reset requires 5 kV minimum voltage to operate. Reset operation time is proportional to system voltage. Example: at 15 kV, reset occurs 30 seconds after system voltage restoration. Indicator auto-resets after a four hour time duration. Longer time resets are available upon request.

Description
All fused taps use LOW trip rating. For 600 A Overhead applications, use LOW trip rating. For 600 A Overhead applications, use HIGH trip rating.

Accessories for Series TPM, VCM and OLM Fault Indicators


FO-Cable06 Remote Fiber Optic Indicator for Underground Fault Indicators with LED Display can be extended to the outside of enclosures and/or vaults for ease of access and fault location. All the hardware for mounting the remote end of the cable to the enclosure is included. The display has a large reective bolt to enhance visibility. FTT (Field Test Tool) Permits eld testing and reset of fault indicators and provides assurance that the indicator is properly functioning. The test tool is lightweight, portable and incorporates a built-in magnet which operates the indicator trip and reset functions. The unit is equipped with provisions for hotstick handling and operation.

Cat. No. FTT FO-CABLE06

Description
Field Test Tool, overall dimensions 2 in. wide x 3 in. high x 58 in. deep Remote Fiber Optic Indicator for UFI

w w w. tnb.c a

A55

Fisher Pierce

Cable Accessories

Faulted Circuit Indicators


Test Point V2 Voltage Indicator
Easy way to visually determine the energized status of underground distribution circuits The V2 Voltage Indicator consists of a self-powered voltage sensor connected to a neon light that ashes when energized. Simply plug it into any IEEE 836 standard capacitive test point to determine the energized status of underground distribution circuits. Because the ash rate is proportional to the phase-to-phase system voltage, as indicated in the chart, one V2 model supports a wide range of applications from 5 to 35 kV.

Test Point

Test Point Mounting Plug

Flashing Neon Light Indicates Energized Status

EPDM Molded Rubber Housing


3-1/4 (44) 2 (51) 3/8 (10)

Pulling Eye for Hotstick Installation and Removal

1-3/4 (44)

(all dimensions in inches with millimeter equivalents in parentheses)

Voltage 5 kv 10 kv 15 kv 20 kv

Flash Rate
20 40 70 100

Voltage 25 kV 30 kV 35 kV

Flash Rate
140 160 180

A56

w w w. tnb.c a

Elastimold

Cable Accessories

Faulted Circuit Indicators


Test Point V2 Voltage Indicator (contd)
Wide Application Range Single model supports applications from 5 kV to 35 kV. Easy to Read Flash rate per minute indicates system voltage (see chart). IEEE 386 Test Interface Mounts to 200 and 600 A elbows, splices and other cable accessory components equipped with IEEE 386 capacitive test points. Rugged Construction Molded EPDM-rubber housing for shielded, sealed and corrosion-resistant construction. Built-In Pulling Eye Enables safe, easy hotstick installation and removal from test point. 20-Year Neon Bulb Yields long, maintenance-free service life. Testable with V2-TB Easily tested for conrmation of proper operation with the V2-TB voltage indicator test box.

V2-TB Test Box for easy eld testing of V2 Voltage Indicators If the V2 Neon Voltage Indicator indicates a power failure in an underground distribution circuit, youll want to ensure that its actually the circuit thats failed and not the V2 itself. For fast, simple assurance, eld test the V2 with the compact, portable V2-TB Voltage Indicator Test Box, powered by replaceable C batteries.
Cat. No. V2 V2-TB Description
Voltage Indicator with Neon Display Voltage Indicator Test Box

w w w. tnb.c a

A57

Elastimold

Cable Accessories

Underground Distribution Switchgear


Molded Vacuum Switches and Fault Interrupters
MVS Molded Vaccum Switches Spring-energy, load-switching devices that make, carry and interrupt load currents through 600 A on 5 to 38 kV distribution systems. MVS Molded Vacuum Switches include molded-in elbow connection interfaces and spring-energy mechanisms. Available in both single- and three-phase models, units are manually operated with a hotstick. Motor operator, SCADA and auto-transfer control options are available.
EPDM Molded Rubber Insulation MVSs are fully sealed and submersible. Vacuum Switching and Vacuum Interruption Components are maintenance-free and require no gas or oil. Compact and Lightweight Small footprint enables MVSs to t in tight padmount, subsurface, vault or riser pole installations.

Single-Phase Switches Approximate Weight: 30 lb.

12-1/2 (318)

4-1/16 (103)

12-1/2 (318)

6-15/64 (176)

6-7/16 (164)

5-1/2 (140)

6-15/64 (176)

5-1/2 (140)

6-1/16 (154) 8-15/16 (227) 43 Open


o

43o 8-5/32 (207) Open Closed

10-5/32 (258)

Closed

13-7/16 (341)

8-15/16 (227)

13-7/16 (341)

8-1/32 (204) 6-51/64 (173)

1-35/64 (39) 25-27/32 (656) 23-25/32 (604)

(4) Mounting Holes, 58 in. Dia. x 78 in. (16 x 22 mm)

(4) Mounting Holes, 58 in. Dia. x 78 in. (16 x 22 mm)

Available with 600 A one-piece bushings or 200 A wells on either/both terminals.

A58

w w w. tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


Molded Vacuum Switches and Fault Interrupters
26 in. (660 mm) 14 in. (356 mm)

Three-Phase Switches Approximate Weight: 135 lb.

5-12 in. (140 mm) 18-12 in. (483 mm) 5-12 in. (140 mm)

21 in. (533 mm) 19 in. (483 mm) 9-12 in. (241 mm) 18 in. (470 mm)

Available with 600 A one-piece bushings or 200 A wells on either/both terminals.

Ratings
Maximum Design Voltage (kV) Frequency (Hz) BIL Impulse (kV) One-Minute AC Withstand (kV) Fifteen-Minute DC Withstand (kV) Load Interrupting & Loop Switching (Amp) Transformer Magnetizing Interrupting (Amp) Capacitor or Cable Charging Interrupting (Amp) Asymmetrical Momentary and 3-Operation Fault Close (Amp) Symmetrical One-Second Rating (Amp) Continuous Current (Amp) Eight-Hour Overload Current (Amp) 15.5 50/60 95 35 53 600 21 40 20 12,5 600 900 27 50/60 125 60 78 600 21 40 20 12,5 600 900 38 50/60 150 70 103 600 21 40 20 12,5 600 900

Application Information Construction: Submersible, corrosion resistant, fully shielded Ambient Temperature Range: -40C to 65C Certied Tests MVS loadbreak switches have been designed and tested per applicable portions of IEEE, ANSI, NEMA and other industry standards, including: IEEE C37.74 Standard for Subsurface, Vault and Padmounted Load-Interrupting Switches IEEE 386 Standard for Separable Connectors and Bushing Interfaces IEC 265 International Standards for Load-Interrupting Switches ANSI C57.12.28 Standard for Padmount Enclosures
Cable Connection Bushings

Open Position

43o

Closed Position

Patented Silicone Rubber Diaphragm Separates Line and Ground Potential Operating Handle

Spring Operating Mechanism Contained within 304 Stainless Steel Housing

Insulated Drive Rod Assembly

Molded EPDM Rubber Insulation and Shielding

Vacuum Interrupter Contact System

w w w. tnb.c a

A59

Elastimold

Cable Accessories

Underground Distribution Switchgear


MVI Molded Vacuum Fault Interrupters
Make, carry and automatically interrupt currents through 25,000 A symmetrical on 5 to 38 kV distribution systems MVI Molded Vacuum Fault Interrupters include molded-in elbow connection interfaces and tripfree mechanisms. They are available in single- and three-phase models. Units are self-powered and include current-sensing and electronic control.
Combines Vacuum Interrupters, Programmable, Electronic, Self-Powered Controls and EPDM Rubber Insulation Components provide compact, lightweight and submersible overcurrent protection. Field Programmable with a Wide Range of Time-Current Characteristic (TCC) Curves and Trip Settings TCC curves provide predictable tripping for ease of coordination with upstream and/or downstream protective devices. Control Monitors the Circuit Condition When the programmed parameters are exceeded, a signal is sent to the tripping mechanism. Motor Operators and Controls Available Enable radial feeders or loops to be recongured, either manually or via SCADA.

Front View Single-Phase


30-58 in. (778 mm) 29-18 in. (740 mm) 12-12 in. (318 mm)

Front View Three-Phase


32-78 in. (156 mm) Ground Lug 6-14 in. (156 mm) 14-332 in. (358 mm) Mounting

5-12 in. (140 mm) 18-12 in. (470 mm) Mounting 5-12 in. (140 mm) 19 in.. (483 mm) Mounting

200 A Wells
8-6164 in. (227 mm) Well Interface Accepts Standard Bushing Inserts

5-12 in. (140 mm)

5-2732 in. (148 mm)

600 A T Elbow Interface


Programmable Control & Current Transformer 600 A Bushing Interfaces Closed/ Tripped

Open/ Reset

600 A Bushings

Conforms to ANSI Std. 386

8-6164 in. (227 mm) 9-12 in. (241 mm) 8-1516 in. (227 mm) 2-5764 in. (73 mm) 600 Series Elbow Interfaces

10-5764 in. (277 mm)

Locking Features 17-4564 in. (277 mm)

Alternate Handle Position; Handle may be Repositioned in 60 Increments

A60

w w w. tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


MVI Molded Vacuum Fault Interrupters
Ratings
Voltage Class (kV) Maximum Design Voltage (kV) Frequency (Hz) BIL Impulse Withstand (kV) One-Minute AC Withstand (kV) Five-Minute DC Withstand (kV) Continuous Current (A) Load Interrupting and Loop Switching (A) Transformer Magnetizing Interrupting (A) Capacitor or Cable Charging Interrupting (A) Symmetrical/Asymmetrical Interrupting Capability (kA) Current Sensor Ratio 15.5 17 50/60 95 35 53 600 600 21 40 12.5/20 1,000:1 15.5 17 50/60 95 35 53 600 600 21 40 16/25.6 1,000:1 15.5 15.5 50/60 95 35 53 600 600 21 40 20/32 1,000:1 27 29 50/60 125 60 78 600 600 21 40 12.5/20 1,000:1 35 38 50/60 150 70 103 600 600 21 40 12.5/20 1,000:1 35 38 50/60 150 70 103 600 600 21 40 25/40 1,000:1

Application Information Meets ANSI C37.60 requirements Ambient Temperature Range: -40C to 65C Certied Tests MVI Molded Vacuum Fault Interrupters have been designed and tested per applicable portions of IEEE, ANSI, NEMA and other industry standards, including: ANSI C37.60 Standard for Fault Interrupters IEEE 386 Standard for Separable Connectors and Bushing Interfaces ANSI C57.12.28 Standard for Padmounted Enclosures
Patented Silicone Rubber Diaphragm Separates Line and Ground Potential Control Module (1-Phase) Sensing Module (3-Phase) Positive Contact Position Operating Handle Cable Connection Bushings

Spring Operating Mechanism with Tripping

Insulated Drive Rod Assembly

Molded EPDM Rubber Insulation and Shielding

Vacuum Fault Interrupter Contact System

w w w. tnb.c a

A61

Elastimold

Cable Accessories

Underground Distribution Switchgear


Molded Vacuum Switches and Fault Interrupters
Choose from ve electronic control options to interrupt faults Molded Vacuum Interrupters are provided with self-powered electronic control packages requiring no batteries or external power. Depending on the application, ve electronic control options are available for the MVI see below and on following page.
Include Self-Powered Electronic Control Packages No batteries or external power are required. Controls send a signal to the vacuum interrupters to trip open and interrupt the fault when an overcurrent condition is detected. Field-Selectable Fuse or Relay Curves and Trip Settings One device for many protection schemes.

Internal Control This control is integral to the unit (no separate control box). It is accessible via a computer connection to view or modify settings. This control is used on ganged three-phase or single-phase MVI interrupters. Phase and ground trip, as well as inrush restraint, are available. The E-Set software enables the user to connect to the internal control, either in the shop or in the eld, to program or change settings. An MVI-STP-USB programming connector is required to connect between the PC and the MVI. With a computer connected to the MVI control, the user can view real-time currents, the number of overcurrent protection operations, current magnitude of the last trip and the phase/ground fault targets. This is the standard control option.
NOTE: E-Set can be downloaded from www.elastimoldswitchgear.com

External Control with Single-/Three-Phase Trip Selection (Style 10 and 310) This control is mounted externally to the mechanism and provides the ability to select TCCs by setting DIP switches on the front panel. Each phase can be assigned a different minimum trip setting by means of manual rotary switches. This control is used on one, two or three single-phase MVI mechanisms.

External Control with Phase and Ground Trip (Style 20 and 320) This control is mounted externally to the mechanism and provides the ability to select phase minimum trip (one for all three phases), time delay for phase tripping, ground trip as a percent of phase minimum trip and ground trip delay by means of manual rotary switches. This control may be used on ganged three-phase or three single-phase MVI mechanisms.

A62

w w w. tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


Molded Vacuum Switches and Fault Interrupters
External Control with Three-Phase Trip Only (Style 30 and 330) This control is mounted externally to the mechanism and provides the ability to select phase minimum trip (one for all three phases) by means of a manual rotary switch. It also has an RS-232 port for connection to a PC to view the last trip data. This control is used on ganged three-phase or three single-phase MVI mechanisms.

External Control with Selectable Single-/Three-Phase Trip Function (80 and 380 Control) This control is mounted externally to the mechanism of the interrupter and provides the ability to select between a single-phase trip and a three-phase trip. The 80 and 380 Control can be used with one three-phase interrupter or with three single-phase interrupters. For three-phase applications, the ground trip function can be blocked from the front panel. Manual trip and reset target buttons are also located on the front panel. This control uses the E-Set software, which enables programming via a computer using the MVI-STP-USB adapter. E-Set features custom TCC curves and provides access to the last fault event information, as well as real-time current per phase.

Curve Reference No.

Curve No.

Curve Type

Curve Reference No.

Curve No.

Curve Type

Relay Curves (minimum trip 30600A) MVI-TCC-01 MVI-TCC-02 MVI-TCC-03 MVI-TCC-04 MVI-TCC-05 MVI-TCC-06 MVI-TCC-07 MVI-TCC-08 MVI-TCC-09 MVI-TCC-10 MVI-TCC-11 MVI-TCC-12 MVI-TCC-13 MVI-TCC-14 MVI-TCC-16 MVI-TCC-17 MVI-TCC-1823 MVI-TCC-2427 MVI-TCC-2831
1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 17 1823 2427 2831 E Slow E Standard Oil Fuse Cutout K Kearney QA Cooper EF Cooper NX-C CO-11-1 CO-11-2 T CO-9-1 CO-9-2 Cooper 280ARX F Kearney KS GE Relay CO-8-1CO-8-6 CO-9-3CO-9-6 CO-11-3CO-11-6

Fuse Curves (minimum trip 10200A) MVI-TCC-54 MVI-TCC-55 MVI-TCC-56 MVI-TCC-57 MVI-TCC-58 MVI-TCC-59 MVI-TCC-60
54 55 56 57 58 59 60 E Slow E Standard Oil Fuse Cutout K Kearney QA Cooper NX-C T

w w w. tnb.c a

A63

Elastimold

Cable Accessories

Underground Distribution Switchgear


Molded Vacuum Switches and Fault Interrupters
The following diagram shows how to construct a catalogue number for Molded Vacuum Switches and Interrupters. Catalogue numbers are shown below. EXAMPLE: The catalogue number for a Molded Vacuum Interrupter on a three-phase, 27 kV system, with 600 A terminal and parking stands between bushings is MVI3-21-27-66-PS.
Note: Availability of selected conguration will be veried at quotation time.

S U F F I X

Switch Type R N Blank


Riser Pole Network Subsurface

Main Interface Voltage Class 15 27 38 Device S I


Switch Interrupter 15.0 kV 27.0 kV 38.0 kV

2 6

200 A Bushing Well 600 A Bushing

Interface End Interface Phases 1 3


Single-Phase Three-Phase

E R AB

600 A T Body End Interface Rotated 180 Air Bushings (for Riser Pole)

Indicates eld that must be lled in to complete order.

2 6

200 A Bushing Well 600 A Bushing

Controls and Accessories


External 20 Control with Phase and Ground Trip (to be used on ganged three-phase MVI mechanism) External 30 Control with Three-Phase Trip Only (to be used on ganged three-phase MVI mechanism) External 80 Control with Selectable Single-/Three-Phase Trip Function (to be used on ganged three-phase MVI mechanism) External 10 Control with Single Trip Selection (to be used on one single-phase MVI mechanism) External 10 Control with Single-/Three-Phase Trip Selection (to be used on three single-phase MVI mechanisms) External 20 Control with Phase and Ground Trip (to be used on three single-phase MVI mechanisms) External 30 Control with Three-Phase Trip Only (to be used on three single-phase MVI mechanisms) External 80 Control with Selectable Single-/Three-Phase Trip Function (to be used on three single-phase mechanisms 120VAC Motor Operator and Controller for MVS3 or MVI3 Units 1224VDC Motor Operator and Controller for MVS3 or MVI3 Units Parking Stand for MVS or MVI (between bushings for single- or three-phase units) Parking Stand for MVS3, MVI3 or RMVI3 on Mechanism Cover Double Parking Stand for MVS3, MVI3 or RMVI3 (between bushings and on mechanism cover) Bail Tab Plate Installed for Three-Phase Units Only Customer Settings to be Programmed at the Factory Leave sufx blank for internal (self-contained) control.

Cat. No. Suffix 20 30 80 110 310 320 330 380 MO120A MO12D PS MPS PS6 BT P

Description

MVS Molded Vacuum Switches


Cat. No. Single-Phase Vacuum Switches MVS1-21-15-XX MVS1-21-15-6EX MVS1-21-27-XX MVS1-21-27-6EX MVS1-21-38-XX
15 kV 2-Way 1-Phase Switch 15 kV 2-Way 1-Phase Switch Elbow Interface 25 kV 2-Way 1-Phase Switch 25 kV 2-Way 1-Phase Switch Elbow Interface 35 kV 2-Way 1-Phase Switch 14 (356) 15 (381) 14 (356) 15 (381) 14 (356)

Description

Width in. (mm)

Height in. (mm)

Depth in. (mm)

Weight lb. (kg)

Diagram

*
30 (14)

6 (152)

24 (610)

Three-Phase Vacuum Switches MVS3-21-15-XX MVS3-21-27-XX MVS3-21-38-XX


15 kV 2-Way 3-Phase Switch 25 kV 2-Way 3-Phase Switch 35 kV 2-Way 3-Phase Switch 21 (533) 26 (660) 19 (483) 135 (61)

* **

* Height includes handle. ** 3-Phase Vacuum Switches are motor-ready.

A64

w w w.tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


MVI Molded Vacuum Interrupters***
Cat. No. Description Width in. (mm) Height in. (mm) Depth in. (mm) Weight lb. (kg) Diagram

Riser Pole (Three-Phase Installations Only) RMVI3-21-15-6ABX-YY RMVI3-21-27-6ABX-YY RMVI3-21-38-6ABX-YY RMVI1-21-15-6ABX-3YY RMVI1-21-27-6ABX-3YY RMVI1-21-38-6ABX-3YY
15kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals 25kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals 38kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals 15kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals, 1-Phase Trip Selectable 27kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals, 1-Phase Trip Selectable 38kV 2-Way 3-Phase Interrupter with Air Bushings on Top Terminals, 1-Phase Trip Selectable 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 45 (1,143) 45 (1,143) 45 (1,143) 45 (1,143) 45 (1,143) 45 (1,143) 25 (635) 25 (635) 25 (635) 25 (635) 25 (635) 25 (635) 150 (68) 150 (68) 150 (68) 150 (68) 150 (68) 150 (68)

Subsurface Single-Phase Vacuum Switches MVI1-21-15-XX MVI1-21-15-6EX MVI1-21-27-XX MVI1-21-27-6EX MVI1-21-38-XX MVI1-21-38-6EX
15kV 2-Way 1-Phase Interrupter 15kV 2-Way 1-Phase Interrupter, Elbow Interface 27kV 2-Way 1-Phase Interrupter 27kV 2-Way 1-Phase Interrupter, Elbow Interface 38kV 2-Way 1-Phase Interrupter 38kV 2-Way 1-Phase Interrupter, Elbow Interface 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 31 (787) 31 (787) 31 (787) 31 (787) 31 (787) 31 (787) 9 (229) 11 (279) 9 (229) 11 (279) 9 (229) 11 (279) 45 (20) 45 (20) 45 (20) 45 (20) 45 (20) 45 (20)

Subsurface Three-Phase Vacuum Switches MVI1-21-15-XX-3YY MVI1-21-27-XX-3YY MVI1-21-38-XX-3YY MVI3-21-15-XX-YY MVI3-21-27-XX-YY MVI3-21-38-XX-YY
***Air bushings on top terminal. 15kV 2-Way 3-Phase Interrupter, 1-Phase Trip Selectable Ext. Control 27kV 2-Way 3-Phase Interrupter, 1-Phase Trip Selectable Ext. Control 38kV 2-Way 3-Phase Interrupter, 1-Phase Trip Selectable Ext. Control 15kV 2-Way 3-Phase Interrupter 27kV 2-Way 3-Phase Interrupter 38kV 2-Way 3-Phase Interrupter 20 (508) 20 (508) 20 (508) 20 (508) 20 (508) 20 (508) 31 (787) 31 (787) 31 (787) 33 (838) 33 (838) 33 (838) 9 (229) 9 (229) 9 (229) 10 (254) 10 (254) 10 (254) 145 (66) 145 (66) 145 (66) 145 (66) 145 (66) 145 (66)

Accessories (order separately)


Cat. No. MVI-STP-USB MV1PMB MV3PMB MV3HPMB MV13PMB 35AL-11 35AL-12 MVI-TESTER Description
Adapter for Connection between MVI Units with Internal Control and a Computer for Programming/Viewing Settings Pole-Mounting Bracket for 1-Phase Units Only Pole-Mounting Bracket for 3-Phase Units Only Horizontal Pole-Mounting Bracket for 3-Phase Units Only Pole-Mounting Bracket for Three 1-Phase Units Only Connector Bare Wire Type 34"16 Rod for Riser Pole Units Qty. of 1 Needed per Phase Connector 2-Hole Spade Type 34"16 Rod for Riser Pole Units Qty. of 1 Needed per Phase Tester for Electric Control Style 80

Weights and dimensions are approximate. X = 6 for 600A or 2 for 200A or 6E for 600A T interface. Y = 10, 20, 30, 80 for different electronic controls. Leave blank for internal (self-contained) control. Accessories should be added as sufx to the main catalog number unless otherwise noted. Other congurations are available. Please consult your local representative on congurations not shown here. The 3-Phase Vacuum Interrupters are motor-ready.

w w w. tnb.c a

A65

Elastimold

Cable Accessories

Underground Distribution Switchgear


Multi-Way Switchgear and Transfer Packages
Multi-Way Unit Construction Multi-way vault and padmount units are built using MVS, MVI and MCAN modules as required by the application. These are mounted onto the ES multi-way common bus system and assembled on a free-standing, oor-mounted frame. At this stage, the product is ready to be used in vault installations. For padmount installations, a double-sided, drop-over, painted, mild steel enclosure is provided. Munsell Green 7GY 3.29/1.5 is the standard enclosure color. Other colors are available upon request. Painted stainless steel or berglass enclosures are available as options.
Common Bus Assembly Vault-Style Unit

Padmount Unit: Tap (Load) Side


Mild or Stainless Steel Enclosures available*

Top Lifts Up for Ease of Operation

MVI Mechanism on 1-Phase Protection Tap (3-Phase also available) Internal Electronic Control and Current-Sensing Device (3-Phase MVI and External Controls also available) Parking Stand

Internal Electronic Control and Current-Sensing Device (3-Phase MVI and External Controls also available)

Ground Rod

200A Wells (shown); 600A Bushings available

* Also available with a berglass enclosure.

A66

w w w. tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


Multi-Way Switchgear and Transfer Packages
The following diagram shows how to construct a catalogue number for Multi-Way Switchgear or Transfer Packages. Catalogue number are shown on page A61 for the most common congurations. EXAMPLE: The catalogue number for an auto-transfer package for padmount installation on a 3-phase, 27 kV system, with two MVI protected taps, 600 A terminals and standard mild steel enclosure is ATD324-AAPP-6666.

Switch Type AT ES
Auto Transfer Multi-Way Switch

Components by Way A B C D
3-Phase Switch Motor Operator Auto Transfer Solid Tap/Direct Bus Connection (600 A or 200 A) 3-Phase MVI Fault Interrupter, 20 Control 3-Phase MVI Fault Interrupter, 30 Control 1-Phase Fault Interrupter 1-Phase Fault Interrupter, 10 Control 1-Phase Fault Interrupter, 80 Control 1-Phase Fault Interrupter, 20 Control 1-Phase Fault Interrupter, 30 Control 3-Phase MVI Fault Interrupter, 80 Control 3-Phase MVI Fault Interrupter 3-Phase MVS Switch with UAD Control 3-Phase MVI Fault Interrupter Motor Operator, 1224VDC 1-Phase MVS Switch 3-Phase MVS Switch 3-Phase MVS with 1224VDC Motor 3-Phase MVS with 120VAC Motor 3-Phase MVI Fault Interrupter Motor Operator, 120VAC 3-Phase MVI Fault Interrupter with UAD Control

Enclosure Material Blank S


Mild Steel Stainless Steel

Type V S D P
Vault Subsurface Double-Side Padmount Single-Side Padmount

J K L M N O P Q R S T U V W Z

Cabinet Depth Padmount Blank


54 in.

Phases 1 3
1-Phase 3-Phase

Interface by Way 2 6
200 A Bushing Well 600 A Bushing

Voltage Class 1 2 3
15.0 kV 27.0 kV 38.0 kV

Number of Ways 2 3 4
2-Way 3-Way 4-Way

Example: ATD324-AAPP-6666 Custom padmount enclosure dimensions are available. Parking stands are standard on padmount units. Consult your Regional Sales Ofce on multi-way congurations that include 38kV MVIs. 3-Phase MVS and MVI are motor-ready. Auto-transfer ways 1 and 2 are always A.

Way 1 A

Way 2 A

Way 3

Way 4

w w w. tnb.c a

A67

Elastimold

Cable Accessories

Underground Distribution Switchgear


Multi-Way Switchgear and Transfer Packages
Switching and Sectionalizing Switchgear
Cat. No. Vault ESV313-TTT-XXX ESV323-TTT-XXX ESV333-TTT-XXX ESV314-TTTT-XXXX ESV324-TTTT-XXXX ESV334-TTTT-XXXX Padmount PMVS1-21-15-XX PMVS1-21-27-XX PMVS1-21-38-XX ESD312-T-XX ESD322-T-XX ESD332-T-XX ESD313-TTT-XXX ESD323-TTT-XXX ESD333-TTT-XXX ESD314-TTTT-XXXX ESD324-TTTT-XXXX ESD334-TTTT-XXXX
15kV 2-Way 3-Phase Switch 27kV 2-Way 3-Phase Switch 38kV 2-Way 3-Phase Switch 15kV 2-Way 3-Phase Switch 27kV 2-Way 3-Phase Switch 38kV 2-Way 3-Phase Switch 15kV 3-Way 3-Phase Switch 27kV 3-Way 3-Phase Switch 38kV 3-Way 3-Phase Switch 15kV 4-Way 3-Phase Switch 27kV 4-Way 3-Phase Switch 38kV 4-Way 3-Phase Switch 36 (914) 36 (914) 36 (914) 36 (914) 36 (914) 36 (914) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 30 (762) 30 (762) 30 (762) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 30 (762) 30 (762) 30 (762) 42 (1,067) 42 (1,067) 42 (1,067) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 54 (1,317) 310 (141) 310 (141) 310 (141) 680 (308) 680 (308) 680 (308) 1,250 (567) 1,250 (567) 1,250 (567) 1,380 (626) 1,380 (626) 1,380 (626) 15kV 3-Way 3-Phase Switch 27kV 3-Way 3-Phase Switch 38kV 3-Way 3-Phase Switch 15kV 4-Way 3-Phase Switch 27kV 4-Way 3-Phase Switch 38kV 4-Way 3-Phase Switch 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 48 (1,219) 36 (914) 36 (914) 36 (914) 36 (914) 36 (914) 36 (914) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 750 (340) 750 (340) 750 (340) 880 (399) 880 (399) 880 (399)

Description

Width in. (mm

Height in. (mm) Depth in. (mm)

Weight lb. (kg)

Diagram

X = 6 for 600A or 2 for 200A.Other congurations are available. Consult your local representative for congurations not shown here.

Single-Side Padmount ESP313-BJB-626


84 in. (2,134 mm)

Double-Side Padmount ESD3X4-IIPP-6622-S


54 in. (1,372 mm)

42 in. (1,067 mm)

54 in. (1,372 mm)

Subsurface ESS3X2-TT-66
33-18 in. (841 mm)

Vault ESV3X4-TTTT-2222

MSV3 Switch

35-38 in. (899 mm) 19 in. (483 mm)

5-12 in. (140 mm)

48 in. (1,219 mm)

Stainless Steel Bottom Rails

A68

w w w. tnb.c a

Elastimold

Cable Accessories

Underground Distribution Switchgear


Multi-Way Switchgear and Transfer Packages
Overcurrent Protection Switchgear
Cat. No. Vault ESV313-TPP-XXX ESV323-TPP-XXX ESV313-TTP-XXX ESV323-TTP-XXX ESV314-TPPP-XXXX ESV324-TPPP-XXXX ESV314-TTPP-XXXX ESV324-TTPP-XXXX ESV314-TTTP-XXXX ESV324-TTTP-XXXX Padmount PMVI1-21-15-XX PMVI1-21-27-XX PMVI1-21-38-XX PMVI1-21-15-XX-3YY PMVI1-21-27-XX-3YY PMVI1-21-38-XX-3YY ESD312-P-XX ESD322-P-XX ESD332-P-XX ESD313-TPP-XXX ESD323-TPP-XXX ESD333-TPP-XXX ESD313-TTP-XXX ESD323-TTP-XXX ESD333-TTP-XXX ESD314-TPPP-XXXX ESD324-TPPP-XXXX ESD334-TPPP-XXXX ESD314-TTPP-XXXX ESD324-TTPP-XXXX ESD334-TTPP-XXXX ESD314-TTTP-XXXX ESD324-TTTP-XXXX ESD334-TTTP-XXXX
15 kV 3-Way 3-Phase (1) Source Switch, (2) Vacuum Interrupter Taps 27 kV 3-Way 3-Phase (1) Source Switch, (2) Vacuum Interrupter Taps 660 (299) 15 kV 3-Way 3-Phase (2) Source Switches, (1) Vacuum Interrupter Tap 27 kV 3-Way 3-Phase (2) Source Switches, (1) Vacuum Interrupter Tap 15 kV 4-Way 3-Phase (1) Source Switch, (3) Vacuum Interrupter Taps 40 (1,016) 27 kV 4-Way 3-Phase (1) Source Switch, (3) Vacuum Interrupter Taps 15 kV 4-Way 3-Phase (2) Source Switches, (2) Vacuum Interrupter Taps 880 (399) 27 kV 4-Way 3-Phase (2) Source Switches, (2) Vacuum Interrupter Taps 15 kV 4-way 3-Phase (3) Source Switches, (1) Vacuum Interrupter Tap 27 kV 4-Way 3-Phase (3) Source Switches, (1) Vacuum Interrupter Tap 48 (1,219) 22 (559)

Description

Width in. (mm) Height in. (mm) Depth in. (mm)

Weight lb. (kg)

Diagram

15 kV 2-Way 1-Phase Interrupter 27 kV 2-Way 1-Phase Interrupter 38 kV 2-Way 1-Phase Interrupter 30 (762) 15 kV 2-Way 3-Phase Interrupter 1-Phase Trip Selectable Ext. Control 27 kV 2-Way 3-Phase Interrupter 1-Phase Trip Selectable Ext. Control 38 kV 2-Way 3-Phase Interrupter 1-Phase Trip Selectable Ext. Control 680 (308) 15 kV 2-Way 3-Phase (1) Vacuum Interrupter Tap 27 kV 2-Way 3-Phase (1) Vacuum Interrupter Tap 38 kV 2-Way 3-Phase (1) Vacuum Interrupter Tap 15 kV 3-Way 3-Phase (1) Source Switch, (2) Vacuum Interrupter Taps 54 (1,372) 27 kV 3-Way 3-Phase (1) Source Switch, (2) Vacuum Interrupter Taps 38 kV 3-Way 3-Phase (1) Source Switch, (2) Vacuum Interrupter Taps 15 kV 3-Way 3-Phase (2) Source Switches, (1) Vacuum Interrupter Tap 54 (1,372) 27 kV 3-Way 3-Phase (2) Source Switches, (1) Vacuum Interrupter Tap 38 kV 3-Way 3-Phase (2) Source Switches, (1) Vacuum Interrupter Tap 15 kV 4-Way 3-Phase (1) Source Switch, (3) Vacuum Interrupter Taps 54 (1,372) 27 kV 4-Way 3-Phase (1) Source Switch, (3) Vacuum Interrupter Taps 38 kV 4-Way 3-Phase (1) Source Switch, (3) Vacuum Interrupter Taps 15 kV 4-Way 3-Phase (2) Source Switches, (2) Vacuum Interrupter Taps 54 (1,372) 27 kV 4-Way 3-Phase (2) Source Switches, (2) Vacuum Interrupter Taps 38 kV 4-Way 3-Phase (2) Source Switches, (2) Vacuum Interrupter Taps 15 kV 4-Way 3-Phase (3) Source Switches, (1) Vacuum Interrupter Tap 54 (1,372) 27 kV 4-Way 3-Phase (3) Source Switches, (1) Vacuum Interrupter Tap 38 kV 4-Way 3-Phase (3) Source Switches, (1) Vacuum Interrupter Tap 72 (1,829) 54 (1,372) 72 (1,829) 1,500 (680) 48 (1,219) 54 (1,372) 1,380 (626) 72 (1,829) 54 (1,372) 72 (1,829) 1,500 (680) 48 (1,219) 54 (1,372) 1,380 (626) 72 (1,829) 54 (1,372) 72 (1,829) 1,500 (680) 48 (1,219) 54 (1,372) 1,380 (626) 72 (1,829) 54 (1,372) 72 (1,829) 1,500 (680) 48 (1,219) 54 (1,372) 1,160 (526) 72 (1,829) 54 (1,372) 72 (1,829) 1,500 (680) 54 (1,372) 1,160 (526) 36 (914) 48 (1,219) 42 (1,067) 48 (1,219) 42 (1,067) 36 (914) 30 (762) 310 (141)

X = 6 for 600 A or 2 for 200 A. YY = 10, 20, 30, 80 for different electronic controls. Consult your Regional Sales Ofce on 38 kV multi-way congurations.

w w w. tnb.c a

A69

Elastimold

Cable Accessories

Molded Fuse Products


Fused Elbows
Probe

Upper Elbow Half

The fastest, most cost-effective way to improve a distribution systems reliability Replace existing 200 A tap elbows with Elastimold Fused Elbows to protect light-duty underground distribution systems, including sub-loops, radial taps, junctions, transformers and other equipment. Elastimold Fused Elbows provide full-range current-limiting fusing with 50 kA interrupting capability. They are rated for 5 kV ungrounded to 28 kV grounded Wye. Plus they provide 15/25 kV hotstick-operable, loadbreak elbow switching.

Probe Lug

Fuse

Crimp Lug

Hose Clamp

Lower Elbow Half

Combined Full-Range Current-Limiting Fusing 15/25 kV Hotstick-Operable, Loadbreak Elbow Switching Quickly improve the distribution systems reliability without the expense of adding a separate piece of switchgear or replacing existing sectionalizing cabinets. High Fault Close Rating Current-limiting fuses improve the fault close rating of the elbow (10 kA) to that of the fuse, thereby reducing the risk of component damage or personnel injury. EPDM Molded Rubber Deadfront Construction Elbows are fully sealed and submersible, and they insulate, shield and eliminate exposed live parts. Two-Piece Housing Enables easy fuse replacement.

Application Information Construction: Submersible, non-venting, deadfront, corrosion resistant Ambient Temperature Range: -30C to 65C Certied Tests Elastimold Fused Elbows have been designed and tested per applicable portions of IEEE, ANSI and other industry standards, including: ANSI C37.40 Standard for Current-Limiting Fuse Service Conditions ANSI C37.41 Standard for Current-Limiting Fuse Design and Testing ANSI C37.47 Standard for Current-Limiting Fuse Ratings and Specications IEEE 386 Standard for Separable Connectors

Ratings
System Voltage Class (kV) Nominal Fuse Voltage (kV) Rated Maximum Fuse Voltage (kV) Frequency (Hz) BIL Impulse Withstand (kV) One-Minute AC Withstand (kV) Fifteen-Minute DC Withstand (kV) Corona Extinction (kV) Symmetrical Interrupting Capability (Amp) Current Rating (Amp) 15 8.3 8.8/10 50/60 95 34 53 11 50,000 380 25* 15.5 15.5 50/60 125 40 78 19 50,000 620 25/28* 17.2 17.2 50/60 140 45 78 21.5 50,000 345

* The 15.5 kV L-G rated fuse requires 75% grounded load to be applied on a 25 kV system. The 17.2 kV L-G rated fuse requires at least 75% grounded load to be applied on a 28 kV system. Fuses are only suitable for the system voltage class shown if the recovery voltage across the fuse will not exceed its rated maximum voltage. For three-phase applications, this generally requires that protected transformers be gndYgndY and have at least 50% grounded load. Fuse replacement requires the elbow to be de-energized.

A70

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Fuse Products


Fused Elbows
Electrical Characteristics of Elastimold EFX-E Elbow Fuses
System Voltage Class (kV) Nominal Fuse Voltage Rating (kV) Current Rating Cat. No. (A)
3 6 8 10 12 18 15 8.3 20 25 30 40 45 65 80 6 8 25 15.5 10 12 18 20 3 6 8 10 12 25/28 17.2 18 20 25 30 40 45

Rated Max. Voltage (kV)

Maximum Continuous Current (2) (6) 25C


4.3 9.5 11.5 14.0 19.0

40C
4.2 9.0 11.0 13.5 18.5 20 25 33.0 36.5 42.0 47.0 68.0 77.5 8.0 10.0 12.5 15.5 19.5 22.5 4.2 9.0 11.0 13.5 17.5 19.5 23.0 30.5 34.5 40.0 45.0

65C
3.9 8.5 10.5 13.0 17.5 19.0 24.0 31.0 34.5 40.0 45.0 64.5 73.5 7.7 9.5 12.0 15.0 18.5 21.5 3.9 8.5 10.5 13.0 16.5 18.5 22.0 29.0 32.5 38.0 42.5

Peak Arc Minimum (kV)


30 32 28 28 26 26 26 26 26 26 26 23 22 52 40 40 38 38 38 51 54 46 46 43 45 45 45 45 45 45

Total l2t Melt l2t (A2-Sec)


100 620 800 800 920 1,31 1,62 3,66 5,25 8,7 12,8 34 51,2 620 800 800 920 1,62 2,2 100 620 800 800 920 1,31 1,62 3,66 5,25 8,7 12,8

Maximum (A2-Sec) (3) (4)


350 2,7 4 4 8 9,5 11 22 30 50 70 200 280 3 4,3 4,3 8 13 16,5 510 3,25 4,6 4,6 8,5 10 12,5 27,5 37,5 62,5 87,5

EFX083003-E EFX083006-E EFX083008-E EFX083010-E EFX083012-E EFX083018-E EFX083020-E EFX083025-E EFX083030-E EFX083040-E EFX083045-E EFX083065-E EFX083080-E EFX155006-E EFX155008-E EFX155010-E EFX155012-E EFX155018-E EFX155020-E EFX172003-E EFX172006-E EFX172008-E EFX172010-E EFX172012-E EFX172018-E EFX172020-E EFX172025-E EFX172030-E EFX172040-E EFX172045-E

10.0

21.0 26.0 34.0 37.5 43.0 49.0 70.0 80.0 8.5 10.5 13.0 16.0 20.0 23.5 4.3 9.5 11.5 14.0 18.0

8.8

15.5

17.2

20.0 24.0 31.5 35.5 41.0 46.0

1. Designs have a 50,000 A RMS Symmetrical Rating (except 3 A, 17.2 kV which was tested at 44 kA maximum). 2. Fuses have a Rated Maximum Application Temperature (RMAT) of 65 C. RMAT is the maximum temperature of the air, in contact with the elbow housing, at which fuses have been shown to be suitable for use. 3. Tabulated Maximum Total I2t values are for currents of 50,000 A at the nominal voltage of the fuse. Values for 8.3kV fuses at 10kV are approximately 30% higher. Values for 17.2 kV fuses at 15.5 kV are approximately 20% lower. 4. Maximum total I2t values are reduced for currents below 50,000A. For example, at 10,000A, maximum total I2t values are approximately 15% less than the published values. 5. Peak arc voltages listed are for 50,000A currents at the rated maximum voltage listed. Reduced currents and voltages will reduce the peak arc voltage. For more information, contact your T&B Regional Sales Ofce. 6. Maximum continuous currents at ambient temperatures other than those listed may be determined by derating the fuses by 0.2% per degree C over 25C. For example: At 40C the derating would be 15 x 0.2 = 3%, making the maximum continuous current of a 17.2kV, 25A fuse 31.5 x 0.97 = 30.5 A. 7. Time-current characteristic curves are published at 25C. Reduction in the long time melting current of the fuses (approximately one hour and longer) due to higher ambient temperatures is the same as described above for maximum continuous currents.

w w w. tnb.c a

A71

Elastimold

Cable Accessories

Molded Fuse Products


Fused Elbows
Recommended Elastimold EFX-E Elbow Fuse at 40C Ambient Temperature
Recommended Fuse Current Ratings (Amperes) Fuse Voltage 1-Phase Transformer kVA
10 15 25 37.5 50 75 100 167 250 333 500

8.3 kV Transformer 1-Phase Voltage Rating (kV), Phase to Ground 2.4 A


12 20 25 45 65

15.5 kV (17.2 kV) 7.2 B


3 6a 8 12 20 25 40 65

4.16 B
6 10 20 25 40 65 80

4.8 B
6a 6 8 12 20 30 45 80

7.62 B
3 3 6 8 12 20 25 45 65

12 B
3 3 6 6 10 18 25 45 65

14.4 B
6a 6a 6a 6 6 10 18 -25 -45

16 B
6a 6a 6a 6a 6 8 12 20 -30 -45

A
18 20 30 65 80

A
12 20 25 45 80

A
10 12 18 25 45 65

A
12 18 25 45 80

A
12 18 -25 -40

A
10 18 20 -30 -45

A
-12 -20 -25 -45

B
(3a) (3a) -3 (6a) (6a) -8 -10 -20 -30 -45

Recommended Elastimold EFX-E Elbow Fuse at 40C Ambient Temperature


Recommended Fuse Current Ratings (Amperes) Fuse Voltage 1-Phase Transformer kVA
15 22.5 30 45 75 100 112.5 150 200 225 300 500 750 1 1. 2. 3. 4.

8.3 kV Transformer 1-Phase Voltage Rating (kV), Phase to Ground 2.4 A


10 12 20 30 40 45 65 80

15.5 kV (17.2 kV) 8.32 A


12 18 20 25 45 80

4.16 B
6 8 12 20 30 45 65 80 80

4.8 B
3 6a 6 10 20 25 25 40 65 65 80

A
12 18 20 25 40 45 65

A
18 18 20 30 40 45 80

B
3 6a 6 8 12 20 25 30 45 65 80

7.27.96 A B
18 20 20 30 65 80 3a 3 6a 6 8 12 12 20 25 30 45 80

12.47 B
3a 3 3 6a 8 10 12 20 25 25 40 80

A
10 12 12 18 30 45 80

B
6a 6a 6a 6a 6 8 8 12 18 20 25 45 65

13.214.4 A B
10 12 12 18 30 45 6a 6a 6a 6a 6 8 8 12 18 18 25 45

20.8 A
8 8 12 18 -25 -40

B
6a 6a 6a 6a 6a 6a 6 6 10 10 18 -25 -45

22.924.9 A B
-18 -25 -40 (3a) (3a) (3a) (3a) -3 (6a) (6a) -6 -8 -10 -12 -25 -40

Column A = 140200% of transformer rating and Column B = 200300% of transformer rating. Ratings in parenthesis are 17.2 kV fuses. 8.3 kV, 345 A fuses and 15.5 kV, 620A fuses are used in the small (size 1) elbow housing; 8.3 kV, 6580 A fuses and 17.2 kV, 345 A fuses are used in the large (size 3) elbow fuse housing. Recommended fuses meet inrush criteria of 12 times transformer full-load current for 0.1 second and 25 times transformer full-load current for 0.01 second. Fuses also meet cold-load pickup criteria of 6 times transformer full-load current for 1 second and 3 times transformer full-load current for 10 seconds.

a. Fuse allows greater than 300% of transformer rating.

A72

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
The following diagram shows how to construct a catalogue number for Fuse Housings and Full-Range Current-Limiting Fuses.
Indicates eld that must be lled in to complete order.

168FLR1
8-78 in. (225 mm)

274FLR1
9-14 in. (235 mm)

168FLR3 A = 8-78 in. (225 mm) 274FLR3 A = 9-14 in. (235 mm)
A

Fuse Test Port A


Two Direct Test Ports

Conductor Size 180 190


6 4 2 1 1/0 2/0 3/0 4/0 4 2 1 1/0 2/0 3/0 4/0

6-14 in. (159 mm)

Blank Two Capacitive Test Points Nominal Fuse Voltage Rating 168 274 274
8.3 kV 15.5 kV 17.2 kV

6-14 in. (159 mm)

200 Housing 1 3
Small Large**

210 220 230 240

10-12 in. (270 mm) 10-58 in. (270 mm)

10-58 in. (270 mm)

Cable Insulation Diameter (in.) A B C D


0.575 in.0.740 in. 1519 mm 0.635 in.0.905 in. 1623 mm 0.805 in.1.060 in. 2027 mm 0.890 in.1.220 in. 2531 mm

250 260 270

10-58 in. (270 mm)

* Small Housing is used with 8.3kV (345A) and 15.5kV (620A) rated fuses. ** Large Housing is used with 8.3kV (65A and 80A) and 17.2kV (345A) rated fuses.

1. All dimensions rounded up to the nearest eighth inch. 2. Also available with direct test port. 3. Dimensions with Direct Test Port units are 10-14 in. (260 mm) or 10-58 in. (270 mm). 4. 168FLR3 uses a large housing with a 15 kV, 200 A elbow interface.

Indicates eld that must be lled in to complete order.

8.3 kV (345 A)/15.5 kV (620 A) Fuse


9-1/4 in. (235 mm)

Amperage Rating
2-1/4 in. (54 mm)

Voltage Rating 083 155 172


8.3 kV 15.5 kV 17.2 kV

003 8.3/17.2 kV 006 8.3/15.5/17.2 kV 008 8.3/15.5/17.2 kV 010 8.3/15.5/17.2 kV 012 8.3/15.5/17.2 kV 018 8.3/15.5/17.2 kV

3A 6A 8A 10 A 12 A 18 A 20 A 25 A 30 A 40 A 45 A 65 A 80 A

8.3 kV (6580 A)/17.2 kV (345 A) Fuse

2-1/4 in. (54 mm)

020 8.3/15.5/17.2 kV 025 8.3/17.2 kV 030 8.3/17.2 kV 040 8.3/17.2 kV

13-1/2 in. (343 mm)

045 8.3/17.2 kV 065 8.3 kV

All dimensions rounded up to the nearest eighth inch.

080 8.3 kV

w w w. tnb.c a

A73

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Application Information Construction: Submersible, non-venting, deadfront, corrosion resistant Ambient Temperature Range: -30C to 65C for 650 A fuses; -30C to 40C for >50 A fuses. Certied Tests Elastimold Molded Current-Limiting Fuses have been designed and tested per applicable portions of IEEE, ANSI, NEMA and other industry standards, including: ANSI C37.40 Standard for Current-Limiting Fuse Service Conditions ANSI C37.41 Standard for Current-Limiting Fuse Design and Testing ANSI C37.47 Standard for Current-Limiting Fuse Ratings and Specications ANSI/IEEE 386 Standard for Separable Connectors and Bushing Interfaces Ratings
System Voltage Class (kV) Rated Maximum Fuse Voltage (kV) Frequency (Hz) BIL Impulse Withstand (kV) One-Minute AC Withstand (kV) Fifteen-Minute DC Withstand (kV) Corona Extinction (kV) Symmetrical Interrupting Capability (A) Current Rating (A) 5 5.5 50/60 60 34 53 11 50 80180 15 8.3/10** 50/60 95 34 53 11 50 10115 25/28* 15.5/17.2** 50/60 125/140 4045 78 19/21.5 50 10100 35 23 50/60 150 50 103 26 50 1050

* 15.5 kV L-G rated fuses require 75 % grounded load to be applied on a 25 kV system. ** 17.2 kV L-G rated fuses require at least 75 % grounded load to be applied on a 28 kV system. Fuse replacement requires the MCLF to be de-energized. Fuses are only suitable for the system voltage class shown if the recovery voltage across the fuse will not exceed its rated maximum voltage. For three-phase applications, this generally requires that protected transformers be gndY-gndY and have at least 50 % grounded load.

Interchangeable Molded Rubber End Fittings

Replaceable Molded Rubber Current-Limiting Fuse

Assembled Fuse Unit

Assembled Fuse Unit with Optional Wall-Mounting Bracket

A74

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Electrical Characteristics of Encapsulated Fuses Used in MCLF
Nominal Fuse Voltage Rating (kV) Current Rating (A)
80 100 5.5 125 150 180 10 20 30 40 8.3 50 65 80 100 115 10 20 30 15.5 40 50 65 80 100 10 20 23.0 30 40 50

Fuse Catalogue Number M05CLF080 M05CLF100 M05CLF125 M05CLF150 M05CLF180 M15CLF010 M15CLF020 M15CLF030 M15CLF040 M15CLF050 M15CLF065 M15CLF080 M15CLF100 M15CLF115 M25CLF010 M25CLF020 M25CLF030 M25CLF040 M25CLF050 M25CLF065 M25CLF080 M25CLF100 M35CLF010 M35CLF020 M35CLF030 M35CLF040 M35CLF050

Rated Maximum Voltage (kV)

Maximum Continuous Current (2) (6) 25C 40C


86 108 84 105 133 154 180 13 22 33 41 47 71 84 103 116 13 22 33 41 45 66 84 100 13 22 33 40 46

Peak Arc Total l2t (kV) (5)

Minimum Melt l2t (A2Sec)


22,100 56,700

Maximum Total l2t (A2Sec) (3) (4)


110,000 280,000 530,000 860,000 1,270,000 4,000 11,000 30,000 50,000 70,000 100,000 185,000 330,000 480,000 3,700 10,000 30,000 50,000 70,000 110,000 255,000 380,000 4,800 13,000 38,000 61,000 82,000

5.5

137 159 185 14 23

15

109,200 176,000 259,000

28

800,000 1,620 5,250 8,700 12,800 25,200 47,000 78,300 115,150 800,000 1,620 5,250 8,700 12,800 25,200

10.0

35 43 51 73 87 106 120 14 23

26

8.3

25

46

17.2

35 43 47 68

45

15.5

88 100 14 23

40 61

54,400 80,000 800,000 1,620 5,250 8,700 12,800

23.0

35 41 47

60

1. Designs have a 50,000 A all U/CERMSs Symmetrical Rating. 2. 1050 A fuses have a Rated Maximum Application Temperature of 65C, and 65180 A fuses have a Rated Maximum Application Temperature of 40C. (RMAT is the maximum temperature of the air in contact with the MCLF housing at which the fuses have been shown suitable for use.) 3. Tabulated Maximum Total I2t values are for currents of 50,000 A at the nominal voltage of the fuse. Fuses that have a Rated Maximum Voltage higher than their Nominal Voltage Rating will have a higher I2t let-through when applied at voltages up to these higher values. For example, Maximum Total I2t values are increased by approximately 30% when 8.3 kV fuses are applied at 10kV and approximately 25% when 15.5kV fuses are used at 17.2 kV. 4. Maximum total l2t values are reduced for currents below 50,000 A. For example, at 10,000 A, l2t values are approximately 15% less than the published values. 5. Peak arc voltages quoted are for 50,000A currents at the rated maximum voltage listed. Reduced currents and voltages will reduce the peak arc voltage. Consult the factory for further information. 6. Maximum continuous currents at higher ambient temperatures may be determined by derating the fuses by 0.2% per degree C over 25 C. For example: At 40C, the derating would be 15 x 0.2 = 3%, making the maximum continuous current of a 20 A fuse 23.0 x 0.97 = 22 A.

w w w. tnb.c a

A75

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Recommended MCLF at 40C Ambient Temperature
Recommended Fuse Current Ratings (Amperes) Fuse Voltage 1-Phase Transformer kVA A
10 15 25 37.5 50 75 100 167 250 333 500 750 1 20 30 50 65 -100 -150 -180

(5.5 kV) 8.3 kV 2.4 B


10a 10 20 30 40 65 -80 -150

15.5 kV 7.2 7.62 B


10a 10a 10a 10 10 20 30 50 65 100

23 kV 16 34.5 B
10a 10a 10a 10a 10a 10 10 20 30 50

Transformer 1-Phase Voltage Rating (kV), Phase to Ground 4.16 A


20 30 40 65 (100) -125 -180

4.8 B
10a 10a 10 20 30 40 50 -80

12 B
10a 10a 10a 10 10 20 30 50 65 100

14.4 B
10a 10a 10a 10a 10a 10 20 30 50 65 100

A
20 30 50 -80 -100 -150

B
10a 10a 10 20 20 30 50 65 -100 -150

A
20 30 50 65 115

A
20 30 50 65 115

A
20 30 50 65 100

A
20 30 30 65 80 100

B
10a 10a 10a 10a 10a 10 10 30 40 50 80 100

A
20 30 50

A
20 20 40

B
10a 10a 10a 10a 10a 10a 10 20 30 40

-125 -180

Recommended MCLF at 40C Ambient Temperature


Recommended Fuse Current Ratings (Amperes) Fuse Voltage 1-Phase Transformer kVA
15 22.5 30 45 75 100 112.5 150 200 225 300 500 750 1,000 1,500 2,000

8.3 kV Transformer 1-Phase Voltage Rating (kV), Phase to Ground 2.4 A


30 40 40 50 65 -80 -100 -180

15.5 kV (17.2 kV) 8.32 A


20 30 30 50 80 115

23 Kv 34.5 A
20 30 40 50

4.16 B
10a 10 10 20 40 50 65 -80 -100 -125 -150

4.8 B A
20 20 30 40 40 65 -100 -125 -180

A
20 20 30 40 50 65 -100 -180

B
10a 10a 10a 10 20 30 30 40 50 65 -80 -125 -180

7.27.96 A B
20 20 30 40 65 -80 -125 -180 10a 10a 10a 10a 10 20 20 30 30 40 50 -80 -125 -180

B
10a 10a 10a 10a 10 10 20 20 30 50 50 80 115

12.47 A B
20 30 50 65 100 10a 10a 10a 10a 10a 10 10 10 20 20 30 50 80 100

13.214.4 A B
20 30 50 65 100 10a 10a 10a 10a 10a 10 10 10 20 20 30 50 65 100

20.8 A
20 30 50 65 100

B
10a 10a 10a 10a 10a 10a 10a 10a 10 10 20 30 50 65 100

22.924.9 A B
10 20 30 40 65 80 10a 10a 10a 10a 10a 10a 10a 10a 10 10 20 30 40 65 80

B
10a 10a 10a 10a 10a 10a 10a 10a 10a 10a 10 20 30 40

10a 10a 10a 10 20 30 30 50 65 65 -100 -150

1. Column A = 140200% of transformer rating and Column B = 200300% of transformer rating. 2. Ratings in parentheses are 5.5kV fuses. 3. Recommended fuses meet inrush criteria of 12 times transformer full-load current for 0.1 second and 25 times transformer full-load current for 0.01 second. Fuses also meet cold-load pickup criteria of 6 times transformer full-load current for 1 second and 3 times transformer full-load current for 10 seconds. a. Fuse allows greater than 300% of transformer rating.

A76

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Model 22
19-12 in. (343 mm) 16-58 in." (422mm) 5-18 in. (130 mm) 8-316 in. (208 mm)

Model 222
23-58 in. (343 mm) 16-58 in. (422 mm) 5-18 in. (130 mm)

Approx. Weight 30 lb. (13.6 kg)

8-316 in. (208 mm)

4 in. (102 mm)

Approx. Weight 35 lb. (15.9 kg)

Model 2222
27-58 in. (702 mm) 16-58 in. (422 mm) 9-316 in. (233 mm) 5-18 in. (130 mm)

4 in. (102 mm)

4 in. (102 mm)

Approx. Weight 30 lb. (13.6 kg)

Model 66
19-58 in. (498 mm) 16-58 in. (422 mm) 5-18 in. (130 mm) 9/16 in. (233 mm)

5-18 in. (130 mm)

Approx. Weight 40 lb. (18.1 kg)

Model 6E2
Lifting Eye 916 in. (14 mm) x 1 in. (25 mm) Mounting Slots on 5-12 in. (140 mm) Centers 18-58 in. (473 mm) 22-12 in. (572 mm)

2-34 in. (70 mm)

11-18 in. (283 mm)

6-38 in. (162 mm)

34 in. (19 mm)

Approx. Weight 30 lb. (13.6 kg)

w w w. tnb.c a

A77

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Model 6E6
5-18 in. (130 mm)

Lifting Eye

916 in. (14 mm) x 1 in. (25 mm) Mounting Slots on 5-12 in. (140 mm) Centers 18-58 in. (473mm)

22-12 in. (572 mm)

2-34 in. (70 mm)

11-18 in. (283 mm)

6-38 in. (162 mm)

12 in. (13 mm)

Other models are available such as 26. Approx. Weight 30 lb. (13.6kg)

The following diagram shows how to construct a catalog number for a Molded Current-Limiting Fuse:
Indicates eld that must be lled in to complete order.

Voltage Class 5 15 25 35
5.0 kV 15.0 kV 25.0 kV 35.0 kV

Mounting Brackets Amperes 5 kV 10 20 30 50 65 80 100 115 125 150 200


80 100 125 150

15 kV 25 kV 35 kV
10 20 30 40 50 65 80 100 115 10 20 30 40 50 65 80 100 10 20 30 40 50

Mounting Bracket with Parking Stands and WMB Wall Bolted Style Hold Down Straps (HDS) Mounting Bracket with Parking Stands and WMBQ Wall Quick Release Style Hold Down Straps (QRS) See page A79 for additional options.

See page A75 for additional options.

Bushings 22 222
200 A Bushing Wells both ends 200 A Bushing Well on one end and two 200 A Bushing Wells on the other end 600 A Bushings on both ends 600 A Elbow Connector on one end and a 600 A Bushing on the other end; this arrangement is not available at 35 kV

2222 Two 200 A Bushing Wells on both ends 66 6E2 6E6

See outline drawings preceding this chart for additional details.

See page A75 for additional options.

A78

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Mounting Options
32-3/4 in. (832 mm) 29-3/4 in. (756 mm)

5-1/2 in. (140 mm)

6-3/4 in. (171 mm) 15 to 60

Approx. Weight 8 lb. (3.6 kg) Optional WMB Mounting Bracket with Adjustable Parking Stands for Vertical Mounting and Fuse Hold-Down Strips

9/16 in. (14 mm) x 1 in. (25 mm) Mounting Slots

Optional TMA Universal Tilt Mounting

Optional Fuse Mountings


Option No. HDS QRS WMB WMBQ SMB TMA-EM Description
Bolted-Style Hold-Down Strap (Qty: 1 required per end fitting) Quick-Release Style Hold-Down Strap (Qty: 1 required per end fitting) Wall-Mounting Bracket with Parking Stands and Bolted-Style Hold-Down Straps Wall-Mounting Bracket with Parking Stands and Quick-Release Style Hold-Down Straps Support Mounting Bracket for use with Models 6E2 or 6E6 end-fitting arrangements includes Bolted-Style Hold-Down Strap Tilt Mounting Adapter bolts to bottom of Wall-Mounting Bracket WMB or WMBQ to enable up to 60 angle mounting (Qty: 2 required per installation)

The option number may be added as a sufx to the MCLF catalogue number.

End Fitting Catalogue Numbers


200 A Bushing Well End Fitting 5, 15, 25, 35 Double 200 A Bushing Well End Fitting 5, 15, 25, 35 600 A Bushing End Fitting 5, 15, 25, 35 600 A Elbow Connector End Fitting 5, 15, 25 EF6E is equipped with a standard through-hole spade lug (Type 03700). Use this table only if end ttings are to be ordered and shipped separately from the fuse. See pages A77-A78 for assembled units.

Option No. EF2 EF22 EF6 EF6E

Description

System Voltage Class

IEEE 386-1995 Interface Reference


Figure 3 Figure 3 Figures 11 and 13 Figure 11

Assembly/Disassembly Tool
3/8 in. (10 mm) Sq. Drive

3/16 in. (5 mm) Hex

Other Options
Option No. MCLF-ADT Description
Hex Wrench for set screw removal and replacement when disassembling end fittings. Supplied as standard with replacement fuses.

w w w. tnb.c a

A79

Elastimold

Cable Accessories

Surge Arresters
Metal Oxide Varistor (MOV) Surge Arresters
Fully shielded, fully submersible for convenient energized connection with 200 A loadbreak or deadbreak components up to 35 kV Voltage surges that exceed the BIL rating of the distribution system components will cause damage to the installed equipment. To protect against these surges, overhead surge arresters are widely used. Their application is understood since overhead lines and equipment are directly affected by voltage surges (e.g. lightning). However, the use of overhead arresters alone will not guarantee proper protection of the insulation in the underground portion of an electrical distribution system. The let through surge from the riser pole arresters into the underground systems could be enough to cause damage to the aging equipment insulation. Elastimold MOV Surge Arresters provide high-voltage lightning and switching surge protection of transformers, cable, equipment and other components typically located on underground power distribution systems. Proper placement, voltage selection and coordination with riser pole arresters minimize damaging surge voltages by improving protective margins. Typical applications include installing an arrester at the end of a radial system or at both ends of an open point on a loop system. Additional arresters can be added at strategic locations upstream from the end point for optimum protection. Metal Oxide Varistor (MOV) Surge Arresters are available in three styles: Elbow (ESA), Parking Stand (PSA) and Bushing (BSA). The PSA and BSA arresters permit direct connection, eliminating the need for additional accessories. ESA Elbow Arresters are also available with a 200 A deadbreak interface for mating with other deadbreak accessories. The following page highlights the different installation options using Bushing and Parking Stand Arresters where Elbow Arresters are normally used. Using BSAs and PSAs will contribute to saving space inside transformers and improving operability.
IEEE 386 Interfaces; IEEE C62.11 Provide convenient energized connection with other 200 A loadbreak or deadbreak components. EPDM Molded Rubber Construction Fully shielded and fully submersible for a variety of applications. Compact Size Enables installation in your existing cabinetry, saving you money. Three Styles of Arresters Available Surge arresters t your application and are easy to install. Direct Connection on PSA and BSA Versions Eliminates the need for additional accessories, saving even more money. #4 AWG Ground Lead Tethered to the Jacket Withstands 10,000 A for 10 cycles without fusing. Controls end plug when ejected, preventing uncontrolled trajectory. Maintains the housing shield ground connection after failure.

Ratings
High Current, Short Duration All MOV Arresters withstand two discharges of 40 kA crest All MOV Arresters withstand 20 surges of Low Current, Long Duration 75 A/2,000 microseconds duration All MOV Arresters withstand 22 operations of 5 kA crest at 8 x 20 microseconds duration while energized at rated voltage for the initial 20 operations and at maximum continuous operating voltage (MCOV) for the final two operations

Duty Cycle Test

Following each of the preceding tests, MOV Arresters demonstrate thermal recovery at MCOV.

A80

w w w. tnb.c a

Elastimold

Cable Accessories

Surge Arresters
Installation Options

Bushing Well Loadbreak Bushing Insert

BSA Bushing Surge Arrester

Loadbreak Feed-Through Insert

Feed-Through

ESA Elbow Surge Arrester

Parking Stand

PSA Parking Surge Arrester

w w w. tnb.c a

A81

Elastimold

Cable Accessories

Surge Arresters
Loop-Feed Circuit (Type 2 Transformer)
Two Elbow Arresters and a Feed-Through This is one approach using elbow arresters only. (One of the elbow arresters could be mounted on the H1A bushing if operating procedures permit.) Elbow Arrester and Parking Stand Arrester This approach can reduce overcrowding (by eliminating the feed-through device). This is desirable in a mini-pad transformer.

Bushing Arrester and Parking Stand Arrester* This approach is best for increasing operability and reducing transformer overcrowding. The bushing arrester enables the source cable to be positioned on H1A, which conforms with some operating practices. A bushing arrester mounted on H1A can be directed downward without interference. Potential interference between an elbow arrester on H1B and a cable parked on P is eliminated. The bushing arrester requires signicantly less space than an elbow arrester used with a feed-through insert. Operability is enhanced because the open point can be closed by moving the parked cable to H1B without removing an arrester.
* Transformers must be specied with bushing wells.

Additional Margin of Protection An additional margin of protection may be gained by adding an arrester at the next transformer upstream on each side of the open point. This application is dependent on the system voltage and condition of the cable. If an additional arrester is added in the circuit, it can be an elbow arrester in combination with a feedthrough insert or it can be a bushing arrester. Use of a bushing arrester will reduce transformer faceplate overcrowding.
OR

Other Congurations Other congurations are possible, such as specifying a bushing arrester on every transformer. This enables the open point to be quickly and easily moved to any point in the circuit while maintaining the surge protection (without moving all of the portable surge arresters). The externally mounted bushing arrester provides the surge protection benets without the negative factors of an under-oil arrester.

A82

w w w. tnb.c a

Elastimold

Cable Accessories

Surge Arresters
Radial-Feed Circuit (End Point)
Single-Bushing Transformer To add surge protection to a single-bushing transformer, utilize a bushing arrester or an elbow arrester with a feed-through insert.

Two-Bushing Transformer To add surge protection to a two-bushing transformer at the end point of a radial-feed circuit, add an elbow arrester to the unoccupied bushing or utilize a bushing arrester.

Conversion of a Radial-Feed Transformer to a Loop-Feed, Open-Point Transformer To convert a single-bushing transformer to a loop-feed, open-point transformer, add a parking stand arrester and an elbow arrester in combination with a feed-through insert.

Protective Characteristics
Class MCOV* (kV RMS) Duty Cycle Rating (kV RMS)
3 6 10 12 15 18 10 12 15 18 21 24 27 30

Maximum Discharge Voltage (kV Crest) 8 x 20 Microsecond Currentwave 1.5 kA 3 kA 5 kA 10 kA 20 kA


10.5 20.5 30.5 40.0 48.0 56.5 30.5 40.0 48.0 56.5 65.5 78.5 87.5 98.5 11.0 21.5 32.5 42.5 51.0 60.0 32.5 42.5 51.0 60.0 69.5 83.5 93.0 101.5 11.5 23.0 34.5 45.0 54.0 64.0 34.5 45.0 54.0 64.0 74.0 89.0 99.0 108.0 13.0 25.5 38.5 50.0 60.0 71.0 38.5 50.0 60.0 71.0 82.5 99.0 110.0 120.0 14.5 30.0 43.5 56.5 68.0 80.5 43.5 56.5 68.0 80.5 93.2 112.0 124.5 136.0

15kV 2.55 15kV 5.1 8.4 15kV 15kV 10.2 15kV 12.7 15.3 15kV 8.4 25kV 25kV 10.2 25kV 12.7 15.3 25kV 17.0 25kV 35kV 19.5 22.0 35kV 35kV 24.4 * MCOV = Maximum Continuous Operating Voltage

w w w. tnb.c a

A83

Elastimold

Cable Accessories

Surge Arresters
MOV Surge Arresters
To specify and order an MOV Surge Arrester: 1) Determine the appropriate Maximum Continuous Operating Voltage (MCOV) for your system voltage using the Arrester Application Table below. 2) Specify the appropriate Elastimold catalogue number from the Selection Chart. Arrester Application Table
System Line-to-Line Voltage kVrms Nominal Maximum
2.40 4.16 4.80 6.90 8.32 12.47 13.20 13.80 13.80 6.90 8.32 12.47 13.20 13.80 13.80 20.78 20.78 23.00 24.94 24.94 28.00 2.54 4.40 5.08 7.26 8.80 13.20 13.97 14.50 14.50 7.26 8.80 13.20 13.97 14.50 14.50 22.00 22.00 24.34 26.40 26.40 29.80

Selection Chart
MCOV* kV RMS Solidly Grounded Neutral Circuits
2.55 2.55 5.10 5.10 5.10 8.40 8.40 8.40** 10.20 5.10 5.10 8.40 8.40 8.40** 10.20 12.70 15.30** 15.30 15.30 17.00** 17.00

Cat. No. 167BSA-3 167BSA-6 167BSA-10 167BSA-12 167BSA-15 167BSA-18 273BSA-10 273BSA-12 273BSA-15 273BSA-18 273BSA-21 167ESA-3 167ESA-6 167ESA-10 167ESA-12 167ESA-15 167ESA-18 273ESA-10 273ESA-12 273ESA-15 273ESA-18 273ESA-21 167PSA-3 167PSA-6 167PSA-10 167PSA-12 167PSA-15 167PSA-18 273PSA-10 273PSA-12 273PSA-15 273PSA-18 273PSA-21

Description

Voltage MCOV Class kV RMS


2.55 5.10 15kV 8.40 10.20 12.70 15.30 8.40 10.20 25kV 12.70 15.30 17.00 2.55 5.10 15kV 8.40 10.20 12.70

Picture

3-Wire Ungrounded Circuits


2.55 5.10 5.10 8.40 8.40 15.30 15.30 15.30 15.30 8.40 8.40 15.30 15.30 15.30 15.30

15 kV Class

BSA Bushing Surge Arrester (includes assembly tool) See Notes 14

25 kV Class

ESA Elbow Surge Arrester See Notes 1, 2, 5

15.30 8.40 10.20 25kV 12.70 15.30 17.00 2.55 5.10 15 kV 8.40 10.20 12.70

* MCOV = Maximum Continuous Operating Voltage. ** Preferred arrester MCOV for this system voltage.

PSA Parking Stand Arrester See Notes 13

15.30 8.40 10.20 25kV 12.70 15.30 17.00

1. Elastimold PSA and BSA Arresters are equipped with a fully rated 200 A switching and fault-close loadbreak bushing. 2. Elastimold Arresters use high-strength, silver epoxy-bonded MOV blocks and shunted spring connections for the best circuit connection. 3. A 36 in. 4 AWG ground lead is provided with each unit. 4. BSA installed by turning internal hex bolt (accessed through the 200A bushing interface) with a 516" hex wrench and bent-wire torque wrench supplied with each unit. 5. For 15 kV and 25 kV class deadbreak system Elbow Arresters, use catalog number 156ESA with the appropriate duty cycle rating.

A84

w w w. tnb.c a

Elastimold

Cable Accessories

Surge Arresters
MOV Surge Arresters (contd)
To specify and order an MOV Surge Arrester: 1) Determine the appropriate Maximum Continuous Operating Voltage (MCOV) for your system voltage using the Arrester Application Table below. 2) Specify the appropriate Elastimold catalogue number from the Selection Chart. Arrester Application Table
System Line-to-Line Voltage kVrms 35 kV Class Nominal Maximum MCOV* kV RMS Solidly Grounded Neutral Circuits
22.00** 24.40

Selection Chart
Cat. No. Description Voltage MCOV Class kV RMS Picture

3-Wire Ungrounded Circuits


22.00

375BSA-24

19.50

23.00 24.34 34.50 36.51 34.50 36.51 * MCOV = Maximum Continuous Operating Voltage. ** Preferred arrester MCOV for this system voltage.

375BSA-27

BSA Bushing Surge Arrester See Notes 14

22.00

375BSA-30

24.40

375ESA-24

19.50

375ESA-27

ESA Elbow Surge Arrester See Notes 23

35 kV

22.00

375ESA-30

24.40

375PSA-24

19.50

375PSA-27

PSA Parking Stand Arrester See Notes 13

22.00

375PSA-30

24.40

1. Elastimold PSA and BSA Arresters are equipped with a fully rated 200 A switching and fault-close loadbreak bushing. 2. Elastimold Arresters use high-strength, silver epoxy-bonded MOV blocks and shunted spring connections for the best circuit connection. 3. A 36 in. 4 AWG ground lead is provided with each unit. 4. BSA installed by turning internal hex bolt (accessed through the 200 A bushing interface) with a 5/16 in. hex wrench and bent-wire torque wrench supplied with each unit. 5. For 15 kV and 25 kV class deadbreak system Elbow Arresters, use catalogue number 156ESA with the appropriate duty cycle rating.

w w w. tnb.c a

A85

Elastimold

Cable Accessories

Molded Vacuum Recloser


The Elastimold Recloser, in either single-phase or threephase congurations, is fully compatible with SEL Controls
Smart, Light and Flexible The Elastimold Recloser is world-class, by design. It responds to every hardware requirement that utilities want.
Smart Our recloser is Smart Grid ready with three integral load-side voltage sensors and provision to add source-side voltage sensors, if desired. It was designed to be fully compatible with the industrys No. 1 name in controls, Schweitzer Engineering Laboratories. Light The three-phase Elastimold Recloser weighs 33% less than existing typical units. The simplicity of the mechanism design, and the compactness of the encapsulated components, contribute to making the Elastimold Recloser easier to move and install. Flexible The Elastimold Recloser is modular, so eld upgrades and retrots are easy and fast. The single phase recloser has a pole rotation mounting bracket for easier installation. Made with Your Needs in Mind We designed the Elastimold Recloser only after extensive talks with electric utilities. Its features, from easier-to-see open/close indicators to the many robust extra features that we consider standard, are there because of you.

Solid Dielectric Insulation Current & Voltage Sensors Current Transformer Top Silicone Sheds

Side Silicone Terminal

Integrated Pole Mounting Bracket Lifting Rings Vacuum Bottle

Highly-Visible 360 Indicators

Manual Tripping Lever Main Body EPDM Insulation Solid Dielectric Diaphragm Load Side Voltage Sensor Pull Rod Assembly Bottom Silicone Sheds Upper Cover

Recloser Operation The Elastimold Molded Vacuum Recloser (MVR) operates electrically by energizing a magnetic actuator system with a completely sealed housing. Each pole contains a vacuum interrupter sealed in solid dielectric insulation for mechanical and high dielectric strength. An open-closed position indicator provides a 360-degree view. An external manual trip assembly is located on the side; when in the down position, it maintains the recloser in a lockout position until it is manually restored. All electrical control connections are made through a sealed single-environment control cable connector on the side. The combination of the molded vacuum recloser with microprocessor controls accurately detects a wide range of line disturbances and provides reliable, high-speed isolation for adverse conditions.

Lower Cover

Magnetic Actuator

Position Indicator

A86

w w w. tnb.c a

Elastimold

Cable Accessories

Molded Vacuum Recloser


Catalogue Numbering System
Indicates eld that must be lled in to complete order.

S e q u e n t i a l

N u m b e r s *

Phases 1 3
Single-Phase Three-Phase

Control Model Voltage Class 15 27 38


15.0 kV 27.0 kV 38.0 kV

Sequential Numbers*
Control, Cable Length and Other Accessories

1 2 3

SEL-351R, SEL-351R Falcon (14-pin) SEL-651R (32-pin) SEL-351RS Kestrel (single-phase only)

Source-Side Voltage Sensing Interrupting Rating 12


25 kV Future

N 1 3

No One Voltage Sensor Three Voltage Sensors

* Consult your T&B sales representative for complete catalogue number conguration. SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.

Accessories
Cat. No. 3188D0120G1 3188D0121G1 3188C0122G1 3188C0123G1 3070A1191P1 3070A1190P1 3188C0075G1 3188D0119G1 3188B0126G1 3180A0661P1 3070B0913G1 1548FH-ANC3JNAA 1548FH-ANC3XNA1 Description
Three-phase Line Side Arrester Frame Three-phase Load Side Arrester Frame Single-phase Line Side Arrester Frame Single-phase Load Side Arrester Frame Wildlife Protector Top Bushing (one per phase) Wildlife Protector Side Bushing (one per phase) Source-side Voltage Sensors (one per phase) Substation Mounting Frame NEMA 2-hole pad NEMA 4-hole pad Aerial Lug Fisher Pierce Overhead Faulted Circuit Indicator Adaptive Trip ; 4 hr automatic reset time with current reset override (60 sec. after restoration of power), five ultra-bright LEDs for increase visibility display
TM

Fisher Pierce Overhead Faulted Circuit Indicator Adaptive Trip ; 4 hr automatic reset time with current reset override (60 sec. after restoration of power), with 4 hr temporary fault reset time, temporary fault indication option, four red and one amber LED
TM

Ratings and Specications


15 kV
Nominal System Voltage (kV RMS) Rated Maximum Voltage (kV RMS) Nominal Frequency (Hz) Phase Spacing on Three-Phase Units (Inches) BIL (kV) Power Frequency Withstand Dry (kV) Power Frequency Withstand Wet (kV) Continuous Current (A RMS) Eight (8) Hour Overload Current (A RMS) CT Ratio 14.4 17.1 50 or 60 15.5 150 50 45 800 960 1,000 to 1

27 kV
25 29.3 50 or 60 15.5 150 50 45 800 960 1,000 to 1

38 kV*
35 38 50 or 60 15.5 170 70 60 800 960 1,000 to 1 Interrupting Current (kA RMS Symmetrical) Making Current (kA Asymmetrical Peak) Creepage Distances (Inches Line to Ground) Arc-Extinction Medium Insulation Medium Mechanical Operations Operating Temperatures Voltage Sensor Accuracy (Load/Line) CT Accuracy Weight (SinglePhase/Three-Phase)

15 kV
12.5 32.5 41.5 Vacuum EPDM/Silicon Rubber 10,000 40C to 65C 3% / 1% Class 1 57 lb. / 208 lb.

27 kV
12.5 32.5 41.5 Vacuum EPDM/Silicon Rubber 10,000 40C to 65C 3% / 1% Class 1 57 lb. / 208 lb.

38 kV*
12.5 32.5 41.5 Vacuum EPDM/Silicon Rubber 10,000 40C to 65C 3% / 1% Class 1 58 lb. / 211 lb.

* Single phase 38 kV units are rated for use on grounded systems only. Three-phase 38 kV units can be used for single-phase tripping on grounded systems only. For ungrounded systems, three-phase tripping is required.