Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

N2XSEKRY 3 X (25-300) MM 3.6/6 KV

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

www.kmi.co.

id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Conductor
Inductance
(mH/km)
Current - Carrying
Capacity
at 30 C *
Short circuit
current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max.
(A)
in ground
Max.
(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEKRY 3 x (25-300) mm 3.6/6 kV
N2XSEKRY 3 x (25-300) mm 3.6/6 kV
Cu / XLPE / CTS / PVC / LS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specifcation : IEC 60502-2
Application :
For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
25 48.0 5,808
35 51.0 6,673
50 54.0 7,623
70 58.5 9,072
95 62.5 10,626
120 67.0 12,228
150 71.0 13,892
185 76.5 16,710
240 83.0 19,840
300 90.0 23,560
Electrical Data
25 0.727 0.927 0.342 156 146 3.58 1.03
35 0.524 0.668 0.325 189 175 5.01 1.03
50 0.387 0.494 0.313 224 205 7.15 1.03
70 0.268 0.342 0.296 278 250 10.01 1.03
95 0.193 0.247 0.285 335 298 13.59 1.03
120 0.153 0.196 0.276 384 337 17.16 1.03
150 0.124 0.160 0.268 434 377 21.45 1.03
185 0.0991 0.128 0.262 495 423 26.46 1.03
240 0.0754 0.099 0.255 576 485 34.32 1.37
300 0.0601 0.080 0.252 648 540 42.90 1.37
1
B
M
3
3
-
0
1


R
e
v
.

2
.
0

/

2
0
0
9
Galvanized Steel Wire Armor
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specifcation : IEC 60502-2
Conductor
Inductance
(mH/km)
Current - Carrying
Capacity
at 30 C *
Short circuit
current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max.
(A)
in ground
Max.
(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEKRY 3 x (25-300) mm 6/10 kV
N2XSEKRY 3 x (25-300) mm 6/10 kV
Cu / XLPE / CTS / PVC / LS / PVC / SWA / PVC
Application :
For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
25 53.0 6,897
35 56.0 7,697
50 59.0 8,650
70 63.5 10,135
95 67.5 11,829
120 71.5 13,437
150 77.0 15,920
185 81.0 18,024
240 87.5 21,238
300 93.0 24,670
Electrical Data
25 0.727 0.927 0.368 158 146 3.58 1.03
35 0.524 0.668 0.349 190 174 5.01 1.03
50 0.387 0.494 0.335 226 205 7.15 1.03
70 0.268 0.342 0.316 280 250 10.01 1.03
95 0.193 0.247 0.303 336 297 13.59 1.03
120 0.153 0.196 0.293 385 336 17.16 1.03
150 0.124 0.160 0.284 437 376 21.45 1.03
185 0.0991 0.128 0.277 497 423 26.46 1.37
240 0.0754 0.099 0.267 576 484 34.32 1.37
300 0.0601 0.080 0.261 649 539 42.90 1.37
1
B
M
3
3
-
0
2


R
e
v
.

2
.
0

/

2
0
0
9
Galvanized Steel Wire Armor
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specifcation : IEC 60502-2
Conductor
Inductance
(mH/km)
Current - Carrying
Capacity
at 30 C *
Short circuit
current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max.
(A)
in ground
Max.
(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEKRY 3 x (25-300) mm 8.7/15 kV
N2XSEKRY 3 x (25-300) mm 8.7/15 kV
Cu / XLPE / CTS / PVC / LS / PVC / SWA / PVC
Application :
For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
25 59.0 8,160
35 62.0 9,122
50 65.0 10,110
70 69.5 11,806
95 73.5 13,469
120 79.0 15,740
150 82.5 17,559
185 87.0 19,833
240 93.5 23,304
300 99.0 26,514
Electrical Data
25 0.727 0.927 0.395 159 145 3.58 1.03
35 0.524 0.668 0.374 192 174 5.01 1.03
50 0.387 0.494 0.359 228 204 7.15 1.03
70 0.268 0.342 0.338 281 249 10.01 1.03
95 0.193 0.247 0.324 339 297 13.59 1.03
120 0.153 0.196 0.312 388 336 17.16 1.03
150 0.124 0.159 0.302 438 375 21.45 1.37
185 0.0991 0.128 0.294 496 421 26.46 1.37
240 0.0754 0.098 0.283 576 483 34.32 1.37
300 0.0601 0.080 0.275 649 538 42.90 1.37
1
B
M
3
3
-
0
3


R
e
v
.

2
.
0

/

2
0
0
9
Galvanized Steel Wire Armor
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specifcation : IEC 60502-2
Conductor
Inductance
(mH/km)
Current - Carrying
Capacity
at 30 C *
Short circuit
current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max.
(A)
in ground
Max.
(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEKRY 3 x (35-300) mm 12/20 kV
N2XSEKRY 3 x (35-300) mm 12/20 kV
Cu / XLPE / CTS / PVC / LS / PVC / SWA / PVC
Application :
For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.
Special Features on Request
Fire Resistance
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
35 67.5 10,368
50 70.5 11,464
70 76.5 13,948
95 80.0 15,701
120 84.5 17,477
150 88.5 19,540
185 92.5 21,726
240 98.5 25,040
300 104.0 28,283
Electrical Data
35 0.524 0.668 0.395 193 173 5.01 1.03
50 0.387 0.494 0.379 228 203 7.15 1.03
70 0.268 0.342 0.357 283 249 10.01 1.03
95 0.193 0.247 0.341 341 296 13.59 1.37
120 0.153 0.196 0.328 389 335 17.16 1.37
150 0.124 0.159 0.318 438 374 21.45 1.37
185 0.0991 0.128 0.308 496 420 26.46 1.37
240 0.0754 0.098 0.296 576 481 34.32 1.37
300 0.0601 0.079 0.287 649 537 42.90 1.37
1
B
M
3
3
-
0
4


R
e
v
.

2
.
0

/

2
0
0
9
Galvanized Steel Wire Armor
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specifcation : IEC 60502-2
Conductor
Inductance
(mH/km)
Current - Carrying
Capacity
at 30 C *
Short circuit
current at 1 sec
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
in air
Max.
(A)
in ground
Max.
(A)
Conductor
Max.
(kA)
Screen
Max.
(kA)
N2XSEKRY 3 x (50-300) mm 18/30 kV
N2XSEKRY 3 x (50-300) mm 18/30 kV
Cu / XLPE / CTS / PVC / LS / PVC / SWA / PVC
Application :
For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.
Special Features on Request
Oil Resistance
UV Resistance
Flame Retardant Cat. A, B, C
Flame Retardant Non Category
Anti Termite
Anti Rodent
Low Smoke Zero Halogen
Note :
Conductor Shape
50 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum 2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
50 85.0 15,999
70 90.0 18,015
95 94.0 20,007
120 98.0 21,870
150 102.0 23,925
185 106.0 26,379
240 112.0 29,868
300 117.5 33,789
Electrical Data
50 0.387 0.494 0.421 230 203 7.15 1.37
70 0.268 0.342 0.396 284 247 10.01 1.37
95 0.193 0.247 0.378 340 294 13.59 1.37
120 0.153 0.196 0.364 389 333 17.16 1.37
150 0.124 0.159 0.351 438 372 21.45 1.37
185 0.0991 0.128 0.340 496 417 26.46 1.37
240 0.0754 0.098 0.326 575 479 34.32 1.37
300 0.0601 0.079 0.315 646 532 42.90 1.37
1
B
M
3
3
-
0
5


R
e
v
.

2
.
0

/

2
0
0
9
Galvanized Steel Wire Armor

You might also like