E560 Cmu80 DB PDF
E560 Cmu80 DB PDF
E560 Cmu80 DB PDF
Industrial
IT
Remote Terminal Unit
Data Sheet
Communication Unit 560CMU80
Application
The 560CMU80 is the CMU board
(CMU = communication unit) of the remote terminal
unit RTU560E.
The essential tasks are:
Managing and controlling of the I/O boards
Reading process events from the input
boards.
Writing commands to the output boards.
Serial communication with up to three control
centers
Managing the time base for the RTU560E
station and synchronizing the I/O boards.
Handling the dialogue with RTU560E's and
Web-Browser (PPP-Protocol) via the MMI
interface or via Ethernet (optional).
Characteristics
The two microprocessors are the essential
hardware parts of the board, which share
themselves in the tasks.
AMD SC400 32 Bit Main Processing Unit
SLC 8 Bit Serial Line Controller
The SLC with its serial interfaces transmits RS485
signals. For example it works only as master for the
RTU I/O bus.
The AMD SC400 is responsible for the other tasks.
The AMD SC400 handles the absolute time and
date for the RTU. The 560CMU80 stores
configuration files power fail save in a removable
CompactFlash
TM
memory card. That allows the
RTU560 to have valid configuration data after
power on and RTU560E will be available again
after a short initialization.
The serial communication interfaces
CP1 Communication Port 1
CP2 Communication Port 2
MMI Man Machine Interface
are designed to RS232C standard
The serial communication interface
CPA Communication Port A
is designed to RS485 standard
The Ethernet communication interface (R0002 only)
10BaseT
560CMU80 indicates operational and error states
by LEDs on the housing top.
Ethernet:
A (1x) green Activity
L (1x) green Link
C (1x) yellow Copy Data
CP1, CP2, CPA:
Tx (3x) green Transmit data
ports 1, 2, A
Rx (3x) green Receive data
ports 1, 2, A
CE (3x)yellow Communication error
ports 1, 2, A
The exact definitions for the LEDs have to be taken
from the functional description of the RTU560
releases.
Doc.-No.: 1KGT 150 493 V002 1 1
ABB Utilities
Data Sheet Communication Unit 560CMU80 Industrial
IT
RTU560
MMI / DB9
CPA / RJ45
AMD
SC400
FPGA
ASIC
BIOS
+
DIP32
SMSC
37C93x
AMD SCC
85C30
80C251+
DualPort
RAM
Compact
Flash
RS232
RS485
optional
SMSC
91C94
10BaseT / RJ45
RS232
RS232
CP1 / RJ45
CP2 / RJ45
RS485
E-Bus SPB /
DIN41612
Com / 2 x 5 pole
Modem
Modem
Modem1 / RJ45
Modem2 / RJ45
PC104-Bus
S
P
A
-
B
U
S
Fig. 1: Block diagram communication unit 560CMU80
2 Doc.-No.: 1KGT 150 493 V002 1
ABB Utilities
Industrial
IT
RTU560 Data Sheet Communication Unit 560CMU80
Technical Data
In addition to the RTU560 general technical data,
the following applies:
Main Processing Unit MPU
Microprocessor: ELAN 400 (486) @
66 MHz
(incorporating an
Intel 486
TM
class 32-bit
processor)
RAM: 16 MByte
Flash Memory: 32 MByte
CompactFlash
TM,
removable
(delivered with firmware)
Serial Line Controller SLC
Controller Type: 80C251
RAM: 32 kByte
Dual Ported RAM: 16 kByte
MMI Interface
Physical Interfaces: RS232C
Bit rate: fix 38400 bit/s
Serial Interfaces 1 and 2
Physical Interfaces: RS232C
Bit rate: 38400 bit/s
Serial Interfaces A
Physical Interface: RS485
Bit rate: 19200 bit/s
Ethernet Interfaces (R0002 only)
Interface: 10BaseT / RJ45
Alarm- / Warning Relays
Switching current 6 A (@ 250 V AC)
1 A (@ 200 V DC)
Switching voltage 250 V AC, 200 V DC
Power Consumption
5 V DC: 650 mA
Mechanical Layout
Printed Circuit: 6HE, Euro-card format
(233.4 x 160 mm)
2 slots (8R, 40 mm)
Weight: approx. 0.4 kg
Connector Types
Subrack connector: Indirect, 48 pole
Type F DIN 41612
Serial Interfaces
1, 2, A, : RJ45 jack, 8-pole
Ethernet (R0002): RJ45 jack, 8-pole
MMI interface: Sub-D, 9-pole, male
Modem: SAMTEC TW series 2-row
32-pole, male
SAMTEC TW series 2-row
4-pole, male
Environmental Conditions
Temperature: 0 ... 70 C
Relative humidity: 5 ... 95 %
(non condensing)
Ordering Information
560CMU80R0001 1KGT008800 R0001
560CMU80R0002 1KGT008800 R0002
Doc.-No.: 1KGT 150 493 V002 1 3
ABB Utilities
Data Sheet Communication Unit 560CMU80 Industrial
IT
RTU560
4 Doc.-No.: 1KGT 150 493 V002 1
ABB Utilities GmbH
Kallstadter Str.1, 68309 Mannheim
Telefon: +49 (0) 621 381-7592
Telefax: +49 (0) 621 381-7622
www.abb.de/uta