Parallel Operation of Alternators
Parallel Operation of Alternators
Parallel Operation of Alternators
Aim
LEARNING OUTCOMES
• Describe the conditions necessary for the safe connection of a generator to live
bus-bars.
• Describe the “lamps dark” and “sequence lamps” operation.
• Explain the meaning of kW, kVA and power factor.
• Explain with a phasor diagram, the effect of change of prime-mover input during
parallel operation, making reference to power factor, kW and kVA .
• Explain with a phasor diagram, the effect of change of field excitation during
parallel operation, making reference to power factor, kW and kVA .
• Explain how parallel operation may be continued if the AVR of one generator
should fail to regulate automatically.
• Explain why reverse power protection is necessary in the event of power loss by
the prime mover of one generator.
• State with reasons whether two alternators with different number of poles may be
run in parallel.
Overview
___________________________________________________________________
PTM / Jul 2002 76 SP / SMA
Module : Electrical Engineering MT 3011
(a) The terminal voltage of the incoming machine and the already running alternator
on the bus bar must be equal.
(c) The phase sequence of the two voltages must be the same.
(d) The emf of the incoming generator and the bus bars must be in phase.
The circuit breaker of the incoming generator must be closed when the voltages of
the two generators are in phase with each other i.e. waveform of both bus bar and
incoming generator are synchronised.
In this way, with the incoming machine slightly fast, it will immediately assume load.
If switch on when running slow, it would take motoring load which might possibly
operate the reverse power relay. That is why reverse power relays are provided
with time lag, to give sufficient time to correct the fault.
___________________________________________________________________
PTM / Jul 2002 77 SP / SMA
Module : Electrical Engineering MT 3011
Bus Bars
R
Line Voltage
Y
Line Voltage
B
Circuit
Breaker
Alternator
Phase
Winding
Phase
Voltage
Figure 1
Three lamps can be connected across the switch as shown in Figure 2 to form a
simple synchroscope.
When the phase angle, Ø, between bus bar and in-coming machine voltages
becomes zero, VR, VY, VB, all become zero and the lamps becomes dark. The e.m.f.
of the bus bar and the incoming generator are in phase. This is the required
condition for closing the switch.
L L L
Y1
B1
___________________________________________________________________
PTM / Jul 2002 R1 78 SP / SMA
Incoming
Generator
Module : Electrical Engineering MT 3011
VR
R2 R1
VB
B2
B1
VY
Y2 Y1
VR V R1 V
V Y2 Y
V V Y1
R2
V VB2
B1
VB
Figure 2
___________________________________________________________________
PTM / Jul 2002 79 SP / SMA
Module : Electrical Engineering MT 3011
L L L
Incoming
Generator
VR
R2 R1
VB VR V R1
V Y2
V
Y1
V
B2 B1 R2
VY
V
B1
Y2 Y1
Bus Bars V
B2
R Figure 3
B
Incoming Voltmeter
V S F V
___________________________________________________________________
PTM / Jul 2002 80 Bus SP
Bar/ SMA
Incoming Synchroscope Voltmeter
Generator
Module : Electrical Engineering MT 3011
Figure 4
Synchronising Power
The synchronising current, Ic set up by this e.m.f. takes power from the machine that
is running faster and delivers it to the machine that is running slower. Thus the faster
machine is pulled back or accelerated by motor action, until their voltages come
more nearly into phase.
(A time delay of say 5 seconds prevents reverse power tripping due to surges at
synchronising).
This action reduces Ec and therefore reduces Ic so that again, the synchronising
current limits itself. The greater the phase displacement of the e.m.f.s when the
synchronising switch is closed, the greater are Ec and Ic and the more violent is the
action pulling the machines into phase. This sets up dangerous high values of
torque on the shafts against the driving torque of the prime movers.
E'1
0-
Ec φ
___________________________________________________________________
PTM / Jul 2002 81 E1
SP / SMA
E2
Module : Electrical Engineering MT 3011
Figure 5
The current Ic again lags behind Ec by the angle θ determined by the ratio of
reactance to resistance in the circuit between the machines.
P1 = E1Ic cos α
P2 = E2Ic cos β
The mechanical power which is exchanged between the machines while they are
out of phase and which brings them into phase is very important for the successful
operation of alternators in parallel. It is called synchronising power and the
circulating or synchronising current is so called because it keeps the machine in
synchronism.°
___________________________________________________________________
PTM / Jul 2002 82 SP / SMA
Module : Electrical Engineering MT 3011
E1
I1
I2
XS
IS
Terminal volttage
R across a load
E1 E2
E1 E2
E2
External Local
Circuit Circuit
Figure 6
Suppose the alternator 1 gets extra input, its rotor will accelerate and emf E1
will get ahead of E2. As a consequence there is a resultant voltage Ec = E1 - E2 in
the local series circuit which will drive a current, Ic through the two armatures.
From Fig. 7 it is seen that Ic known as synchronising current is almost in phase with
E1 and in phase opposition to E2.
___________________________________________________________________
PTM / Jul 2002 83 SP / SMA
Module : Electrical Engineering MT 3011
It is thus seen that there is an automatic synchronizing action, tending to retard the
faster machine and accelerate the slower machine, thereby maintaining the
synchronism.
E1
IC
Ec
2
Local Circuit
E2
Figure 7
Suppose the 2 alternators are now equally loaded such that I1 = I2 and internal pf
cos θ1 = cos θ2. If fuel supply to alternator 1 is increased by governor setting Ic is set
up as before.
For alternator 1
For alternator 2
___________________________________________________________________
PTM / Jul 2002 84 SP / SMA
Module : Electrical Engineering MT 3011
From Figure 8 which shows the phasor diagram giving distribution of load, it is clear
that
Thus it can be stated that the effect of increasing fuel to prime-mover is to make it
take an increase share of the load whereas the other alternator operating in parallel
with it is relieved of its load by a corresponding amount.
E1
I '
1
'
1
I
1
1
IC
Ec
'
I2
'
2 2
I2
Figure 8
E1
I '
1 Figure 9 shows the
E
2 graphical summation of
' vectors shown above.
1
I
1
1
IC
Ec
'
I2
' 2
2
2 I
___________________________________________________________________
PTM / Jul 2002 85 SP / SMA
E2
Module : Electrical Engineering MT 3011
Figure 9
If two alternators are equally loaded and the currents are I1 and I2 at internal pf
angles θ1 and θ2 respectively.
EC = E1 - E2
which circulates a load current Ic. This circulating current Ic must be added to I1 and
I2 to get the new currents. These are I1’ for alternator I and I2’ for alternator 2.
From Figure 10 which is a phasor diagram showing the effect of excitation, it is seen
that though I1’ has increased, its real power component is unchanged and similarly
I2’ has decreased but its real component remains the same.
It can thus be said that a change in the excitation modifies the distribution of reactive
power but the division of active or real power is unaltered.
___________________________________________________________________
PTM / Jul 2002 86 SP / SMA
Module : Electrical Engineering MT 3011
E1 E1
E2 E2
I '
' 1
1 I
1
Ec Ec
IC
IC
2
'
I2 2
'
I2
E2 E2
Figure 10
Alternators in parallel must be driven at the same electrical speed; that is at the
same frequency. The terminal voltages of all parallel connected generators must be
the same, since their terminals are all respectively connected together.
Hence a 4-pole alternator, driven at 1800 rpm may be operated in parallel with a 6-
pole alternator driven at 1200 rpm. Each generates a 60 cycle e.m.f. and therefore
is driven at the same electrical speed.
___________________________________________________________________
PTM / Jul 2002 87 SP / SMA