IX INVERTER -
I Point Wiring
1 Wiring for the following light points with 2 x
2.5 sq. mm + 1 x 1.5sqmm (green ) PVC
insulated copper conductor FR wires of
650/1100 Volts grade in concealed / exposed
PVC conduits/ PVC Trunking as called for
including providing 6 amp flush type switches
(as, approved),including providing and fixing
of White Polycarbonate modular cover
plate for switch boxes.
2 Wiring to looped light points with 2x1.5 sq. Nos 250 400.00 100,000.00
mm. FR/PVC insulated copper conductor
1100 V grade wires in concealed or surface
mounted 20/25 mm dia PVC conduit /
existing MS Trunking as required.
Including earthing of fixtures and outlet
box with 1.5 sq. mm. FR PVC insulated
copper conductor 1100 V grade green earth
wire. (Including providing GI flexible
conduit from 'Tee' to fixture).
3 Supplying and fixing of 2 nos. 6 amp outlet Nos 120 650.00 78,000.00
international / universal type pin
including providing 1 no. 6 amp indicator
switch ( Red ) housed in 16 gauge MS box
with approved White Polycarbonate
modular cover for outlet boxes.( For UPS,
wiring & conduiting are separate items ).
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ
4 Supplying and fixing of 1 nos. 6 amp 5-pin Nos 120 310.00 37,200.00
outlet with ROUND PIN including providing
1 no. 6 amp switch housed in 16 gauge MS
box with approved White Polycarbonate
modular cover for outlet boxes.( For Raw
Power at W/Station , wiring and
conduiting are separate items)
9 UPS Wiring for , 6 amp light plug outlet with Nos 10 1,200.00 12,000.00
1.5 sq. mm PVC insulated copper conductor
FR wires in concealed/exposed PVC conduits
including providng 6 amp switch, MS box for
housing switches sockets, approved White
Polycarbonate modular cover to outlet
boxes and earthing. ( HVAC Fire Dampers )
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ
10 Wiring for 16 amp power outlet points with 4 Set 4 3,600.00 14,400.00
sq. mm PVC insulated copper conductor wires (Two
for the first socket outlet and 2.5 sq. mm PVC outlets
insulated copper conductor FR wires for the )
second outlet 650/1100 Volts grade in
concealed/exposed PVC conduits as called for
including providing 16 amp flush type 6 pin
socket and switch, MS outlet boxes for power
outlets. Approved White Polycarbonate
modular cover to outlet boxes and earthing.
(Only two outlets shall be connected to each
circuit)
11 Wiring for 16 amp power outlet points with 4 Nos 2 3,200.00 6,400.00
sq. mm PVC insulated copper conductor wire
of 650/1100 Volts grade in
concealed/exposed PVC conduits including
providing 16 amp flush type combined 6 pin
sockets and switch, approved White
Polycarbonate modular cover to MS outlet
boxes and earthing. (Only one outlet shall be
connected to each circuit).
III
MAIN PANELS/PDU's/ DB'S & CABLES & CABLE TRAYS
j Sheet metal enclosed, double door,6 way TPN Nos 2 14,500.00 29,000.00
DB with 18 Nos. of 10/20 amp SPMCB i.e. 18
Nos. of 10/20 amp SPMCB arranged in 3 rows
& controlled by 1 No. 40 amp TPN MCB &
neutral link, with 20 DP MCB protection for
Each Phase, complete with Neutral + Earth
Links. ( FOR SRV UPS DB'S)
l 3 x 10 SQ MM RM 0 -
m 3 X 4 SQ MM RM 0 -
a 50 x 6 MM GI TAPE RM 0 - -
b 40 x 6 MM GI TAPE RM 0 - -
c 25 x 6 MM GI TAPE RM 0 - -
d 8 SWG bare GI wire. RM 0 30 -
e 50 x 6 MM COPPER TAPE RM - -
f 25 x 3 MM COPPER TAPE RM -
g 25 x 3 MM COPPER TAPE in PVC SLEEVE RM 150 450.00 67,500.00
2 Providing earthing stations (B Class GI pipe Each 0 - -
earthing) complete as per I.S. specifications
(GI pipe shall be 50 MM dia) (GI pipe 16 feet
and depth of pit 17 feet). (With Heavy Duty
Manhole)
c. 110 MM DIA RM 0 - -
(6 KG PER SQ CM -
e. 50 MM DIA RM 0 - -
(6 KG PER SQ CM - CLASS
5. Providing and laying the following GI pipe
including digging and back filling of trench up to
a maximum depth of 750 mm.
a. 100 MM DIA (B Class) RM 30 500.00 15,000.00
6. Providing manholes 600 x 600 x 600 MM Each 4 1,500.00 6,000.00
deep along with CI ( Heavy ) manholes covers.
VII
CONDUITING FOR FIRE ALARM ,ACCESS CONTROL, BMS, CCTV, & SECURITY SYSTEM
IX
SUPPLY & INSTALLATION OF INVERTER
1. Supplying, installation, testing and Set 0 -
commissioning of 10 KVA invertor DSP pure
Sinewave output single phase input and single
phase output including batteries suitable for 15
minutes back up, trolley on wheels to house the
batteries. The inverter should have the following
features :
- Quick change-over from Mains to Inverter Mode