Katalog Elektronik
Katalog Elektronik
Katalog Elektronik
Company Profile
Milestones
Oil Insulated Instrument Transformers
- Current Transformers
- Capacitive Voltage Transformers
- Inductive Voltage Transformers
Epoxy Resin Insulated Transformers
- Indoor Type Current and Voltage Transformers
- Outdoor Type Current and Voltage Transformers
Disconnecting Switches
Quality Assurance
Contents
Social Contributions
Company
Profile
EMEK ELEKTRK ENDSTRS A.. aim to manufacture
high quality and reliable products, taking both safety
and environmental requirements into consideration.
EMEK quality for design and manufacturing, has been
certified by both local and international institutes.
EMEK has become a renowned world trademark for
delivery, quality and service.
EMEK was established in 1969 as the first company of
BARMEK Holding and production began in a small
workshop in Ankara.
EMEK signed a licence agreement with Balteau,
Belgium in 1971 for the transfer of technology to
manufacture oil filled current transformers and
inductive voltage transformers up to 170 kV. The
agreement also included transfer of technology for cast
epoxy resin instrument transformers.
In 1972, EMEK moved to her new plant, 23 km from
downtown Ankara. Today, the plant comprises of
11,500 m covered area and 27,500 m open area.
In 1975, EMEK signed another technology transfer
agreement with ICAR Italy, for manufacturing of
capacitive voltage transformers and LV power
capacitors.
north america
europe
CANADA
COSTA RICA
CUBA
DOMINICAN REPUBLIC
EL SALVADOR
GUETAMALA
MEXICO
PANAMA
TRINIDAD&TOBAGO
USA
AUSTRIA
CROATIA
DENMARK
ESTONIA
FRANCE
GERMANY
GREECE
HUNGARY
IRELAND
ITALY
KOSOVA
LUXEMBOURG
MALTA
MOLDOVA
NORTHERN CYPRUS
NORWAY
PORTUGAL
ROMANIA
RUSSIA
SPAIN
SWEDEN
SWITZERLAND
TURKEY
UKRAINE
UNITED KINGDOM
asia
EMEK Manufacture;
Instrument Transformers
Oil filled current transformers up to 420 kV,
Capacitive voltage transformers up to 420 kV,
Oil filled inductive voltage transformers up to 420 kV,
Epoxy Resin Transformers
Indoor type epoxy resin current and voltage
transformers up to 36 kV,
Outdoor type epoxy resin current and voltage
transformers up to 36 kV,
Disconnecting Switches
Disconnecting switches up to 245 kV,
Capacitors
Low voltage power capacitors
africa
south america
BRAZIL
CHILE
COLOMBIA
ECUADOR
PERU
VENEZUELA
EGYPT
ETHIOPHIA
GHANA
KENYA
LBYA
MALI
MOROCCO
MOZAMBIQUE
NIGERIA
SOUTH AFRICA
TANZANIA
TUNISIA
UGANDA
ZAMBIA
ZIMBABWE
middle east
IRAN
IRAQ
JORDAN
LEBANON
OMAN
PALESTINE
QATAR
SAUDI ARABIA
SYRIA
UNITED ARAP EMIRATES
YEMEN
oceania
AUSTRALIA
FIJI
NEW ZEALAND
PAPUA NEW GUINEA
AZERBAIJAN
BANGLADESH
BRUNEI
CAMBODIA
HONG KONG
INDIA
INDONESIA
JAPAN
KRYGYZSTAN
LAOS
MALAYSIA
MONGOLIA
MYANMAR
NEPAL
PAKISTAN
PHILIPPINES
SINGAPORE
SOUTH KOREA
SRI LANKA
TAIWAN
TAJIKISTAN
THAILAND
TURKMENISTAN
VIETNAM
MILESTONES
1980
1990
1994
1969
1971
1982
1972
1984
1973
1975
1976
1998
1985
2006
1988
2008
2010
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESCRIPTION
Production
EMEK current transformers are
manufactured in Ankara Turkey.
CURRENT
TRANSFORMERS
UP TO 420 KV
General Description
We manufacture oil insulated current transformers up to
420 kV
Above 170 kV, Cascade type transformers which include two or
three bushings is provided.
Primary and secondary cores are housed in porcelain / polymeric
insulator or tank.
Transformers are hermetically sealed.
Well proven hair pin technology is used.
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESIGN CHARACTERISTICS
Frequency
50 Hz, 60 Hz
Secondary Current
1 A, 2 A or 5 A, others on request.
Primary Current
up to 4000 A
Thermal and Dynamic Ratings
Short time thermal current ratings up to 50 KA/ 3 sec and
dynamic current ratings up to 125 KA peak.
Continuous Thermal Current
1.2 x In continuous (up to 2.0 x In on request).
Insulation
Oil impregnated paper, high dielectric strength, low dielectric
losses.
Graded layers with well rounded edges enable a uniformly
distributed field over the whole unit.
Insulating Oil
The insulating oil is mineral oil in conformity with IEC 60296.
Before impregnation, moisture and gases are removed from
the oil by special processes.
Drain plug for taking samples and oil refilling facilities are
provided on request.
Floating type oil level indicator is standard supply.
Oil Impregnation
Heat and vacuum are applied to the fully insulated windings
after assembly of the current transformer for drying purposes,
followed immediately by the oil impregnation procedure.
Bracelets
All bracelets used on transformers are made from
aluminium alloy.
Head
The housing head is fabricated from corrosion protected
aluminium.
Every housing is subject to pressure and vacuum test before
assembly.
Base Plate
Base of the transformers are fabricated from steel and
galvanised.
Name Plate
Name plates are stainless steel and weatherproof.
Altitude
Standard design is suitable up to 1000 m above sea level.
Optional Accessories
Capacitive tap
Steel support structure
Primary connectors
Marshalling box
Earthing
Earthing terminals are located on the base of the
transformers.
Clamp type terminals are available on request.
Maintenance
Maintenance free, simple recommendations;
Clean the bushing at regular
intervals depending on the degree of pollution.
Ensure that there is no oil leakage.
Painting
External surface of the transformers, which are already
corrosion protected, are additionally painted grey. Other
colours are available on request.
Earthquake Design
Standard design is up to 0.6g.
CURRENT
TRANSFORMERS
UP TO 420 KV
1
2
5
4
8
Assembly
Before the assembly, following visual checks should be made;
There are no oil leaks,
The bushing is not damaged,
The aluminium protective cover on the bellows is not damaged,
There is no damage on the primary terminals,
The oil level indicator indicates sufficient oil level.
3
10
Packing
The transformers are packed in rugged wooden crates which are
suitable for overseas transportation.
The transformers are encapsulated in polyethylene covers to
keep them from environmental effects.
Wooden crates can be lifted by either a fork lift or by a crane
with slings.
Hermetic Seal
Oil volume variations are compensated with stainless steel
bellows placed in the head of the transformers. With this
facility there will be no contact between air and oil in the
transformers.
The dielectric strength will remain unchanged for the life time
of the CT.
Mechanical Strength
Applied load to the primary terminal
in horizontal and vertical is in conformity
with IEC 60044.1 and IEC 60186.
Ambient Temperature
Standard design is suitable for
temperature range -50 C to +50C.
Other ranges on request.
Bushings
Brown, Grey glazed porcelain or composite.
Primary Terminals
Primary terminals are made from tin plated copper.
Vertical and horizontal primary terminals are available.
Dimensions depend on rated primary current.
Stud, nema pad or clamp type primary terminals are available.
11
12
Cores
Grain oriented silicon steel is used.
The core shapes are toroidal with or without air gap.
Electrolytic copper suitable to withstand rated continuous
current and short time thermal current is used for primary
winding.
Enamelled electrolytic copper wire is used for
Secondary winding.
8
13
10-Secondary Windings
11-Secondary Windings Support
12-Oil
13-Base Plate
14-Lifting Holes
15-Secondary Terminals
16-Oil Sampling Valve
17-Oil Filling Tap
8-Primary Winding
9-Oil
10-Oil Filling Tap
11- Tank
12-Secondary Windings
13- Secondary Box
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESCRIPTION
CAPACITIVE
VOLTAGE
TRANSFORMERS
UP TO 420 KV
Production
EMEK capacitive voltage transformers are
manufactured in Ankara Turkey.
General Description
We manufacture oil insulated capacitive voltage transformers
up to 420 kV
CVTs are composed of two seperate part: capacitive voltage
divider and tank.
Above 170 kV, Multiple bushings are supplied for capacitive
voltage divider part.
Oil inside the tank and the capacitive voltage divider is different
and they do not mix with each other.
Transformers are hermetically sealed.
Porcelain / polymeric insulator can be supplied upon request.
10
11
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESIGN CHARACTERISTICS
Frequency
50 Hz, 60 Hz
Magnetic Unit
Description
The hot dip galvanised steel tank houses oil impregnated
magnetic unit.
Paper Insulation
Oil impregnated paper is used which has high dielectric
strength, low dielectric losses.
Mechanical Strength
Applied load to the primary terminal in horizontal and vertical
is in conformity with IEC 60044.5 and IEC 60186.
Ambient Temperature
Standard design is suitable for temperature range -20 C to +40 C.
Oil Impregnation
Heat and vacuum are applied to the fully insulated windings
after assembly of the magnetic unit for drying purposes.
Accessories
Fixing holes, lifting holes, secondary terminal box, name plate,
warning plates are also provided in our standard design.
Tank
Tank is made from hot dip galvanised steel and painted with
grey colour.
The magnetic unit consists of the reactor (inductance
coil), short circuit protection device, anti ferro resonance
filter and intermediate transformer.
CAPACITIVE
VOLTAGE
TRANSFORMERS
UP TO 420 KV
EMEK
EMEK
HV terminal
PTFE (teflon)
Special Capacitor
Capacitor
Porcelain
Tuning
The CVT is tuned in the factory and sealed. No further tuning
on site is required.
Description
The capacitor stacks in Emek CVTs are the mixed type
which means paper and plastic film are used together
as the dielectric.
Capacitor elements are stacked and bound together to
maintain constant pressure.
The electrodes are made of soft rolled aluminium.
12
Packing
The transformers are packed in rugged
wooden crates which are suitable for overseas transportation.
The transformers are encapsulated in polyethylene covers to
keep them from environmental effects.
Wooden crates can be lifted by either a fork lift or by a crane
with slings.
Capacitive Unit
Optional Accessories
Steel support structure
Primary connectors
Marshalling box
If required mount line traps can be provided at order stage.
Bushings
Capacitor stacks are housed in porcelain
or polymeric insulator.
Bushings are brown, grey glazed porcelain
or composite.
Maintenance
Maintenance free, simple recommendations;
Clean the bushing at regular
intervals depending on the degree of pollution.
Ensure that there is no oil leakage.
Altitude
Standard design is suitable up to 1000 m above sea level.
Bracelet
All bracelets used on transformers are made of aluminium alloy.
Oil Impregnation
Heat and vacuum are applied after assembly of the
capacitive unit for drying purposes, followed
immediately by oil impregnation procedure
LV Insulator
MV Insulator
EMEK
Earthquake Design
Standard design is up to 0.6g.
Core
High quality sheet steel cores are used.
Enamelled electrolytic copper wire is used for primary windings.
Enamelled electrolytic copper wire is used for secondary
windings.
Oil Insulation
The insulating oil is mineral oil in conformity with IEC 60296.
Before impregnation, moisture and gases are removed from the
oil by special processes.
Drain plug for taking samples and oil refilling facilities are
provided on request.
Floating type oil level indicator is standard supply.
CORRECT
MAX INCLINATION
WRONG
Oil Insulation
The insulating oil is synthetic oil.
Before impregnation, moisture and gases are removed from
the oil by special process.
* Other technical specifications may be available
upon request.
13
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESCRIPTION
INDUCTIVE
VOLTAGE
TRANSFORMERS
UP TO 420 KV
Production
EMEK inductive voltage transformers are
manufactured in Ankara Turkey.
General Description
We manufacture oil insulated inductive voltage transformers
up to 420 kV
Up to 36kV, IVTs are manufactured tank type, primary and
secondary windings are housed in galvanised stainless steel tank.
From 36kV up to 170kV, IVTs are manufactured as bushing type,
primary and secondary windings are housed in
porcelain / polymeric insulator.
Above 170kV, IVTs are manufactured as cascaded bushing type,
primary and secondary windings are housed in two bushings.
Transformes are hermetically sealed.
14
15
OIL INSULATED
INSTRUMENT TRANSFORMERS
DESIGN CHARACTERISTICS
Frequency
50 Hz, 60 Hz
Altitude
Standard design is suitable up to 1000 m above sea level.
Painting
External surface of the transformers, which are already corrosion
protected, are additionally painted grey colour.
Bracelet
All bracelets used on transformers are made of aluminium
alloy.
Earthquake Design
Standard design is up to 0.6g.
Mechanical Strength
Applied load to the primary terminal in horizontal and vertical
is in conformity with IEC 60044.2 and IEC 60186.
Optional Accessories
Steel support structure
Primary connectors
Marshalling box
Voltage factor
1.2 x Un continuous / 1.9 x Un for 30 sec.
Ambient Temperature
Standard design is suitable for temperature range
-50 C to +50 C.
Hermetic Seal
Oil volume variations are compensated with stainless steel
bellows placed in the head of the transformers.
With this facility there will be no contact between air and oil.
The dielectric strength will remain unchanged for the life time
of the VT.
INDUCTIVE
VOLTAGE
TRANSFORMERS
UP TO 420 KV
Primary Terminals
Primary terminals are made of tin plated brass.
Vertical and horizontal primary terminals are available on request.
Name Plate
Name plates are stainless steel and weatherproof.
EMEK
CORRECT
Core
High quality sheet steel cores are used.
Enamelled electrolytic copper wire is used for primary windings.
EMEK
MAX INCLINATION
WRONG
2
3
Bushing
Brown, grey glazed porcelain or composite.
Oil Insulation
The insulating oil is mineral oil in conformity with IEC 60296.
Before impregnation, moisture and gases are removed from
the oil by special processes.
Drain plug for taking samples and oil refilling facilities are
provided on request.
Floating type oil level indicator is standard supply.
Maintenance
Maintenance free, simple recommendations;
Clean the bushing at regular intervals depending on
the degree of pollution.
Ensure that there is no oil leakage.
10
9
Oil Impregnation
Heat and vacuum are applied to the fully insulated windings
after assembly of the inductive voltage trasformers for drying
purposes, followed immediately by oil impregnation procedure.
11
12
16
13
16
Packing
The transformers are packed in rugged
wooden crates which are suitable for
overseas transportation.
The transformers are encapsulated in polyethylene covers to
keep them from environmental effects.
Wooden crates can be lifted by either a fork lift or by a crane
with slings.
EMEK
Paper Insulation
Oil impregnated paper is used which has high dielectric strength
and low dielectric losses.
Accessories
Fixing holes, lifting holes, secondary terminal box, name plate,
warning plates are also provided in our standard design.
Assembly
Before the assembly, following visual checks should be made;
There are no oil leaks
The insulator is not damaged
There is no damage on the primary terminals
The oil level indicator indicates sufficient oil level
14
15
17
DESCRIPTION
Packing
The transformers are packed in rugged wooden crates which are
suitable for overseas transportation.
The transformers are encapsulated in polyethylene covers to keep
them from environmental effects.
INDOOR TYPE
CURRENT
TRANSFORMERS
Assembly
Before the assembly, following visual checks should be made;
Ensure that there is no crack on the body
Ensure that the body is clean
Ensure that there is no damage on the base and secondary
terminal box.
Current transformers can be assembled in any position.
Production
EMEK indoor type epoxy resin insulated current transformers are
manufactured in Ankara Turkey.
General Description
We manufacture indoor type epoxy resin insulated current transformers
up to 36 kV
Primary and secondary cores are moulded in epoxy resin to
ensure product with high reliability, maintenance free,
small weight, mounting in any position, high mechanical strength.
DESIGN CHARACTERISTICS
Epoxy Resin
The cores and windings of the current transformer are
moulded in epoxy resin.
Vacuum is applied during material preparation and
the casting processes.
Primary Terminals
Primary terminals are made of tin plated brass or copper.
Stud, nema pad or clamp type primary terminals are available.
Cores
Grain oriented silicon steel is used.
The core shapes are toroidal without air gap.
Electrolytic copper strips suitable to withstand rated
continuous current and short time thermal current is used for
primary winding
Enamelled electrolytic copper wire is used for secondary
winding.
Base Plate
Base of the transformers are fabricated from sheet steel
and are hot dip galvanised.
19
Primary Terminals
Primary terminals are made of tin plated brass.
Core
High quality sheet steel cores are used.
Enamelled electrolytic copper wire is used
for primary windings.
Enamelled electrolytic copper wire is used
for secondary windings.
Base Plate
Base of the transformers are fabricated from Aluminium
Secondary Terminal Box
The secondary terminals are provided with a transparent covering.
If VTs are used for revenue metering provision can be made to
seal the cover.
Earthing
Earthing terminal is located on the body of the transformers
Ambient Temperature
Standard design is suitable for temperature range -25C to +40C.
DESCRIPTION
Maintenance
Maintenance free, our simple recommendations are;
Cleaning of the body to eliminate deposits of all type of pollution.
INDOOR TYPE
VOLTAGE
TRANSFORMERS
Production
EMEK indoor type epoxy resin insulated voltage transformers are
manufactured in Ankara Turkey.
General Description
We manufacture indoor type epoxy resin insulated voltage transformers
up to 36 kV
Primary and secondary windings are moulded in epoxy resin to
ensure product with high reliability, maintenance free,
small weight, mounting in any position, high mechanical strength.
Packing
The transformers are packed in rugged wooden crates which are
suitable for overseas transportation.
The transformers are encapsulated in polyethylene covers to keep
them from environmental effects.
DESIGN CHARACTERISTICS
Frequency
50 Hz, 60 Hz
Rated Secondary Voltage
110/3, 100/3, 110/3, 100/3 V etc. in conformity with
customer requirement.
20
Assembly
Before the assembly, following visual checks should be made;
Ensure that there is no crack on the body
Ensure that the body is clean
Ensure that there is no damage on the base and secondary
terminal box.
Voltage transformers can be assembled in any position
21
DESCRIPTION
DESIGN CHARACTERISTICS
Production
EMEK outdoor type epoxy resin insulated current transformers are
manufactured in Ankara Turkey.
Frequency
50 Hz, 60 Hz
General Description
We manufacture outdoor type epoxy resin insulated current
transformers up to 36 kV
Primary and secondary cores are moulded in epoxy resin to
ensure product with high reliability, maintenance free,
small weight, mounting in any position, high mechanical strength.
Secondary Current
1 A, 2 A or 5 A, others on request.
Primary Current
Up to 3000 A
Thermal and Dynamic Ratings
Short time thermal current up to 40 KA/ 3 sec and dynamic
current ratings up to 100 KA peak are possible.
OUTDOOR TYPE
CURRENT
TRANSFORMERS
Primary Terminals
Primary terminals are made of tin plated brass or copper.
Stud, nema pad or clamp type primary
terminals are available.
Cores
Grain oriented silicon steel is used.
The core shapes are toroidal without air gap.
Electrolytic strips copper suitable to
withstand rated continuous current and short
time thermal current is used for primary
windings.
Enamelled electrolytic copper wire is used for secondary windings.
Base Plate
Base of the transformers are fabricated from Aluminium
Name Plate
Name plates are stainless steel and weatherproof.
Secondary Terminal Box
The secondary terminals box is polypropylene (also cover)
or epoxy with aluminium cover.
If CTs are used for revenue metering provision can be made
to seal the covers.
Earthing
Earthing terminal is located on the body of the transformers.
Ambient Temperature
Standard design is suitable for temperature range -25C to +40C.
Altitude
Standard design is suitable up to 1000 m above sea level.
Maintenance
Maintenance free, our simple recommendations are;
Cleaning of body to eliminate deposits of all type of pollution.
Special Tools & Spare Parts
No special tools, no servicable parts or spare parts are required.
Packing
The transformers are packed in rugged wooden crates which are
suitable for overseas transportation.
The transformers are encapsulated in polyethylene covers to keep
them from environmental effects.
Assembly
Before the assembly, following visual checks should be made;
Ensure that there is no crack on the body
Ensure that the body is clean
Ensure that there is no damage on the base and secondary
terminal box.
Current transformers can be assembled in any position
22
23
DESCRIPTION
Production
EMEK outdoor epoxy resin insulated voltage transformers are
manufactured in Ankara Turkey.
General Description
We manufacture outdoor type epoxy resin insulated voltage transformers
up to 36 kV
Primary and secondary windings are moulded in epoxy resin to
ensure product with high reliability, maintenance free,
small weight, mounting in any position, high mechanical strength.
Frequency
50 Hz, 60 Hz
Earthing
Earthing terminal is located on the body of the transformers.
Ambient Temperature
Standard design is suitable for temperature
range -25C to +40C.
Maintenance
Maintenance free, our simple
recommendations are;
Cleaning of the body to eliminate deposits
of all type of pollution.
DESIGN CHARACTERISTICS
Voltage factor
Phase to Ground Connection : 1.2 x Un continuous / 1.9 x Un
for 30 sec.
Phase to Phase Connection : 1.2 x Un continuous
OUTDOOR TYPE
VOLTAGE
TRANSFORMERS
Epoxy Resin
Whole cores and windings of the voltage transformer
are moulded with the epoxy resin.
Vacuum is applied during material preparation and
casting processes.
Primary Terminals
Primary terminals are made of tin plated brass.
Core
High quality sheet steel cores are used.
Enamelled electrolytic copper wire is used for primary
windings.
Enamelled electrolytic copper wire is used for secondary
windings.
Base Plate
Base of transformers are hotdip galvanized steel
Secondary Terminal Box
The secondary terminals are provided with a transparent covering.
If VTs are used for revenue metering provision can be made to
seal the cover.
24
25
DISCONNECTING SWITCHES
DESCRIPTION
CENTER BREAK
HORIZONTAL
OPENING
DOUBLE ROTATING
UP TO 245 KV
Production
EMEK disconnecting switches are manufactured in
Ankara Turkey.
General Description
We manufacture disconnecting switches up to 245 kV
Center break, horizontal opening, double rotating type
disconnecting switches are available.
Motor or manual operating mechanism can be supplied
uponrequest.
26
27
DESIGN CHARACTERISTICS
Frequency
50Hz, 60Hz
Rated Current
Up to 2500A
Short time Thermal Current
Short time thermal current up to 40kA / 1 second is available.
Under fault conditions pressure between contacts increase,
provide excellent short time current capability.
Number of Poles
One or three poles are available
Each pole contains a frame, two rotating post insulators and two
main contacts that move horizontally.
DISCONNECTING SWITCHES
Main Blades
Red coloured aluminium main and earthing blades are supplied.
Electrical and Mechanical interlock is supplied between main
and earthing blades.
Earthing Blades
The material of earthing blades is aluminium which is provided
in red colour.
In case required one or two earthing blades can be supplied.
Motor and manual operating mechanism can be provided.
Operating Mechanism
Motor and manual operating mechanisms are available.
Control Mechanism
Local/remote switch is provided to avoid local and remote
control at the same time.
Ambient Temperature
Standard design is suitable for temperature range -25 C to 40 C. The universal joint between the gear box and the rotating
mechanism ensures silent and safe operation.
Altitude
Standard design is suitable up to 1000m above sea level.
Motor
The motors can be AC or DC upon request and can run
between 85% and 110% of rated voltage.
Main Contacts
Manual operation is
Self clearing silver plated contacts are able to withstand
possible only after
environmental pollutants.
Up to 1600A rated current main contacts are 20m silver coated mechanical and electrical
interlocks are in effect,
copper, for higher current levels 30 m silver coated copper is
thus accidental motor
provided.
Finger type main contacts ensure auto alignment during the
operation during hand
operation is impossible.
closing operation.
The pressure on the contacts in closed position is adequate for
Motors can be controlled
remotely or locally, with the
keeping the temperature rise within limits.
The main contacts rotate 90 degrees to open and close the
push buttons located in the
control cubicle.
disconnector.
Control Cubicle
The control cubicle is made of high grade stainless
steel to prevent corrosion.
Painting or similar maintenance is not required during
the switchgear lifetime.
The control cubicle contains a thermostat to control
heater to prevent condensation.
Breathing vents are fitted with brass screen mesh to
prevent insect entry.
Bearing
The bearings, which carry the major mechanical load of the
disconnectors, are made of stainless steel and Teflon (PTFE)
components.
Bearings are closed to the environment and do not require
maintenance.
The post insulators are mounted on rotating bearings, which
are mounted on the U type frame.
Auxillary Contacts
Auxiliary contacts are procured from well known
manufacturers who have specialized and are experienced
in this type or switches.
In our standard design 8NO 8NC auxillary contacts with two
limit switches are supplied. The number of
contact may vary according to request.
4 NO 4NC auxillary contacts for earthing
blade is supplied in our standard desgin.
The number of contact may vary according
to request.
Packing
The disconnecting switches are packed in
rugged wooden crates which are suitable for
overseas transportation.
Insulators and active parts are packed in separate boxes.
Assembly
Before the assembly, following visual checks should be made;
Ensure that there is no crack on the insulators
Ensure that the surface of insulator is clean
Ensure that there is no damage on mechanical parts
CENTER BREAK
HORIZONTAL
OPENING
DOUBLE ROTATING
UP TO 245 KV
28
29
QUALITY ASSURANCE
QUALITY POLICY
We will do the real customer satisfaction by supplying faultless
products with convenient price and delivery at the right time.
After sales service will be supplied along the service life.
To reach this aim, we believe that it is necessary;
To adapt customer requests and expectations at changing market
conditions by taking into consideration environmental impacts
To improve quality and profitability continually.
To get superiority to rival companies by cost reducing.
To supply staffs participation, training and satisfaction.
Standards
All products are subjected to full routine tests as
described in the relevant standards.
Type tests can also be performed (except short time current test)
in our own testing laboratories but should be negotiated
during the order stage.
IEC, BS, ANSI, AS, CSA, GOST and other standards on request .
Testing facilities
Type and routine tests as described in IEC, ANSI, AS, BS, CSA etc. are carried
out (except short time current test for CTs) at the testing facilities of EMEK, located
in Ankara.
Testing facilities include apparatus and systems for testing dry and wet
insulation (power frequency & impulse), partial discharge, accuracy, power factor & loss
angle, RIV, artificial ageing and mechanical strength.
Operation tests of our climatic chamber under severe ice condition and at the
temperature limit -40 / +150 C are possible.
Test facilities for transformer oil and insulation paper are also available.
Tests can be performed between 16 2/3 to 60 Hz.
Temperature and humidity controlled calibration center is available.
Certificates
EMEK was granted ISO 9001 certification by the Turkish Standards Institute (TSE).
Additionally, EMEK was also accredited with ISO 9001 from Independent Institutes
since 1997. Currently EMEK has ISO 9001:2008 and ISO 14001:2004 certificates from
ABS Quality Evaluations Inc.
Test Reports
Despite Emek's testing facilities, our products have also been tested at several
Independent Testing Laboratories such as ; KEMA, CESI, VEIKI, ICMET, STRI, IPH...etc
Upon customer request, we have performed more than 150 Type Tests for our products.
31
Social Contributions
The Chairman and the executive staff of EMEK
ELEKTRK ENDSTRS A.. is active in the energy sector
both in Turkey and in the world not only through their
positions as the founder and/or member of the local and
international non-governmental organizations, but also
presented reports and scientific studies.
The World Energy Council, of which Hseyin ARABUL, the
chairman of EMEK, is the Deputy President and
President of Turkish National Committee, makes studies
for reliable and effective generation, transmission and
distribution of energy and environmental friendly
utilization of the energy resources. Additionally, the
Committee discusses the problems, future energy policies
and energy resources of Turkey by organizing congresses,
symposiums, conferences, public sessions and panels and
offers solutions.
BARMEK Group has also played an active role in the
foundation of many non-governmental organizations
like Electromechanical Industrialists' Association (EMSAD),
Electricity Distribution Firms' Association (ELDER),
Defense Industry Manufacturers' Association (SASAD).
Electric Industry Businessmen's Association (ELSIAD),
Middle East Technical University Development Foundation.
Prof. Dr. M. Parlar Foundation and Metal Goods Industry
Employers' Union (MESIS).
EMEK has right to change the information and datas without prior notice
All updated datas can be reached from our web site www.emek.com.tr
All rights reserved.