Smoke Detector
SPECIFICATION DATA
FEATURES
Integral Microprocessor
Non-volatile Memory
Environmental Compensation
Wide 0.67 percent to 3.77 percent/ft. Sensitivity Range
Pre-Alarm Sensitivity Capability
Continuous Self-Diagnosis and Storage of
Environmental and Operational Data
Electronic Addressing and Device Mapping
Day/Night Sensitivity Adjustment
One Red and One Green Status LED
Standard, Relay, and Fault Isolator Mounting Bases
Design and Manufacture per ISO 9001 Standards
GENERAL
The XLS-PS Intelligent Photoelectric Smoke Detector gathers
analog information from its smoke sensing element and
converts it into digital signals. An on-board microprocessor
measures and analyzes these signals. It compares the
information to historical readings and time patterns to make an
alarm decision. Digital filters remove signal patterns that are
not typical of fires, thus eliminating most unwanted alarms.
Detection sensitivity varies upward and downward to remain
constant relative to the changing sensitivity baseline (percent
obscuration). This technique is called differential sensing. It
enables the detector to be nearly independent of its installed
environment and physical conditions. About every 10
minutes, the detector adjusts and updates the sensitivity
baseline for its sensing element to compensate for
environmental changes caused by dirt, humidity, aging, and
small amounts of normal ambient smoke. About once an
hour, the microprocessor writes this information to its
permanent memory so the detectors learned baseline is not
lost, even when the detector is removed for cleaning.
74-2064
DESCRIPTION
APPLICATION
TYPICAL WIRING
The detector mounting bases accept 18 AWG (0.75 sq. mm.),
16 AWG (1.0 sq. mm.), and 14 AWG (1.5 sq. mm.) wire sizes.
MAX. RESISTANCE
PER WIRE
MUST NOT EXCEED 10 OHMS
TERM DESCRIPTION
1NOT USED
2 DATA IN/OUT (+)
3 NOT USED
4 DATA IN ()
4
REMOTE LED ()
5
REMOTE LED (+)
6 NOT USED
7 DATA OUT ()
2
DATA IN ()
DATA OUT ()
DATA IN (+)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE
TO NEXT DEVICE
C8251
NORMALLY NORMALLY
CLOSED
OPEN
COMMON
CONTACT RATING
1.0 AMP @ 30 VDC
(PILOT DUTY)
TERM DESCRIPTION
1NORMALLYCLOSED
2 DATA IN/OUT (+)
3 COMMON
4 DATA IN (-)
5NOT USED
6NORMALLY-OPEN
7 DATA OUT (-)
2
DATA IN ()
DATA OUT ()
DATA IN (+)
TO NEXT DEVICE
74-2064
C8252
7
1
Sensitivity Range:
ULI/ULC - 0.67 percent to 3.77 percent obscuration/foot
TERM DESCRIPTION
1NOT USED
2 DATA IN/OUT (+)
3 DATA IN (-)
4 NOT USED
5NOT USED
6DATA OUT (-)
7 NOT USED
2
DATA IN ()
DATA OUT ()
DATA IN (+)
Pre-alarm Sensitivity:
75 percent of Alarm Sensitivity Setting
TO NEXT DEVICE
Operating Voltage:
15.2 to 19.95Vdc (19Vdc nominal)
C8253
C8254
CAUTION
Mounting:
Signature Series detectors mount to bases (see next item,
Mounting Bases). For North American 1-gang boxes;
3-1/2 in. or 4 in. octagon boxes; and European BESA and
1-gang boxes with 60.3 mm fixing centers, you can use
the SIGA-SB Mounting Base. For 4 in. square electrical
boxes (purchased locally) 1-1/2 in. (38 mm) deep, SIGAIS Trim Skirt is used with SIGASB4 Mounting Base.
Mounting Bases:
SIGA-SB, SIGA-SB4 Standard Base
SPECIFICATIONS
Sensing Element:
Photoelectric - Light Scattering Principle
Operating Environment:
Air Velocity Range: 0 to 5,000 ft/min (0 to 25.39 m/s)
Temperature: 32 to 120F (0 to 49C)
Humidity: 0 to 93% RH, non-condensing
Storage Temperature: -4F to +140F (-20 to +60C)
SIGA-IB, SIGA-IB4 Isolator Base. This base includes a builtin line fault isolator. A detector must be installed for it to
operate. The integral isolator relay is controlled by the
sensor or the loop controller. A maximum of 96 isolator
bases can be installed on one circuit. The isolator base
does not support the SIGA-LED Remote LED.
74-2064
Accessories:
Remote LED SIGA-LED (SIGA-SB or SIGA-SB4 Standard
Base only). It features a North American size 1-gang
plastic face plate with a white finish and red alarm LED.
SIGA-TS Trim Skirt - Supplied with 4 in. bases, it can also
be ordered separately to use with the smaller bases.
LED Operation:
On-board Green LED flashes when polled.
On-board Red LED flashes when in alarm.
Both LEDs glow steady when in alarm (stand-alone mode).
Compatible Remote Red LED (model SIGA-LED) flashes
when in alarm.
Compatibility:
XLS1000 Loop Controllers
Address Requirements:
One Device Address
Standards:
International ISO 9001 standards
Approvals:
UL, ULC