Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

XLSPS Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

XLS-PS Intelligent Photoelectric

Smoke Detector
SPECIFICATION DATA

FEATURES

Integral Microprocessor
Non-volatile Memory
Environmental Compensation
Wide 0.67 percent to 3.77 percent/ft. Sensitivity Range
Pre-Alarm Sensitivity Capability
Continuous Self-Diagnosis and Storage of
Environmental and Operational Data
Electronic Addressing and Device Mapping
Day/Night Sensitivity Adjustment
One Red and One Green Status LED
Standard, Relay, and Fault Isolator Mounting Bases
Design and Manufacture per ISO 9001 Standards

GENERAL
The XLS-PS Intelligent Photoelectric Smoke Detector gathers
analog information from its smoke sensing element and
converts it into digital signals. An on-board microprocessor
measures and analyzes these signals. It compares the
information to historical readings and time patterns to make an
alarm decision. Digital filters remove signal patterns that are
not typical of fires, thus eliminating most unwanted alarms.
Detection sensitivity varies upward and downward to remain
constant relative to the changing sensitivity baseline (percent
obscuration). This technique is called differential sensing. It
enables the detector to be nearly independent of its installed
environment and physical conditions. About every 10
minutes, the detector adjusts and updates the sensitivity
baseline for its sensing element to compensate for
environmental changes caused by dirt, humidity, aging, and
small amounts of normal ambient smoke. About once an
hour, the microprocessor writes this information to its
permanent memory so the detectors learned baseline is not
lost, even when the detector is removed for cleaning.

Copyright 1996 Honeywell Inc. All Rights Reserved

Continuously running self-diagnostics update device statistics


and store them in a history log in non-volatile memory. The
history log contains information such as detector type, serial
number, and address; manufacture date; hours of operation;
analog signal patterns just before the last alarm; and time and
date of last alarm.
The electronically coded serial number and address enable
controllers on the same circuit to automatically map the location
of the detector and use that information in as-built drawings.
The detector can issue pre-alarm warnings to alert local staff
to potential fire conditions before entering into a full alarm
condition. The pre-alarm value is 75 percent of the alarm
value setting.
The detector can be set up to automatically change sensitivities
during unoccupied periods of expected lower ambient
background conditions. Day/night periods are an example.

74-2064

XLS-PS INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR

DESCRIPTION

APPLICATION

The XLS-PS Intelligent Photoelectric Smoke Detector


contains its own microprocessor to provide on-site analysis of
environmental conditions for immediate alarm detection and
response. It runs continuous self-checks to track its own
operation and maintain a history of environmental conditions.
The microprocessor stores the results of the self-check in a
history log in the sensors permanent, non-volatile memory.
Some or all of this information can be printed for review from
the control panel on the XLS1000 Loop Controller, a Personal
Computer (PC) laptop interface, or the SSST Signature
Series Service Tool. History log information includes:

Although photoelectric detectors have a wide range of fire


sensing capabilities, they are best suited for detecting slow,
smoldering fires (wood pyrolysis and smoldering cotton). They
are also very suitable for poly urethane foam and n-Heptane
fires. They are not suitable for open wood and liquid fires
without smoke.

TYPICAL WIRING
The detector mounting bases accept 18 AWG (0.75 sq. mm.),
16 AWG (1.0 sq. mm.), and 14 AWG (1.5 sq. mm.) wire sizes.

detector type, serial number, and address


date of manufacture, hours of operation, and last
maintenance date
current detector sensitivity values and the extent of
environmental compensation
original detector sensitivity values
number of recorded alarms and troubles
time and date of last alarm
analog signal patterns just before the last alarm
up to 32 possible trouble codes that the detector can use
to specify faults

NOTE: Sizes 16 AWG (1.0 sq. mm.) and 18 AWG


(0.75 sq. mm.) are preferred for ease of installation.
REMOTE LED
(SIGA-LED)

On-board intelligence permits the detector to operate in


stand-alone mode. If controller communication fails for more
than 4 seconds and remains powered, all devices on that
circuit go into stand-alone mode. The circuit acts like a
conventional alarm receiving circuit. Each detector on the
circuit continues to collect and analyze information from its
surroundings. The detector alarms if the preset smoke
obscuration level is reached. If the detector is mounted to a
relay base, the relay operates.

MAX. RESISTANCE
PER WIRE
MUST NOT EXCEED 10 OHMS
TERM DESCRIPTION
1NOT USED
2 DATA IN/OUT (+)
3 NOT USED
4 DATA IN ()
4
REMOTE LED ()
5
REMOTE LED (+)
6 NOT USED
7 DATA OUT ()

2
DATA IN ()

DATA OUT ()

DATA OUT (+)

DATA IN (+)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE

On-board intelligence also means less information needs to


be sent between the detector and the loop controller. Other
than regular supervisory polling response, the detector only
needs to communicate with the loop controller when it has a
new condition to report. This feature provides very fast
response time and allows use of a lower baud rate for
communication on the loop. The lower baud rate offers
several advantages including:

TO NEXT DEVICE
C8251

Standard Detector Base, SIGA-SB, SIGA-SB4

NORMALLY NORMALLY
CLOSED
OPEN

COMMON

CONTACT RATING
1.0 AMP @ 30 VDC
(PILOT DUTY)

less sensitivity to circuit wire characteristics


less sensitivity to noise glitches on the cable
less emitted noise from the wiring

Each detector automatically identifies dirty or defective


conditions and issues a dirty detector message.

TERM DESCRIPTION
1NORMALLYCLOSED
2 DATA IN/OUT (+)
3 COMMON
4 DATA IN (-)
5NOT USED
6NORMALLY-OPEN
7 DATA OUT (-)

2
DATA IN ()

DATA OUT ()

DATA IN (+)

DATA OUT (+)

FROM SIGNATURE CONTROLLER


OR PREVIOUS DEVICE

TO NEXT DEVICE

Relay Detector Base, SIGA-RB, SIGA-RB4

74-2064

C8252

XLS-PS INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR

7
1

Sensitivity Range:
ULI/ULC - 0.67 percent to 3.77 percent obscuration/foot
TERM DESCRIPTION
1NOT USED
2 DATA IN/OUT (+)
3 DATA IN (-)
4 NOT USED
5NOT USED
6DATA OUT (-)
7 NOT USED

User-selected Alarm Sensitivity Settings:


Most Sensitive: 1.0 percent/ft.
More Sensitive: 2.0 percent/ft.
Normal: 2.5 percent/ft.
Less Sensitive: 3.0 percent/ft.
Least Sensitive: 3.5 percent/ft.

2
DATA IN ()

DATA OUT ()

DATA IN (+)

DATA OUT (+)

FROM SIGNATURE CONTROLLER


OR PREVIOUS DEVICE

Pre-alarm Sensitivity:
75 percent of Alarm Sensitivity Setting

TO NEXT DEVICE

Operating Voltage:
15.2 to 19.95Vdc (19Vdc nominal)

C8253

Isolator Detector Base, SIGA-IB, SIGA-IB4


Operating Current:
Quiescent: 45A at 19V
Alarm: 45A at 19V
Emergency Stand-alone Alarm Mode: 18 mA
Pulse Current: 100 A (100 msec)
During Communication: 9 mA maximum
Shipping Weight:
0.5 lb. (0.23 kg)
TAMPER-RESIST LEVER ARM
-BREAK OFF TO DISABLE(LOCATED ON BASE)

Carton Dimensions in Inches (Millimeters):


5 (127) wide by 3-3/5 (91) high by 5 (127) deep
Construction and Finish:
High Impact Engineering Polymer - White
ACCESS SLOT FOR
TAMPER-RESIST
MECHANISM

All electronics utilize surface mount technology (SMT) for


smaller size and greater immunity to RF noise. A conformal
coating is used for humidity and corrosion resistance. All
critical contacts are gold plated.

C8254

CAUTION

Mounting:
Signature Series detectors mount to bases (see next item,
Mounting Bases). For North American 1-gang boxes;
3-1/2 in. or 4 in. octagon boxes; and European BESA and
1-gang boxes with 60.3 mm fixing centers, you can use
the SIGA-SB Mounting Base. For 4 in. square electrical
boxes (purchased locally) 1-1/2 in. (38 mm) deep, SIGAIS Trim Skirt is used with SIGASB4 Mounting Base.

This detector does not operate without electrical power.


As fires frequently cause power interruption, discuss
further safeguards with your fire protection specialist.
This detector does NOT sense fires that start in areas
where smoke cannot reach the detector. Smoke from
fires in walls, roofs, or on the opposite side of closed
doors may not reach the detector to alarm it.

Mounting Bases:
SIGA-SB, SIGA-SB4 Standard Base

SPECIFICATIONS

SIGA-RB, SIGA-RB4 Relay Base. This base includes a relay.


Normally open or closed operation is selected during
installation. The dry contact is rated for 1 A at 30Vdc
(pilot duty). The relays contact positions are supervised
to issue a trouble message if the detector is accidentally
jarred and the contacts switch position. The relay base
does not support the SIGA-LED Remote LED.

Sensing Element:
Photoelectric - Light Scattering Principle
Operating Environment:
Air Velocity Range: 0 to 5,000 ft/min (0 to 25.39 m/s)
Temperature: 32 to 120F (0 to 49C)
Humidity: 0 to 93% RH, non-condensing
Storage Temperature: -4F to +140F (-20 to +60C)

SIGA-IB, SIGA-IB4 Isolator Base. This base includes a builtin line fault isolator. A detector must be installed for it to
operate. The integral isolator relay is controlled by the
sensor or the loop controller. A maximum of 96 isolator
bases can be installed on one circuit. The isolator base
does not support the SIGA-LED Remote LED.

74-2064

XLS-PS INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR

Accessories:
Remote LED SIGA-LED (SIGA-SB or SIGA-SB4 Standard
Base only). It features a North American size 1-gang
plastic face plate with a white finish and red alarm LED.
SIGA-TS Trim Skirt - Supplied with 4 in. bases, it can also
be ordered separately to use with the smaller bases.
LED Operation:
On-board Green LED flashes when polled.
On-board Red LED flashes when in alarm.
Both LEDs glow steady when in alarm (stand-alone mode).
Compatible Remote Red LED (model SIGA-LED) flashes
when in alarm.
Compatibility:
XLS1000 Loop Controllers
Address Requirements:
One Device Address
Standards:
International ISO 9001 standards
Approvals:
UL, ULC

Home and Building Control


Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524

Home and Building Control


Honeywell Limited-Honeywell Limite
155 Gordon Baker Road
North York, Ontario
M2H 2C9

Honeywell Latin American Division


Miami Lakes Headquarters
14505 Commerce Way Suite 500
Miami Lakes FL 33016

Honeywell Europe S.A.


3 Avenue du Bourget
B-1140 Brussels Belgium

Honeywell Asia Pacific Inc.


Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong

Helping You Control Your World


74-2064

3-96

Printed in U.S.A. on recycled paper


4 post-consumer paper fibers
containing at least 10%

You might also like