National Iranian Gas Company (N.I.G.C.) : S3 / S6 Compressor Stations Special Specification
National Iranian Gas Company (N.I.G.C.) : S3 / S6 Compressor Stations Special Specification
National Iranian Gas Company (N.I.G.C.) : S3 / S6 Compressor Stations Special Specification
SPECIAL SPECIFICATION
THIS DOCUMENT IS OUR PROPERTY AND SHALL NOT BE USED NOR REPRODUCED WITHOUT OUR WRITTEN AUTHORIZATION
Date :
17/10/00
01.24
CE DOCUMENT EST NOTRE PROPRIETE ET NE DOIT ETRE NI UTILISE, NIREPRODUIT SANS NOTRE AUTORISATION ECRITE.
Rv./Amend.
1
Etablis./Establ.
Hubert PHAM
Projet/Project
Ph. PEZE
Vrif/Check
Ph. SAINTE-FOI
Approbat./Approval
R. ORTIGER
N RC291.SP.000.1600.0004
Page 1/35
REVISION RECORD
Revision
Date
Established
Checked
Project
Approved
Issue for
28/07/00
HPH
PSF
PZE
ROR
First Issue
17/10/00
HPH
PSF
PZE
ROR
Up dated Client
comments incorporated
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 2/35
CONTENTS
1.
SCOPE.........................................................................................................................5
2.
GENERAL ..................................................................................................................5
2.1
DEFINITION OF TERMS...........................................................................................5
2.2
3.
3.1
GENERAL ...................................................................................................................5
3.2
PARTICULAR .............................................................................................................6
3.3
4.
5.
5.1
5.2
5.3
ATS ..............................................................................................................................9
5.4
EPMS..........................................................................................................................10
5.5
MANUAL CONTROL...............................................................................................10
6.
DESIGN.....................................................................................................................11
6.1
GENERAL .................................................................................................................11
6.2
7.
THE SWITCHBOARD............................................................................................13
8.
CIRCUIT BREAKERS............................................................................................14
8.1
GENERAL .................................................................................................................14
8.2
8.3
8.4
SAFETY SHUTTERS................................................................................................15
8.5
AUXILIARY CIRCUITS...........................................................................................15
8.6
8.7
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 3/35
9.
9.1
DEFINITION .............................................................................................................17
9.2
INTERLOCK .............................................................................................................17
10.
10.1
CURRENT TRANSFORMERS.................................................................................18
10.2
11.
12.
CABLE COMPARTMENT.....................................................................................22
13.
14.
14.1
14.2
14.3
NAMEPLATES..........................................................................................................24
14.4
CIRCUIT CABLES....................................................................................................25
14.5
INSTRUCTION PLATES..........................................................................................25
14.6
15.
SPECIAL TOOLS....................................................................................................26
16.
SPARE PARTS.........................................................................................................26
17.
QUALITY ASSURANCE........................................................................................26
18.
TEST CERTIFICATES...........................................................................................27
18.1
18.2
ROUTINE TEST........................................................................................................27
19.
20.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 4/35
1.
SCOPE
This specification covers the design, manufacture, workshop test, supply (with spare
parts) and site assistance of two 20 kV metal clad switchboards to implement the
S3& S6 Compressor Stations of the second Iranian Gas Trunkline (IGAT-II).
2.
GENERAL
2.1
DEFINITION OF TERMS
Within the context of this document, the following words shall meanings stead:
2.2
- NIGC
- SHALL
- SHOULD
- CONTRACTOR
- SUPPLIER
3.
3.1
GENERAL
Refer to Design Basis Doc N RC291.SP.000.B100.0001.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 5/35
3.2
PARTICULAR
a)
01.02
- IEC60044-1
Current transformers
- IEC 60044-2
Voltage transformers
- IEC 60255
Electric relays
- IEC 60269
Low-voltage fuses
- IEC 60282-1
High-voltage fuses
- IEC 60298
- IEC 60445
- IEC 60473
- IEC 60529
- IEC 60694
- ISO 9001/9002
Assurance Quality
b)
Supplier shall confirm in writing that he is able to comply in all respects with
this standard and also with other standards specified in the requisition.
c)
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 6/35
3.3
1
4.
REFERENCED DOCUMENTS
- Design Basis
No. RC291.SP.000.B100.0001
No. RC291.PL.300.E040.0001
No. RC291.PL.600.E040.0001
- Electrical Philosophy
No. RC291.SP.000.1600.0001
SITE CONDITIONS
Both compressor stations are located at high altitude.
Extract from Design Basis Doc N RC291.SP.000.B100.0001 :
Altitude, Above mean sea level
Ambient temperature minimum
Ambient temperature maximum
Design temperature
S3 Station
2061 m
- 19 C
+ 37 C
35 C
S6 Station
1373 m
- 14 C
+ 43 C
40 C
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 7/35
5.
OPERATING CONDITION
5.1
NORMAL CONFIGURATION :
1
20kV
Line1
20kV
Line2
NC B1
20kV
Bus A
NC
NC
NC
D1
B4
B2
Bus C
Bus B
20kV
B3 NO
NC
B5
NC
B6
Spare
TR 01
2 MVA
380V B14
Bus A
TR 02
NO
NO
B18
2 MVA
B15
Bus C
TR 03
NO
B19
2 MVA
NC B16
Bus B
FAULT ON BUS A
Among various fault hypothesis, there is one particular case where a bus
disconnecting switch (D1 in above figure) is useful :
When 20kV bus A fails, line 1 over-current relay opens circuit breaker B1.
The Electrical Power Management Computer (see separate specification) in turn
shall open B4 , B5 and B14.
The operator may now open manually the disconnecting switch D1. When D1 is
opened, HV bus A is isolated. The operator may turn over the 20kV bus A to the
maintenance team.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 8/35
In order to restore power supply, the operator may close tie breaker B3, close B5 to
activate transformer TR2, close B15, close B18 to activate 380V bus A.
In the mean time, the sub-panels ATS switches any active breaker on LV source A
over to the other healthy LV source B.
After successful operations, the operator has to check and then balance loads if
necessary. Motors shall be restarted by the SCS.
For other reconfiguration following a fault, refer to another document : Electrical
Philosophy quoted in 3.3 Referenced Documents.
5.3
ATS
20 kV line1
20 kV line2
HV 301
HV 601
630A
24kV
630A
630A
Bus A
B4
B1
D1
B2
630A
Bus C
630A
630A
B3
630A
16kA 1sec
Bus B
630A Spare
An automatic transfer of 20kV sources (ATS) shall be provided. This system shall be
programmed into the modern programmable protective relays at each circuit breaker.
When there is no voltage on Line1, the ATS shall open breaker B1. One set of 3
single phase VTs, line side, shall be provided for this purpose. The ATS then closes
bus tie B3 to reactivate Bus A , if there is voltage on Bus B. One set of 3 single
phase bus B VTs shall be provided.
Symmetrically when there is no voltage on Line2, the ATS shall open breaker B2.
One more set of 3 single phase VTs, line side, is required. The ATS then closes bus
tie B3 to reactivate Bus B , if there is voltage on Bus A. One set of 3 single phase
bus A VTs shall be provided.
When there are no voltage on both lines simultaneously, the ATS shall open the two
line breakers and send to the 380V Electrical Power Management Computer a
request to start the emergency generator.
When Bus A is not available and voltage on Line2 happens to disappear, the ATS
shall send to the 380V Electrical Power Management Computer a request to start the
emergency generator.
Symmetrically, when Bus B is not available and voltage on Line1 happens to
disappear, the ATS shall send to the 380V Electrical Power Management Computer
a request to start the emergency generator.
When network voltage comes back, and in order to ensure a source transfer without
power break, there is a synchronization procedure made by the Electrical Power
Management Computer at the 380V side.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 9/35
5.4
1
EPMS
In this compressor station, there is an Electrical Power Management System
(EPMS). The EPMS manages the high voltage switchboard, the step down
transformers, the low voltage main switchboard and the 380V emergency generator.
The EPMS has the following functions :
- Remote control of HV and LV circuit breakers from the operators work station
(display, alarms and switching)
- Change over of faulty transformer
- Change over of faulty power source
- Plant load shedding by overload criteria
- Plant load shedding by too low 20 kV criteria
- Plant load unshedding
- Supervision of generator start and loading sequence
- Generator synchronization when network comes back
- Generator synchronization on planned outage
- Supervision of generator unloading and stop sequence
- At priority sub-panels : change over of feeder on failure of main bus A (or bus B).
- Deny parallel running of step-down transformers
- Events logging
- Disturbance recorder
- Communication with other computers in local area network or in wide area
network.
5.5
MANUAL CONTROL
The EPMS is the normal operating mode. In case of non availability of the EPMS,
there shall be no power break. The switchboard shall continue to operate faithfully
with all safety features as with the EPMS. A selector switch, "local/remote" shall be
provided for this case.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 10/35
6.
DESIGN
6.1
GENERAL
The switchboard shall be metal clad type. Circuit breakers shall be withdrawable.
There shall be no maintenance disconnecting switches on both sides of the circuit
breaker.
Power components in each cubicle, shall be arranged in separate compartments with
metal partition intended to be earthed :
- Circuit breaker compartment
- Bus bar compartment
- Power cable compartment
Fault occurring in any of the compartment shall be restricted to that compartment,
shall not cause break-down of other compartments, or shall not cause damage to
adjacent cubicles.
All equipment and materials shall be new and the best of their respective kind, of
repetitive industrial construction, with Quality Assurance ISO 9001-9002.
Bus bars shall be made of hard drawn electrolytic copper.
Bus bars and connections shall be fully rated, braced and shall withstand
symmetrical short circuit current, asymmetrical short circuit current, dynamic peak
current and thermal short time current over the full length of the switchboard.
The switchboard enclosure shall be of the naturally ventilated design and shall not
rely on any forced cooling.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 11/35
6.2
PANEL CONSTRUCTION
The switchboard shall be made of a series of prefabricated air insulated panels or
cubicles in juxtaposition. Cubicles shall be of self supporting, flush-front design
having a neat and clean appearance. Steel sheet shall be 2mm minimum
The line-up shall be arranged in such manner that an expansion can be possible at
both ends.
For packing purpose and site re-assembly, each sub-bar shall be predrilled and tinned
at their ends. All bolted connections shall be made with high tensile strength bolts
effectively secured against loosening, effectively coated against corrosion.
The switchboard shall have front access for operation.
Each cubicle shall be marked with a suitable mimic diagram. The control switch
(on/off) is part of the mimic diagram. Cubicle front label shall indicate the function
of the cubicle. Inside identification labels shall be under or near each piece of
equipment. .
The switchgear shall be designed and manufactured to facilitate inspection, cleaning,
repair and maintenance and to ensure absolute safety during operation, inspection
and maintenance.
No cast iron or cast aluminum shall be used in any part of the switchgear which is
subjected to mechanical stress.
Particular care shall be taken to prevent the occurrence of electrochemical corrosion
at the interfaces between dissimilar metals. This requirement shall also apply to the
termination of Aluminum core cables.
All joints and conductors shall have their jointing surfaces properly tinned where
necessary to prevent oxidization and undue heating.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 12/35
7.
1
THE SWITCHBOARD
HV 301
HV 601
630A
24kV
630A
630A
630A
Bus A
630A
Bus C
630A
630A
16kA 1sec
Bus B
630A Spare
3 wires, 50Hz
630A rms
40kA peak
- Rated voltage
24 kV
- Service Voltage
20 kV
50 kV rms 1 mn
125 kV peak
Functions
Incoming panels
Transformer panels
Spare Transformer panel
Bus tie
Bus disconnecting switch
Bus sections
Rating
CTs
630A
3 CTs
630A
3Cts
630A
3Cts
630A
3Cts
630A
630A
VTs
3 VTs
M & Relays
MPDPD
MPDPD
MPDPD
MPDPD (1)
2 X 3 VTs
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 13/35
8.
CIRCUIT BREAKERS
8.1
GENERAL
Circuit breakers shall be of SF6 squelching medium, spring loaded type, wound up
by an electric motor, with closing and tripping coils.
Normal activation shall be provided by electrical local or remote control. Manual
spring loading and control shall also be possible.
Circuit breakers shall be trip-free.
Facilities to test the breaker in "test" position or in "withdrawn" positions shall be
provided.
8.2
8.3
The method of closing and tripping shall be by one trip coil and by one close
coil. The closing and tripping circuits shall be protected by miniature circuit
breakers.
b)
c)
d)
b)
Mechanical interlock of the circuit breaker with the cable earth switch is in
such a manner that this latter may be switched on only if the circuit-breaker is
withdrawn or else when it is on, the circuit breaker cannot be inserted.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 14/35
c)
Particular interlocks :
- Transformer circuit breaker: the low side circuit breaker may be closed only
when the high side breaker is already closed (by control wiring).
- Bus Disconnecting Switch : see description in 9 below.
8.4
8.5
8.6
SAFETY SHUTTERS
a)
b)
c)
d)
e)
AUXILIARY CIRCUITS
a)
b)
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 15/35
All panels shall be provided with mechanically operated "on" and "off"
indicators which shall be positively driven in both directions and shall be
visible from the front of the equipment.
b)
All circuit breakers shall be provided with a truck mounted hand operated
mechanical trip device which shall be protected against inadvertent tripping.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 16/35
9.
DISCONNECTING SWITCH
9.1
DEFINITION
INTERLOCK
As hinted in 5.1 and 8.3, the disconnecting switch D1 must be mechanically
interlocked with the two circuit breakers B1 an B4.
Two conditions are required to open D1 :
- When breaker B1 is in open position, one key, key K1 is freed. K1 is emprisoned,
when B1 is closed. When breaker B4 is in open position, one key, key K4 is
freed. K4 is emprisoned when B4 is closed.
- At D1 cubicle, one lock with 2 keys shall be provided. These two keys are
necessarily keys K1 and key K4.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 17/35
10.
INSTRUMENT TRANSFORMERS
10.1
CURRENT TRANSFORMERS
VOLTAGE TRANSFORMERS
Voltage transformers shall be in accordance with IEC 60044-2.
Voltage transformers shall single phase with one primary and one secondary.
The preferred secondary voltage is 110V/3.
Accuracy class is 1.
For accuracy reason, total load including lead wires must exceed 10% of VT output.
Loading resistance shall be added to fulfill to condition.
Supplier shall check and guarantee that VT output is within reasonable limit. A
calculation note shall be submitted to Contractor for approval.
HV side :
Voltage transformers shall be protected on the HV side by high rupturing capacity
fuses.
HV fuses shall be withdrawable. They shall have strike pin and signal contacts.
Their location shall be readily accessible for a safe replacement whilst the bus bars
remain live.
LV side :
Voltage transformers shall be protected on the LV side by miniature circuit breakers.
Miniature circuit breakers shall have position contacts and fault contacts
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 18/35
All protective devices on both sides shall be capable of handling the inrush currents
under all service conditions, without abnormal ageing or deterioration. The rating of
the protection devices shall be selected in such a way that selective coordination with
up and down stream protection is guaranteed.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 19/35
11.
1
Circuit breaker on
- Green
- Yellow
:
Protective relay operates
A mimic diagram is required.
One local/remote selector shall be provided
Control orders (ON and OFF of circuit breakers) from the EPMSD shall be by hard
wires.
On each cubicle, a loss of DC source monitoring relay shall be provided : local pilot
light and remote alarm.
All pilot lights shall be electro-luminescent diodes.
Meters and Protective relays
Meters and relays shall be built into one Metering & Protection Digital
Programmable Device.
See required metering functions and required protective functions in the Over all HV
& LV single line diagram quoted in 3.3 Referenced Documents.
The over-current relay shall be multi-curve : constant, inverse, very inverse etc. . .
according to IEC 60255. All relays shall be insensitive to CT saturation .
Each relay shall have a communication port RS 485 to link them to the 380V
Electrical Power Management Computer at 130m away.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 20/35
ATS :
The ATS ability shall be programmed in the protective relays located at the two
incomers and at the bus tie. See above 5.3.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 21/35
12.
CABLE COMPARTMENT
In the cable compartment there are :
- One three phase earthing switch
- Three current transformers
- Three voltage transformers when required
- Three neon signal lamp presence of voltage.
- Power cables terminations.
The earthing switch shall have a making capacity equal to the maximum
symmetrical short circuit current.
The earthing switch shall be mechanically interlocked with the circuit breaker as per
IEC 60298.
In addition, the earthing switch shall be mechanically interlocked with the upstream
earthing switch (line incoming) or mechanically interlocked with the downstream
circuit breaker (step down transformers) .
Bottom plate for cables shall be provided. For single core cable, mounting plate shall
be of non-magnetic material.
Inside the compartments adequate provisions shall be fitted for earthing the screen
and/or armoring of each cable independently.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 22/35
13.
All metallic non-current carrying parts shall be bonded together and bonded to
an earth bar which shall run the entire length of the equipment.
b)
The earth bar cross section, when made of copper, shall withstand bus duty at
150 A/mm maximum.
c)
The main earth bar shall be so positioned and prepared to receive bonding
straps from the incoming and outgoing cables.
d)
The main earth bar shall be provided with studs at each end to receive the
earthing cables or tapes as specified in the requisition.
e)
All doors shall be bonded to the switch-gear body by means of flexible copper
bonds, which shall be so arranged that it is not possible for the bonds to be
trapped in the doors. Particular attention shall be given to the size and method
of earthing and bonding of withdrawable items of equipment.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 23/35
14.
AUXILIARY EQUIPMENT
14.1
14.2
14.3
NAMEPLATES
The following manufacturer name plate shall be visible on the assembly:
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 24/35
14.4
CIRCUIT CABLES
Each circuit of the assembly shall be provided with the following circuit
identification labels:
14.5
a)
Circuit identification tag number. The circuit labels shall be repeated on both,
fixed portion and removable unit.
b)
INSTRUCTION PLATES
When the operation sequence of certain equipment in the assembly is not evident,
e.g. mechanical interlocking features, instruction plates shall be provided fixed near
the point of operation. The instruction shall be given as far as possible in pictorial
manner
14.6
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 25/35
15.
1
SPECIAL TOOLS
SUPPLIER shall propose a full list of special tools and devices as deemed necessary
for the erection and maintenance related to a site far from Suppliers technical
support.
The minimum suggested special tools for two switchboards is :
16.
SPARE PARTS
- Provide six 20kV spare VT fuses (for 2 switchboards)
- Provide twelve spare miniature circuit breakers for the all the LV circuit, control,
alarm, power (for 2 switchboards)
- Provide twenty pilot lamps, ten neon lamps (for 2 switchboards)
- Provide any other spare parts as deemed necessary for a good maintenance
service.
SPARE PARTS FOR TWO YEARS :
In option the SUPPLIER shall provide a spare parts list for two years maintenance.
This list shall be itemized and priced.
17.
QUALITY ASSURANCE.
The Supplier shall have a Quality Assurance Procedure, based on ISO 9001 and
9002 standards controlling the quality of the design and assembling work during all
stages of the production process. QA Procedure shall be submitted to Contractors
evaluation. Contractor shall be allowed to factory control at random product quality
of his material without any kind of limitation.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 26/35
18.
TEST CERTIFICATES.
18.1
18.2
ROUTINE TEST
Routine tests in accordance IEC 60298, IEC 60694 are required to make sure of a
minimum compliance to ordered material. Results shall be recorded in a test report.
Routine test of assemblies and components shall be performed during factory
inspection: circuit breakers, switches, voltage transformers, current transformers.
Contractor or NIGC (end user) shall witness the tests. Supplier shall notify
Contractor in due time, at least one month, before testing takes place.
Inspection and tests shall be carried out on the complete assembled switchgear or
parts thereof when delivered with time intervals.
Transportable units can be wired together.
The following checks and tests shall at least be carried out.
Switchgear shall be visually inspected on technical execution and conformity with
the latest issue of the approved drawings and with the order. Spot checks shall be
made to verify:
- the degree of protection of the enclosure,
- the degree of protection within the compartments,
- the effectiveness and reliability of safety shutters, partitions and shrouds,
- the effectiveness and reliability of operating mechanism, locks and interlock
system,
- the insulation of the bus bar system,
- the creepage distances and clearances,
- the proper mounting of components,
- the internal wiring and cabling system,
- the correct wiring of main and auxiliary circuits,
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 27/35
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 28/35
19.
Supplier shall provide with his proposal the following minimum information:
- Preliminary single-line diagram
- Preliminary general arrangement and floor plan drawings
- Minimum clearance around the assemblies for ventilation and maintenance
b)
c)
If after order placement, the switch-gear details are changed, shall immediately
provide revised data sheets and resubmit to Purchaser these information. New
data shall be guaranteed and binding the Vendor.
Instructions for transport, storage shall be given as an integral part of the order.
d)
Provide ten set of drawings, documentation and printed matters. Provide one
set of time current curves on log paper covering protective relays provided
with equipment .
e)
Information and data shall be supported with such photographs and drawings
as necessary to completely describe the equipment being offered.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 29/35
20.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 30/35
TECHNICAL PARTICULARS
Front label 2 : Network Line1
Front label 7 : Network Line2
Network Line 1 , Network Line 2
Rev. 1
Item
Qty
Description
Circuit Breaker
Breaking medium
Rated continuous current
Breaking capacity
Closing coil
Tripping coil
Spring motor
Earthing switch, make current
Auxiliary contacts, spare, voltage free
: withdrawable
: SF6
: 630 A rms
: 16 A rms 1 sec
: one, 110 VDC
: one, 110 VDC
: 110 V DC
: 16 kA rms
: 4 NC + 4 NO
: 150/5A
: by Suppliers calculation
: star connected
: 20 kV / 3
: 110 / 3 V class 1
Suppliers
Comments
: by Suppliers calculation
metering function
protective function
communication function
automatic transfer function
events recorder
disturbance recorder
See meters and relays on over all single diagram
RC291.PL.300.E040.0001.
Mechanical Interlock : Line 1 Breaker (cubicle 2) to key interlock
with disconnecting switch (cubicle 3).
Mechanical Interlock : In addition to IEC 298 requirement, the earth
switch shall have an upstream key interlock.
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 31/35
TECHNICAL PARTICULARS
Front label 1: Transformer TR 301
(or 601)
Front label 6: Transformer TR 303
(or 603)
Rev. 1
Item
Qty
Description
Suppliers
Comments
Circuit Breaker
: withdrawable
Breaking medium
: SF6
Rated current
: 630 A rms
Breaking capacity
: 16 A rms 1 sec
Closing coil
: one, 110 VDC
Tripping coil
: one, 110 VDC
Spring motor
: 110 V DC
Earthing switch, make current
: 16 kA rms
Auxiliary contacts, spare, voltage free : 4 NC + 4 NO
01.02
Rv.
: 60/5A
: by Suppliers calculation
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 32/35
TECHNICAL PARTICULARS
Front label 4 : Bus Disconnecting Switch
Rev. 1
Item
Qty
Description
Suppliers
comments
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 33/35
TECHNICAL PARTICULARS
Front label 5 : Bus Tie
Rev. 1
Item
Qty
Description
Bus A
Bus C
Suppliers
Comments
Bus B
3
3
01.02
Rv.
Date
1
Amend.
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 34/35
Voltage transformers
Primary
Secondary
With load resistance
Voltage transformer output
01.02
: by Suppliers calculation
Rv.
Date
1
Amend.
: star connected
: 20 kV / 3
: 110 / 3 V class 1
17/10/00
Date
N RC291.SP.000.1600.0004
Page : 35/35