VFD Manual Chino
VFD Manual Chino
VFD Manual Chino
. Safety Precautions..........................................................................................4
1. Before the Power-up ...............................................................................................................4
2. During the Power-up...............................................................................................................5
3. During the Operation ..............................................................................................................5
. Wiring .............................................................................................................9
1. Main Circuit Wiring Schematic Diagram ...............................................................................9
2. Description of Terminal Block..............................................................................................10
3. Basic Connection Diagram ...................................................................................................12
4. Precautions on Wiring...........................................................................................................13
. Commissioning .................................................................................................
1. Checks before the Commissioning .......................................................................................19
2. Commissioning Methods ......................................................................................................19
1. Options........................................................................! .
2. Disposition ..................................................................! .
Danger
Caution
Danger
Be sure to turn off the input power supply before wiring.
Do not touch any internal electrical circuit or component when the charging lamp is still on after the
AC power supply is disconnected, which means the inverter still has high voltage inside and it is very
dangerous.
Do not check components and signals on the circuit boards during the operation.
Do not dissemble or modify any internal connecting cord, wiring or component of the inverter by
yourself.
Be sure to make correct ground connection of the earth terminal of the inverter.
Never remodel it or exchange control boards and components by yourself. It may expose you to an
electrical shock or explosion, etc.
! Caution
Do not make any voltage-withstanding test with any component inside the inverter. These
semi-conductor parts are subject to the damage of high voltage.
Never connect the AC main circuit power supply to the output terminals U.V W of the inverter.
The main electric circuit boards of CMOS and IC of the inverter are subject to the effect and damage
of static electricity. Dont touch the main circuit boards.
Check if the inverter has got any damage or deformation during the transportation and
handling.
Check if there is one piece of HY series inverter and one copy of the instruction manual
available when unpacking it.
Check the information on the nameplate to see if the specifications meet your order
(Operating voltage and KVA value).
Check if there is something wrong with the inner parts, wiring and circuit board.
Check if each terminal is tightly locked and if there is any foreign article inside the inverter.
Check if the operator buttons are all right.
Check if the optional components you ordered are contained.
INPUT
OUTPUT
Freq-Range:
HY07D543B
3PH380V50Hz
3PH380V17.5A7.5KW
0.1400Hz
Model HY A 07D5 43 B
Software Version
Voltage Rating, 43 means 3-phase 380V
Inverter Capacity, 07D5 means 7.5KW
Serial No., P means P series, J means J Series
Trade Mark
. Safety Precautions
1. Before the Power-up
! Caution
Check to be sure that the voltage of the main circuit AC power supply matches the input
voltage of the inverter.
The symbol,
of the earth terminals of the motor and the inverter for safety.
No contactor should be installed between the power supply and the inverter to be used for
starting or stopping of the inverter. Otherwise it will affect the service life of the inverter.
Danger
R.S.T terminals are power input terminals, never mixed with U.V.W terminals. Be sure that the
wiring of the main circuit is correct. Otherwise it will cause damages of the inverter when the
power is applied to it.
Caution
!
Do not carry the front cover of the inverter directly when handling. It should be handled with
the base to prevent the fall-off of the front cover and avoid the dropping of the inverter, which
may possibly cause the injuries to people and the damages to the inverter.
Mount the inverter on a metal or other noncombustible material to avoid the risk of fire.
Install the inverter in a safe location, avoiding high temperature, direct sunlight, humid air or
water.
Keep the inverter from the reach of children or persons not concerned.
The inverter can only be used at the places accredited by our company. Any unauthorized
working environment may have the risks of fire, gas explosion, electric shock and other
incidents.
Install a heat sink or other cooling device when installing more than one inverter in the same
enclosure so that the temperature inside the enclosure be kept below 40 to avoid overheat or
the risk of fire.
Be sure to turn off the power supply before dissembling or assembling the operation keypanel
and fixing the front cover to avoid bad contact causing faults or non-display of the operator.
Do not install the inverter in a space with explosive gas to avoid the risk of explosion.
If the inverter is used at or above 1000m above seal level, the cooling efficiency will be worse,
so please run it by de-rating.
Do not install any contactor and other components of capacitor or varistor on the output side of
the inverter. Otherwise it will cause malfunctions and damages of components of the inverter.
Do not install any switch component like air circuit breaker or contactor at the output of the
inverter. If any of such components must be installed because of the requirements of process
and others, it must be ensured that the inverter has no output when the switch acts. In addition,
it is forbidden to install any capacitor for improvement of power factor or any varistor against
thunder at the output. Otherwise it will cause malfunctions, tripping protection and damages of
components of the inverter. Please remove them as shown in the below diagram.
It will affect the service life of the inverter if a contact is connected to the front end of input of
the inverter to control its starts and stops. Generally it is required to control it through FOR or
REV terminals. Special attention should be paid to its use in the case of frequent starts and
stops.
Please use an independent power supply for the inverter. Do avoid using the common power
supply with an electrical welder and other equipment with strong disturbance. Otherwise it will
cause the protection or even damage of the inverter.
X
KM
U
Inverter V
W
X
Do not plug the connectors of the inverter during the power up to avoid any surge into
the main control board due to plugging, which might cause the damage of the inverter.
Always have the protective cover in place before the power up to avoid electrical
shock injury.
Never connect or disconnect the motor set while the inverter is in running. Otherwise it
will cause over-current trip and even burn up the main circuit of the inverter.
Never remove the front cover of the inverter while the inverter is powered up to avoid
Do not come close to the machine when the fault restart function is used to avoid
anything unexpected. The motor may automatically restart after its stop.
The function of STOP Switch is only valid after setting, which is different with the use
! Caution
Do not touch the heat sink, braking resistor, or other heat elements to avoid being scald.
Be sure that the motor and machine is within the applicable speed ranges before
starting operation because the inverter is quite easy to run from lower speed to higher speed.
Do not check the signals on circuit boards while the inverter is running to avoid danger.
Be careful when changing the inverter settings. The inverter has been adjusted and set
before ex-work. Do not adjust it wantonly. Please make proper adjustments according to the
required functions.
Do consider the vibration, noise and the speed limit of the motor bearings and the
mechanical devices when the inverter is running at or above the frequency of 50Hz.
Type
HY00D423B
HY0D7523B
HY01D523B
HY02D223B
Input Voltage
Single & Three Phase
220V 50Hz
Single & Three Phase
220V 50Hz
Single & Three Phase
220V 50Hz
Single & Three Phase
220V 50Hz
Power
(KW)
Inverter
Output
Capacity
Current
(KVA)
(A)
Suitable Motor
(KW)
0.4
1.0
2.5
0.4
0.75
2.0
5.0
0.75
1.5
2.8
7.0
1.5
2.2
4.4
11
2.2
HY0D7543B
3380V 50Hz
0.75
2.2
2.7
0.75
HY01D543B
3380V 50Hz
1.5
3.2
4.0
1.5
HY02D243B
3380V 50Hz
2.2
4.0
5.0
2.2
HY03D743B
3380V 50Hz
3.7
6.8
8.5
3.7
HY05D543B
3380V 50Hz
5.5
10
12.5
5.5
HY07D543B
3380V 50Hz
7.5
14
17.5
7.5
HY001143B
3380V 50Hz
11
19
24
11
HY001543B
3380V 50Hz
15
26
33
15
HY18D543B
3380V 50Hz
18.5
32
40
18.5
HY002243B
3380V 50Hz
22
37
47
22
HY003043B
3380V 50Hz
30
52
65
30
HY003743B
3380V 50Hz
37
64
80
37
HY004543B
3380V 50Hz
45
72
91
45
HY005543B
3380V 50Hz
55
84
110
55
HY007543B
3380V 50Hz
75
116
152
75
HY009043B
3380V 50Hz
90
134
176
90
HY011043B
3380V 50Hz
110
160
210
110
HY013243B
3380V 50Hz
132
193
253
132
HY016043B
3380V 50Hz
160
230
304
160
HY018543B
3380V 50Hz
185
260
340
185
HY020043B
3380V 50Hz
200
290
380
200
HY022043B
3380V 50Hz
220
325
426
220
HY025043B
3380V 50Hz
250
481
480
250
HY028043B
3380V 50Hz
280
427
560
280
HY030043B
3380V 50Hz
300
450
580
300
HY031543B
3380V 50Hz
315
460
605
315
2. General Specifications
Inverter Series
HY-A
Control Mode
SPWM
Input Power
5-Digits Display &
Status Indicator
Lamp
Communication
Control
Operation
Temperature
RS-485
-10~40
Vibration
Below 0.5G
Setting
Frequency Control
Accuracy
Resolution
Output
Resolution
Operator Setting
Method
Analog Setting
Method
Other Functions
Cont
Humidity
Range
eral
Ramp Control
V/F Curve
0.10~400.00Hz
Digital0.01%-10~40, Analog0.1% 2510
Digital0.01Hz, Analog1 of Max. Operating Frequency
0.01Hz
Press directly to set.
External Voltage 0-5V0-10V4-20mA0-20mA.
Frequency lower limit, starting frequency, stopping frequency, three skip
frequencies can be respectively set.
Selectable 4-speed steps ramp-up and -down time (0.1-6500s).
Set V/F curve at will
Torque Control
Torque increase is settable by max. 10.0%. The starting torque can reach
150% at 1.0Hz.
6 multi-function input terminals for 8speed steps control, program operation,
Multi-Inputs
Multi-Outputs
Other Functions
reset and restart, frequency track, PLC control, traverse function, drawing
control, auto energy-savings, carrier adjustable by max. 16KHz, etc.
Overload
Protection
Drivefor constant torque 150%/1 min. for the kinds of fan 120%/1min.
FUSE
Protection Functions
Protection
Over-voltage
Low Voltage
Instant Stop and
Restart
Stall Prevention
Output End
Shorts
Other Functions
Its better to lay the inverter on a rack and keep it in a proper package.
It is better not to store the inverter for long time. Long time storage of the inverter will lead to
the deterioration of electrolytic capacity. If it needs to be stored for a long time make sure to
power it up one time within a year and the power-up time should be at least above five hours.
When powered up the voltage must be increased slowly with a voltage regulator to the rated
voltage value.
2. Installation Site and Environment
The inverter should be installed at the following location:
Free from direct sunshine, high temperature and heavy dust fall.
There must be enough space left around the inverter for easy maintenance and cooling. See
Diagram .
The inverter must be installed vertically with the smooth ventilation for effective cooling.
If there is any instability when installing the inverter, please put a flat board under the
inverter bottom base and install it again. If the inverter is installed on a loose surface, stress
may cause damage of parts in the main circuit so as to damage the inverter.
If several inverters are installed, upper and lower, together in one cabinet, please add heat
120
dissipation plates and leave enough space between the inverters. See Diagram.
50
120
50
UNIT: mm
. Wiring
1. Main Circuit Wiring Schematic Diagram(
)
Power supply:
Verify that the inverters rated voltage coincides with AC power supply voltage to avoid
a damage of the inverter.
No fuse breaker:
Electromagnetic contactor:
Note: Do not use the electromagnetic contactor as the on/off button of power supply for
the inverter.
AC reactor:
Inverter:
Be sure to make correct connections of the main circuit wires and control signal wires of
the inverter.
P+
PR
P+
PR
HY03D743B
HY02D223B-HY03D723B
PR
HY05D543B-HY07D543B
PR
HY0D7543B-HY03D743B
P1
HY001143B~HY003043B
HY05D523B-HY07D523B
HY003743B-HY016043B
HY18D523B-HY002223B
P1
DRV
FA
DCM
SPL
SPM
SPH
FC
FB
DRV
+10
RST
VI
REV
AI
FOR
ACM
FOR
AM
RS-
RS+
Function Description
Input terminal of AC line power.220V class, for both single/three phase,
single phase connected to any two phases
U.V.W
P.Pr
P1P
PN
E
Function Description
Factory setting
FOR
Multi-Input 1
Forward run
REV
Multi-Input 2
Reverse run
RST
Multi-Input 3
Reset
SPH
Multi-Input 4
High speed
SPM
Multi-Input 5
Middle Speed
SPL
Multi-Input 6
Low Speed
EVIPV
P24
+10
+10V
0~+10V
Input
4~20mA
Input
VI
AI
ACM
corresponding
corresponding
to
the
to
the
DRV
UPF
DC24V/100mA
FAEFA
FBEFB
3A/250VAC
Multi-Output 4 (N/O)
3A/250VAC
0~10V
FCEFC
KAEKA
KBEKB
AM
RS+ RS-
The wiring of the inverter is divided into two parts, main circuit terminal connections and control
circuit terminal connections. The user can see the main circuit terminals, and the control circuit
terminals after removing the cover of enclosure. The terminals must be connected correctly as the
following wiring circuit diagrams.
4. Precautions on Wiring
1)
While wiring the sizes and specifications of wires should be selected and the wiring should
be executed according to the electrical engineering regulations to ensure the safety.
It is better to use shielded wire or wire and conduit for power cord and ground the shielded
layer or two ends of wire conduit.
Be sure to install a Non Fuse Breaker (NFB) between the power supply and the input
terminals (R.S.T). (If using ground fault circuit interrupter, please choose one corresponding
to high frequency)
Output wires mustnt be in touch of the metal part of the inverter enclosure, or it will result in
earth short-circuit.
Phase-shifting capacitors, LC, RC noise filters, etc, can never be connected to the output
terminals of the inverter.
The main circuit wire must be enough far away from other control equipments.
When the wiring between the inverter and the motor exceeds 15 meters for 220V class or 30
meters for 380V class, much higher dV/dT will be produced inside the coil of the motor,
which will cause the destruction to the interlay or insulation of the motor. Please use a
dedicated AC motor for the inverter or add a reactor at the inverter.
Please lower the carrier frequency when there is a longer distance between the inverter and
the motor. Because the higher the carrier frequency is the bigger the leakage current of
high-order harmonics in the cables will be. The leakage current will have unfavorable effect
on the inverter and other equipment.
The signal line should be separately laid in a different conduit with the main circuit wire to
avoid any possible interference.
Please use the shielded cable with the size of 0.5-2mm2 for signal lines.
Use the control terminals on the control panel correctly according to your needs.
3 Grounding
Choose grounding wires according to the basic length and size of the technical requirements
of the electric equipment.
Do avoid sharing grounding wire with other large power equipment such as electric welder,
power machine, etc. The grounding wire should be kept away from the power supply wires
for large power equipment.
The grounding method for several inverters together should be done as the first and second
diagrams below. Avoid the third loop.
1Good
2Good
3Not good
indicating frequency,
FOR
REV
HZ
R/min
current, AC V, DC V,
Rev., frequency,
revolution, counter,
current,
temperature, etc.
revolution, etc.
FOR/REV Switch
Value change key
F /
R
Shift key
Run key
PROG
Function key
ENTER
Par.set key
STOP
RUN
RESET
HLKD0002
RUN
Stop/Reset key
Status
Description
FOR
on
REV
on
HZ
on
on
ROTT
on
A ROTT
on
Displaying AC or DC voltage.
HZ ROTT
on
HZ A ROTT
on
2
Description of Display Items
Display
Indic.lamp
on
Meaning
Present output frequency is 50.00HZ
Present set frequency is 50.00HZ
Present output current is 3.0A
Present output revolution is 1440r/min
Present DC voltage is 510.1V
Present AC voltage is 380.0V
Present inverters temperature is 35.0
Present counters value is 105
Present target value of PID is 50.0%
Present
I feedback value of PID is 48.0%
Present time of power-on is 12 hours
Total run time of inverter is 108 hours
Procedures
Display
Indicator
Lamp
Explanation
Power up,
Operation of
power
Dsp2.0 flash
Vr2.00
000.00
PROG
FOR
HZ
FOR
HZ
Enter programming
Display the function of PD000
000.00
FOR
HZ
50.00
END
50.00
PD001
050.0
FOR
FOR
HZ
HZ
50.00
FOR
HZ
FOR
HZ
FOR
HZ
FOR
PD000
ENYER
ENTER
PROG
RUN
50.00
0.00 5 0.00
DISP
005.0
PROG
01440
DISP
50.00
FOR ROTT
50.00
FOR
HZ
FOR
HZ
FOR
HZ
FOR
HZ
FOR
HZ
Stop
PROG
F/R
050.0
030.00
030.00
ENTER
30.00
STOP
Note:
means flashing.
means bright.
For monitoring AC, DC, T and other items they can be only switched and displayed after the
parameter setting.
When it is powered up again after a power breakdown the inverter will display the screen
previous to
. Commissioning
1. Important Checks before the Commissioning
If there is any wrong connected wires? Pay special attention to the terminal of U.V.W; Make
sure the power supply wires are connected to R.S.T, not U.V.W.
If there is any metal powder or wires left on the base plate of the inverter or the terminal
block, which may cause short circuit.
If screws are tightly locked and if the connecting parts are loose.
2. Commissioning Methods
The procedure of the operator is factory set up for the control mode of HY series. The
commissioning can be carried out through the digital operator. Generally, the commissioning can
be conducted at 5.00 Hz.
Procedures
Power up
ENTER
RUN
STOP
Display
dsp1.1Vr2.0
000.0
000.00
050.00
50.00
50.00
50.00
Indicator Lamp
Explanation
Self detect when power up,
FOR
Hz
FOR
Hz
Switch to adjustable
FOR
Hz
value of PD003
FOR
Hz
FOR
Hz
FOR
Hz
Categ
ory
Code
PD000
PD001
PD002
Set
Function
Range
&
Function
Explanation
Setting
Parameter Lock
0Invalid
Source of Run
0Operator
Commands
2Communication port
Source of Operating
Frequency
Factory
1Valid
0Operator
1External terminal
1External terminal
2Communication port
0
0
0
PD003
Main Frequency
0.00~400.00 Hz
0.00
PD004
Base Frequency
0.01~400.00 Hz
50.00
PD005
Max Operating
50.00~400.00 Hz
50.00
Frequency
PD006
PD007
Min. Frequency
0.01~20.00 Hz
PD008
Max. Voltage
0.1V*
220/380
PD009
Intermediate Voltage
0.1V*
PD010
Min. Voltage
0.1~50.0V
PD011
PD012
Reserved
PD013
Parameter Reset
PD014
Accel. Time 1
0.1~6500.0S
PD015
Decel. Time 1
0.1~6500.0S
PD016
Accel. Time 2
0.1~6500.0S
PD017
Decel. Time 2
0.1~6500.0S
PD018
Accel. Time 3
0.1~6500.0S
PD019
Decel. Time 3
0.1~6500.0S
PD020
Accel. Time 4
0.1~6500.0S
PD021
Decel. Time 4
0.1~6500.0S
PD022
Reserved
PD023
PD024
PD025
Starting Mode
PD026
Stopping Mode
PD027
Starting Frequency
0.1~10.0 Hz
0.5
PD028
Stopping Frequency
0.1~10.0 Hz
0.5
0.0~20.0%
2.0
0.0~25.0S
0.0
0.0~25.0S
0.0
0.0~20.0S
5.0
0~200%
150
00~10
2.50/3.0
0.50
0.00
00
1
1
0
0
DC Braking level
PD031
PD029
PD030
PD032
PD033
DC Braking time at
start
DC Braking time at
stop
Frequency track time
Current
level
for
frequency track
PD034
0.5
. Descriptions of Functions
PD000 Parameter Lock
**
Set Range01
Unit1
Factory Setting0
0 Invalid.
1 Valid, i.e. the parameters are locked. Except this parameter other parameters can not be
changed.
This parameter is set to prevent non-maintenance personnel from setting other parameters by
mistake. After the parameters are locked the operating frequency can be changed by pressing
or .
PD001 Source of Operation Commands
Set Range02
Unit1
Factory Setting0
Unit1
Factory Setting0
1 Set by external terminals. Operating frequency is controlled by analog signals input via
external terminals. The signal type is determined by PD070. For the related parameters refer to
PD070-PD076.
2 Set by communication ports. Operating frequency is given via the serial communication.
PD003 Main Frequency
Set Range0.00400.00 Hz
**
Unit0.01 Hz
Factory Setting0.00
In the digital operator mode, the inverter will run at the set value of PD003. During running, the
operating frequency can be changed by pressing or . During multi-speed running, the main
frequency is taken as the frequency of Speed 1.
In the external control multi-speed mode, if PD002 is set to 1, i.e. given by an external terminal,
Speed 1 will be given by the analog of the external terminal.
The setting of main frequency is limited by the maximum operating frequency.
The related parameters of PD002, PD080 are adjustable during operation.
PD004 Base Frequency
Set Range0.01400.00 Hz Unit0.1Hz
Factory Setting50.00
This parameter must be set according to the rated frequency of operating voltage on the motors
nameplate. Under normal conditions do not change the set value of base frequency at will. If it is
equipped with a special motor this value should be set properly according to the characteristics of
the motors parameters. Otherwise it may cause the damage to the equipment.
Unit0.01 Hz
Factory Setting50.00
This parameter is set for the maximum operating frequency of the inverter.
The following are several curves and set values often used for reference. Specific curves must be
set according to concrete characteristics of mechanical load.
220
220
220
15
55
24
0.5 2.5
50
0.5
25
0.5
50
25
50
220
220
220
27.5
110
45
13.5
16
20
0.5 2.5
50
0.5
25
0.5
50
2.5
50
Intermediate Frequency
Set Range0.01400.00 Hz
Unit0.01 Hz
Factory Setting2.50
This set value of intermediate frequency is limited by the set value of base frequency.
Unit0.01 Hz
Factory Setting0.50
This parameter is set for the min. starting frequency of V/F curve.
The following table has specific factory settings of V/F curve, accel./decal., time and carrier for
the inverter of A series:
Unit0.1V
Factory Setting220/380V
This parameter should be set according to the rated value of the motors nameplate. The factory
setting is 380V for 380V class motor and 220V for 220V class motor. The setting range of this
parameter is restricted by the voltage rating of the inverter. In case of the motor relatively far away
from the inverter this set value can be increased properly.
PD009 Intermediate voltage
Set Range0.1500.0V
Unit0.1V
Factory Setting15/27.5
This parameter is set for an intermediate voltage value of arbitrary V/F curve. If it is set
improperly, it will cause over-current or under-torque of the motor, or even tripping of the inverter.
When the intermediate frequency is increased the voltage will increase the output torque and at the
same time also the output current. When changing this parameter please pay attention to
monitoring the output current to avoid the inverters tripping due to over-current.
The factory setting of intermediate voltage for 220V class inverter is 15, while the factory setting
of intermediate voltage of 380V class inverter is 27.5.
This set value of intermediate voltage is limited by the set value of max voltage. When the
voltage is increasing to a certain value at intermediate frequency the torque compensation will lose
its function. When adjusting this parameter the output current of the inverter should be increased
from low to high slowly according to the load of machines until it meets the starting requirement.
Do not be quick to increase it by large amplitude. Otherwise it might cause the tripping of the
inverter or the damage of the machines.
PD010 Min. Voltage
Set Range0.150.0V
Unit0.1V
Factory Setting*
This parameter is set for the min. starting voltage of V/F curve.
The factory setting of min. voltage for 220V class inverters is 8, and the factory setting of
min.voltage for 380V class inverters is 13.5.
This set value is limited by the voltage at the max. frequency.
Code
Model
Code
Model
A00D423B 15.0
7.5
A003043B 17
8.5
30
30
A0D7523B 14.0
A003743B 16
35
35
A01D523B 14.0
10
10
A004543B 16
40
40
A02D223B 13.0
6.5
10
10
A005543B 15
7.5
45
45
A03D723B 13.0
6.5
15
15
A007543B 15
7.5
50
50
A05D523B 12.0
6.0
15
15
A009043B 14
75
75
A07D523B 11.0
5.5
20
20
A011043B
100
100
A001123B 10.0
5.0
25
25
A013243B 13
6.5
150
150
A001523B 10.0
5.0
30
30
A016043B 13
6.5
150
150
A18D523B 9.0
4.5
35
35
A018543B 12
200
200
A002223B 9.0
4.5
50
50
A020043B 12
200
200
A0D7543B 22
11
A022043B
11
5.5
250
250
A01D543B 22
11
10
10
A025043B
11
5.5
250
250
A02D243B 21
10.5
15
15
A028043B
11
5.5
250
250
A03D743B 21
10.5
15
15
A030043B 10
250
250
A05D543B 20
10
15
15
A031543B 10
250
250
A07D543B 20
10
20
20
A034543B 10
250
250
A001143B
19
9.5
20
20
A037543B 10
250
250
A001543B
19
9.5
20
20
A040043B 10
250
250
A18D543B 18
25
25
A041543B 10
250
250
A002243B
25
25
18
14
**
Unit0.01 Hz
Factory Setting0.00
This is set for preventing workers from false operation to avoid over-heat or some other
mechanical faults, which might be caused due to too low operating frequency.
The setting of Frequency Lower Limit must be less than the set value of Frequency Upper Limit.
PD012 Reserved
Unit1
Factory Setting00
When the value for a parameter is set improper or is abnormal for some reasons this parameter can
be set to 08 to restore it to the factory setting and then reset. After the parameters are locked (in
case of PD000=1) the parameters cant be reset. They can only be reset after unlock. For related
parameters refer to PD000.
PD014Accel. Time 1
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting
**
Set Range0.16500.0S
Unit0.1S
Factory Setting *
Ramp-up time means the time needed for the inverter to increase the frequency from 0Hz to the
maximum operating frequency (See t1 in the diagram). Ramp-down Time means the time needed
for the inverter to decrease the frequency from the maximum operating frequency to 0Hz (See t2
in the diagram).
F
Max Oper. F.
t1
t2
Note:
The versions previous to Vr2.0 took 50Hz as the base of ramp time.
HY-A Series inverter have altogether 4 Ramp Times. For Ramp Time 2.3.4 the user can select the
different ramp up or down time through the external terminals or switching of ramp time
according to the actual needs. In the internal control multi-speed operation, different ramp time
can be selected through easy PLC.
Generally the default of the inverter is Ramp Time 1, which is factory set depending on the model.
Ramp Time 4 is for the jogging ramp time. For the factory setting of parameters refer to the table
in PD007.
The related parameters: PD044~PD049 and P084~PD085
P022
Factory Reserved
Set Range01
Unit1
Factory Setting1
Unit1
Factory Setting1
0STOP invalid.
1STOP valid.
This parameter set is only valid when PD001 is set to l or 2.
When the control mode is set for external terminals or communication control, STOP key on the
panel can be chosen to be valid or invalid. When choosing it as valid, STOP key can stop the
inverter in running. When it needs to restart, the former running signal must be released before
restarting the inverter.
PD025 Starting Mode
Set Range01
Unit1
Factory Setting0
Two starting modes are available for the needs of different equipment.
0Start from the starting frequency.
When PD029 is set to 0, i.e. DC braking is invalid at start, it starts running from the starting
frequency. When PD029 is set to any non-zero value, i.e. DC braking is valid at start, itl first
performs a DC braking at start, and then starts from the starting frequency.
For the related parameters refer to PD035, PD031 and PD029.
1Start by frequency track
This setting can be used for the restarting of large inertia load. When restarting, the inverter will
trace the former frequency from the set frequency downward. In case of large inertia equipment,
when restarting, it can implement the running command and track the former frequency right
away without waiting for the complete stop of the equipment to save time.
Note: When the inverter is restarted by frequency track, it will start tracking the frequency from
its set frequency downward, and search it at the highest speed. When restarting, the current
becomes higher, and over-current or stall may occur. So attention must be paid to the adjustment
of current level of frequency track. Generally, PD033 is adjusted around 100. The concrete value
can be set according to the characteristics of mechanical load.
Run comm..
Set F.
Ouput F.
Output Power
Unit1
Factory Setting0
Two stopping modes are available for the needs of different equipment.
0Decelerating Stop
When PD030 is set to 0, DC braking is invalid. When DC braking is invalid, the inverter will
decelerate to the stopping frequency, and then stop outputs, and the motor will coast to stop. When
PD030 is set to any non-zero value, DC braking is valid, and the inverter will first decelerate to
the stopping frequency, and then stop by DC braking.
DC braking at stop is usually used for high position stop or for positioning control. It must be
noticed that frequent uses of DC braking will cause over-heat of the motor.
For the related parameters refer to PD028, PD031 and PD030.
1Coasting Stop
When the inverter receives a STOP command, it will immediately stop output and the motor will
coast to stop. When the coasting stop mode is selected, DC braking is invalid.
PD027 Starting Frequency
Set Range0.110.0 Hz
Unit0.1Hz
Factory Setting0.5
Starting frequency is the initial frequency when the inverter is started. If the starting frequency is
set to 4.0Hz, the inverter will run between 4.0 Hz and the maximum operating frequency after its
start at 4.0Hz . The actual maximum operating frequency is limited by the upper limit of
frequency.
For the related parameters refer to PD025, PD031 and PD029.
PD028 Stopping Frequency
Set Range0.110.0 Hz
Unit0.1Hz
Factory Setting0.5
When stopping the inverter will decrease its frequency to the stopping frequency and then stop
running or start DC braking to stop.
If PD030 is set to 0, DC braking is invalid at stop and the inverter will stop running.
If PD030 is set for valid, the inverter will stop by DC braking.
For the related parameters refer to PD026, PD031 and PD030.
PD029
Unit0.1S
Factory Setting0.0
This parameter is set for DC Braking at start and the
lasting time of DC Braking current to the motor. If it
is set to zero it means DC braking is invalid.
DC braking at start is normally used in the
Pd027
So the DC braking can be executed before starting the motor to prevent the inverter from tripping.
This setting is valid only when PD025 is set to 0. For the related parameters refer to PD025,
PD031 and PD027.
PD030
Factory Setting0.0
Pd028
T
Pd030
PD031.
PD031
Unit0.1%
Factory Setting2.0
This parameter is set for the DC braking voltage to the motor at start and stop. It can be adjusted
for different braking voltage. When adjusting the parameter it must be increased slowly from
lower value to high value until the sufficient braking torque is achieved.
The voltage at maximum frequency is 100% voltage.
PD032
Unit0.1S
Factory Setting2.0
This parameter is set as frequency track time when the inverter is started by frequency track after
an external abnormality or temporary power breakdown. For starting or stopping of some large
inertia load, if restarting a machine after its complete stop, it will waste much time because of its
large inertia of load. But if the frequency track is started, it is not necessary to wait for the
machine to come to a full stop for restart. The inverter will trace the frequency from high to low
with the set frequency. After searching it will continue to accelerate to reach the set frequency.
PD033
Unit1%
Factory Setting150
When the inverter is tracing the frequency this set value is taken as the level for output current.
When the output current is higher than this level the inverter will decrease the frequency to restore
the current below the level and then it will execute the frequency track again.
PD035 Up/down
Factory Setting
0.01
This parameter can be set in combination with PD078 for Up/Down of external control and the
speed of increase and decrease.
In case of PD078=1 the step length of Up/Down=the set value of PD035, i.e., the range can be set
to 0.01~25HZ.
In case of PD078=0 the step length of Up/Down=the set value of PD035 10, i.e., the range can
be set to 0.1~25.0HZ.
Note: 015 corresponds to 020K Hz
Unit1
Factory Setting5
The carrier frequency has some relation with the electromagnetic noise of the motor, and
meanwhile the level of the carrier frequency has certain relation with the heating capacity of the
inverter and the interference to the environment. See the following table
Carrier
Electromagnetic
Heating Capacity
Interference to
Frequency
Noise
Low
High
Small
Little
High
Low
Large
Great
the Environment
10
11
12
13
14
15
10
11
13
15
17
20
Carrier
Frequency
0.7
1 1.5
KHz
As shown in the table above, the higher the carrier is, the lower the electromagnetic noise of the
motor will be, but the stronger its interference to other systems will be and the greater the heating
capacity of the inverter will have. Under higher ambient temperature and heavier load of the motor
the carrier frequency should be decreased properly to improve the heat characteristics of the
inverter.
The factory setting of carrier frequency is depending on the model. For specific data refer to the
table in the description of PD007.
PD042 Jogging Frequency
Set Range0.00400.00
**
Unit0.01
Factory Setting5.00
The parameter set can realize the jogging function when the inverter is tested. The jogging
operation can be only achieved through the external terminals, which can be set by multi-input
terminals. Jogging frequency is limited by the frequency upper/lower limits. While the jogging
function is implemented, other running commands are invalid. The ramp-up time of jogging
frequency is set by Ramp-up Time 4. When the jog button is released the inverter will stop output
immediately. In case of jogging function please set the corresponding multi-input terminals to 07
or 08.
This function is only valid at stop. It is invalid at running. For the related parameters refer to
PD044-PD049.
Unit1
Factory Setting1
This parameter can be set for no impact slow start or slow stop of the inverter when starting or
stopping. When starting S-curve the inverter will make accelerating or decelerating curve of
different speed rates according to Ramp Time.
When PD043 is set as 0, S-curve is invalid, i.e. it will accelerate or decelerate in linear. Without
consideration of stall the actual accel/decal time = (PD008+PD043)/2. The parameter is only valid
when PD008 is less than PD043.
PD044
Factory Setting 02
PD045
Factory Setting 03
PD046
Factory Setting 10
PD047
Factory Setting 17
PD048
Factory Setting 18
PD049
Factory Setting 19
Set Range0032
UnitNo
00: Invalid.
01: RUN
02: FOR
Forward Rotation
03: REV
Reverse Rotation
04: STOP
Stopping
05: FOR/REV
06: JOG
Jogging
10: RST
Reset. This terminal can be used for reset after a fault is removed.
11: Reserved
12: Over-heat of heat sink or motor: This contact can be used to detect over-heat of the heat
sink or motor to protect the motor and inverter.
13: External Control Timer 1 Start: When the contact is closed, the timer will start and begin to
count time. When the timer reaches the set point the corresponding
multi-inputs will act.
14: External Control Timer 2 Start
15~16Reserved
17: High speed
High, middle and low speed can compose three kinds of operation mode
with different frequencies. In the three terminals the high-end signal has
20: Multi-speed 1
21: Multi-speed 2
22: Multi-speed 3
23: Ramp Time 1: This terminal can be used to select the ramp time of the inverter.
24: Ramp Time 2: 4 kinds of ramp time are available for choice.
25: UP Function
When the switch of this terminal acts the frequency setting of the inverter
will be increased or decreased by one unit. When the switch of the
terminal is hold the frequency will increase or decrease rapidly to a point
and then increase or decrease
at even speed. When the power is up again after the power breakdown the
changed frequency will not be memorized.
When this terminal is set for the counter it can receive the pulse signal of
250HZ and counts.
When this contact acts it will clear the present counting values displayed,
restore C00 and restart counting.
29Drawing Start
clear suspend.
32: PID Valid
When this contact is closed, PID function starts. PID Function start is
only valid during operation.
Note:
The above functions with the mark of are dedicated to the inverter of A series, which
may be not available for P or J series.
The functions of above 17 22 and 31 are not available for P series, and the function of
above 32 is not available for J series.
Explanation:
1. Three multi-function terminals can be used for the connection method of three-wire
system for the realization of switching of FOR/REV rotation, which is extensively applied in
the cases of FOR/REV switching of photoelectric switches.
Select FOR, REV and RST.
Parameter setting:
STOP RUN
rotation
PD045=03 for REV Rotation
Action Description:
When triggering FOR, the inverter will rotate forward
(start);
When triggering REV, the inverter will rotate reverse;
When pressing STOP, the inverter will stop.
2. RUN, DCM, F/R can be used for Start, Stop and switching of FOR/REV:
Select FOR and REV
K1
FOR
K2
REV
DCM
Parameter setting:
PD001=1 for external control
PD044=01 for RUN function
This function is only valid when PD080 is set to 0, 1 and 2. Under the disturbance and
internal control multi-speed it is invalid.
2)
Any two multi-inputs can be combined for 4 kinds of ramp time for selection.
3)
The related multi-inputs are set for Ramp Time 1, 2. Take the terminals of SPH and SPM as
example, when SPH PD047 is set to 23 and SPM PD048 is set to 24, SPH and SPM are now
Ramp Time 1, 2.
SPH
SPM
Result
OFF
OFF
Ramp Time 1
ON
OFF
Ramp Time 2
OFF
ON
Ramp Time 3
ON
ON
Ramp Time 4
RUN
SPL
SPM
SPH
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON/OFF
ON
OFF
Result
Main speed, the frequency runs at
the set value of PD003.
Low speed, the frequency runs at
the set value of PD086.
Middle speed, the frequency runs
ON/OFF
ON/OFF
ON
Note:
1This function is only valid when PD080 is set to 1, i.e. for 4-Speed of external control.
2Low, middle and high speed frequency are determined by Frequency 2,3, 4.
3Ramp time is determined by Ramp Select terminal.
4When all high, middle and low speeds have signal inputs it will give priority in the sequence
of high, middle and low speed.
5. Description of UP and DOWN Function:
Max.operating Frequency
Set frequency
F.Lower Limit
Up Command
Down Command
UP
DOWN
Result
ON
OFF
Frequency increase
OFF
ON
Frequency decrease
ON
ON
Note:
1The function of UP and DOWN is only valid when the operator is selected for the source of
the operating frequency, i.e. PD002=0.
2When the UP terminal is closed the frequency of the inverter will increase.
3When the DOWN terminal is closed the frequency of the inverter will decrease.
4When both UP and DOWN terminals are closed at the same time the frequency will neither
increase nor decrease. It is regarded as invalid.
5When the frequency reaches the max operating frequency it will stop increasing.
6When the frequency reaches the min frequency or its lower limit, it will stop decreasing.
7After a power breakdown the set value of PD003 will be memorized instead of the frequency.
8When using the function of UP and DOWN, the keys of of the panel are valid. After
changing the values it needs to press SET (ENTER) key for confirmation and then the
inverter can implement the action. Meanwhile the value will write to PD003, which will be
memorized after a power breakdown.
9When keeping pressing UP or DOWNthe frequency will increase or decrease rapidly to a
point and then increase or decrease at even speed.
10The value changed by UP or DOWN can be set through PD077 for confirmation of whether
it should be memorized or not memorized. For details refer to PD077.
6.
7.
C00
C00
cn
t1
t2
Note:
1The signal width triggered should not be lower than 2 msect1t22msec.
2When the counting value is reached the corresponding multi-output contact will act.
3This counter can only count again after reset.
4When reaching to 65535 the counter will not count again.
8. Description of AutoPLC Clear Suspend:
For details refer to 10. Example Application of AutoPLC Suspend in Appendix 1 and the
description of related parameters in PD117.
PD050
Factory Setting01**
PD051
Factory Setting05
PD052
Factory Setting02
PD053
Factory Setting00
Set Range0032
Unit1
06 Uniform Frequency 1 Reach: The contact will act when the output frequency of the inverter
reaches the designated frequency (PD060).
07Uniform Frequency 2 reach: The contact will act when the output frequency of the inverter
reaches the designated frequency (PD061).
08 In Accel: The contact will act when the inverter is in ramp-up.
09 In Decel: The contact will act when the inverter is in ramp-down.
10 Inverter Over-load Alarm: The contact will act when the inverter detects over-load.
11 Motor Overload Alarm: The contact will act when the inverter detects over-load of the
motor.
12 In Over-torque Detect: The contact will act when the inverter detects over-torque.
13 Low Voltage Alarm:
The contact will act when the inverter detects low voltage.
14 Single Step End: The contact will act and generate one pulse when the inverter finishes a
single step in implementation of program operation.
15 Process End: The contact will act and generate one pulse when the inverter finishes all
the steps (i.e. after one cycle) in implementation of program operation.
16Set Counter Reach: The contact will act when the inverter implements the external counter
and the counting value is equal to the set value (PD065).
17Middle Counter Reach: The contact will act when the inverter implements the external
counter and the counting value is greater than or equal to the set value (PD066).
18 External Control Timer 1 reach: The contact will act when the timer reaches the set value.
19External Control Timer 2 reach:
20420mA disconnected: When AI input signal is opened the contact will act.
25Auxiliary Pump 1: This contact controls the starting and stopping of auxiliary pumps. For
details refer to Operation of Multi-pumps.
26Auxiliary Pump 2
27Drawing reach: The contact will act when the drawing action is finished. The contact will
automatically reset when the inverter stops.
28PID Lower Limit Alarm: This contact will act when the PID feedback is smaller than the
lower limit (the set value of PD162).
29PID Upper Limit Alarm: This contact will act when the PID feedback is greater than the
upper limit (the set value of PD161).
30Fan act: When the temperature of the inverter is increased or it is in running, this contact will
act.
31Electromagnetic Relay Act: When the contact pulls in, the corresponding multi-function
terminal will act.
32Braking Resistor Act: When the inverter is in running and the DC voltage reaches the
braking voltage the contact will act.
Note:
The above functions with the mark of are dedicated to the inverter of A series, which
may be not available for P or J series.
The functions of above 14, 15 and 27 are not available for P series, and the functions of
above 25, 26, 28 and 29 are not available for J series.
PD054
Multi-Output AM
Set Range07
**
Unit1
Factory Setting0
Unit0.1%
Factory Setting100.0
This parameter can be used to adjust the output voltage value of Multi-output 6 to adapt to
frequency meters with different measuring range and also used to correct a frequency meter. For
example, for an externally connected frequency meter with the measuring range of 0~5V, a
multi-function terminal can be used to display its operating frequency. Then it can be corrected
with this parameter. It can be achieved by setting PD055=50 .
PD056 Skip Frequency 1
**
Unit0.01Hz
Factory Setting0.0
**
Unit0.01Hz
Factory Setting0.5
F
PD058
PD057
PD059
PD056
PD059
These three frequency skipping points are set for avoiding a mechanical resonance point. In case
of PD059=0, all skip frequencies are invalid. The actual skip frequency range is two times that of
PD059, as shown in the above diagram.
PD060
Uniform Frequency 1
**
PD061
Uniform Frequency 2
Set Range0.00400.00 Hz
PD062
Unit0.01 Hz
Factory Setting0.00
**
Unit0.01 Hz
Factory Setting0.50
When the output frequency is more than the uniform frequency the corresponding multi-outputs
will act. The uniform frequency range acts as a hysteresis loop.
When the inverter is in the operation of multi-pumps, PD060 (Uniform Frequency 1) is used as
high speed frequency and PD061 is set as low speed operating frequency. The definitions of the
corresponding multi-function contacts are changed.
t
T
Uniform
Uniform
Frequency
Frequency Range
When output F. is higher
than uniform F, the corresp.
multioutputs act.The
t
t
Multi-Output
Uniform Fequency
Unit: 1
Factory Setting0.01
Unit: 1
Factory Setting0
Timer 1 is a timer of 0.1s ~ 10.0s and Timer 2 is a timer of 1s ~ 100s. When the timer start at
multi-inputs is closed (on) the timer starts to count time. When it reaches the set time the
corresponding multi-output contact will act. When the timer start is opened (off) the timer time at
the multi-output will be reset.
ON
ON
PD063
For example, set PD063=5.0s. When the external control terminal (Multi-Input) is valid the output
terminal will be valid after five (5.0) seconds, the signal of which can be used to control other
corresponding signals.
PD065
Counting Value
**
Set Range065500
Unit1
Factory Setting0
An external terminal of multi-function can be used as a trigger for the counter. When the counter
reaches the set value of PD065 the corresponding multi-output contact will act. After the counter
is cleared and reset it will start counting again. A proximity switch or optoelectronic switch can be
used for the triggering signals.
PD066
Intermediate Counter
Set Range0-65500
Unit1
Factory Setting0
Refer to PD065.
PD070
Analog Input
Set Range010
Unit1
Factory Setting0
00~10V
10~5V
20~20mA
34~20mA
5XIA
6VI+XIA/2
73VA+XIA/4
8XIA+XIB/2
Unit1
Factory Setting20
The setting of this parameter is related to the analog responding speed. The higher the value of
PD071 is set, the lower the analog responding speed will be.
PD073
PD075
Unit0.01 Hz
Factory Setting0.00
Unit1
Factory Setting0
0Positive direction
1Negative direction
Bias direction means the instruction of FOR/REV rotation command. Positive bias indicates
forward rotation while negative bias indicates reverse rotation. For details refer to the diagram
in PD076.
PD072
Unit0.01Hz
Factory Setting50.00
PD074
Unit1
Factory Setting0
0Positive direction
1Negative direction
Bias direction means the instruction of FOR/REV rotation command. Positive bias indicates
forward rotation while negative bias indicates reverse rotation. For details refer to the diagram
in PD076.
PD076
Unit1
Factory Setting0
Rev. Area
50 Hz
0
4mA
5V
12mA
For. Area
10V
20mA
F
50
0
4mA
10V
20mA
F
40
0V
4
2V 10V
20mA
10
40
F
0V
4mA
10
PD077
2V
4.8mA
10V
20mA
UP/DOWN Function
Set Range0-1
0Not memorized
Unit1
Factory Setting0
1Memorized
This parameter can be set for the selection of whether the values changed by the UP or DOWN
shall be memorized or not after stop. The changed values whether to be memorized or not means
when they are changed by UP or DOWN during operation and the inverter is restarted after stop
these changed values shall be memorized or not after restart. When PD077 is set to 0, the changed
value will not be memorized and when it is set to 1, the changed values will be memorized. The
set values of PD003 will be memorized after restart.
For the related parameters refer to PD044-PD049.
PD078
UP/DOWN Speed
Set Range0-1
Unit1
Factory Setting0
PD080
PLC Operation
Set Range05
Unit1
Factory Setting0
* This function is not available for the inverter of P series. Default is normal operation.
0Normal operation, i.e. the inverter is running in the normal control mode.
1External control 4-Speeds (Refer to the function description and diagram of three terminals of
high, middle and low speed in C050C055)
2External control multi-speeds
Main F
FOR
Multispeed1
Multispeed2
Multispeed3
Multi-function Terminals
Results
Multi-speed 1
Multi-speed 2
Multi-speed 3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
Note:
It is only valid to realize the external control 8-Speeds operation when Multi-inputs are set for
Multi-speed 1, 2, 3 and PD080 is set to 2.
Multi-speed 1, 2, 3 can be used to make up 7-Speeds and 8-Speeds adding the main
frequency .
The frequencies of Speed Step 1 ~ Step 7 are determined by PD086~PD092.
Each ramp time is determined by the external multi-function terminal.
The directions of each program operation are determined by the external multi-function
terminals.
The main frequency can be set in two ways. One method is to set it through PD003 and
another is to set it through the potentiometer. When PD002 is set to 1 the frequency of Main
Frequency is set by the potentiometer. For the related parameters refer to PD003, PD002 and
PD086~PD092.
3Disturbance (Traverse function)
This is a special parameter in the chemical fiber and printing and dying industries to realize the
traverse function. Except the commands of stop, external faults and emergency stop all other
commands are not accepted at running.
F
PD003
PD092
PD101
PD102
PD092
PD086
Note:
The frequency at each inflection point is determined by PD003 and PD086.
Skip Frequency is determined by PD092.
Running Time is determined by Timer PD101 and PD102.
The related parameters: PD003, PD086~PD102.
4Internal control Multi-speeds
PD101
PD102
PD103
PD104
PD105
PD106
PD107
PD108
T
Note:
Main speed and 7-speeds composes 8-speeds.
The ramp time of each speed step is set by PLC Ramp Time CD079. Refer to the detail
descriptions of CD079.
Running Time is set by Timer PD101~PD108. For the control steps not to be used the timer
can be set to 0.
Running direction of each speed step is determined by CD078.
In the internal control multi-speed operation the running time and direction are determined by
the setting of internal parameters. Any switching of external time and FOR/REV rotation is
invalid.
5Drawing
This is a special parameter for the constant speed of unwinding and rewinding. By using this
function the linear speed constant in certain accuracy can be realized.
F
PD086
PD087
PD003
T
Note:
Through triggering of the external multi-function terminal the drawing action begins.
In implementation of the drawing action the actual running time is T=PD10110.
when the drawing action is finished the inverter will run at the constant seed of PD087 and the
corresponding multi-output contact will act at the same time. Until receiving the STOP
command the inverter will stop running and the multi-output contact will reset.
PD081 Auto PLC
Set Range03
Unit1
Factory Setting0
Pd087
Pd091
Pd088
Pd003
Pd092
Pd089
Pd087 Pd102
Pd103
Pd086
Pd108
Note:
When the command of auto program operation is given the inverter will run with each
parameters. But it will stop first and then restart at changing of each step and will stop
automatically after running for one cycle. The inverter will not restart and run until it receives
another command of operation.
The frequencies of each speed step are set by PD003 and PD086PD092.
The running times of each speed step are set by PD101PD108.
The running direction is set by P082
PD082 PLC Running Direction
Set Range0255
Unit1
Factory Setting0
This parameter is only valid when PD080 is set to 4. This parameter setting determine the running
direction of each frequency of PD086~PD092 and PD003 in the program operation. The setting
method is as follows:
The rotation direction is set first in the binary 8 bits mode, and then converted to a decimal value
for the setting of this parameter. For instance:
Bit07
7
0
0For.
1Rev.
Main SpeedPD003
Frequency 1PD086
Frequency 2PD087
Frequency 3PD088
Frequency 4PD089
Frequency 5PD090
Frequency 6PD091
Frequency 7PD092
For.
Rev.
For.
Rev.
For.
For.
Rev.
For.
Unit1S
Factory Setting0
Bit0
Ramp Time
Determine the Ramp time of each speed step in the binary 16 bit mode
Step 8
Step 7
Step 6
Step 5
Step 4
Step 3
Step 2
Step 1
t8
t7
t6
t5
t4
t3
t2
t1
120+121+125+126=99
So PD084 is set to 99
Attach20=1
21=2
24=16 25=32
22=4
23=8
26=64 27=128
Frequency 2
Factory Setting
15**
PD087
Frequency 3
Factory Setting
20
PD088
Frequency 4
Factory Setting
25
PD089
Frequency 5
Factory Setting
30
PD090
Frequency 6
Factory Setting
35
PD091
Frequency 7
Factory Setting
40
PD092
Frequency 8
Factory Setting
0.5
Set Range0.00400.00 Hz
Unit0.01 Hz
This parameter is set in combination of the multi-inputls to select 4-speeds of external control,
multi-speeds of external control or multi-speeds of internal control. For the relevant parameters
refer to the description of PD080 and PD101~PD108.
PD101
Timer 1
Factory Setting
10.0**
PD102
Timer 2
Factory Setting
10.0
PD103
Timer 3
Factory Setting
0.0
PD104
Timer 4
Factory Setting
0.0
PD105
Timer 5
Factory Setting
0.0
PD106
Timer 6
Factory Setting
0.0
PD107
Timer 7
Factory Setting
0.0
PD108
Timer 8
Factory Setting
0.0
Set Range0.06500.0S
Unit0.1S
This parameter is set for the internal control multi-speeds and the running time of drawing
function. For the relevant parameter refer to PD080 and PD086~PD102.
PD117
Factory Setting0
0Not memorized
1Memorized
This parameter is set to determine whether the inverter is to realize the suspending function in
AutoPLC mode. In case of PD117=1 it can memorize the status in which the inverter is running
and will memorize it at stop or fail. It will continue to run when returning to normal. In case of
PD117=0 it will not memorize. For specific applications refer to Example Application 10 in
Appendix 1.
PD118
Set Range01
Unit1
Factory Setting1
Unit1%
Factory Setting150
When the inverter is in ramp-up, due to overload or too short ramp-up time, the output current of
the inverter will go up quickly and exceed the set standard level. When this happens, the inverter
will stop accelerating. When the current returns under its set value, the inverter will go on to
accelerate.
100% current is the rated current of the motor. When this parameter is set to 0, the stall prevention
function is invalid.
PD120
Unit1%
Factory Setting0
When the inverter is running at constant speed, due to load fluctuation and other reasons, the
current will increase. When the current exceeds its set standard value, the inverter will lower the
output frequency. When the output current returns to its normal range, the inverter will accelerate
again to its set frequency.
100% current is the Rated Current of the motor. When this parameter is set to 0 the stall
prevention function is invalid.
PD121 Decel. Time for Stall Prevention at Constant Speed
Factory Setting5.0
When the inverter is used for the loads of kinds of fan and pump PD120 can be set to 120. When
the current of the inverter is greater than 120% the output frequency will decrease and the current
will also decrease accordingly. After the current returns to normal the frequency will return to
normal slowly, so as to achieve the stall prevention function. The decreasing speed of the
frequency is determined by PD121. For the Related parameters refer to CD 122.
PD122
Unit1
Factory Setting150
Refer to PD118.
Unit1
Factory Setting0
0When reaching the frequency it starts to detect over-torque and when over-torque is detected it
continues to run.
1When reaching the frequency it starts to detect over-torque and when over-torque is detected it
stop running.
2It detects over-torque during running and when over-torque is detected it continues to run.
3It detects over-torque during running and when over-torque is detected it stop running.
PD124
Unit1%
Factory Setting0
When the output current exceeds the over-torque detection level and also exceeds half of the set
time of over-torque detection (factory setting: 1.0s), the over-torque detection will indicate, and
the corresponding multi-function alarm contact will act. When it exceeds the set time, the inverter
will turn to self-protection. When this parameter is set to 0, the over-torque detection will be
invalid
PD125
Set Range0.120.0s
Unit0.1s
Factory Setting1.0
When the inverter detects that the output current has exceeded the motor current set value, the
inverter begins to calculate the over-torque time. When the over-torque time has exceeded half of
the set detect time, the corresponding multi-function output contact will act, and produce the
over-torque alarm, while the inverter will keep running. When the over-torque time has exceeded
the set detect time (set by PD125), the inverter will turn to self-protection, display the fault
information and stop output..
For the related parameters refer to PD124.
*PD130
Unit1
Factory Setting0
Unit1
Factory Setting60
Unit1
Factory Setting5S
Aux. pump
OFF
1O
N
OFF
O
PD13
*PD133
Unit1
Factory Setting60S
start.
*PD134
Unit1
Factory Setting60S
*PD135
Unit1
Factory Setting95%
Unit1
Factory Setting30S
Unit1
Factory Setting80%
Sleep Frequency
Set Range0.00400.0
Unit 1
Factory Setting20.00
*PD139
Unit1
Factory Setting20S
Lasting time of
stop voltage level
F
PD13
Wake-up level
PD13
7
Lasting time of
F
Sleep frequency
sleep frequency
PD139
PD138
Wake-up
Start to sleep
T
Yes
Turn On
No
FPD061
TPD134
Operating F
F=PD060
No
Yes
Yes
P PD135
No
TPD133
No
TPD139
Yes
No
No
FPD138
Aux.Pump
Run
No
TPD131
TPD139
Yes
Yes
No
Yes
FPD060
Enter Sleep
TPD133
Yes
Yes
No
P PD137
Aux.Pump
Run
Yes
Yes
FPD061
TPD134
Yes
Wakeup
Yes
Aux.Pump
Stop
Yes
Note:
T Run Time
F Operating Frequency
PD141
Unit0.1V
Factory Setting*
It is set according to the rated voltage value of the nameplate of the motor. For the inverters of
230V class the factory setting is 220, while for the inverters of 400 V class the factory setting is
380.
PD142
Unit0.1A
Factory Setting*
It is set according to the rated value of the nameplate of the motor. This parameter can be used to
restrict the output current of the inverter to prevent over-current and protect the motor. If the
current of the motor has exceeded this value the inverter of AC motor will turn to self-protection.
PD143
Unit1
Factory Setting04
This parameter is set for the number of the motors pole according to the nameplate of the motor.
PD144
Unit1r/min
Factory Setting1440
This is set according to the actual revolution of the motor. The displayed value is the same as this
set value. It can be used as a monitoring parameter, which is convenient to the user. This set value
corresponds to the revolution at 50Hz.
PD145 Auto Torque Compensation
Set Range0.110.0 %
Unit0.1%
Factory Setting2.0%
100%
Torgue Compens.
Unit1
Factory Setting40
The setting of motor no-load current will affect the value of slip compensation. The current is
100% of the rated current of the motor.
PD147
Unit0.1
Factory Setting0.0
When the inverter drives the motor the slip becomes bigger due to the increase of load. This
parameter can be set for slip compensation to decrease the slip and make the running speed of the
motor closer to the synchronous revolution.
PD150
Unit1
Factory Setting1
0Invalid
1Valid
When the input power is not stable and if the voltage is too high the operation of the motor with
the power exceeding the rated voltage will cause increase of the temperature of the motor, damage
of its insulation and unstable output torque. This auto voltage regulation can automatically
stabilize the output voltage within the rated voltage range of the motor under the condition of
unstable output power supply
When this function is set to invalid the output voltage will fluctuate.
PD151
Unit 1%
Factory Setting 0
When it is set to zero this function is invalid. When Auto energy saving function is started the
inverter will run at the full voltage during ramp-up or -down. During the operation at constant
speed the inverter can automatically calculate the optimum voltage value according to the power
of load and supply power to the load to achieve the goal of energy saving.
Output Voltage
100%
70%
F
Auto energy saving can reduce the normal output voltage by max 30%. For the load with frequent
changes or closing to full load, this function is not suitable.
PD152
Factory Setting1.0 s
When the inverter is set for fault restart and if it has a fault trip with the time exceeding the set
value of PD152 the inverter will restart. When using this function pay more attention to the safety.
PD153
Unit1
Factory Setting0
0Invalid, i.e. the inverter will not restart after an instantaneous power breakdown.
1Start by frequency track. Refer to PD032.
PD154
Set Range0.15.0S
Unit0.1S
Factory Setting0.5
This parameter is set for the maximum allowable power failure time. If exceeding the set time the
inverter will continue to stop output after power on. To restart the inverter it needs to follow the
general starting procedures.
PD155
Unit1
Factory Setting00
After the abnormal conditions (such as over-current and over-voltage) happens the inverter will
automatically reset and restart. If the starting mode is set to normal mode it will start according to
the normal procedures. If it is set to start by frequency track it will start in the frequency track
mode. After starting it will restore the set number again if there is no more abnormality happened
within 60 seconds. If there is still any error and it reaches the set number the inverter will stop
output. It can only be started after reset. When PD155 is set to zero the inverter will not carry out
the functions of automatic reset and restart.
*PD156
**
Unit0.1%
Factory Setting100%
**
Unit0.1s
Factory Setting5.0s
**
Unit0.01s
Factory Setting0
Target Value
Set Range0~100.0%
**
Unit1%
Factory Setting*
from temperature transmitter, or pressure transmitter, etc. Under PID control, the feedback signal
input path is the analog current signal of 4-20mA.
PID closed-loop control is valid when Multi-input PID is started.
PID Control Block Diagram:
Target value
After regulation
Time
Before regulation
Target value
After regulation
Time
**
Set Range01
Unit
Factory Setting0
**
Set Range0100%
Unit
Factory Setting100%
**
Set Range0100%
Unit
Factory Setting0%
PD163
Communication Addresses
Set Range00250
Unit
Factory Setting00
When the inverter is set for RS-485 Communication interface control, each of the inverters will be
set for its individual identification number through PD163.
00No communication function.
01~250Address for the inverters
PD164
04800 b/s
19600 b/s
Unit
219200 b/s
334800 b/s
Factory Setting1
PD165
Unit
Factory Setting0
ASCII
code
30H
31H
32H
33H
34H
35H
36H
37H
Byte
ASCII
Code
38H
39H
41H
42H
43H
44H
45H
46H
Stop bit
Even parity
Stop bit
Odd parity
Stop bit
8E1
Start bit
Stop bit
Even parity
Stop bit
Odd parity
Stop bit
8E1
Start bit
3AH
DATA
ADDR
FUNC
LEN
n-1
DATA0
CRC
END
CR0DH
LF0AH
STXStarting unit
3AH
ADDR communication address,8-bit data is composed of
two ASC byte.
00Broadcast mode is MODBUS
01~250Address of the corresponding inverters.
FUNCFunction code 8-bit data is composed of two ASC byte.
01FUNC READ, Read the data of function code
02FUNC WRIT, write the data of function code
03Write control data
04Read control status data
05Write inverter frequency data
06Reserved
07Reserved
08Loop test
aRead function code data
Format:
ADDR 01 LEN FUNC Data
ADDR=0 means no answer
jogr
jogf
jog
r/f
stop
rev
for
run
Track start
Braking
r/f
jogging
running
r/f
jog
run
DATA<Data characters> data content. 2n ASCII compose n bytes, it have fifty ASC at
most.
LRClongitudinal redundancy check
ASCII mode: Get LRC methods is that add ADDR to the last data, if the result is more than
256,then the result subtract 256 until the result is less then 256 (if the result is 128H, take 28H),
then 100H subtract the result get LRC.
For example: write 30.00Hz to inverter of 01write to PD003
STX
ADDR
FUNC
LEN
DATA
LRC
END
0 1
0 2
0 3
0 0 0 B B 8
3 7
CR LF
3AH 30H 31H 30H 32H 30H 33H 30H 30H 30H 42H 42H 38H 33H 37H
Calculate LRC: 01H+02H+03H+00H+0BH+B8H=C9H
C9H subtracted from 100H: 37H
So the sent data is following3AH 30H 31H 30H 32H 30H 33H 30H 30H 30H
42H 42H 38H 33H 37H 0DH 0AH
0DH 0AH
ADDR
FUNC
LEN
Dn-1~D(0)
CRC
50ms
Quiet
50ms
FUNC
LEN
DATA
CRC
01H
02H
03H
7FH 0CH
PD170
Display Items
Set Range 05
Unit1
Factory Setting0
This parameter is only valid when Bit 2 is set to 1 in PD171. For the details refer to PD171.
0Inverter Temperature
1Counter Value
2PID Target Value
3PID Feedback Value
4Present running time of power up (Unit: Hour)
5Total running time of power up (Unit: Hour)
PD171
Unit1
Factory Setting0
This parameter is set for selection of displaying of DC voltage, AC voltage and other items so that
the customer can monitor and view them in sequence through the switch key.
It can be is set first in the binary 3 bits mode, and then converted to a decimal value.
Bit2
Bit1 Bit0
0Invalid
1Valid
DC Voltage
AC Voltage
Select to display items of PD170.
1
In the contents displayed the factory setting is to show output frequency, set frequency, output
current and output revolution through the switch key. If it is necessary to view and monitor other
items they can be set through PD170 and PD171.
PD172
Fault Clear
**
Set Range0010
Unit1
Factory Setting00
Unit1A
Factory Setting*
PD175
Inverter Model
Set Range01
0Constant torque
PD176
Unit1
050Hz
160Hz
Factory Setting0
Factory Setting*
PD177
Fault Record 1
Factory Setting
PD178
Fault Record 2
Factory Setting
PD179
Fault Record 3
Factory Setting
PD180
Fault Record 4
Factory Setting
When it has no fault record it shows . After access to this parameter the fault display can be
checked.
PD181
Software Version
Factory Setting*
Manufacture date
4 3
Factory Setting*
PD183
Week
Month
Year
Serial No.
Factory Setting*
Note:
* means the said parameter has a variety of set values or should be set specifically according to
concrete conditions.
** means the said parameter can be set during the operation.