MTU10V1600DS550 550kVA Standby FuelOpt
MTU10V1600DS550 550kVA Standby FuelOpt
MTU10V1600DS550 550kVA Standby FuelOpt
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
380V
3
0.8
50
440
550
836
400V
3
0.8
50
440
550
794
415V
3
0.8
50
440
550
765
980
572RSL4029
150 C/40 C
4 LEAD WYE
1100
572RSL4029
150 C/40 C
4 LEAD WYE
1200
572RSL4029
150 C/40 C
4 LEAD WYE
//
//
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
10V 1600 Diesel Engine
- 17.5 Liter Displacement
- Common Rail Fuel Injection
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
//
//
//
//
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- PMG (Permanent Magnet Generator) supply to regulator
- 300% Short Circuit Capability
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//
STANDARD EQUIPMENT*
//
Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filters
Closed Crankcase Ventilation
Jacket Water Pump
Thermostats
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for
up to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
//
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
CANBus ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
APPLICATION DATA
//
Engine
//
Manufacturer
Model
Type
Arrangement
Displacement: L (Cu In)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Max Power: kWm (bhp)
Speed Regulation
Air Cleaner
//
MTU
10V 1600 G80F
4-Cycle
10-V
17.5 (1,068)
12.2 (4.8)
15 (5.91)
17.5:1
1,500
Electronic Isochronous (ADEC)
493 (661)
0.25%
Dry
//
109.4 (28.9)
82.9 (21.9)
62.5 (16.5)
50 (122)
0.125 (0.5)
390 (103)
227 (12,909)
75 (4,265)
51.6 (2,934)
16.4 (22)
//
Fuel Consumption
61 (16)
60 (15.9)
99.3 (26.2)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 C (0 F)
24
1,050
//
Air Requirements
29 (1,017)
554 (19,564)
187 (6,618)
Fuel System
//
Exhaust System
540 (1,004)
83 (2,924)
15 (60.2)
Drawing above for illustration purposes only, based on standard open power 400 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
3,416 x 1,873 x 2,032 mm (134.5 x 73.75 x 80 in)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
C/F
CO
C/F
MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 556 (77 3E) 2014-08
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.