X2500

Engine type

16V4000G63F

Alternator type

LSA 51.2VL90

GENERAL CHARACTERISTICS

DESCRIPTIVE
Electronic governor
Mechanically welded chassis with antivibration
suspension

Frequency (Hz)

50

Reference voltage (V)

400/230

Max power ESP (kVA)

2500

Max power ESP (kWe)

2000

Max power PRP (kVA)

2272.7

Max power PRP (kWe)

1818.2

Intensity (A)

3609

Optional control panel

M80

Optional Control Panel

TELYS

Optional control panel

KERYS

Air cooler for wiring temperature of 47/50C with


electric fan
Exhaust compensators with flanges
24 V charge alternator and starter

DIMENSIONS AND NOISE LEVELS

Delivered with oil

DIMENSIONS COMPACT VERSION

Manual for use and installation

Length (mm)

4818

Width (mm)

1885

Height (mm)

2158

Dry weight (kg)

14235

POWERS

POWER DEFINITION
PRP : Prime Power is available for an unlimited number
of annual operating hours in variable load applications, in
accordance with ISO 8528-1.
ESP : The standby power rating is applicable for
supplying emergency power in variable load applications in
accordance with ISO 8528-1.
Overload is not allowed.

Voltage

415/240
400/230
380/220

ESP

PRP

Standby Amps

kWe

kVA

kWe

kVA

2000
2000
2000

2500
2500
2500

1818
1818
1818

2273
2273
2273

3478
3609
3798

TERMS OF USE
According to the standard, the nominal power assigned by the
genset is given for 25C Air Intlet Temperature, of a barometric
pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity.
For particular conditions in your installation, refer to the derating
table.

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.

X2500
TECHNICAL SPECIFICATIONS
GENERAL ENGINE DATAS

EXHAUST

Cylinder arrangement

MTU
16V4000G63F , 4temps, TURBO ,
AIR/WATER 16 X
V

Displacement (C.I.)

76.27

Bore (mm) x Stroke (mm)

170 x 210

Compression ratio

16.5

Speed (RPM)

1500

Pistons speed (m/s)


Maximum stand-by power at rated
RPM (kW)
Frequency regulation (%)

10.5

BMEP (bar)

20.61

Governor type

ELEC

Engine model

2162

Exhaust gas temperature (C)

485

Exhaust gas flow (L/s)

5800

Max. exhaust back pressure (mm EC)

500

FUEL
Consumption @ 110% load (L/h)

N/A

Consumption @ 100% load (L/h)

436

Consumption @ 75% load (L/h)

331

Consumption @ 50% load (L/h)

232

Maximum fuel pump flow (L/h)

1500

0.5

COOLING SYSTEM
Radiator & Engine capacity (L)

N/A

Max water temperature (C)

104

Outlet water temperature (C)

100

Fan power (kW)

N/A

Fan air flow w/o restriction (m3/s)


Available restriction on air flow (mm
EC)
Type of coolant

N/A

Thermostat (C)

79/92

N/A
COOLELF-MDX

OIL
Oil capacity (L)

300

Min. oil pressure (bar)

3.5

Max. oil pressure (bar)

Oil consumption 100% load (L/h)

1.31

Carter oil capacity (L)

240

HEAT BALANCE
Heat rejection to exhaust (kW)

N/A

Radiated heat to ambiant (kW)

90

Haet rejection to coolant (kW)

730/320

AIR INTAKE
EMISSIONS
Emission PM (g/kW.h)

N/A

Emission CO (g/kW.h)

N/A

Emission HCNOx (g/kWh)


Emission HC (g/kW.h)

N/A
N/A

Max. intake restriction (mm EC)


Intake air flow (L/s)

150
2300

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.

X2500
ALTERNATOR SPECIFICATIONS
GENERAL DATAS

OTHER DATAS

Alternator brand

LEROY SOMER

Continuous Nominal Rating 40C (kVA)

2345

Alternator type

LSA 51.2VL90

Number of phase

Standby Rating 27C (kVA)


Efficiencies 4/4 load (%)

2580
96.5

Power factor (Cos Phi)

0.8

Air flow (m3/s)

2.5

Altitude (m)

0-1000

Short circuit ratio (Kcc)

0.43

Overspeed (rpm)

2250

Direct axis synchro reactance unsaturated (Xd) (%)

290

Number of pole

Quadra axis synchro reactance unsaturated (Xq) (%)

174

Excitation system
Insulation class / T class, continuous
40C
Regulation

AREP

Open circuit time constant (T'do) (ms)

3050

H / H-125

Direct axis transcient reactance saturated (X'd) (%)

21.3
263

Harmonic factor, no load TGH/THC

<3.5

Wave form : NEMA=TIF-(TGH/THC)

INF50

Wave form : CEI=FHT-(TGH/THC)

INF2

Number of bearing

Coupling
Voltage regulation at established rating
(%)
Recovery time (Delta U = 20%
transcient) (ms)

DIRECT

Short circuit transcient time constant (T'd) (ms)


Direct axis subtranscient reactance saturated (X''d)
(%)
Subtranscient time constant (T"d) (ms)
Quadra axis subtranscient reactance saturated (X"q)
(%)
Zero sequence reactance unsaturated (Xo) (%)

R449

11.1
26
13.8
2.6

Negative sequence reactance saturated (X2) (%)

12.5

0.5

Armature time constant (Ta) (ms)

49

700

No load excitation current (io) (A)

1.4

Full load excitation current (ic) (A)

4.7

Full load excitation voltage (uc) (V)

53

Recovery time (Delta U = 20% transcient) (ms)


Engine start (Delta U = 20% perm. or 50% trans.)
(kVA)
Transcient dip (4/4 load) - PF : 0,8 AR (%)

700

No load losses (W)

20400

Heat rejection (W)

68000

4500
11.3

DIMENSIONS AND NOISE LEVELS


EUR40 SI CONTAINER
Canopy
Length (mm).
Width (mm).
Height (mm).
Dry weight (kg).
Tank capacity (L).
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)

EUR40 SSI CONTAINER


EUR40 Si
12192
2438
2896
25150
500
85
108

Canopy
Length (mm).
Width (mm).
Height (mm).
Dry weight (kg).
Tank capacity (L).
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)

EUR40 SSi
12192
2438
2896
25880
500
79
102

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.

X2500
CONTROL PANEL
M80, transfer of information

TELYS, ergonomic and user-friendly

The M80 is a dual-function control unit. It can be used


as a basic terminal block for connecting a control box
and as an instrument panel with a direct read facility,
with displays giving a global view of your generating
set's basic parameters.

The highly versatile TELYS control unit is complex yet


accessible, thanks to the particular attention paid to
optimising its ergonomics and ease of use. With its
large display screen, buttons and scroll wheel, it
places the accent on simplicity and communication.

Offers the following functions:

The TELYS offers the following functions:

Engine parameters: tachometer, working hours


counter, coolant temperature indicator, oil pressure
indicator, emergency stop button, customer
connection terminal block, CE

Electrical measurements: voltmeter, frequency


meter, ammeter.
Engine parameters: working hours counter, oil
pressure, coolant temperature, fuel level, engine
speed, battery voltage.
Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternator
min./max., battery voltage min./max., emergency
stop, fuel level.
Ergonomics: wheel for navigating around the
various menus.
Communication: remote control and operation
software, USB connections, PC connection.
For more information on the product and its options,
please refer to the sales documentation.

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.

KERYS, coupling and adaptability

The KERYS control unit has been designed to fulfil


the specific requirements of professionals in terms of
operating and monitoring generating sets. It therefore
offers a wide range of functions.
This control unit is fitted as standard to all generating
sets designed to be used for coupling and is offered
as an option across the rest of our range.
The KERYS can be built into the central console,
fitted directly on the generating set, or in a separate
cabinet, to fulfil all the requirements for low and high
output power plants.
>The KERYS offers the following functions:
Electrical measurements: voltmeter, frequency
meter, ammeter.
Engine parameters: working hours counter, oil
pressure, coolant temperature, fuel level, engine
speed, battery voltage.
Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternator
min./max., battery voltage min./max., emergency
stop.
Additional functions: coupling, website,
diagnostic aid, assistance and maintenance, graphs
and archiving, load impact management, 8 available
installation configurations, certification in line with
international standards.
For more information, please refer to the sales
documentation.
Additional specifications :Website, Troubleshooting,
Assistance and Maintenance, Plotting and logging,
Load impact, 8 configurations available, Compliance
with international standards...

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.

You might also like