J66
J66
GENERAL CHARACTERISTICS
Frequency (Hz) Reference voltage (V) Max power ESP (kVA) Max power ESP (kWe) Max power PRP (kVA) Max power PRP (kWe) Intensity (A) Standard Control Panel Optional control panel 50 400/230 66 52.8 60 48 95 NEXYS TELYS
Length (mm) Width (mm) Height (mm) Dry weight (kg) Tank capacity (L)
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.
POWERS
Voltage 415/240 400/230 380/220 240 TRI 230 TRI 220 TRI 220/127 200/115 53 53 53 53 53 53 53 53 ESP kWe kVA 66 66 66 66 66 66 66 66 kWe 48 48 48 48 48 48 48 48 PRP kVA 60 60 60 60 60 60 60 60 92 95 100 159 166 173 173 191 Standby Amps
TERMS OF USE
According to the standard, the nominal power assigned by the genset is given for 25C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table. For the generating sets used indoor, where the acoustic pressure levels depends on the installation conditions, it is not possible to specify the ambient noise level in the exploitation and maintenance instructions . You will also find in our exploitation and maintenance instructions a warning concerning the air noise dangers and the need to implement appropriated preventive measures.
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.
J66K
ENGINE SPECIFICATIONS
GENERAL ENGINE DATAS
Engine model Cylinder arrangement Displacement (C.I.) Bore (mm) x Stroke (mm) Compression ratio Speed (RPM) Pistons speed (m/s) Maximum stand-by power at rated RPM (kW) Frequency regulation (%) BMEP (bar) Governor type JOHN DEERE 4045TF120 , 4-temps, Turbo , N/A 4 X L 4.48 106 x 127 17 : 1 1500 6.35 70 +/- 2.5% 11.24 Mechanical
EXHAUST
Exhaust gas temperature (C) Exhaust gas flow (L/s) Max. exhaust back pressure (mm EC) 545 176 750
FUEL
Consumption @ 110% load (L/h) Consumption @ 100% load (L/h) Consumption @ 75% load (L/h) Consumption @ 50% load (L/h) Maximum fuel pump flow (L/h) 17.5 16 12 8.5 108
OIL
Oil capacity (L) Min. oil pressure (bar) Max. oil pressure (bar) 13.5 1 5 0.02 12.5
COOLING SYSTEM
Radiator & Engine capacity (L) Max water temperature (C) Outlet water temperature (C) Fan power (kW) Fan air flow w/o restriction (m3/s) Available restriction on air flow (mm EC) Type of coolant Thermostat (C) 23.6 105 93 1.4 2.53 20 Gencool 82-94
HEAT BALANCE
Heat rejection to exhaust (kW) Radiated heat to ambiant (kW) Haet rejection to coolant (kW) 54 8 35
EMISSIONS
Emission PM (mg/Nm3) Emission CO (mg/Nm3) Emission HCNOx (g/kWh) Emission HC (mg/Nm3) 60 190 N/A 150
AIR INTAKE
Max. intake restriction (mm EC) Intake air flow (L/s) 625 66
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.
J66K
ALTERNATOR SPECIFICATIONS
GENERAL DATAS
Alternator brand Alternator type Number of phase Power factor (Cos Phi) Altitude (m) Overspeed (rpm) Number of pole Excitation system Insulation class / T class, continuous 40C Regulation Harmonic factor, no load TGH/THC Wave form : NEMA=TIF-(TGH/THC) Wave form : CEI=FHT-(TGH/THC) Number of bearing Coupling Voltage regulation at established rating (%) Recovery time (Delta U = 20% transcient) (ms) LEROY SOMER LSA 43.2 M45 3 0.8 0 1000 2250 4 SHUNT H / H / 125K N/A < 2% < 50 < 2% 1 Direct +/- 0.5% 500 ms
OTHER DATAS
Continuous Nominal Rating 40C (kVA) Standby Rating 27C (kVA) Efficiencies 4/4 load (%) Air flow (m3/s) Short circuit ratio (Kcc) Direct axis synchro reactance unsaturated (Xd) (%) Quadra axis synchro reactance unsaturated (Xq) (%) Open circuit time constant (T'do) (ms) Direct axis transcient reactance saturated (X'd) (%) Short circuit transcient time constant (T'd) (ms) Direct axis subtranscient reactance saturated (X''d) (%) Subtranscient time constant (T"d) (ms) Quadra axis subtranscient reactance saturated (X"q) (%) Zero sequence reactance unsaturated (Xo) (%) Negative sequence reactance saturated (X2) (%) Armature time constant (Ta) (ms) No load excitation current (io) (A) Full load excitation current (ic) (A) Full load excitation voltage (uc) (V) Recovery time (Delta U = 20% transcient) (ms) Engine start (Delta U = 20% perm. or 50% trans.) (kVA) Transcient dip (4/4 load) - PF : 0,8 AR (%) No load losses (W) Heat rejection (W) 60 66 89 0.27 0.39 304 182 1270 11.9 50 5.9 5 7.4 0.5 6.7 8 0.4 1.6 30 500 ms 156 15.5 1120 5890
CONTAINMENT 48H
Canopy Length (mm). Width (mm). Height (mm). Dry weight (kg). Tank capacity (L). Acoustic pressure level @1m in dB(A) (associated uncertainty) Sound power level guaranteed (Lwa) in dB(A) M128 DW48 2344 1060 1989 1687 700 74 (0.47) 92
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.
J66K
CONTROL PANEL
NEXYS, comprehensive and simple TELYS, ergonomic and user-friendly
The NEXYS is a versatile control unit allowing operation in manual or automatic mode. Equipped with an LCD screen, the user-friendly NEXYS offers high-quality basic functions to guarantee simple, reliable operation of your generating set. Offers the following functions: Standard electrical measurements: voltmeter, frequency meter, ammeter. Engine parameters: working hours counter, engine speed, battery voltage, fuel level. Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed (> 60 kVA), charging alternator fault, low fuel level, emergency stop. For more information, please refer to the sales documentation.
The highly versatile TELYS control unit is complex yet accessible, thanks to the particular attention paid to optimising its ergonomics and ease of use. With its large display screen, buttons and scroll wheel, it places the accent on simplicity and communication. The TELYS offers the following functions: Electrical measurements: voltmeter, frequency meter, ammeter. Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage. Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop, fuel level. Ergonomics: wheel for navigating around the various menus. Communication: remote control and operation software, USB connections, PC connection. For more information on the product and its options, please refer to the sales documentation.
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.