VTT10000 Manual PDF
VTT10000 Manual PDF
VTT10000 Manual PDF
VESDA
VESDA Test
Transformer
(VTT-100)
The Americas
Vision Fire & Security
700 Longwater Drive
Norwell, MA 02061, USA
Ph
+781 740 2223
Toll Free 800 229 4434
Fax
+781 740 4433
www.vesda.com
Private and Confidential
February 2004
This document may not be reproduced, in whole or in part, by any means without the prior
express written permission of the copyright owner. Copyright 2003 Vision Fire & Security Pty
Ltd A.C.N. 008 009 514. The manufacturer reserves the right to change designs or
specifications without obligation and without further notice. VESDA, LaserTEKNIC, LaserPLUS,
LaserSCANNER, LaserCOMPACT, LaserFOCUS, VESDAnet, VESDAlink, ASPIRE, AutoLearn,
VSM, VConfig, InfoWORKS, PROACTIV, PRECISION and VSC are trademarks used under
licence by the distributor.
Part No.: 20333
Revision No. 03
VESDA
VESDA
Table of Contents
1.0
Introduction
2.0
3.0
Equipment Set Up
4.0
5.0
Smoke Test
6.0
References
7.0
Specification
8.0
Compliance
9.0
Ordering Information
VESDA
1.0
VESDA
Introduction
This Guide describes the use of the VESDA Test Transformer (VTT-100
previously known as the Hot Wire Test Power Supply Unit (PSU)) to test
very early warning aspirated smoke detection equipment. The unit provides
6VAC output from 220-240VAC or 110-120VAC mains supply. High current
is passed through a test cable in order to heat it, which causes its insulation
to burn giving off smoke. A timer is incorporated to provide a selectable
burn period of up to 3 minutes.
Note:
The timer also helps to prevent the unit being inadvertently left on for
an extended period. The unit must never be left on and unattended!
The rocker switch on the top of the unit is the on/off switch. When power is
applied and the unit is turned on the (green) POWER indicator on the
timer flashes and power is applied to the output terminals until the set time
has elapsed. Once the timer has timed out the output is switched off and
the (red) OUT indicator on the timer illuminates. The POWER indicator
then stops flashing and remains illuminated. The timer is reset when the
switch is turned off and will run for the full selected period when the switch
is turned on again.
Note:
The on/off switch may be illuminated while the unit is switched on.
This is not an indication that the output is active.
The unit must be operated for no more than three (3) minutes
continuously and must be left off immediately after operating for a period of
at least seven (7) minutes to allow it to cool.
Note:
2.0
When performing a hot wire test ensure that local standards and regulations
are understood and have been adhered to where applicable. Also, ensure
that the VESDA detection equipment being proved/tested is isolated from
both the local fire authority notification alerts and any suppressant actioning
devices.
WARNING - The hot wire test is intended to trigger a response from
the Aspirating Detector under test ensure that the
consequences of this activation are understood and
under control.
Precautions must also be taken to ensure that all people present are aware
that the test is being conducted and that those who are required to remain
in the immediate vicinity of the test are suitably attired for the smoke levels
about to be created.
WARNING - Avoid inhaling the smoke plume as it contains small
quantities of HCl.
The wire burn tests, particularly the 1m and 2 x 1m tests, produce
sufficiently high temperatures to generate small quantities of hydrogen
chloride. However, test personnel are unlikely to be exposed to
concentrations of hydrogen chloride that exceed the Occupational Exposure
Standard (OES) of 5ppm in a 15 minute period unless they are directly
exposed to the smoke plume.
VESDA
VESDA
1.
2.
3.
4.
Turn the unit off and disconnect the power supply cord.
Eject the fuse drawer.
Remove the existing fuse and replace with one of the correct rating.
(See below.)
Reinsert the fuse drawer.
The timer must be in mode A with the scale set to min (minutes) and the
scale showing from 0 to 3 (maximum of three minutes operation). The
timer should appear like this:
Due to the nature of Hot Wire tests there is a minor fire hazard. It is
strongly recommended that an appropriate type of fire extinguisher (e.g.
CO2 or dry powder) is available during the test.
It is the responsibility of the person carrying out the tests that the electrical
equipment used is maintained at all times for safety. In particular, check
that the supply voltage selector is set appropriately, the correct fuse is fitted
for the selected voltage and that a power cord with suitable local approvals
is used.
If in doubt, please seek guidance from a suitably qualified electrician.
3.0
Equipment Set Up
CAUTION:
If the voltage selector does not match the supply voltage in use then do the
following:
1.
2.
3.
4.
If the timer does not match this picture then do not operate the unit.
Contact VESDA support to resolve this issue.
It is recommended to confirm the accuracy of the burn period using a
stopwatch and a suitable multimeter connected to the output terminals
before conducting any live tests. If this is necessary, seek guidance from a
suitably qualified electrician.
Remotely switching power to the VTT-100 from the mains outlet can assist
in the reduction of possible smoke inhalation by personnel.
Turn the unit off and disconnect the power supply cord.
Using a screwdriver, undo the screws that hold the transparent cover
in place and remove the cover.
Select the correct voltage (to match your supply) on the selector
switch.
Replace the transparent cover and redo the cover screws.
If the fuse is not the correct rating for the supply voltage in use then do the
following:
VESDA
VESDA
5.0
Smoke Test
Ensure that the local fire panel is isolated from the external fire reporting
equipment and that any automatic extinguishing or suppressant systems
are similarly isolated.
Connect power to the VTT-100 and turn the switch on.
At this point, there is 6VAC applied across the test wire, the switch will
illuminate and the green indicator on the timer will begin to flash. The test
wire will become hot and a small quantity of smoke will be generated.
The test wire samples should be carefully measured and cut to the required
length. The ends should be stripped at approximately 15mm using a
suitable tool. If in doubt, please seek guidance from a suitably qualified
electrician.
WARNING - The test wire becomes very hot during the test and will
cause burns if held in the hand. Care must be taken
throughout this test process.
4.0
Turn the unit off after the timed burn period is complete.
Smoke shall be generated and the time for the detection should be
recorded to ensure that transport and alarm times are within the local
regulatory requirements.
6.0
References
Note that appropriate guidance should be noted to the local and applicable
standards and regulations such as the following:
BS5389 Part1: 2002
BS6266:1992
BS6266:2002 (which cross references to the BFPSA Code of Practice)
NFPA 76 :2002
BFPSA Code of Practice for Category 1 Aspirating detection systems,
Appendix A.
This Appendix is published on the BFPSA website at www.bfpsa.org.uk.
BFPSA British Fire Protection Systems Association.
VESDA
7.0
Specification
Type:
Voltage Input:
Input Rating:
Fuse:
Output:
Operating Time:
Protection:
9.0
VTT-10000
220-240VAC, 50Hz or 110-120VAC, 60Hz
800mA @ 240VAC, 50Hz, 1.6A @ 120VAC, 60Hz
220-240VAC, 800mA(T) (Anti-surge)
110-120VAC, 1.6A(T) (Anti-surge)
6VAC nominal, 20A
Maximum on time: 3 minutes (180 seconds)
Minimum off time between tests: 7 minutes (420
seconds)
IP30
8.0
Compliance
Safety:
EMC:
VESDA
Ordering Information
VTT-10000
VTT-10000-AUS
VTT-10000-UK
VTT-10000-EUR
VTT-10000-USA
Australia
United Kingdom
Europe
United States
Further Information
Contact your nearest Vision Fire & Security office or distributor for further
information.