Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sunny Boy 3000tl Us Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88

PV Inverter

SUNNY BOY
3000TL-US / 4000TL-US / 5000TL-US
Installation Manual

SB3-5TLUS22-IA-en-12 | Version 1.2

CA

US

YOUR ^DDISTRIBUTOR
SOLIGENT
800-967-6917
www.soligent.net

SMA America, LLC

Copyright 2013 SMA America,LLC. All rights reserved.


No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form
or by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior
written permission of SMA America,LLC.
Neither SMA America,LLC nor SMA Solar Technology Canada Inc. makes representations, express
or implied, with respect to this documentation or any of the equipment and/or software it may
describe, including (with no limitation) any implied warranties of utility, merchantability, or fitness for
any particular purpose. All such warranties are expressly disclaimed. Neither SMA America,LLC nor
its distributors or dealers nor SMA Solar Technology Canada Inc. nor its distributors or dealers shall
be liable for any indirect, incidental, or consequential damages under any circumstances.
(The exclusion of implied warranties may not apply in all cases under some statutes, and thus the
above exclusion may not apply.)
Specifications are subject to change without notice. Every attempt has been made to make this
document complete, accurate and up-to-date. Readers are cautioned, however, that
SMAAmerica,LLC and SMA Solar Technology Canada Inc. reserve the right to make changes
without notice and shall not be responsible for any damages, including indirect, incidental or
consequential damages, caused by reliance on the material presented, including, but not limited to,
omissions, typographical errors, arithmetical errors or listing errors in the content material.
All trademarks are recognized even if these are not marked separately. Missing designations do not
mean that a product or brand is not a registered trademark.

SMA America, LLC


3801 N. Havana Street
Denver, CO 80239 U.S.A.
SMA Solar Technology Canada Inc.
2425 Matheson Blvd. E
8th Floor
Mississauga, ON L4W 5K5
Canada

Installation Manual

SB3-5TLUS22-IA-en-12

SMA America, LLC

IMPORTANT SAFETY INSTRUCTIONS


SAVE THESE INSTRUCTIONS
This manual contains important instructions for the following products:
Sunny Boy 3000TL-US (SB 3000TL-US-22)
Sunny Boy 4000TL-US (SB 4000TL-US-22)
Sunny Boy 5000TL-US (SB 5000TL-US-22)
This manual must be followed during installation and maintenance.
The product is designed and tested according to international safety requirements, but as with all
electrical and electronic equipment, certain precautions must be observed when installing and/or
operating the product. To reduce the risk of personal injury and to ensure the safe installation and
operation of the product, you must carefully read and follow all instructions, cautions and warnings
in this manual.

Warnings in this Document


A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice,
which, if not correctly performed or adhered to, could result in damage to or destruction of part or all
of the SMA equipment and/or other equipment connected to the SMA equipment or personal injury.
Symbol

Description
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

Warnings on this Product


The following symbols are used as product markings with the following meanings.
Symbol

Description
Warning regarding dangerous voltage
The product works with high voltages. All work on the product must only be
performed as described in the documentation of the product.
Beware of hot surface
The product can become hot during operation. Do not touch the product during
operation.
Electric arc hazards
The product has large electrical potential differences between its conductors. Arc
flashes can occur through air when high-voltage current flows. Do not work on the
product during operation.
Risk of fire
Improper installation of the product may cause a fire.
Observe the operating instructions
Read the documentation of the product before working on it. Follow all safety
precautions and instructions as described in the documentation.

Installation Manual

SB3-5TLUS22-IA-en-12

SMA America, LLC

General Warnings
General Warnings
All electrical installations must be made in accordance with the local and NationalElectrical Code
ANSI/NFPA 70 or the Canadian Electrical Code CSAC22.1. This document does not and is not
intended to replace any local, state, provincial, federal or national laws, regulation or codes
applicable to the installation and use of the product, including without limitation applicable
electrical safety codes. All installations must conform with the laws, regulations, codes and
standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the
compliance or non-compliance with such laws or codes in connection with the installation of the
product.
The product contains no user-serviceable parts.
For all repair and maintenance, always return the unit to an authorized SMA Service Center.
Before installing or using the product, read all of the instructions, cautions, and warnings in this
manual.
Before connecting the product to the electrical utility grid, contact the local utility company. This
connection must be made only by qualified personnel.
Wiring of the product must be made by qualified personnel only.

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

Table of Contents

Table of Contents
1 Information on this Document. . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Skills of Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3 Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 Sunny Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2 DC Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Type Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.1 Sunny Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.2 DC Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3.3 Symbols on the Type Labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12

Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zigbee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Secure Power Supply (SPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Retrofit Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Arc-Fault Circuit Interrupter (AFCI). . . . . . . . . . . . . . . . . . . . . . . . . . .
SD Card Slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Varistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SMA OptiTrac Global Peak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21
23
23
23
24
24
24
24
24

5 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1
5.2
5.3
5.4

Selecting the Mounting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Mounting the Wall Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the Inverter and DC Disconnect. . . . . . . . . . . . . . . . . . . . .
Attaching the Anti-Theft Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation Manual

SB3-5TLUS22-IA-en-12

25
28
30
32

Table of Contents

SMA America, LLC

6 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1 Safety during Electrical Connection. . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2 Overview of the Connection Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.1 Connection Area of the Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2.2 Connection Area of the DC Disconnect . . . . . . . . . . . . . . . . . . . . . . 35

6.3 AC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.1 Conditions for the AC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.2 Connecting the Inverter to the Utility Grid . . . . . . . . . . . . . . . . . . . . 37

6.4 DC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4.1 Safety during DC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4.2 Conditions for the DC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4.3 Connecting the PV Array . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

6.5 Connecting the Secure Power Supply Module . . . . . . . . . . . . . . . . . 43


6.6 Connecting the Zigbee Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.1 Making Settings via the Rotary Switches . . . . . . . . . . . . . . . . . . . . . . 47
7.1.1 Overview of the Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.1.2 Changing the Country Data Set and the Display Language . . . . . . 49
7.1.3 Changing the Display Language . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

7.2 Commissioning the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

8 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.1 Changing the Country Data Set Using a Communication Product . . 52
8.2 Activating and Setting SMA OptiTrac Global Peak . . . . . . . . . . . . . 52

9 Display and LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


9.1 Switching On the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9.2 Calling Up Messages of the Start Phase . . . . . . . . . . . . . . . . . . . . . . 53
9.3 LED Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

10 Disconnecting the Inverter from Voltage Sources . . . . . . . . . . 55


10.1 Disconnecting the DC Disconnect from Voltage Sources. . . . . . . . . . 57

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

Table of Contents

11 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
11.1
11.2
11.3
11.4
11.5

Event Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking the PV System for Ground Faults . . . . . . . . . . . . . . . . . . . .
Replacing DC Varistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59
60
71
71
73

12 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
12.1 Disassembling the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
12.2 Packing the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.3 Disposing of the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

13 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1 DC/AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1.1 Sunny Boy 3000TL-US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1.2 Sunny Boy 4000TL-US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
13.1.3 Sunny Boy 5000TL-US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

13.2
13.3
13.4
13.5
13.6
13.7
13.8

Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Climatic Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Storage Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

80
80
81
81
82
82
82

14 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
15 Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
16 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

Installation Manual

SB3-5TLUS22-IA-en-12

1 Information on this Document

SMA America, LLC

1 Information on this Document


Validity
This document is valid for the following device types as of firmware version HP V02.05.00.R,
KP V02.50.55.R:
Sunny Boy 3000TL-US (SB 3000TL-US-22)
Sunny Boy 4000TL-US (SB 4000TL-US-22)
Sunny Boy 5000TL-US (SB 5000TL-US-22)

Target Group
This document is for qualified persons. Only persons with the appropriate skills are allowed to perform
the tasks described in this document (see Section2.2 "Skills of Qualified Persons", page12).

Additional Information
Links to additional information can be found at www.SMA-Solar.com.
Document title

Document type

Capacitive Leakage Currents

Technical information

Shade Management

Technical information

Module Technology

Technical information

Symbols
Symbol

Explanation
Indicates information that is important for a specific topic or
objective, but is not safety-relevant.

Indicates a requirement for meeting a specific goal.

Desired result

A problem that could occur

Nomenclature
Complete designation

Designation in this document

SMA America Production, LLC

SMA

SMA Solar Technology Canada Inc.

SMA

Sunny Boy

Inverter, product

10

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

2 Safety

2 Safety
2.1 Intended Use
The Sunny Boy is a transformerless PV inverter which converts the direct current of a PV array into
grid-compliant alternating current and feeds it into the utility grid.
The inverter can be installed in the following grid configurations:
208Y/120 VAC Wye
120/240 VAC Split phase
The inverter is transformerless and has no galvanic isolation. Therefore, the inverter may only be
operated with ungrounded PV arrays. Furthermore, the PV array must be installed in accordance with
the National Electrical Code, Article 690.35 "Ungrounded Photovoltaic Power Systems" and the
locally valid regulations for ungrounded PV arrays. Additionally, the PV array (PV modules and
cabling) must have protective insulation and the PV modules used must be suitable for use with this
inverter. PV modules with a high capacity to ground may only be used if their coupling capacity does
not exceed 1,400 nF (for information on how to calculate the coupling capacity, see Technical
Information "Capacitive Leakage Currents" at www.SMA-Solar.com).
All components must remain within their permitted operating ranges at all times.
The inverter is suitable for indoor and outdoor use.
Do not mount the inverter on flammable construction materials.
Do not mount the inverter in areas where highly flammable materials are stored.
Do not mount the inverter in areas having a potentially explosive atmosphere.
Only use this product in accordance with the enclosed documentation and with the local standards
and directives. Any other use may cause injury to persons or property damage. For safety reasons,
it is forbidden to modify the product or install components that are not explicitly recommended for this
product or distributed by SMA.
The enclosed documentation is an integral part of this product.
Read and adhere to the documentation.
Keep the documentation in a convenient place for future reference.

Radio Frequency Exposure


The inverter can be fitted with a ZigBee wireless interface. If this is the case, do not remain
within 8 in. (20 cm) of the inverter for any length of time.

Installation Manual

SB3-5TLUS22-IA-en-12

11

2 Safety

SMA America, LLC

2.2 Skills of Qualified Persons


The tasks described in this document may only be performed by qualified persons. The qualified
person must have the following skills:
Knowledge of how an inverter works and is operated
Training in how to deal with the dangers and risks associated with installing and using electrical
devices and plants
Training in the installation and commissioning of electrical devices and plants
Knowledge of all applicable standards and directives
Knowledge of and adherence to this document and all safety precautions

2.3 Safety Precautions


Danger to life from electric shock due to high voltages in the inverter
High voltages that can cause fatal electric shocks are present in the live components of the inverter.
All work on the inverter may only be carried out by qualified persons.
Prior to performing any work on the inverter, disconnect the inverter on the AC and DC sides
(see Section10 "Disconnecting the Inverter from Voltage Sources", page55).
Only operate the inverter with the enclosure lid closed.
Do not open the upper enclosure lid.
Danger to life from electric shock due to damaged devices
Operating a damaged inverter can lead to hazardous situations that result in death or serious
injuries due to electric shock.
Only operate the inverter if it is technically safe and in full working order.
Check the inverter regularly for visible damage.
Only operate the inverter if there is no visible damage.

Risk of burns due to hot surfaces


The surface of the inverter can become very hot. Touching the surface can result in burns.
Do not touch hot surfaces.
During operation, do not touch any parts other than the lower enclosure lid of the inverter.
Observe the safety messages on the inverter.

12

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

2 Safety

Damage to the inverter due to electrostatic discharge


Touching electronic components can cause damage to or destroy the inverter through electrostatic
discharge.
Ground yourself before touching any components.
Observe local regulations
All electrical installations must comply with the electrical standards applicable on-site and the
National Electrical Code (ANSI/NFPA 70). Installations in Canada must comply with the
applicable Canadian standards.

Installation Manual

SB3-5TLUS22-IA-en-12

13

3 Scope of Delivery

SMA America, LLC

3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage.
Contact your distributor if the scope of delivery is incomplete or damaged.

Figure1:

Components included in the scope of delivery

Item

Quantity

Description

Inverter

Wall mounting bracket for the inverter

DC Disconnect

Wall mounting bracket for the DC Disconnect

Antenna for ZigBee communication*

M5 x 8 cheese-head screw

M5 x 12 cheese-head screw

M6 x 16 cheese-head screw

M5 conical spring washer (including 1 spare)

M6 conical spring washer

Installation manual, user manual, production test report,


supplementary sheet with the default settings

* optional

14

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

4 Product Description

4 Product Description
4.1 Sunny Boy
The Sunny Boy is a transformerless PV inverter which converts the direct current of a PV array into
grid-compliant alternating current and feeds it into the utility grid.

Figure2:

Sunny Boy design

Item

Description

Cooling fins

Type label

Display

Lower enclosure lid screws

Antenna for ZigBee communication*

LEDs

DC Disconnect

Lower enclosure lid

Upper enclosure lid


* optional

Installation Manual

SB3-5TLUS22-IA-en-12

15

4 Product Description

SMA America, LLC

The Sunny Boy is a multi-string inverter that has two input areas, A and B, each with its own
MPP tracker. This continually determines the maximum power point and controls the voltage on the
PV modules accordingly. The two separate MPP trackers make it possible to connect different
PV strings to input areas A and B. The PV strings may vary in the number of PV modules, their
orientation to the sun and shading.

Symbols on the Inverter


Symbol

16

Description

Explanation

Inverter

This symbol defines the function of the


green LED. The green LED indicates the
operating state of the inverter.

Observe the documentation.

This symbol defines the function of the


red LED. The red LED indicates an error.
Read this document for instructions on
how to correct the error.

Communication

This symbol defines the function of the


blue LED. The blue LED indicates the
communication state of the inverter.

Equipment grounding
conductor terminal

Connection for the AC equipment


grounding conductor

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

4 Product Description

4.2 DC Disconnect
The DC Disconnect is a DC load-break switch which safely disconnects the PV array from the inverter.

Figure3:

DC Disconnect design

Item

Description

Bracket for grounding the DC Disconnect enclosure

Rubber grommet for the enclosure opening

Bracket for hanging in the retainer

Type label 1

Conduit knockouts

Type label 2

Enclosure lid screws

Enclosure lid

Switch

Symbols on the DC Disconnect


Symbol

Installation Manual

Description

Explanation

Equipment grounding
conductor terminal

Connection for the DC equipment


grounding conductors

SB3-5TLUS22-IA-en-12

17

4 Product Description

SMA America, LLC

4.3 Type Labels


4.3.1 Sunny Boy
The type label provides a unique identification of the inverter. The type label is located on the
right-hand side of the enclosure.

Figure4:

Type label design

Item

Description

Explanation

Model

Inverter device type

S/N

Inverter serial number

Date of manufacture

Inverter manufacture date (month/year)

Device-specific characteristics

The information on the type label is required for both safe operation of the inverter and for customer
support from the SMA Service Line. The type label must remain permanently affixed to the inverter.

18

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

4 Product Description

4.3.2 DC Disconnect
The type label provides a unique identification of the DC Disconnect. The type label is located on the
right-hand side of the enclosure.

Figure5:

Layout of the type label

Item

Description

Explanation

Product name

Item No.

DC Disconnect device type

Date of manufacture

DC Disconnect manufacture date


(month/year) of the

Device-specific characteristics

Serial No.

DC Disconnect serial number

You will require the information on the type label to use the DC Disconnect safely and when seeking
customer support from the SMA Service Line. The type label must remain permanently affixed to the
DC Disconnect.

Installation Manual

SB3-5TLUS22-IA-en-12

19

4 Product Description

SMA America, LLC

4.3.3 Symbols on the Type Labels


Symbol

Description

Explanation

Danger to life due to high


voltages

The product operates at high voltages.


All work on the inverter may only be
carried out by qualified persons.

Risk of burns due to hot surfaces The product can become hot during
operation. Avoid contact during
operation. Allow the product to cool
down sufficiently before carrying out
any work. Wear personal protective
equipment such as safety gloves.

20

Observe the documentation.

Observe all documentation that is


supplied with the product.

ETL test mark

The product has been certified by


Intertek as being in accordance with the
applicable directives.

FCC test mark

The product complies with the


requirements of the applicable
FCC standards.

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

4 Product Description

4.4 Display
The display shows the current operating data of the inverter (e.g. current power, daily energy,
total energy) as well as events or error messages. The power and energy are displayed as bars in the
diagram.

kWh

kVAr
kW

kVArh
kWh
MVArh
MWh

A
B

C
D

K
Figure6:

Display layout (example)

Position

Description

Explanation

Power

Current power

Day

Daily energy

Total

Total energy generated since the initial start-up of


the inverter

Active functions

Displays the activated or active functions for


communication, network system services or
temperature derating

Line conductor

Line conductor involved for the values displayed

Event number relating to the


utility grid

Event number of errors relating to the utility grid

Output voltage/output current

Displays output voltage and output current of a


line conductor in alternation

Event number relating to the


inverter

Event number of errors relating to the inverter

Input voltage/input current

Displays input voltage and input current of an


input in alternation

Installation Manual

SB3-5TLUS22-IA-en-12

21

4 Product Description

SMA America, LLC

Position

Description

Explanation

Event number relating to the


PV array

Event number of errors relating to the PV array

Text line

Displays an event message or error message

Power and yield curve

Displays the power curve of the last 16 feed-in


hours or the energy yields of the last 16 days
In order to switch between the displays,
tap once on the enclosure lid.

Symbols on the Display


Symbol

Description

Explanation

Tapping

You can operate the display by tapping it


(see Section9 "Display and LEDs", page53).

Telephone receiver

Indicates a fault that cannot be corrected on site


Contact the SMA Service Line

22

Wrench

Indicates a fault that can be corrected on site by


a qualified person

Connection quality

Indicates the quality of the ZigBee connection


to other ZigBee devices

Speedwire connection

Indicates that communication via Speedwire is


active and that there is a network connection

Webconnect function

Indicates that there is a connection to


Sunny Portal

Temperature symbol

Indicates that the power of the inverter is limited


due to excessive temperature

Power limitation

Indicates that external active power limitation via


the Power Reducer Box is active

PV array

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

Symbol

4 Product Description

Description

Explanation

Inverter

Grid relay

Grid relay closed:


indicates that the inverter is feeding into the
utility grid
Grid relay open:
indicates that the inverter is disconnected from
the utility grid

Utility grid

4.5 Zigbee
If an antenna is included in the inverter scope of delivery, the inverter is equipped with a ZigBee
interface. ZigBee is a wireless networking standard that allows the establishment of a connection
between SMA inverters and other ZigBee-enabled devices. Using this system, the inverter can
transmit data to a Zigbee-enabled communication system which can make the data available on the
Internet via certain supported monitoring programs.

4.6 Communication Interface


The inverter can be fitted with a communication interface (e.g. RS485 or Speedwire with Webconnect
function). This communication interface enables the inverter to communicate with SMA communication
products or other inverters (for information on supported products, see www.SMA-Solar.com).
You can only set the inverter parameters via SMA communication products.
Depending on the type of communication, RS485 or Speedwire, the parameters and messages are
displayed differently on the communication products.
Example: How the country data set parameter is displayed
For communication with RS485: CntrySet parameter
For communication with Speedwire: Set country standard parameter
You can adjust the country data set of the inverter before commissioning or within the first ten
operating hours via the two rotary switches in the inverter. All other operating parameters can only
be set via communication products.

4.7 Secure Power Supply (SPS)


The inverter has an SPS module that can supply the PV array energy to an additional outlet connected
to the inverter in the event of grid failures of longer durations. The SPS module also has a connection
for the fan retrofit kit, enabling an external fan to be controlled.
Installation Manual

SB3-5TLUS22-IA-en-12

23

4 Product Description

SMA America, LLC

4.8 Fan Retrofit Kit


The fan retrofit kit is used for additional inverter cooling at high ambient temperatures (for information
on installation and configuration, see the fan retrofit kit installation manual). The fan retrofit kit can be
retrofitted, installed at the factory if specified in the order, or included in the regular scope of delivery.

4.9 Arc-Fault Circuit Interrupter (AFCI)


In accordance with the National Electrical Code, Article 690.11, the inverter has a system for the
recognition of electric arc detection and interruption. An electric arc with a power of 300 W or
greater must be interrupted by the AFCI within the time specified by UL 1699B. A tripped AFCI can
only be reset manually. You can deactivate the automatic arc fault detection and interruption (AFCI)
via a communication product in "Installer" mode if you do not require this function. The 2011 edition
of the National Electrical Code, Section 690.11 stipulates that newly installed PV systems attached
to a building must be fitted with a means of detecting and disconnecting serial electric arcs (AFCI) on
the PV side.

4.10 SD Card Slot


The inverter is equipped with an SD card slot. You can use the SD card when required to update the
inverter firmware.

4.11 Varistors
The DC Disconnect is equipped with four varistors on the DC side. Varistors are voltage-dependent
resistors that protect the inverter on the DC side against surge overvoltages. It may be necessary under
certain circumstances to replace the varistors (see Section11.5 "Replacing DC Varistors", page73).
Despite this protection against surge overvoltages, PV arrays must be designed in such a way that the
maximum system voltage of the inverter is not exceeded (see Section13 "Technical Data", page77).

4.12 SMA OptiTrac Global Peak


SMA OptiTrac Global Peak is a further development of the MPP tracking tool SMA OptiTrac. MPP
tracking is a process that determines the highest usable power in the PV system at any given time.
The power generated by the PV array depends on the level of solar irradiation and the temperature
of the PV modules. As a result, the optimum operating point for maximum power (MPP) changes
constantly throughout the day.
SMA OptiTrac ensures that the operating point of the inverter always follows the MPP exactly.
In addition, with the aid of SMA OptiTrac Global Peak the inverter can detect the presence of several
maximum power points within the available operating range, such as may occur with partially shaded
strings in particular. The available power of the partially shaded strings can therefore be almost
completely fed into the utility grid.
SMA OptiTrac Global Peak is deactivated as standard and should, in the event of partially shaded
PV modules, be activated and set via a communication product (see Section 8.7).

24

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

5 Mounting

5 Mounting
5.1 Selecting the Mounting Location
Requirements for the mounting location:

Danger to life due to fire or explosion


Despite careful construction, electrical devices can cause fires.
Do not mount the inverter in areas where highly flammable materials are stored.
Do not mount the inverter in areas having a potentially explosive atmosphere

The inverter can become hot during operation


Touching the enclosure can result in burn injuries.
Install the inverter in such a way that it cannot be touched accidentally.
The inverter must be mounted to a solid building ground (e.g., concrete or block wall) or on
drywall to a beam or stud.
In living areas, make sure that the building ground is not made of plasterboard or similar.
When in operation, the inverter makes noises which can be perceived as a nuisance.
The mounting location must be suitable for the weight and dimensions of the inverter with
DC Disconnect (see Section13 "Technical Data", page77).
The mounting location must not be exposed to direct sources of water spray such as sprinklers
or gutters.
Climatic conditions must be met (see Section13 "Technical Data", page77).
The mounting location should be freely and safely accessible at all times without the necessity
for any auxiliary equipment, such as scaffolding or lifting platforms. Non-fulfillment of these
criteria may restrict servicing.
The mounting location should not be exposed to direct solar irradiation. Direct solar irradiation
can increase the operating temperature of the inverter. As a result, the inverter reduces its power
output in order to remain within the operating limits.
To ensure optimal operation, the ambient temperature must be below 104F (40C).
The inverter can, however, be operated at higher ambient temperatures without risk in the event
of any possible reductions in output power.

Installation Manual

SB3-5TLUS22-IA-en-12

25

5 Mounting

SMA America, LLC

Dimensions for mounting:

Figure7:

26

Wall mounting bracket dimensions

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

5 Mounting

Recommended Clearances

Figure8:

Recommended clearances

To ensure optimal operation, maintain recommended clearances to walls, other inverters or


objects. This will prevent the inverter from reducing its power due to high temperatures.
If the inverter is mounted outdoors, the clearance between the DC Disconnect and the floor must
be 3 ft. (914 mm). This prevents the ingress of splashing water into the DC Disconnect.
Do not place or hang any objects on the inverter.

Installation Manual

SB3-5TLUS22-IA-en-12

27

5 Mounting

SMA America, LLC

Observe the permitted mounting position:

Figure9:

Permitted and prohibited mounting positions

Mount the inverter in a permitted mounting position with the display at eye level. This ensures
that there can be no ingress of moisture into the inverter and that you can read display messages
and LED signals without any difficulty.

5.2 Mounting the Wall Mounting Bracket


Additionally required mounting material (not included in the scope of delivery):
2 or 3 screws (minimum diameter 14 in. (6 mm)) that are suitable for the foundation

2 or 3 washers (minimum external diameter 34 in. (18 mm)) that are suitable for the screws
2 or 3 screw anchors that are suitable for the foundation. Do not use hollow-wall anchors or
toggle bolts for mounting on drywall.
If the inverter is to be protected against theft, 1 padlock (see Section5.4 "Attaching the
Anti-Theft Device", page32)
1. Attach the DC Disconnect bracket to the wall
mounting bracket of the inverter using the screws
and conical spring washers included in the delivery
and tighten them with an Allen key (AF 4) (torque:
44 in.-lbs (5.0 Nm)). Tighten the two upper screws
(M5x12) from the rear and the lower (M5x8) from
the front.

28

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

5 Mounting

2. Align the wall mounting bracket horizontally at the mounting location.


3.
Danger to life due to electric shock or explosion if you drill into supply lines
There may be gas pipes or electric cables behind the mounting points which could be damaged
when drilling the holes for the wall mounting bracket.
Make sure that there are no supply lines behind the mounting points.
4. Mark the position of the drill holes using the wall mounting bracket and screw the wall mounting
bracket onto the wall using the screws and washers.
For mounting on a stone wall, use one hole on
the right-hand and left-hand side and the lower
hole in the wall mounting bracket.

For mounting on a stud or post in a drywall


construction, use the two holes at the center.

Installation Manual

SB3-5TLUS22-IA-en-12

29

5 Mounting

SMA America, LLC

5.3 Mounting the Inverter and DC Disconnect


1.
Risk of injury when lifting the inverter, or if it is dropped
The inverter is heavy (see Section13 "Technical Data", page77). Risk of injury exists due to
incorrect lifting and due to the inverter falling during transport or when hanging in the wall
mounting bracket.
Lift and transport the inverter horizontally in the mounting position. Use the recessed grips
on the sides for this.
2. Hang the inverter in the wall mounting bracket.

3. Ensure that the inverter is securely in place.

4. Remove the lower lid.

Lower lid off

5. Carefully pierce the rubber grommet on the upper side of the DC Disconnect using a
screwdriver.

30

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

5 Mounting

6. Place the DC Disconnect into the retainer from the


front.

Position the DC Disconnect

7. Attach the DC Disconnect to the ground connection


on the inverter using the grounding bracket. Use the
M6x8 screw included in the delivery, the
corresponding conical spring washer and an Allen
key (AF 5) (torque: 53 in-lbs. (6 Nm)). When doing
so, ensure that the holes in the lateral brackets of
the DC Disconnect are flush with the holes in the
retainer.

Position the DC Disconnect

8. Attach the DC Disconnect to the bracket using the


M5x8 screws and conical spring washers included
in the delivery and an Allen key (AF 4) (torque:
44in-lbs. (5 Nm)).

Secure the lid of the DC Disconnect.

9. Feed the inverter DC cable through the rubber


grommet on the upper side of the DC Disconnect.

Inverter cable into DC Disconnect

Installation Manual

SB3-5TLUS22-IA-en-12

31

5 Mounting

SMA America, LLC

5.4 Attaching the Anti-Theft Device


You can protect the inverter from theft by installing a padlock. The padlock secures the inverter to the
wall mounting bracket.
The padlock must meet the following requirements:
The material should be rust-proof.
The lock shackle should be hardened.
The lock cylinder should be secured.
If mounted outdoors, the padlock should be weather-proof.

Figure10: Dimensions of the padlock as anti-theft device

Item

Dimensions

6 mm (0.23 in.)

21 mm to 33 mm (0.83 in. to 1.30 in.)

20 mm to 33 mm (0.79 in. to 1.30 in.)

40 mm to 60 mm (1.57 in. to 2.36 in.)

13 mm to 21 mm (0.51 in. to 0.83 in.)

1. Place the shackle of the padlock through the metal


bracket on the wall mounting bracket and through
the bracket on the rear of the inverter. Whilst doing
so, move the shackle outward from the center of the
inverter.

2. Close the shackle.

32

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

6 Electrical Connection
6.1 Safety during Electrical Connection
Danger to life from electric shock due to high voltages
High voltages are present in the DC cables and later during operation in the conductive components
of the inverter. These can cause fatal electric shocks.
Before working on the inverter, always disconnect the inverter from all voltage sources as
described in Section 10.
Do not open the upper enclosure lid.

Damage to the seal of the enclosure lid during sub-zero conditions


When opening the enclosure lid during sub-zero conditions, the seal of the enclosure lid can be
damaged. There may be an ingress of moisture, which can damage the inverter.
Do not open the inverter when the outside temperature is below 23F ( 5C).
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic
discharge.
Ground yourself before touching any components.
Damage to the inverter due to moisture ingress
Electronic components in the inverter can be destroyed or damaged as a result of the ingress of
moisture.
Only use listed conduit fittings for inserting the conduits into the inverter and the
DC Disconnect.
For outdoor installations, only use rain-tight conduit fittings or conduit fittings for wet locations.
Damage to or failure of the inverter due to incorrectly connected cables
Insecure or high-resistance cable connections (such as incorrectly installed twist-on connectors) can
cause ground faults or arc faults that can lead to the damage or failure of the inverter.
Select and correctly install cable connections that ensure secure, low-resistance connections
for all electrical connections in the PV system.
Observe local regulations
All electrical installations must comply with the electrical standards applicable on-site and the
National Electrical Code (ANSI/NFPA 70). Installations in Canada must comply with the
applicable Canadian standards.

Installation Manual

SB3-5TLUS22-IA-en-12

33

6 Electrical Connection

SMA America, LLC

6.2 Overview of the Connection Area


6.2.1 Connection Area of the Inverter

Figure11: Connection area inside the inverter

Item

Description

Explanation

DC cable

For the connection of the inverter and


DC Disconnect

Pin connector

For the connection of the SPS module

Pin connector

For the connection of the communication


interface

Terminal

For the AC cables

Ground connection

Enclosure opening

Screw connection

(34

For the equipment grounding conductor


in. (19 mm)) For the conduit fitting for inserting the AC cables
For the connection of the ZigBee antenna*

(34

in. (19 mm)) For the conduit fitting for insertion of the optional
data cable

Enclosure opening

Rotary switch

Enclosure opening (34 in. (19 mm)) For the conduit fitting for insertion of the
connection cable of the SPS module

34

SB3-5TLUS22-IA-en-12

For setting the ZigBee ID*

Installation Manual

SMA America, LLC

6 Electrical Connection

Item

Description

Explanation

Enclosure opening

For the cable gland used to insert the connection


cable for the fan retrofit kit*

Rotary switches

For setting the language and country standard

Slot

For SD card

Retainer

For the retrofit fan

Ground connection

For the DC Disconnect grounding bracket

* optional

6.2.2 Connection Area of the DC Disconnect

Figure12: Connection areas of the DC Disconnect

Item

Description

Explanation

Grounding bracket

For attachment to the grounding screw in the inverter

Rubber grommet

For insertion of the connection cable from the inverter

Screw terminals

For the connection of the connection cable from the inverter

Screw terminals

For the connection of the DC equipment grounding conductor

Screw terminals

For the connection of the strings (input B+)

Screw terminals

For the connection of the strings (input A+)

Screw terminals

For the connection of the strings (input B)

Screw terminals

For the connection of the strings (input A)

Installation Manual

SB3-5TLUS22-IA-en-12

35

6 Electrical Connection

SMA America, LLC

6.3 AC Connection
6.3.1 Conditions for the AC Connection
Cable requirements:
Conductor cross-section L1, L2 and N: 12 AWG to 6 AWG (3.3 mm to 13.3 mm)
Conductor cross-section equipment grounding conductor: 6 AWG (13.3 mm)
Isolation stripping length: 12 in. (12 mm)
Solid or stranded wire of copper with no more than 19 single wires
The cable must be designed for the maximum temperature of the AC terminal of
+221F (+105C).
The cables must be designed in accordance with local directives and the National Electrical
Code. Influencing factors for cable dimensioning are, for example, the nominal AC current,
the type of cable, the routing method, cable bundling, ambient temperature, and maximum
desired line losses.
Additionally required mounting material (not included in the scope of delivery):
1 conduit fitting (34 in. (19 mm)), rain-tight or for wet locations when installed outdoors

1 conduit (34 in. (19 mm))

Load-break switch and cable protection:

Damage to the inverter through the use of fuses as disconnecting units in the output circuit
of the inverter
Fuses must not be used as disconnecting units, even if they are installed in a fuse holder listed as
being a load-break switch.
If fuses are installed as overcurrent protection in the output circuit of the inverter, a
disconnection switch or another load-break switch suitable for the load must be installed as a
disconnecting unit in the output circuit of the inverter.
Use a circuit breaker as (a) load-break switch, for example. These can be used both as
overcurrent protection and as disconnecting unit.
In plants with multiple inverters, protect every inverter with a separate circuit breaker or another
overcurrent protective device. Observe the maximum permissible fuse protection
(see Section13 "Technical Data", page77). In doing so, you avoid residual voltages being
present at the respective cables after a disconnection from the utility grid.
Loads installed between the inverter and the circuit breaker must be protected separately.

36

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

6.3.2 Connecting the Inverter to the Utility Grid


Requirements:
The country data set and the display language must be correctly set (see Section7.1 "Making
Settings via the Rotary Switches", page47).
The connection requirements of the grid operator must be met.
The line voltage must be within the permissible range. The exact operating range of the inverter
is specified in the operating parameters.
1. Switch off or open all AC disconnecting switches and circuit breakers in the output circuit of the
inverter and secure against reconnection.
2. Ensure that no voltage is present between the AC cables to be connected.
3. Remove all six screws of the lower enclosure lid using an Allen key (AF 3) and remove the
enclosure lid.
4. Loosen the screw on the display and flip the display
up until it clicks into place. If present, do not kink the
adjacent Zigbee antenna cable.

5. Lead the conduit with the AC cables through the enclosure opening into the inverter and screw
the conduit fitting tight.
6. Strip the insulation of L1, L2, N and the equipment grounding conductor each by 1/2 in. (12 mm).
7. Connect L1, L2 and N to the AC terminals labelled for this purpose:
Raise the safety levers on the terminals as far as
possible.

Installation Manual

SB3-5TLUS22-IA-en-12

37

6 Electrical Connection

SMA America, LLC

Lead the conductors fully into the terminals.

8.
Danger of crushing when safety levers snap shut
The safety levers close by snapping down fast and hard.
Only press the safety levers on the terminals
down with your thumb. Do not grasp the
entire AC connecting terminal plate and do
not place your fingers under the safety
levers.

9. Ensure that the conductors are securely in place in the terminals.


10. Loosen the cheese-head screw on the ground connection using an Allen key (AF 5).
11. Lead the clamping bracket over the equipment
grounding conductor. Arrange the equipment
grounding conductor to the left when doing so.

12. Secure the conical spring washer, the grounding


cable of the SPS module and the clamping bracket
using the cheese-head screw (torque 53 in-lbs.
(6 Nm)). The teeth of the conical spring washer
must face the clamping bracket.

38

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

13. If the display is raised, lower the display and tighten


the display screw by hand. If present, do not kink
the adjacent Zigbee antenna cable.

6.4 DC Connection
6.4.1 Safety during DC Connection
Danger to life due to high voltages on DC conductors
Risk of death or serious injury due to electric shock from touching a DC conductor.
Do not touch the DC conductors.
Danger of electric arcs due to reversed-pole DC conductors
Dangerous electric arcs can form when the DC conductors are connected to the incorrect poles on
the inverter.
Only make the DC connection as described in this document.
Ensure the correct polarity of the DC conductors.

6.4.2 Conditions for the DC Connection


The inverter is transformerless and has no galvanic isolation. Therefore, the inverter may only be
operated with ungrounded PV arrays. Furthermore, the PV array must be installed in accordance with
the National Electrical Code, Article 690.35 "Ungrounded Photovoltaic Power Systems" and the
locally valid regulations for ungrounded PV arrays. Additionally, the PV array (PV modules and
cabling) must have protective insulation and the PV modules used must be suitable for use with this
inverter.
The inverter has two input areas A and B. The strings per input area must be designed identically.
Requirements for the PV Modules
The limiting values for the maximum system voltage and the maximum short-circuit current of the
inverter must not be exceeded (see Section13 "Technical Data", page77).
The PV modules and strings connected to one input area should have the same electrical
properties based on the manufacturer information.

Installation Manual

SB3-5TLUS22-IA-en-12

39

6 Electrical Connection

SMA America, LLC

For an optimum yield all PV modules of one input area should be mounted with the same
inclination and azimuth orientation.
Cable requirements:
Solid or stranded wire of copper with no more than 19 single wires
Conductor cross-section: 12 AWG to 6 AWG (5.3 mm to 13.3 mm)
The DC cables must be designed for the maximum temperature of the DC terminals
of +221F (+105C).
The cables must be designed in accordance with local directives and the National Electrical
Code. Influencing factors for cable dimensioning are, for example, the nominal DC current,
the type of cable, the routing method, cable bundling, ambient temperature, and the maximum
desired line losses.
Additionally required mounting material (not included in the scope of delivery):
Conduit fittings (34 in. (19 mm)), rain-tight or for wet locations when installed outdoors

Conduits (34 in. (19 mm))

6.4.3 Connecting the PV Array


Destruction of the inverter due to overvoltage
If the open-circuit voltage of the PV modules exceeds the maximum system voltage of the inverter,
the inverter can be destroyed by overvoltage.
Ensure that the open-circuit voltage of the PV modules does not exceed the maximum input
voltage of the inverter.
Otherwise, do not connect strings to the inverter; check the design of the PV system.
1. Switch off or open all AC disconnecting switches and circuit breakers in the output circuit of the
inverter and secure against reconnection.
2. If an external DC disconnecting switch is available, switch off or open the DC disconnecting
switch.
3. If there is no external DC disconnecting switch available, cover the PV modules with opaque
material or disconnect the connectors on the PV modules.
4. Ensure that no DC voltage is present on the DC cables of the PV array.

40

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

5. Loosen the screw on the lower side of the


DC Disconnect using an Allen key (AF 4) and
remove the lid of the DC Disconnect.

6. Snap out the required number of knockouts on the


desired side of the DC Disconnect for the
installation of the conduit fittings
(diameter 12 in., 34 in. or 1 in.).

7.
Damage to the DC Disconnect due to enlarged knockouts
Enlarged knockouts enable moisture to penetrate the DC Disconnect which could damage
electronic components in the DC Disconnect.
Do not enlarge the knockouts.
8. Connect the connection cable of the inverter in the
DC Disconnect. Use a flat-blade screwdriver (blade
width 5 mm) for this (torque 15 in-lb. (1.7 Nm)).
Insert the red cable into the RD screw terminal
and tighten the terminal.
Insert the orange cable into the OR screw
terminal and tighten the terminal.
Insert the black cable into the BK screw terminal
and tighten the terminal.
9. Install conduits with conduit fittings in the enclosure openings on the DC Disconnect.
10. Feed the DC cables of the PV strings and the DC equipment grounding conductors through the
conduits into the DC Disconnect.
11. Strip the insulation of the insulated conductors by a length of 12 in. (12 mm).

Installation Manual

SB3-5TLUS22-IA-en-12

41

6 Electrical Connection

SMA America, LLC

12. Insert the equipment grounding conductor of the


PV array into the grounding terminal in the DC
Disconnect and tighten the terminals using a
flat-blade screwdriver (blade width: 5 mm)
(torque: 15 in-lb (1.7 Nm)).

13. Check the PV array for ground faults (see Section11.4 "Checking the PV System for Ground
Faults", page71).
14. Connect the first string for input A to the terminal
blocks for input A. Use a flat-blade screwdriver
(blade width: 5 mm) for this (torque: 15 in-lb.
(1.7 Nm)).
Insert the cable DC+ into the screw terminal +
and tighten the terminal. Ensure the correct
polarity when doing so.
Insert the cable DC into the screw terminal
and tighten the terminal. Ensure the correct
polarity when doing so.
15. If there is another string for input A, connect it in the same way to the terminal blocks for input A.
16. Connect the first string for input B to the terminal
blocks for input B. Use a flat-blade screwdriver
(blade width: 5 mm) for this (torque: 15 in-lb.
(1.7 Nm)).
Insert the cable DC+ into the screw terminal +
and tighten the terminal. Ensure the correct
polarity when doing so.
Insert the cable DC into the screw terminal
and tighten the terminal. Ensure the correct
polarity when doing so.
17. If there is another string for input B, connect it in the same way to the terminal blocks for input B.
18. Ensure that all screw terminals are correctly connected and that the cables are securely
positioned in the screw terminals
19. Turn the rotary switch of the DC Disconnect to the Off position.

42

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

20. Push the DC Disconnect lid diagonally under the


upper edge of the enclosure and press the lid
down. The lid must be flush with the enclosure
edge.

21. Tighten the lid of the DC Disconnect using an Allen


key (AF 4) and the corresponding screw and
conical spring washer (torque : 44 in-lb. (5 Nm)).

Closing the DC Disconnect

6.5 Connecting the Secure Power Supply Module


Circuit Diagram

Installation Manual

SB3-5TLUS22-IA-en-12

43

6 Electrical Connection

SMA America, LLC

Additionally required mounting material (not included in the scope of delivery):


Outlet for secure power supply operation
Switch to activate the emergency power outlet that is designed for at least 120 V (AC) and
10 A
1 conduit fitting (34 in. (19 mm)), rain-tight or for wet locations when installed outdoors

1 conduit (34 in. (19 mm))

Switch and outlet requirements


The switch must be designed for at least 120 V AC and 10 A.
When using pre-assembled switch-outlet combinations, switch and outlet must not be connected
to each other. If they are connected, disconnect them.
No Integrated Ground-Fault Circuit Interrupter (GFCI) for Outlet
The inverter is not equipped with a GFCI for the outlet. If a GFCI protection is desired, you must
use an outlet with integrated GFCI.
Cable Requirements
5 insulated conductors for input switch, output switch, line conductor, neutral conductor and
equipment grounding conductor (EGC) must be available.
To avoid confusion, the colors of the cables for switch and outlet should be different.
Solid or stranded wire of copper with no more than 19 single wires
Conductor cross-section: 16 AWG to 12 AWG (1.3 mm to 3.3 mm)
The cables must be designed for the maximum temperature of the terminals of
+221F (+105C).
Procedure
1. If the inverter is in operation, disconnect it (see Section 10).
2. Loosen the screw on the display and flip the display
up until it clicks into place. If present, do not kink the
adjacent Zigbee antenna cable.

44

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

6 Electrical Connection

3. Remove the filler plugs from the enclosure opening


in the inverter.

4. Install the conduit with conduit fitting in the enclosure opening.


5. Feed the cable through the conduit to the terminals on the SPS module.
6. Strip 1132 in. (9 mm) off the conductor insulation.
7.
Danger of fire due to short circuit
A short circuit can occur in the secure power supply operation if the insulated conductors of the
outlet and the switch have been swapped. The short circuit can cause a fire in the switch.
Insert the insulated conductors for
connecting the switch into the black
terminals.
Insert the insulated conductors for
connecting the outlet into the three-colored
terminals.

8. Ensure that the grounding cable of the module is


connected to the ground connection in the inverter.

9. Secure the conduit fitting from the inside using the counter nut.
10. Connect the insulated conductors that are connected to the three-colored terminals of the SPS
module to the outlet.
Installation Manual

SB3-5TLUS22-IA-en-12

45

6 Electrical Connection

SMA America, LLC

11. Connect the insulated conductors that are connected to the black terminals of the SPS module
to the switch.
12. Attach the supplied warning label to the emergency
power outlet.
13. Label the switch using the supplied label. Label the
closed switch position with "ON" and the opened
switch position with "OFF".

Information on the use of the outlet


You will find further information on the use of the outlet and on the connection conditions in the
user manual supplied. Please inform the PV system operator.

6.6 Connecting the Zigbee Antenna


Screw the antenna into the screw connection on the
inverter hand-tight.

46

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

7 Commissioning

7 Commissioning
7.1 Making Settings via the Rotary Switches
7.1.1 Overview of the Rotary Switches
The inverter can be configured for different countries and for use in backup and off-grid systems via
two rotary switches. The rotary switches can also be used to change the display language.
By default, the inverter is set to a specific country data set. You can see which country data set was
set as default at the factory in the supplementary sheet provided with the factory settings. If the default
country data set of the inverter does not apply to your country, you must change the country data set
and the display language. You can also change the display language independent of the country
data set (see Section 7.1.3).
If you use a communication product, you can also change the country data set after commissioning
using that communication product (see Section 8.1).

Figure13: Configuration area inside the inverter

Item

Description

Rotary switch A for setting the country standard

Rotary switch B for setting the language

Rotary switch C for setting the Zigbee ID

Jumper slot for setting the language to English

Installation Manual

SB3-5TLUS22-IA-en-12

47

7 Commissioning

SMA America, LLC

Possible Settings of the Rotary Switches


Here, you will find a list of possible rotary switch positions and which country data sets and display
languages are represented by each position.
Each country data set contains various operating parameters, which can be individually set according
to each country data set. The operating parameters can be read out using a communication product.
Rotary switch A
position

Rotary switch B
position

Country data set

Default settings

Default settings

Retained

English

Retained

German

Retained

French

Retained

Spanish

Retained

Italian

Retained

Greek

Retained

Czech

Retained

Korean

Retained

Portuguese

Retained

Dutch

Retained

Slovenian

Retained

Bulgarian

Retained

Polish

UL1741*

English

UL1741*

Spanish

UL1741*

French

Other standard

English

Other standard

German

Other standard

French

Other standard

Spanish

Other standard

Italian

Other standard

Greek

Other standard

Czech

Island mode 60 Hz

English

Island mode 60 Hz

German

48

SB3-5TLUS22-IA-en-12

Display language

Installation Manual

SMA America, LLC

7 Commissioning

Rotary switch A
position

Rotary switch B
position

Country data set

Display language

Island mode 60 Hz

French

Island mode 60 Hz

Spanish

Island mode 60 Hz

Italian

Island mode 60 Hz

Greek

Island mode 60 Hz

Czech

Island mode 50 Hz

English

Island mode 50 Hz

German

Island mode 50 Hz

French

Island mode 50 Hz

Spanish

Island mode 50 Hz

Italian

Island mode 50 Hz

Greek

Island mode 50 Hz

Czech

* The country data set is automatically blocked after ten feed-in hours. Then you can only change the country data set by
entering the personal access code you received from SMA on a communication device.

7.1.2 Changing the Country Data Set and the Display Language
If the default country data set of the inverter does not apply to your country, you must change the
country data set and the display language.
1. If the inverter is in operation, disconnect it (see Section 10).
2. Set the rotary switches A and B to the desired
position using a flat-blade screwdriver
(blade width: 2.5 mm) (see Section7.1.1
"Overview of the Rotary Switches", page47).

3. Commission the inverter (see Section 7.2).


The inverter will adopt the setting after commissioning. This can take up to 5 minutes.

Installation Manual

SB3-5TLUS22-IA-en-12

49

7 Commissioning

SMA America, LLC

7.1.3 Changing the Display Language


You can change the display language independent of the country data set. This ensures that the
country data set remains unchanged.
Hint: If you simply remove the jumper, the display language automatically changes to English.
1. If the inverter is in operation, disconnect it (see Section 10).
2. Set the rotary switch A to 0 using a slotted
screwdriver (blade width: 2.5 mm). This ensures
that the country data set remains unchanged.

3. Set the rotary switch B to the desired language


using a slotted screwdriver (blade width: 2.5 mm)
(see Section7.1.1 "Overview of the Rotary
Switches", page47).

4. Commission the inverter (see Section 7.2).


The inverter will adopt the setting after commissioning. This can take up to 5 minutes.

50

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

7 Commissioning

7.2 Commissioning the Inverter


Requirements:
AC overcurrent protection and AC disconnecting unit must be correctly designed.
The inverter must be correctly mounted and closed.
The DC Disconnect must be correctly mounted and closed.
All cables must be correctly connected.
1. Place the lower enclosure lid with the 6 screws onto
the enclosure and tighten them using an Allen key
(AF 3) in the order 1 to 6 (torque: 18 in-lbs. (2.0 Nm).

2. Switch on or close all AC disconnecting switches and circuit breakers in the output circuit of the
inverter.
3. If an external DC disconnecting switch is available, switch on or close the DC disconnecting
switch.
4. Turn the rotary switch of the DC Disconnect to the On position.
The inverter carries out an arc-fault circuit interrupter (AFCI) self test.
The green LED is lit and the display shows the device type, the firmware version, the device
names, the country data set and display language. If communication is via Zigbee or
Speedwire, then the Zigbee status and the versions of the communication assemblies will also
be displayed also after the device names.
The inverter feeds into the grid.
Green LED flashing?
Possible cause of error: The DC input voltage is still too low, or the inverter is monitoring the
utility grid.
Once the DC input voltage is sufficiently high, the inverter goes into operation.
The red LED is lit and an error message and event number appear in the display?
Eliminate the error (see Section11 "Troubleshooting", page59).
The blue LED is glowing or flashing?
Eliminate the communication error (see Section9.3 "LED Signals", page54).

Installation Manual

SB3-5TLUS22-IA-en-12

51

8 Configuration

SMA America, LLC

8 Configuration
8.1 Changing the Country Data Set Using a Communication Product
By default, the inverter is set to a specific country data set. You can see which country data set was
set by default at the factory on the type label and the supplementary sheet with the default settings
provided. If the default country data set of the inverter does not apply to your country or you want to
use the inverter in a backup or off-grid system, then you must change the country data set.
Requirements:
A communication product that is appropriate for the type of communication used must be
available.
The responsible grid operator must approve changes of grid-relevant parameters.
An SMA Grid Guard code for changing the grid-relevant parameters must be available
(for application for the SMA Grid Guard code, see certificate "Application for SMA Grid Guard
Code" at www.SMA-Solar.com).
1. Access the user interface of the communication product.
2. Enter the SMA Grid Guard code.
3. Select the CntrySet or Set country standard parameter and set the required country data set.
4. Save setting.

8.2 Activating and Setting SMA OptiTrac Global Peak


With partially shaded PV modules, you should activate SMA OptiTrac Global Peak and set the time
interval in which the inverter will optimize the MPP of the PV system.
Requirement:
A communication product that is appropriate for the type of communication used must be
available.
Procedure:
1. Log in to the communication product as Installer.
2. Select the parameter MPPShdw.IsOn/OptiTrac Global Peak switched on and set to On.
3. Select the parameter MPPShdw.CycTms/Cycle time of the OptiTrac Global Peak
algorithm and set the required time interval. Hint: The ideal time interval is normally six minutes.
This value should only be increased if the shading situation changes extremely slowly.
The inverter optimizes the MPP of the PV system at the specified time interval.

52

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

9 Display and LEDs

9 Display and LEDs


9.1 Switching On the Display
By tapping on the enclosure lid once you can operate the display as follows:
Switch on the display
Switch through the text line display
Switch between the power curve of the last 16 feed-in hours and the energy yields of the last
16 days

9.2 Calling Up Messages of the Start Phase


If you double tap on the enclosure lid, the display messages of the start phase are repeated.
The following device properties will be displayed in succession:
Device type
Firmware version
Serial number or device name of the inverter
For Zigbee communication: version information of the assembly and status of the Zigbee
communication
The following status messages are possible.
SERVER COM: data transmission active
NET SEARCH: searching for ZigBee network
NET JOINED: network found, but no reply from the gateway
GATEWAY COM: gateway found, but no connection to the server
COM INIT: no data transmission possible
For Speedwire communication: version information of the assembly
Country data set used
Display language

Installation Manual

SB3-5TLUS22-IA-en-12

53

9 Display and LEDs

SMA America, LLC

9.3 LED Signals


The LEDs indicate the operating state of the inverter.
LED

Status

Green

is glowing

Explanation
Operation
If an event occurs, the event message is shown in the display
(see Section 11.1).

Red

is flashing

Conditions for connection to the grid are not fulfilled.

is flashing quickly

The inverter is performing an update.

is glowing

Error
The display shows the error message and event number
(see Section 11.2).

Blue

is glowing

Data transmission active


The inverter has set up a connection to a communication
product and data transmission is active.

is flashing twice

Searching for ZigBee network

is flashing three times Network found, but no reply from the gateway
is flashing four times Gateway found, but no connection to the server
is flashing regularly

No data transmission possible


The inverter is trying to establish a connection to a
communication production. No data can be transmitted,
however.

All LEDs have gone out


If all three LEDs have gone out, the inverter is switched off because the switch of the
DC Disconnect is set to Off or insufficient irradiation is available.
Set the switch of the DC Disconnect to On.

54

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

10 Disconnecting the Inverter from Voltage Sources

10 Disconnecting the Inverter from Voltage Sources


Danger to life due to high voltages in the inverter
Death or serious injury due to electric shock.
Only open the inverter in the order described here.
Before performing any tasks, wait five minutes until the residual voltage has been drained from
the components.

Damage to the seal of the enclosure lid during sub-zero conditions


When opening the enclosure lid during sub-zero conditions, the seal of the enclosure lid can be
damaged. There may be an ingress of moisture, which can damage the inverter.
Do not open the inverter when the outside temperature is below 23F ( 5C).
1. Switch off or open all AC disconnecting switches and circuit breakers in the output circuit of the
inverter and secure against reconnection.
2. If an external DC disconnecting switch is available, switch off or open the DC disconnecting
switch.
3. Turn the rotary switch of the DC Disconnect to Off.

4. Wait until the LEDs and display switch off.


5. Remove all six screws of the lower enclosure lid
using an Allen key (AF 3) and remove the enclosure
lid.

Installation Manual

SB3-5TLUS22-IA-en-12

55

10 Disconnecting the Inverter from Voltage Sources

SMA America, LLC

6.
Damage to the inverter due to electrostatic discharge
The internal components of the inverter can be irreparably damaged by electrostatic discharge.
Ground yourself before touching any components.
7. Ensure that no voltage is present on the AC connecting terminal plate using a suitable measuring
device. Insert the test probe in each round opening of the terminal:
Ensure that no voltage is present between
L1 and N.

Ensure that no voltage is present between L1 and


the equipment grounding conductor.

Ensure that no voltage is present between


L2 and N.

56

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

10 Disconnecting the Inverter from Voltage Sources

Ensure that no voltage is present between L2 and


the equipment grounding conductor.

10.1 Disconnecting the DC Disconnect from Voltage Sources


1. Turn the rotary switch of the DC Disconnect to Off.

2. Wait until the LEDs and inverter display switch off.


3. Loosen the screw on the lower side of the DC
Disconnect using an Allen key (AF 4) and remove
the lid of the DC Disconnect.

4. If an external DC disconnecting switch is available, open the DC disconnecting switch.


5. If there is no external DC disconnecting switch available, cover the PV modules with opaque
material or disconnect the connectors on the PV modules.

Installation Manual

SB3-5TLUS22-IA-en-12

57

10 Disconnecting the Inverter from Voltage Sources

SMA America, LLC

6.
Danger to life due to electric shock when touching the DC conductors and
DC terminals
High voltages are present in the DC cables and DC terminals.
Before performing any tasks, wait five minutes until the residual voltage has been drained.
Do not touch the DC conductors and DC terminals.
7. Ensure that no voltage is present on the DC terminals using a suitable measuring device.
Insert the test probe in each round opening of the terminal.

58

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

11 Troubleshooting
11.1 Event Messages
Display message

Cause

AFCI self-test successful

The inverter has successfully performed the arc fault detection


self-test.

Backup mode on

The inverter is operating in grid parallel operation with adjusted


grid monitoring.

Grid guard code valid

The SMA Grid Guard code entered is valid. Protected parameters


have now been unblocked and you can adjust the parameters.
The parameters will be automatically locked again after
10 feed-in hours.

No new update SDcard

There are no update files relevant for this inverter on the SD card
or the available update has already been carried out.

Grid param.unchanged

The selected rotary switch position is not assigned or it is not


possible to change the grid parameters.

Parameters set successfully

A new country data set has been configured.

SD card is read

The inverter is currently reading the SD card.

Self-test

The self-test is being carried out.

Set parameter

The inverter is setting the parameters.

Standalone op.

The inverter is operating in the secure power supply operation.

Update completed

The inverter has successfully completed the update.

Update main CPU

The inverter is performing an update of the inverter components.

Update communication

The inverter is performing an update of the communications


components.

Update RS485I module

The inverter is updating the RS485i module.

Update Speedwire

The inverter is updating the Speedwire module.

Upd. language table

The inverter is updating the language table.

Update Webconnect

The inverter is updating the Webconnect module.

Update Zigbee

The inverter is performing an update of the ZigBee components


in the inverter.

Update file OK

The update file found is valid.

Installation Manual

SB3-5TLUS22-IA-en-12

59

11 Troubleshooting

SMA America, LLC

11.2 Error Messages


Event number

Display message

Cause and corrective measures

101 to 103

Grid fault

The line voltage or grid impedance at the


connection point of the inverter is too high. The
inverter has disconnected from the utility grid.
Corrective measures:
Check whether the line voltage at the
connection point of the inverter is
permanently in the permissible range.
If the line voltage is outside the permissible
range due to local grid conditions, contact
the grid operator. Ask the grid operator
whether the voltage can be adapted at the
feed-in point or if it would be acceptable to
change the monitored operating limits.
If the line voltage is permanently in the
permissible range and this message is still
displayed, contact the SMA Service Line.

202 to 205

Grid fault

The utility grid has been disconnected, the


AC cable is damaged or the line voltage at the
connection point of the inverter is too low. The
inverter has disconnected from the utility grid.
Corrective measures:
Ensure that the circuit breaker is switched
on.
Ensure that the AC cable is not damaged.
Ensure that the AC cable is connected
correctly.
Check whether the line voltage at the
connection point of the inverter is
permanently in the permissible range.
If the line voltage is outside the permissible
range due to local grid conditions, contact
the grid operator. Ask the grid operator
whether the voltage can be adapted at the
feed-in point or if it would be acceptable to
change the monitored operating limits.
If the line voltage is permanently in the
permissible range and this message is still
displayed, contact the SMA Service Line.

60

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

301

Grid fault

The 10-minute average line voltage is no longer


within the permissible range. The line voltage or
grid impedance at the connection point is too
high. The inverter disconnects from the utility grid
to comply with the power quality.
Corrective measures:
Check whether the line voltage at the
connection point of the inverter is
permanently in the permissible range.
If the line voltage is outside the permissible
range due to local grid conditions, contact
the grid operator. Ask the grid operator
whether the voltage can be adapted at the
feed-in point or if it would be acceptable to
change the monitored operating limits.
If the line voltage is permanently in the
permissible range and this message is still
displayed, contact the SMA Service Line.

401 to 404

Grid fault

The inverter is no longer in grid-parallel


operation. The inverter has stopped feeding into
the utility grid.
Corrective measures:
Check the grid connection for strong,
short-term frequency variations.

501

Grid fault

The power frequency is not within the permissible


range. The inverter has disconnected from the
utility grid.
Corrective measures:
If possible, check the power frequency and
observe how often fluctuations occur.
If there is a high number of fluctuations and
this message is displayed frequently,
contact the grid operator and ask whether
they approve a change of the operating
parameters of the inverter.
If the grid operator approves, discuss any
changes to the operating parameters with
the SMA Service Line.

Installation Manual

SB3-5TLUS22-IA-en-12

61

11 Troubleshooting

SMA America, LLC

Event number

Display message

Cause and corrective measures

601

Grid fault

The inverter has detected an excessively high


proportion of direct current in the line current.
Corrective measures:
Check the grid connection for direct current.
If this message is displayed frequently,
contact the grid operator and check
whether it is possible to raise the limiting
value for monitoring on the inverter.

701

Frq. not permitted


Check parameters

The power frequency is not within the permissible


range. The inverter has disconnected from the
utility grid.
Corrective measures:
If possible, check the power frequency and
observe how often fluctuations occur.
If there is a high number of fluctuations and
this message is displayed frequently,
contact the grid operator and ask whether
they approve a change of the operating
parameters of the inverter.
If the grid operator approves, discuss any
changes to the operating parameters with
the SMA Service Line.

801

Waiting for grid


voltage

There is no line voltage at the AC output of the


inverter.

Grid failure

Corrective measures:

Check fuse

Check the fuse and replace it if necessary.


Check AC installation.
Check whether there is a general power
outage.

62

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

1501

Reconnection fault grid The changed country data set or the value of a
parameter you have set does not correspond to
the local requirements. The inverter cannot
connect to the utility grid.
Corrective measures:
Ensure that the country data set has been
configured correctly. Check the setting of
the rotary switches A and B or select the
parameter Set country standard and
check the value.

3301 to 3303

Unstable operation

There is not enough power at the DC input of the


inverter for stable operation. This may be caused
by snow on the PV modules or insufficient
irradiation. The inverter interrupts the feed-in
operation.
Corrective measures:
Wait for higher irradiation.
If this event recurs at medium irradiation
levels, check the PV system design and the
correct circuitry of the PV array.

3401 to 3402

DC overvoltage
Disconnect generator

Overvoltage at the DC input. The inverter may be


destroyed.
When this message is signaled, it is
accompanied by rapid flashing of the backlight.
Corrective measures:
IMMEDIATELY DISCONNECT
the inverter from voltage sources
(see Section 10).
Check whether the DC voltage is below the
maximum system voltage of the inverter.
If the DC voltage is below the maximum
system voltage of the inverter, reconnect
the DC connectors to the inverter.
If the DC voltage is above the maximum
system voltage of the inverter, ensure that
the PV array has been correctly rated or
contact the PV array installer.
If this message is repeated frequently,
contact the SMA Service Line.

Installation Manual

SB3-5TLUS22-IA-en-12

63

11 Troubleshooting

SMA America, LLC

Event number

Display message

Cause and corrective measures

3501

Insulation resist.

The inverter has detected a ground fault in the


PV array.

Check generator

Corrective measures:
Check the PV system for ground faults
(see Section 11.4).
3601

High discharge curr.


Check generator

The leakage current from the inverter and the


PV array is too high. A ground fault, a residual
current or a malfunction is present.
The inverter interrupts feed-in operation
immediately after exceeding a limiting value and
then automatically re-connects to the utility grid.
Corrective measures:
Check the PV system for ground faults
(see Section 11.4).

3701

Resid.curr.too.high
Check generator

The inverter has detected a residual current


through brief PV array grounding.
Corrective measures:
Check the PV system for ground faults
(see Section 11.4).

3801 to 3802

DC overcurrent
Check generator

The inverter switches off due to an overcurrent on


the DC side.
Corrective measures:
If this event occurs frequently:
Check the design and circuitry of the
PV array.

3901 to 3902

Waiting for DC start


conditions

The input power or the input voltage of the


PV modules is insufficient for utility grid feed-in.

Start cond. not met

Corrective measures:
Wait for higher irradiation.
If this event recurs at medium irradiation
levels, check the PV system design and the
correct circuitry of the PV array.

64

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

4301

Electr. arc detected

The inverter has detected an electric arc.

Check generator

Corrective measures:
Disconnect the inverter from voltage
sources (see Section 10).
Ensure that there are no defective PV
modules, cables or plugs in the PV system.
Re-commission the inverter (see Section 7).

6001 to 6009

Self diagnosis
Interference device

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

6101 to 6112

Self diagnosis
Interference device

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

6202

Self diagnosis
Interference device

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

6301 to 6314

Self diagnosis
Interference device

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

6401 to 6438

Self diagnosis
Interference device

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

6501 to 6502

Self diagnosis
Overtemperature

The inverter has switched off due to excessive


temperatures.
Corrective measures:
Clean the cooling fins and air ducts
(see Section 11.3).
Ensure that the inverter has sufficient
ventilation.

Installation Manual

SB3-5TLUS22-IA-en-12

65

11 Troubleshooting

SMA America, LLC

Event number

Display message

Cause and corrective measures

6603 to 6604

Self diagnosis

The cause must be determined by the


SMA Service Line.

Overload

Corrective measures:
Contact the SMA Service Line.
6701 to 6702

Comm. disturbed

A fault has occurred in the internal


communication of the inverter. The inverter
continues feeding power into the grid.
Corrective measures:
If this event occurs frequently:
Contact the SMA Service Line.

6801 to 6802

Self diagnosis

Inverter input A is defective.

Input A defective

Corrective measures:
Contact the SMA Service Line.

6901 to 6902

Self diagnosis

Inverter input B is defective.

Input B defective

Corrective measures:
Contact the SMA Service Line.

7001 to 7002

Sensor fault

A temperature sensor in the inverter is faulty.


The inverter interrupts the feed-in operation.
Corrective measures:
Contact the SMA Service Line.

7008

Disturbance sensor
display temperature

The ambient temperature sensor is faulty.


The display is not switched off at temperatures
below 13F (25C) and as a result may have
been destroyed. The inverter continues feeding
power into the grid.
Corrective measures:
Contact the SMA Service Line.

7101

SD card defective

The SD card is not formatted correctly or is


defective. The update failed. The inverter
continues feeding power into the grid.
Corrective measures:
Re-format the SD card.
Re-save the files to the SD card.

66

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

7102

Parameter file not


found or defective

The parameter file was not found or is defective.


The update failed. The inverter continues feeding
power into the grid.
Corrective measures:
Copy the parameter file into the SD card
drive:\PARASET directory.

7105

Param. setting failed

Parameters cannot be set via the SD card. The


inverter continues feeding power into the grid.
Corrective measures:
Check the parameters for valid values.
Ensure change rights via SMA Grid Guard
code.

7106

Update file defect.

The update file is defective. The update failed.


The inverter continues feeding power into the
grid.
Corrective measures:
Re-format the SD card.
Re-save the files to the SD card.

7110

No update file found

No new update file was found on the SD card.


The update failed. The inverter continues feeding
power into the grid.
Corrective measures:
Copy the update file into the SD card
drive:\UPDATE directory.

7201 to 7202

Data stor. not poss.

Internal device fault, the inverter continues


feeding power into the grid.
Corrective measures:
If this error occurs frequently, contact the
SMA Service Line.

7303

Update main CPU


failed

Internal device fault. The inverter continues


feeding power into the grid. In very rare cases,
the firmware is damaged and the inverter
interrupts the feed-in.
Corrective measures:
Contact the SMA Service Line.

Installation Manual

SB3-5TLUS22-IA-en-12

67

11 Troubleshooting

SMA America, LLC

Event number

Display message

Cause and corrective measures

7305

Update RS485I
module failed

Internal device fault, the inverter continues


feeding power into the grid.
Corrective measures:
Re-try update.
If this error occurs again, contact the
SMA Service Line.

7311

Update language table Internal device fault, the inverter continues


failed
feeding power into the grid.
Corrective measures:
Re-try update.
If this error occurs again, contact the
SMA Service Line.

7316

Update Speedwire
module failed

Internal device fault, the inverter continues


feeding power into the grid.
Corrective measures:
Re-try update.
If this error occurs again, contact the
SMA Service Line.

7326

Webconnect update
unsuccessful

Internal device fault, the inverter continues


feeding power into the grid.
Corrective measures:
Re-try update.
If this error occurs again, contact the
SMA Service Line.

7335

Zigbee update failed

Internal device fault, the inverter continues


feeding power into the grid.
Corrective measures:
Re-try update.
If this error occurs again, contact the
SMA Service Line.

7508

External fan fault

The fan is contaminated or defective. The inverter


may reduce its power due to overheating. The
inverter continues feeding power into the grid.
Corrective measures:
Clean the fan
Replace the fan.

68

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

7701 to 7712

Self diagnosis

The cause must be determined by the


SMA Service Line.

Interference device

Corrective measures:
Contact the SMA Service Line.
8001

Derating occurred

The inverter has reduced its power output for more


than ten minutes due to excessive temperature.
Corrective measures:
If this message is frequently displayed,
clean the cooling fins and air ducts
(see Section11.3 "Cleaning the Inverter",
page71).
Ensure that the inverter has sufficient
ventilation.

8101 to 8104

Comm. disturbed

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

8204

AFCI self-test failed

The cause must be determined by the


SMA Service Line.
Corrective measures:
Contact the SMA Service Line.

8206

Electr. arc detected


Please confirm by
tapping

The inverter has detected an electric arc and was


recommissioned after a disconnection.
By tapping, you are confirming that you have
repaired any possible damage to PV modules,
cables or plugs in the PV system.
Corrective measures:
Tap on the display within ten seconds of
the display message appearing in order to
recommission the inverter.

Installation Manual

SB3-5TLUS22-IA-en-12

69

11 Troubleshooting

SMA America, LLC

Event number

Display message

Cause and corrective measures

8801 to 8803

No display

This error message can have 3 causes but the


inverter continues to feed into the utility grid.
The ambient temperature is lower than 13F
(25C). The display switched off for protection.
The inverter cannot identify the display type.
No display is connected to the inverter or the
connection is defective.
Corrective measures:
If the display switched off due to the ambient
temperature being too low, wait until the
ambient temperature is above 13F
(25C).
If the ambient temperature is above 13F
(25C), contact the SMA Service Line.

9002

Grid guard code


invalid

The SMA Grid Guard code entered is incorrect.


The parameters are still protected and cannot be
changed.
Corrective measures:
Enter the correct SMA Grid Guard code.

9003

Grid param. locked

The parameters are now locked. The parameters


cannot be changed.
Corrective measures:
Unlock the parameters with the
SMA Grid Guard code.

70

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

Event number

Display message

Cause and corrective measures

9005

Changing grid param. This error can have the following causes:
not possible
The selected rotary switch setting for the
Ensure DC supply
country configuration is not programmed.
The parameters to be changed are
protected.
The DC voltage at the DC input is not
sufficient to run the main CPU.
Corrective measures:
Check the settings of the rotary switches (see
Section7.1.2 "Changing the Country Data
Set and the Display Language", page49).
Enter the SMA Grid Guard code.
Ensure sufficient DC voltage (green LED
lights up or flashes).

11.3 Cleaning the Inverter


Damage to the display due to the use of cleaning agents
If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using only clean water
and a cloth.
If the cooling fins on the rear of the enclosure are dirty, clean them with a soft brush.
If the air ducts on the top of the inverter are dirty, clean them with a soft brush.

11.4 Checking the PV System for Ground Faults


If the inverter displays the event numbers 3501, 3601 or 3701, there could be a ground fault.
The electrical insulation between the PV system to ground is defective or insufficient.

Danger to life due to electric shock


In the event of a ground fault, high voltages can be present in the PV module construction.
Only touch the cables of the PV modules on their insulation.
Do not connect DC cables with ground faults to the inverter.

Installation Manual

SB3-5TLUS22-IA-en-12

71

11 Troubleshooting

SMA America, LLC

Proceed as follows to check each string in the PV system for ground faults.
1. Disconnect the inverter from any voltage sources (see Section 10).
2. Measure voltages:
Measure the voltages between the positive terminal and the ground potential.
Measure the voltages between the negative terminal and the ground potential.
Measure the voltages between the positive terminals and negative terminals.
If the following results are returned simultaneously, there is a ground fault in the PV system.
All measured voltages are stable.
The sum of the two voltages against the ground potential is approximately equal to the
voltage between the positive and negative terminals.
3. Determine the location of the ground fault via the ratio of the two measured voltages.
Example: location of the ground fault
The example shows a ground fault between the second and third PV modules.

4. Eliminate the ground fault.


5. Commission the inverter (see Section 7.2).
6. If there is no ground fault and the message continues to be displayed, contact the
SMA Service Line.

72

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

11 Troubleshooting

11.5 Replacing DC Varistors


In regions where electrical storms or other DC overvoltages frequently occur, the DC varistors lose
their functionality if the PV system is not equipped with additional overvoltage protection. In such
cases, SMA recommends replacing DC varistors with new ones after an operating period of 10 years
in order to ensure that the functionality of the DC varistors remains at a constant level.
Order new varistors directly from SMA (for order numbers, see Page 83).

Damage to the inverter due to overvoltage


If varistors are missing, the inverter is no longer protected against overvoltage.
Do not operate the inverter without varistors in plants with a high risk of overvoltages.
Only recommission the inverter after you have replaced the defective varistors.
1. Disconnect the inverter and the DC Disconnect from voltage sources (see Section 10).
2. Insert the insertion tool into the contacts of the
connecting terminal plate.

3. Remove the varistor from the connecting terminal


plate.

4. Insert the new varistor into the terminal. The labels


of the varistor must face to the right at the inside of
the inverter.

Installation Manual

SB3-5TLUS22-IA-en-12

73

11 Troubleshooting

SMA America, LLC

5. Ensure that the wires of the varistors are secure in the terminal.
6. Remove the insertion tool from the contacts of the connecting terminal plate.
7. Push the DC Disconnect lid diagonally under the
upper edge of the enclosure and press the lid
down. The lid must be flush with the enclosure
edge.

8. Tighten the lid of the DC Disconnect using an Allen


key (AF 4) and the corresponding screw and
conical spring washer (torque : 44 in-lb. (5 Nm)).

Closing the DC Disconnect

9. Commission the inverter (see Section 7.2).

74

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

12 Decommissioning

12 Decommissioning
12.1 Disassembling the Inverter
1. Disconnect the inverter from any voltage sources (see Section 10).
2. Disconnect the DC Disconnect from voltage sources (see Section 10.1).
3. Remove the AC output cable from the inverter.
4. If the SPS module is connected, remove the output cable from the inverter.
5. If a data cable is connected, remove the data cable from the inverter.
6. If the Zigbee antenna is connected, unscrew the antenna.
7. Disconnect the DC cable leading from the inverter to the DC Disconnect and pull it back into the
inverter.
8. Place the lower enclosure lid with the 6 screws on the
enclosure and tighten them using an Allen key (AF 3)
in the order 1 to 6 (torque: 18 in.-lb. (2.0 Nm)).

9.
Risk of burns due to hot enclosure parts
Wait 5 minutes for the enclosure to cool down and the residual voltage has been
drained.
10. Loosen the screws of the DC Disconnect using an Allen key (AF 4) and remove the
DC Disconnect.
11.
Danger to life due to electric shock when touching the DC cables and DC terminals
High voltages are present in the DC cables and DC terminals.
Do not touch the DC cables and DC terminals.
If present, switch off the external DC disconnecting switch or disconnect the PV module
plugs.
12. Remove all DC cables from the DC Disconnect.

Installation Manual

SB3-5TLUS22-IA-en-12

75

12 Decommissioning

SMA America, LLC

13. Unscrew all conduits and conduit fittings.


14. Tighten the lid of the DC Disconnect using an Allen key (AF 4) and the corresponding screw and
conical spring washer (torque : 44 in-lb. (5 Nm)).
15. If the inverter is protected against theft, open the padlock and remove it.
16.
Risk of injury when lifting the inverter, or if it is dropped
The inverter is heavy (see Section13 "Technical Data", page77). Risk of injury exists through
incorrect lifting and through the inverter falling during transport or when hanging in the wall
mounting bracket.
Lift and transport the inverter horizontally in the mounting position. Use the recessed grips
on the sides for this.
17. Lift the inverter off the wall mounting bracket.

12.2 Packing the Inverter


1. Remove the cable glands from the inverter.
2. Pack the inverter. Use the original packaging or packaging that is suitable for the weight and
dimensions of the inverter (see Section13 "Technical Data", page77).

12.3 Disposing of the Inverter


Dispose of the inverter in accordance with the locally applicable disposal regulations for
electronic waste.

76

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

13 Technical Data

13 Technical Data
13.1 DC/AC
13.1.1 Sunny Boy 3000TL-US
DC Input
Maximum DC operating power
Maximum system voltage
Rated MPP tracking voltage range
Rated operating voltage
Minimum operating voltage
Start voltage, no-load status
Maximum operating current
Maximum input current per MPP tracking input
Maximum short-circuit current per
MPP tracking input
MPP tracking inputs
Strings per MPP tracking input

3,200 W
600 V
175 to 480 V
400 V
125 V
150 V
18 A
15 A
19 A
2
2

AC Output
Rated power at 208 V, or 240 V, 60 Hz
Maximum apparent power
Nominal AC voltage
AC voltage range at 208 V nominal
AC voltage range at 240 V nominal
Nominal AC current at 208 V
Nominal AC current at 240 V
Maximum output current
Maximum overcurrent protection
Total harmonic distortion
Nominal AC frequency
AC frequency range at 60 Hz nominal
Power factor at rated power
Connection conductor
Output connections

Installation Manual

3,000 W
3,050 VA
208 V / 240 V
183 V to 229 V
211 V to 264 V
14.5 A
12.5 A
15 A
30 A
4%
60 Hz
59.3 Hz to 60.5 Hz
1
2
L1, L2, N, PE

SB3-5TLUS22-IA-en-12

77

13 Technical Data

SMA America, LLC

Efficiency
Maximum efficiency, max
CEC efficiency, CEC at 208 V AC nominal
CEC efficiency, CEC at 240 V AC nominal

97.1%
96.5%
96.9%

13.1.2 Sunny Boy 4000TL-US


DC Input
Maximum DC operating power
Maximum system voltage
Rated MPP tracking voltage range
Rated operating voltage
Minimum operating voltage
Start voltage, no-load status
Maximum operating current
Maximum input current per MPP tracking input
Maximum short-circuit current per
MPP tracking input
MPP tracking inputs
Strings per MPP tracking input

4,200 W
600 V
175 V to 480 V
400 V
125 V
150 V
24 A
15 A
19 A
2
2

AC Output
Rated power at 208 V, or 240 V, 60 Hz
Maximum apparent power
Nominal AC voltage
AC voltage range at 208 V nominal
AC voltage range at 240 V nominal
Nominal AC current at 208 V
Nominal AC current at 240 V
Maximum output current
Maximum overcurrent protection
Total harmonic distortion
Nominal AC frequency
AC frequency range at 60 Hz nominal
Power factor at rated power
Connection conductor
Output connections
78

SB3-5TLUS22-IA-en-12

4,000 W
4,050 VA
208 V / 240 V
183 V to 229 V
211 V to 264 V
19.5 A
16.7 A
20 A
30 A
4%
60 Hz
59.3 Hz to 60.5 Hz
1
2
L1, L2, N, PE
Installation Manual

SMA America, LLC

13 Technical Data

Efficiency
Maximum efficiency, max
CEC efficiency, CEC at 208 V AC nominal
CEC efficiency, CEC at 240 V AC nominal

97.2%
96.6%
97.0%

13.1.3 Sunny Boy 5000TL-US


DC Input
Maximum DC operating power
Maximum system voltage
Rated MPP tracking voltage range
Rated operating voltage
Minimum operating voltage
Start voltage, no-load status
Maximum operating current
Maximum input current per MPP tracking input
Maximum short-circuit current per MPP tracking
input
MPP tracking inputs
Strings per MPP tracking input

5,300 W
600 V
175 V to 480 V
400 V
125 V
150 V
30 A
15 A
19 A
2
2

AC Output
Rated power at 208 V, 60 Hz
Rated power at 240 V, 60 Hz
Maximum apparent power at 208 V, 60 Hz
Maximum apparent power at 240 V, 60 Hz
Nominal AC voltage
AC voltage range at 208 V nominal
AC voltage range at 240 V nominal
Nominal AC current at 208 V
Nominal AC current at 240 V
Maximum output current
Maximum overcurrent protection
Total harmonic distortion
Nominal AC frequency
AC frequency range at 60 Hz nominal
Power factor at rated power
Installation Manual

4,550 W
5,000 W
4,550 VA
5,050 VA
208 V / 240 V
183 V to 229 V
211 V to 264 V
22 A
21 A
22 A
30 A
4%
60 Hz
59.3 Hz to 60.5 Hz
1
SB3-5TLUS22-IA-en-12

79

13 Technical Data

Connection conductor
Output connections

SMA America, LLC

2
L1, L2, N, PE

Efficiency
Maximum efficiency, max
CEC efficiency, CEC at 208 V AC nominal
CEC efficiency, CEC at 240 V AC nominal

97.0%
96.5%
96.9%

13.2 Protective Devices


DC reverse-polarity protection
Input-side disconnection device
DC overvoltage protection
AC short-circuit current capability
Grid monitoring
Ground-fault monitoring
All-pole sensitive residual-current monitoring unit
DC arc-fault circuit interrupter

Short-circuit diode
DC Disconnect
Varistors
Current control
SMA Grid Guard X
Insulation monitoring: Riso 600 k
Present
DC AFCI

13.3 General Data


Width x height x depth, inverter
Width x height x depth, DC Disconnect
Weight inverter
Weight DC Disconnect
Length x width x height of the inverter packaging
Length x width x height of the DC Disconnect
packaging
Transport weight inverter
Transport weight DC Disconnect
Climatic category according to IEC 60721-3-4
Operating temperature range
Maximum permissible value for relative humidity,
non-condensing
Maximum operating altitude above
Mean Sea Level

80

SB3-5TLUS22-IA-en-12

19516 in. x 2012 in. x 7516 in.


(490 mm x 519 mm x 185 mm)
71332 in. x 114564 in. x 712 in.
(187 mm x 297 mm x 190 mm)
52.9 lb (24 kg)
4.4 lb (2 kg)
24516 in. x 2312 in. x 1012 in.
(617 mm x 597 mm x 266 mm)
143964 in. x 91332 in. x 11 in.
(370 mm x 240 mm x 280 mm)
59.5 lb (27 kg)
6.6 lb (3 kg)
4K4H
40F to +140F ( 40C to +60C)
100%
3,000 m

Installation Manual

SMA America, LLC

Noise emission, typical


Power loss in night mode
Topology
Cooling concept
Fan connection

Electronics degree of protection


Protection class
Overvoltage category
Approvals, as at March 2013

Grid configurations

13 Technical Data

25 dB(A)
<1W
Transformerless
Convection
designed for safe disconnection in accordance
with DIN EN 50178:1998-04
(until 2013 replaced by DIN EN 62109-1)
NEMA 3R
I
IV
UL 1741,
UL 1699B,
IEEE 929-2000,
IEEE 1547,
Canadian Electrical Code
CSA C22.2 N0. 107.1-01
208/120 V Wye,
120/240 V Split-phase

13.4 DC Disconnect
Maximum rated switching current per string input
Maximum switching voltage
Degree of protection

20 A
600 V
NEMA 3R

13.5 Climatic Conditions


According to IEC 60721-3-4, installation type C, class 4K4H
Extended temperature range
Extended humidity range
Extended air pressure range

40F to +140F ( 40C to +60C)


0% to 100%
79.5 kPa to 106 kPa

According to IEC 60721-3-2, transport type E, class 2K3


Temperature range

Installation Manual

40F to +140F ( 40C to +60C)

SB3-5TLUS22-IA-en-12

81

13 Technical Data

SMA America, LLC

13.6 Features
DC connection
AC connection
Display
Zigbee
RS485, galvanically isolated
Speedwire with Webconnect function
Fan retrofit kit
SPS module

Screw terminal
Spring-cage terminal
LC graphic display
optional*
optional
optional
optional
optional*

* only with a corresponding order, no retrofitting possible

13.7 Torques
Lower inverter lid screws
DC Disconnect lid screw
Screws of the DC Disconnect retainer on the
inverter wall mounting bracket
Screws of the DC Disconnect on the retainer
Ground connection in the inverter
Grounding screw in the grounding bracket of the
DC Disconnect on the inverter
DC grounding terminal in the DC disconnect
DC terminals for the PV modules
DC terminal for the inverter DC cable in the
DC Disconnect

18 in.-lbs. (2.0 Nm)


44 in.-lbs. (5.0 Nm)
44 in.-lbs. (5.0 Nm)
44 in.-lbs. (5.0 Nm)
53 in.-lbs. (6.0 Nm)
53 in.-lbs. (6.0 Nm)
15 in.-lbs. (1.7 Nm)
15 in.-lbs. (1.7 Nm)
15 in.-lbs. (1.7 Nm)

13.8 Data Storage Capacity


Energy yields over the course of the day
Daily yields
Event messages for users
Event messages for installers

82

SB3-5TLUS22-IA-en-12

63 days
30 years
250 events
250 events

Installation Manual

SMA America, LLC

14 Accessories

14 Accessories
You will find relevant accessories and spare parts for your product in the following overview.
If required, these can be ordered from SMA or your distributor.
Description

Brief description

SMA order number

DC replacement varistors

Set with 4 varistors incl.


insertion tool

SB-VDC-US02

Fan retrofit kit

Retrofit kit for connecting a fan

FANKIT02-10

RS485 module

Module for communication via


RS485

DM-485CB-US-10

Speedwire module with


Webconnect function

Module for communication with SWDM-10


Sunny Portal via Webconnect

Installation Manual

SB3-5TLUS22-IA-en-12

83

15 Compliance Information

SMA America, LLC

15 Compliance Information
FCC Compliance
This device complies with Part 15 of the FCC Rules and contains FCC ID: SVF-SCOM31.
Operation is subject to the following conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Consult the dealer or an experienced radio/TV technician for help.
The user is cautioned that changes or modifications not expressly approved by
SMAAmerica,Inc. could void the users authority to operate this equipment.

IC Compliance
This device complies with Industry of Canada licence-exempt RSS standard(s) and contains Model
XBee Radio, IC: 9440A-SCOM31.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numrique de la classe B est conforme la norme NMB-003 du Canada.
Operation is subject to the following two conditions:
This device may not cause interference, and
This device must accept any interference, including interferences that may cause undesired
operation of the device.

84

SB3-5TLUS22-IA-en-12

Installation Manual

SMA America, LLC

16 Contact

16 Contact
If you have technical problems concerning our products, contact the SMA Service Line.
We need the following data in order to provide you with the necessary assistance:
Inverter device type
Inverter serial number
Inverter firmware version
Special country-specific settings of the inverter (if applicable)
Type and number of PV modules connected
Mounting location and mounting altitude of the inverter
Three-digit or four-digit event number and display message of the inverter
Optional equipment, e.g., communication products

United States/ SMA America, LLC


Estados
Rocklin, CA
Unidos

+1 877-MY-SMATech (+1 877-697-6283)*

Canada/
Canad

+1 877-MY-SMATech (+1 877-697-6283)***

SMA Canada, Inc.

+1 916 625-0870**

Toronto

* toll free for USA, Canada and Puerto Rico / Llamada gratuita en EE. UU., Canad y Puerto Rico
** international / internacional
*** toll free for Canada / gratuit pour le Canada

Installation Manual

SB3-5TLUS22-IA-en-12

85

SMA Solar Technology

www.SMA-Solar.com
SMA America, LLC
www.SMA-America.com

You might also like