83 Calibration Ultrasonic Flowmeters PDF
83 Calibration Ultrasonic Flowmeters PDF
83 Calibration Ultrasonic Flowmeters PDF
G M - 4055
William Johansen and Joel Clancy
Colorado Engineering Experiment Station, Inc.
Introduction
Ultra-sonic flowmeters are currently being
put into service in large numbers. When used in
custody transfer applications, ultrasonic flowmeter
calibration is required.
There is currently no
standard covering the calibration of ultra-sonic
flowmeters, although AGA Report No. 9 is used as a
guide. The process of calibrating an ultra-sonic
meter will be discussed as well as the calculation of
a flow weighted mean error (FWME) and a
calibration factor in accordance with AGA Report No.
9.
415
continuously.
The suction pressure on the
compressor must be maintained above some
minimum value, which places a limitation on the
differential pressure across the loop. This limitation
on differential pressure places a flowrate limit on
pressurized loop systems that is typically much
lower than that of pipeline based systems.
416
Meter Calibration
417
Calibration Report
2.0
0.5
uJ
"~
-1.0
-1.5
-2.0
0
35,000
21,875
8,750
3,750
3. ft/sec
60000
80000
100000
37,801
21,980
6,890
3,475
37,681.9
21,910.1
6,915.9
3,508.1
-0.315
-0.318
0.376
0.953
qmax
40000
0.75qma~
0.40qm~
0.25qr~
0.10qn~
qmi,
20000
Flowrate (ACFH)
Maximum
Meter Flowrate
of 87500
ACFH
0.0
no -0.5
...............................................................................................................................................................
1.5
Calibration
Flowrates
(ACFH)
87,500
61,250
35,000
21,875
8,750
3,750
Indicated Flowrate
Maximum Flowrate
xlO0.
Desired
Flowrate
(ACFH)
87,500
61,250
Actual
Flowrate
(ACFH)
86,500
60,415
Flowrate
Indicated by
Meter being
Calibrated
(ACFH)
86,183.4
60,190.3
Error
(%)
The percent full-scale values are then multiplied by
the percent error values. The values in the percent
full-scale column and the percent full-scale times
-0.366
-0.372
418
Actual
Flowrate
(ACFH)
86,500
60,415
37,801
21,980
6,890
3,475
Table 3. S u m m e d Values
Percent
Percent F.S.x.
Error (%)
Full Scale
Error
0.5
w
o
0.0
#. -0.s
-0.366
-0.372
-0.315
-0.318
0.376
0.953
0.9886
0.6905
0.4320
0.2512
0.0787
0.0397
Sum = 2.4807
-0.3618
-0.2568
-0.1361
-0.0799
0.0296
0.0378
Sum =-0.7672
-1.0
-1.5
-2.0
- 0.7672
80000
100000
Summary
Ultra-sonic flowmeters are being installed in natural
gas pipelines in large numbers. The calibration of
ultra-sonic flowmeters is performed in accordance
with AGA Report No. 9. The inspection, installation,
and calibration of ultra-sonic flowmeters were
discussed. The FWME calculation example in AGA
Report No. 9 was covered in detail.
= - 0.3093
60000
2.4807
Calibration Factor =
40000
Flowrate (ACFH)
FWME -
20000
= 1.0031
(100 + F W M E )
419
Ultra-sonicMeter
Flow Standard
Compressor
Heat Exchanger
Esl
Flow Control Valve
U/tra-sonic Meter
Flow Standard
Direction of FlowAroundLoop
420
,)