F05
F05
F05
MEASUREMENT
Eric Thompson
Regional Sales Manager
15415 International Plaza Drive, Suite 100
Houston, Texas 77032
Summary
This paper outlines the operating principles and
application of ultrasonic gas flow metering for
custody transfer. Basic principles and underlying
equations are discussed, as are considerations for
applying ultrasonic flow meter technology to station
design, installation, and operation. These
applications are illustrated based on operating
experience with the SICK ultrasonic flow meter,
however many of these issues can be generalized to
other meter manufacturers.
Introduction
The use of ultrasonic meters for custody (fiscal)
applications has grown substantially over the past
several years. This is due in part to the release of
AGA Report No. 9, Measurement of Gas by
Multipath Ultrasonic Meters [Ref 1], Measurement
-G-E-06
Provisional
Ultrasonic
Specification [Ref 2], and the confidence users have
gained in the performance and reliability of
ultrasonic meters as primary measurement devices.
Just like any metering technology, there are design
and operational considerations that need to be
addressed
in
order
to
achieve
optimum
performance. The best technology will not provide
the expected results if it is not installed correctly, or
maintained properly. This paper addresses several
issues that the engineer should consider when
designing ultrasonic meter installations.
Why Use Ultrasonic Meters?
Before discussing installation issues associated with
ultrasonic meters (USMs), it might be good to review
what the benefits of using USMs are. Since the mid1990s the installed base of USMs has grown
steadily each year. It is estimated that more than
$65 million was spent worldwide on purchasing
USMs in 2006. There are many reasons why
ultrasonic metering is enjoying such healthy sales.
Some of the many benefits of this technology
include the following:
x
x
x
x
x
x
x
x
applications.
Non-Intrusive: Minimal pressure drop.
Low Maintenance: No moving parts means
reduced maintenance.
Fault Tolerance: Meters remain relatively
accurate even if sensor(s) should fail.
Integral Diagnostics: Data for determining a
Figure 1
Ultrasonic meters are velocity meters by nature.
This means, they measure the velocity of the gas
Operating Principle
Transducer B
tBA
tAB
Transducer A
L
c v cos D
t BA
L
c v cos D
Path velocity
v Pfad
L 1
1
2 t AB tBA
Figure 4
Figure 2
This figure shows the simple geometry of two
transducers, A and B, at an angle M with respect to
the axis of the straight cylindrical pipe.
Sound Velocity
1
L
1
2 cos D t AB t BA
c v cos D
L
c v cos D
t BA
v Pfad
Figure 3
In Figure 3, L denotes the path length, D denotes
the diameter, and V is the velocity vector. The
transit time (Tab) of an ultrasonic signal traveling with
the flow is measured from Transducer A to
Transducer B. When this measurement is
completed, the transit time (Tba) of an ultrasonic
signal traveling against the flow is measured from
Transducer B to Transducer A. When there is no
L
2 cos D
1
1
t AB t BA
L 1
1
2 t AB t BA
Timing Characteristics
The accuracy required in the travel time
measurement can be found from the equations. For
example, when a velocity of 3 ft/s is measured with
0.5% accuracy along a 3 ft. path length in a gas with
sound velocity of 1,300 ft/s, both travel times are of
order of 2.5 milli-seconds, and their difference is
about 6 micro-seconds, which must be measured
with an error no greater than 30 NANO-seconds!
This minute travel time difference requires highspeed, high-accuracy digital electronics. The travel
times of only a few milli-seconds enable individual
ultrasonic flow velocity measurements at high
repetition rates. Typical rates are 20 to 50 Hz,
depending on pipe diameter. The need for high
repetition rates is evident in cases such as surge
control applications, where the flow may drop from
its set point to its minimum in less than 0.05
seconds.
BASIC DIAGNOSTIC INDICATORS
One of the principal attributes of modern ultrasonic
meters is the ability to monitor their own health, and
to diagnose any problems that may occur. Multipath
meters are unique in this regard, as they can
compare certain measurements between different
paths, as well as checking each path individually.
'
'?
L@
external diagnostics. Internal diagnostics are those
indicators derived only from internal measurements
of the meter. External diagnostics are those
methods in which measurements from the meter are
combined with parameters derived from independent
sources to detect and identify fault conditions. An
example of this would be to compute the gas SOS,
based upon composition, and compare to the
'\
Gain
\+*
+
the presence of strong signals on all *!
multipath USMs have automatic gain control on all
receiver channels. Transducers typically generate
the same level of ultrasonic signal time after time.
The increase in gain on any path indicates a weaker
signal at the receiving transducer. This can be
caused by a variety of problems such as transducer
deterioration, fouling of the transducer ports, or
liquids in the line. However, other factors that affect
signal strength include metering pressure and flow
Sizing of USMs
Traditional measurement devices have been limited
to flow rates that were equivalent to 50-60 feet per
second (fps) maximum. Although high-capacity
turbines operate in the 80-95 fps range, the majority
of installations are still designed for the standard
capacity meter. One of the significant advantages of
ultrasonic meters is their ability to operate accurately
in excess of 100 fps with no damage to the meter.
*
+
?'-of-'@
the capacity of an ultrasonic meter is at least 1
times that of an orifice meter.
Many users specify velocity limits in piping to
minimize the potential for erosion in fittings (bends,
elbows and tees) that can cause failure of the piping
should the wall thickness become too thin. There
have been reports of severe erosion of elbows
downstream of meters that were operated above
100 fps for significant periods of time. However,
there are several other issues that limit high velocity
operation.
Higher velocity operation increases the stress on the
thermowell(s). There have been reported cases of
thermowells cracking when operated at high
velocities. Some work has been performed to
determine how accurate the RTD element remains
when the thermowell is subjected to very high
velocities. Studies indicate that vibration of the
thermowell may cause the RTD to register higher
' ?+-@
' # !
element rubs against the thermowell.
Higher velocities also create more differential
*'
-performance flow
conditioners.
The magnitude of this loss is
somewhat dependent on the type of conditioner
installed. However, typically the pressure drop at 60
fps is on the order of 2-3 psi differential (psid). If the
gas velocity through the meter is increased to 120
fps, the differential becomes 4-9 psid.
The
increased velocity and subsequent differential
pressure also can create higher noise, both audible
and ultrasonic. The ultrasonic noise at these high
+ #
operation.
The audible noise may necessitate
As Found
As Left
Verification Points
1.2
1.0
0.8
0.6
% Error
0.4
0.2
0.0
-0.2
-0.4
-0.6
-0.8
-1.0
-1.2
-1.4
0
20
40
60
80
Meter Velocity (ft/sec)
100
120
140
1.00
As Found
As Left
Verification Points
0.75
0.50
% Error
0.25
0.00
-0.25
-0.50
-0.75
-1.00
0
20
40
60
80
100
120
1374.0
1379.0
1373.0
1378.0
1372.0
Path 3
Path 4
120
110
90
70
50
120
110
100
90
80
70
60
50
1367.0
40
1368.0
1373.0
30
1369.0
1374.0
20
1370.0
1375.0
10
1376.0
Time (sec)
Path 2
1371.0
40
1377.0
30
SOS
1380.0
Path 1
100
Average
1375.0
80
Path 4
60
Path 3
20
Path 2
10
Path 1
1381.0
SOS
Average
Time (sec)
0.908
Path 1
Path 2
1.022
Path 2
Path 3
1.021
Path 3
0.912
Path 4
0.80
0.85
0.90
0.95
0.930
Path 1
1.037
1.005
0.894
Path 4
1.00
1.05
1.10
Path Ratios
0.80
0.85
0.90
0.95
1.00
1.05
1.10
Path Ratios
Meter A
Meter A
Path 2
1.020
Path 2
Path 3
1.020
Path 3
0.80
0.85
0.90
1.014
1.027
0.935
Path 4
0.913
Path 4
0.892
Path 1
0.915
Path 1
0.95
1.00
0.80
1.05
0.85
0.90
0.95
1.00
1.05
CPA Flow
Conditioner
10D
4 + 4 Meter (8 Path)
10D
>5D
1.067
Path 1
0.6
0.4
% Error
1.061
Path 2
0.2
0.0
-0.2
0.960
Path 3
-0.4
-0.6
0.804
Path 4
-0.8
0
10
20
30
40
Velocity (ft/sec)
50
60
70
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Path Ratios
Reduce uncertainty
Verify performance
Improve rangeability
Calibration Labs
There are several flow labs in North America that
provide calibration services. Each will calibrate to
any number of points the designer feels are
necessary. Typically most designers are requesting
{ * \
?-+'@
points have been determined, an adjustment factor
Re-Calibration
AGA 9 does not require an ultrasonic meters to be
re-calibrated, and will not require this in the
upcoming revision. As USMs have no moving parts,
and provide a wide range of diagnostic information,
many feel the performance of the meter can be field
verified. That is, if the meter is operating correctly,
its accuracy should not change, and if it does
change, it can be detected. This, however, remains
to be proven with a significant number of meters.
The use of USMs for custody transfer applications
began increasing rapidly in 1998. Now, with more
than 9 years of installed base, there is significant
information to conclude USMs may not require recalibration. Many companies are not certain as to
whether or not they will retest their meters in the
future. They are waiting for additional data to
support their decision. Manufacturers are also trying
to show the technology may not require recalibration.
During the past several years, many meters have
been re-calibrated in Canada. Their governmental
agency, Measurement Canada, requires USMs to be
re-tested every 6 years. The data obtained from
these meter re-calibrations, from random re-testing
by customers, and long-term data from meters at
calibration labs typically shows the meter to be
within 0.3% of the original calibration assuming the
meter is clean and operating correctly.
Several users in the US have removed meters in the
past year and returned them to the calibration facility
for a quick verification. If the meter is clean, the
performance on these has typically been within 0.10.3%. Unfortunately, there is very limited published
CONCLUSIONS
During the past several years the industry has
learned a lot about USM operational issues. The
traditional 5 diagnostic features, gain, signal-tonoise, performance, path velocities and SOS have
helped the industry monitor the USM. These 5
features provide a lot of information about the
meter at the time of installation, and monitoring
these features on a routine basis can generally
identify metering problems in advance of failure.
More advanced diagnostic indicators, such as
References:
1. AGA Report No. 9, Measurement of Gas by
Multipath Ultrasonic Meters, June 1998.
2. Provisional
Verification
Specification for
and Installation
the Approval,
and use of