HC1 A Manual EN
HC1 A Manual EN
HC1 A Manual EN
Contents
1. Introduction----------------------------------------------------- 1
1.1 Confirmations upon delivery ------------------------------- 2
1.2 Nameplate information -------------------------------------- 2
2. Safety Precautions -------------------------------------------- 2
2.1 Before delivery of current ----------------------------------- 2
2.2 In delivery of current ---------------------------------------- 4
2.3 In running ----------------------------------------------------- 4
3. Inverter standard specifications ---------------------------- 4
3.1 Individual specifications ------------------------------------ 4
3.2 Common specifications ------------------------------------ 6
4. Storage & Installation ---------------------------------------- 7
4.1 Storage --------------------------------------------------------- 7
4.2 Location ------------------------------------------------------- 7
4.3 Position -------------------------------------------------------- 8
5. Wiring ---------------------------------------------------------- 9
5.1 Main circuit schematic diagram ---------------------------- 9
5.2 Terminals ----------------------------------------------------- 10
5.3 Standard Connection Diagram----------------------------- 12
5.4 Wiring Precautions ------------------------------------------ 13
6. Using the digital operator ------------------------------------ 15
6.1 Explanations of the digital operator----------------------- 15
6.2 Display data -------------------------------------------------- 17
6.3 Instructions of the digital operator ------------------------ 18
1
TECORP Electronics
TECORP Electronics
1. Introduction
Thank you for purchasing our high quality HC1-A series inverters.
Before installation and operation please read these instructions in
this manual thoroughly. For your safety, the product should only be
installed, tested and adjusted by professional personnel. If you have any
questions or problems, please contact our local agency.
The information contained in this manual is subject to change
without notice.
WARNING
Always turn off the input power supply before wiring.
Do not touch any inner part of the inverter when the charging lamp is
still on shortly after the AC power is cut off.
Do not check signals while the inverter is running.
Do not attempt to modify or alter the inverter by yourself, doing so
can result in electrical shock or injury or even explosion.
Be sure to ground the E terminal.
! CAUTION
Do not perform voltage withstand tests on the inverter.
Never connect the AC main circuit power supply to output terminals
U.V and W.
A CMOS IC is used in the control board. Handle the control board
and CMOS IC carefully. The CMOS IC can be destroyed by static
electricity if touched directly.
Installation, testing and maintenance must be performed by
professional personnel.
The inverter should be discarded as industrial waste. Avoid burning.
TECORP Electronics
1.1 Receiving
Before unpacking please check the following:
Inspect the entire exterior of the inverter to see there are any scratches
or other damage resulting from shipping.
Check if there is an inverter and an operation manual in the package
as soon as you open the package.
Check the model on the nameplate on the side of the inverter to see if
this is the right model you want.
Check if there is something wrong with the inner parts, wiring and
circuit board.
Use a screwdriver or other tools to check for tightness.
Check if there is any other things in the machine.
Check if the operator buttons are all right.
Check if the optional device you ordered is contained in it.
HC1A07D543B
3 Ph 400V 50/60Hz
OUTPUT
3 Ph 400V 17.5A 7.5KW
Freq- Range:
0.1400Hz
TECORP ELECTRONICS CO., LTD.
MODELHC1 A 07D5 43 B
Software version
Voltage grade 43 means 3 phases 400V
Inverter capacity,07D5 means 7.5KW
Serial number
Product name
TECORP Electronics
2.Safety precautions
2.1 Before delivery of current
! CAUTION
Check to be sure that the voltage of the main circuit AC power
supply matches the rated voltage of the inverter.
! CAUTION
E symbol is the ground terminal, Be sure to ground the ground
terminal.
Do not Connect electromagnetic switches or contactors to the output
circuits.
! WARNING
R.S.T terminals are power input terminals, never mixed with U.V.W
terminals. Be sure that the wiring of the main circuit is correct.
!CAUTION
Always hold the case when carrying the inverter. If the inverter is
held by the front cover, the main body of the inverter may fail,possible
resulting in injury.
Mount the inverter to a metal or other noncombustible material.
Install the inverter in a safe site, avoid high temperature, direct
sunlight, humid air or water.
Keep the inverter from the reach of children or non-workers.
Install a cooling fan or other cooling device when installing more
than one inverters in the same enclosure so that the temperature of the
air entering the inverter is below 40.
X
Check to be sure that the front cover
KM
is attached before turning on the
u
power supply. Do not remove the front
v
M
Inverters
cover during operation.
w
Do not install the inverter in a space
with explosive gas.
If the inverter is used at or above
1000m above seal level, the cooling
X
efficiency will be worse, so please run
it downgraded.
Do not connect contactors and related capacitor or voltage
dependent resistor etc,to the output circuits.
If it is a must to connect such devices, be sure there is no inverter
output when operating these devices.Otherwise,it will result in damage
3
TECORP Electronics
2.3 In running
WARNING
Never add or remove motor group while in running, the surge
current it created will cause damage to the inverter, even burn-up of
the main circuit.
WARNING
Never remove the front cover of the inverter while in running.
Do not come close to the machine when the fault restart function is
used. If the alarm is cleared, the machine may start moving suddenly.
The function of the STOP button can only be available after setting.
It is different from the emergency stop button. Please note.
! CAUTION
Do not touch the heat sink, braking resistor, or Braking Resistor
Unit. These can become very hot.
Be sure that the motor and machine is within the applicable ranges
before starting operation.
Do not check the signals while the inverter is running.
Be careful when changing inverter settings. The inverter has been
set to suitable for general using in factory.
Do consider the noise,vibration,and the speed limit of the motor and
the mechanical devices when the inverter is running at or above the
frequency of 50Hz.
4
TECORP Electronics
3. Standard Specifications
3.1 Individual Specifications
MODEL
Input Voltage
Power
(KW)
Driver
Capacity
(KVA)
HC1A00D423B
HC1A0D7523B
HC1A01D523B
HC1A02D223B
HC1A0D7543B
HC1A01D543B
HC1A02D243B
HC1A03D743B
HC1A05D543B
HC1A07D543B
HC1A001143B
HC1A001543B
HC1A18D543B
HC1A002243B
HC1A003043B
HC1A003743B
HC1A004543B
HC1A005543B
HC1A007543B
HC1A009043B
HC1A011043B
HC1A013243B
HC1A016043B
HC1A018543B
HC1A020043B
HC1A022043B
HC1A025043B
1/3220V
1/3220V
1/3220V
1/3220V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
3400V
0.4
0.75
1.5
2.2
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
200
220
250
HC1A028043B
3400V
280
1.0
2.0
2.8
4.0
2.2
3.2
4.0
6.8
10
14
19
26
32
37
52
64
72
84
116
134
160
193
230
260
290
325
368
Output
Current
(A)
2.5
5.0
7.0
10
2.7
4.0
5.0
8.5
12.5
17.5
24
33
40
47
65
80
91
110
152
176
210
253
304
340
380
426
483
Suitable
Motor
(KW)
0.4
0.75
1.5
2.2
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
200
220
250
412
540
280
5
TECORP Electronics
MODEL
Input Voltage
Power
(KW)
Driver
Capacity
(KVA)
HC1A030043B
HC1A031543B
HC1A037543B
HC1A041543B
HC1A045043B
3400V
3400V
3400V
3400V
3400V
300
315
375
415
450
450
461
550
610
665
Output
Current
(A)
580
605
800
880
960
Suitable
Motor
(KW)
300
315
375
415
450
Frequency Control
Frequency Range
Frequency
Accuracy
Frequency Setting
Resolution
Output Resolution
Operator Setting
Method
Analog Setting
Method
Other functions
General Control
6
Acceleration/Dec
eleration time
V/F Curve
Torque Control
Multi-function
input terminals
HC1-A
SPWM
400V Power Supply340 VAC - 460VAC
220V Power Supply180 VAC 250 VAC
0.10~400.00Hz
Digital0.01%-10~40
Analog0.1% 2510
Digital0.01Hz
Analog1% of Max Operating Frequency
0.01Hz
Pressor or to set
0-5V / 0-10V
4-20mA / 0-20mA
Frequency up/lower limit, start frequency, stopping
frequency, three skip frequencies can be
individually set.
0.1-6500s four selectable combinations of
independent acceleration and deceleration
setting.
Set V/F curve at will.
Max Torque 10.0% Max Output Voltage. The
starting torque can reach 150% at 1.0Hz
6 multifunction input terminals for 8
multi-speed, easy PLC, 4 Accel/Decel
time,UP/DOWN command, external
emergency stop.
TECORP Electronics
Protection Function
ITEM
Communication
Control
Operating
Temperature
Humidity
Vibration
Instantaneous
over current
Over Load
Motor Overload
Protection
Over Voltage
Under Voltage
Momentary
Power Loss
Heat Sink over
heat
Multi-function
output terminals
Other functions
Digital operator
monitor
HC1-A
RS485
-10~40
0-95% relative humidity
0.5G or lower
Approx. 200% rated current.
Inverter:150% 1 minute.
Electronic thermal overload relay.
23 series: DC bus over 400Vdc
43 series: DC bus over 800Vdc
23 series: DC bus voltage drop 200Vdc
43 series: DC bus voltage drop 400Vdc
0-2 seconds: The inverter can be restarted by
speed search.
Protected by thermistor
5 multifunction output terminals for the
displaying and warning of on-running, zero
speed, counting and external fault information.
AVR, Decelerating stop or free-stop, DC brake,
auto restart tracking, easy PLC auto energy
saving, adjustable carrier Frequency (Max
20KHz) etc.
Frequency command,output frequency, speed
output current, output voltage. DC bus voltage
and rotation direction.
4.Storage &Installation
4.1 Storage
This product must be stored in its package box before installation.Pay
more attention to the followings when in storage.
It must be stored in a dry place without rubbish or dust.
7
TECORP Electronics
4.2 Location
Note: The working conditions of the inverter will affect its service
life,please install the inverter under the following conditions.
Ambient operating temperature -10 to 40.
IP rating: IP 20 for all models.
Protected from rain moisture.
Shielded from direct sunshine.
Free from metallic particles and corrosive gas.
Free from excessive vibration.
4.3 Positioning
120
There must be enough space left around the inverter for easy
maintenance and effective ventilation.See Diagram 1.
The inverter must be installed with heat sink ribs oriented vertically
for effective ventilation..
If there is any instability when installing the inverter, please put a flat
board under the inverter bottom base and install again. If the inverter is
installed on a loose surface, stress may cause damage in main circuit.
The inverter should be installed on non-combustible materials, such
as iron plates.
If several inverters are installed together in one cabinet, please add
heat dissipation plates and provide enough space between the inverters.
See Diagram 2.
50
50
HCI-A
CAUTION
Hig h vol ta ge In aid e
WARNING
Do no t c on nect AC po we r t o o ut put tu rbin a ls( U.V.W )
Dis ch ar gi ng time le g rea te r t ha n 5 an co ne s.
Do no t Lns pect comp one nts un less I ns ide H ARGE
120
la mp Is tu rn ed o ft.
Unit:mm
Diagram 1
Diagram 2
TECORP Electronics
5. Wiring
5.1 Main circuit schematic diagram
Power supply: Verify that the inverter rated voltage
coincides with AC power supply voltage.
Magnetic contactor
Note: Dont use the magnetic contactor as the power
supply on/off button for the inverter.
HCI-A
C A U T I O N
Hig h vo ltag e I nai de
W A R N I N G
Do n ot c on nec t AC powe r t o ou tp ut t ur bin als( U.V.W)
Disc har gi ng t ime le gr ea te r th an 5 ancon es .
Do n ot L ns pec t co mpo ne nt s un less I nsid e H AR GE
la mp I s tu rn ed o ft.
TECORP Electronics
5.2 Terminals
5.2.1 Main Circuit Terminals Arrangement
HC1A00D423B-HC1A02D223B
HC1A0D7543B-HC1A03D743B
Pr
HC1A05D543B-HC1A07D543B
S
P1
HC1A001143B-HC1A030043B
R
UPF
HC1A00D423B-HC1A01D523B
HC1A0D7543B-HC1A02D243B
FA
FB
FC
KA
KB
IPV
UPF
DRV
DCM
SPL
RS-
SPM
RS+
UPF DRV FOR REV DCM RST SPH SPM SPL P24 AM
ACM AI
VI
+10
EKB EKA EFC
HC1A02D223B
HC1A03D743B-HC1A07D543B
10
EFB
EFA
PR
TECORP Electronics
FUNCTION DESCRIPTION
Input terminals of AC line power.
External braking resistor terminals.
External DC reactor terminals.
External Braking unit terminals.
Output terminals to motor.
Ground terminal.
Functions
Multi-function input1
Multi-function input2
Multi-function input3
Multi-function input4
Multi-function input5
Multi-function input6
Ground common for input
terminals
+12V power supply
+24V power supply
Power supply for analog frequency
Analog frequency reference
input(voltage)
Analog frequency reference
input(current)
Common for analog input signal
Multi-function output terminal 1
Factory setting
Forward run
Reverse run
Reset
High speed
Medium Speed
Low Speed
11
TECORP Electronics
Pr
P
R
Ac power supply
U
V
W
S
T
Motor
VI
ACM
KA
Multi-function output <relay N/0>
KB
3A/250VAC 3A/30VDC
EV(IPV)
+12V
AI
FC
FA
FB
3A/250VAC
3A/30VDC
DRV
VR(+10V)
10K
Analog Current
input
FOR
REV
SPH
SPM
SPL
UPF
DCM
RST
AM
DCM
ACM
RS+
HC1A00D423B~HC1A02D223B
RSHC1A0D7543B~HC1A03D743B
Dc Reactor
R
Ac power supply
Braking Resistor
P1
Pr
U
V
S
T
Motor
E
VR(+10V)
10K
Analog Current
input
KA
VI
ACM
AI
FC
FA
FB
3A/250VAC
SPH
DRV
SPM
SPL
UPF
DCM
FOR
REV
RST
AM
DCM
ACM
12
RS+
RS-
HC1A05D543B~HC1A07D543B
3A/30VDC
TECORP Electronics
Motor
TECORP Electronics
400V class products) between the inverter and the motor, please choose
a AC motor special for inverters or add a AC reactor on the output side
of the inverter, because a very high dV/dT produced in the motor coil
will cause damage to the insulation of the motor.
220V
Class
400V
Class
Model
HC1A00D423B
HC1A0D7523B
HC1A01D523B
HC1A02D223B
HC1A03D723B
HC1A0D7543B
HC1A01D543B
HC1A02D243B
HC1A03D743B
HC1A05D543B
HC1A07D543B
HC1A001143B
HC1A001543B
HC1A18D543B
HC1A002243B
HC1A003043B
HC1A003743B
HC1A004543B
HC1A005543B
HC1A007543B
HC1A009043B
HC1A011043B
HC1A013243B
HC1A016043B
HC1A018543B
HC1A022043B
HC1A030043B
Screw
M4
M4
M4
M4
M4
M4
M4
M4
M4
M4
M5
M6
M6
M6
M8
M8
M8
M8
M8
M10
M10
M10
M12
M12
M16
M16
M16
Wire size
2~5.5
2~5.5
2~5.5
3.5~5.5
5.5
2~5.5
2~5.5
2~5.5
3.5~5.5
3.5~5.5
5.5
8
8
14
22
22
30
50
38~100
38~100
38~100
60~100
60~100
100~200
250~325
325
250*2p
Note: The parameters above are only for reference, not a standard.
TECORP Electronics
5.4.3 Grounding
Grounding terminal:E
220V class: The third grounding method. (grounding resistance should
be 100 ohm or lower.)
380V class: Special grounding method. (earth resistance should be 10
ohm or lower.)
Choose grounding wires according to the requirements of the electric
equipment.
Avoid sharing grounding wire with other large power equipment. The
grounding wire should be kept away from the power supply wires.
The grounding method for several inverters together should be done
as the first and second diagrams. Avoid the third diagram.
The shorter grounding wire is the better it is.
1Correct
2Correct
3Wrong
15
TECORP Electronics
FOR
REV
HZ
F/
R
R/min
PROG
Run key
STOP
RUN
RESET
HC002
Operation Mode Indicators
forweard run, reverse run,
frequency, current, Speed.
FOR REV
HZ
A ROTT
FOR
REV
PROG
DISP
SET
Run key
RUN
HC001
16
STOP
TECORP Electronics
Status
FOR
On
Forward run
REV
On
Reverse run
HZ
On
On
ROTT
On
HZ A
On
Display DC voltage
ROTT
On
HZ
ROTT
On
On
HZ A ROTT
Explanation
Indicator
HZ
ROTT
HZ
A
HZ
on
Explanation
Present set frequency or
output frequency
Current
Motor speed
ROTT
TECORP Electronics
Data
dsp.1 flashing
Display
Explanation
FOR
Hz
FOR
Hz
FOR
Hz
FOR
Hz
FOR
Hz
FOR
Hz
FOR
Hz
FOR
FOR
ROTT
uEr1.3
000.00
P RO G
E NTER
CD000
000.00
50.00
E NTER
PROG
RUN
DISP
END 50.00
CD001
050.00
50.00
50.00
0.00 50.00
0005.0
DISP
01440
DISP
PROG
F/R
050.00
050.00
050.00
030.00
ENTER
STOP
030.00
030.00
FOR
Hz
REV
Hz
REV
Hz
Switching to frequency
adjustable status.
REV
Hz
REV
Hz
REV
Hz
means on
Stop.
TECORP Electronics
7. Trial Operation
7.1 The important check before running
Is there any wrong connected wires? Pay special attention to the
terminals:U.V.W;
Make sure the power supply wires are connected to R.S.T not U.V.W.
Is there any metal powder or other wires left on the base plate of the
inverter or at the terminals?
Is there any looseness in the parts of screws and terminals?
Is there any short circuit or earth fault in the output parts?
000.00
display set frequency.
FOR Hz
Switching to data adjustable
000.00
status.
FOR Hz
Set a new frequency value that
050.00
ENTER
050.00
RUN
050.00
STOP
050.00
FOR
FOR
Hz
Hz
Running at 50Hz.
Stop.
19
TECORP Electronics
8.Function list
Basic parameter
Function
Item
code
CD000
CD001
CD002
CD003
CD004
CD005
CD006
CD007
CD008
CD009
CD010
20
CD011
CD012
CD013
CD014
CD015
CD016
CD017
CD018
CD019
CD020
Reserved
CD030
Factory
Setting
0.00
220/380
50.00
15/27.5
2.50
8.0/13.5
0.50
50.00
50.00
0.00
0
00
10.0/25.0
10.0/25.0
50.0
50.0
100.0
100.0
200.0
200.0
TECORP Electronics
Factory
Setting
0
0:digital operator
CD033 Control Mode Select 1:external terminals
2:communications
0:digital operator
Frequency command 1:external terminals
CD034
method select
2:communications
Applied Parameter
CD038
CD039
CD040
CD041
CD042
CD043
CD044
CD045
CD046
STOPkey
definition
0~15
0.00~400.00Hz
0:Reverse run forbidden
1:Reverse run available
5
5.00
1
Reserved
Starting Frequency
Stopping Frequency
Torque Boost
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
0.1~10.0Hz
0.1~10.0Hz
010%
0.00~400.00 Hz
0.00~400.00 Hz
0.00~400.00 Hz
0.5
0.5
2.0%
0.00
0.00
0.00
21
TECORP Electronics
Applied
Parameter
CD049
CD050 Multi-input1(FOR) 00:invalid 01:run 02:forward
02
CD051 Multi-input 2(RST) run 03:reverse run 04:stop
03
CD052 Multi-input 3(RST) 05:for/rev run 06:jog
10
07:forward jog 08:reverse jog
CD053 Multi-input 4(SPL) 09:external emergency stop
17
CD054 Multi-input 5(SPL) 10:reset 11:reserved
18
CD055 Multi-input 6
19
12:overheat of motor 17:high
speed 18:medium speed
(SPL)
Input,Output Terminals
CD056
CD057
CD058
CD059
01
05
02
00
1
0.00~400.00Hz
TECORP Electronics
Item
Function
code
CD062
CD063
CD064
CD065
CD066
CD067
CD068
CD069
CD070
CD071
CD072
Factory
Setting
0.00
0.50
00
0
0
0
50.00
0
1
100
1
CD073
Reserved
CD075
23
TECORP Electronics
Function
CD076
CD077
CD078
CD079
CD080
CD081
CD082
CD083
CD084
CD085
CD086
CD087
CD088
CD089
CD090
CD091
CD092
CD093
CD094
CD095
CD119
PLC running
direction
PLC
accel/decel.time
Multi-speed 2
Multi-speed 3
Multi-speed 4
Multi-speed 5
Multi-speed 6
Multi-speed 7
Multi-speed 8
Timer 1
Timer 2
Timer 3
Timer 4
Timer 5
Timer 6
Timer 7
Timer 8
Reserved
Factory
setting
0.00~400.00Hz
0.00~400.00Hz
0.00~400.00Hz
0.00~400.00Hz
0.00~400.00Hz
0.00~400.00Hz
0.00~400.00Hz
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
0.0~6500.0s
15.00
20.00
25.00
30.00
35.00
40.00
0.50
10.0
10.0
0.0
0.0
0.0
0.0
0.0
0.0
TECORP Electronics
Item Function
code
CD120
CD121
CD122
CD123
CD124
CD125
CD126
CD127
CD129
CD130
Motor specifications
Special function parameter
CD131
Rated current
CD132
CD133
CD134
CD139
CD140
CD141
Motor poles
Rated rotational speed
Reserved
CD142
CD143
CD144
CD145
CD146
CD147
CD148
CD149
DC braking level
0.0~20.0%
DC braking time at
0.0~25.0S
starting
DC braking time at stopping
0.0~25.0S
Speed search time
0~20.0S
Speed search current level
0~200%
Power loss allowable
0:invalid 1:restart by
Momentary power ride
speed search
through time
0.1~5.0s
Number of auto restart
010
Auto voltage regulation
0:invalid 1:valid
Auto energy saving
0~10%
Factory
setting
1
150
0
150
1.0
*
*
04
1440
2.0
0.0
0.0
5.0
150
0
0.5
00
1
0
25
TECORP Electronics
Functio
n code
CD150
CD151
CD152
CD153
CD154
Function
P
I
D
Target Value
Target Value Source
CD155
CD156
CD157
CD159
CD160
CD161
CD162
CD163
CD167
CD168
CD169
CD170
CD171
CD172
CD173
CD174
CD175
CD176
CD177
Reserved
CD178
CD179
Manufacture Date
CD180
Sequence Number
CD181
CD250
Reserved
Communication identified NO
Baud rate of communication
Communication agreement
Factory
setting
100%
5.0
*
*
100%
0%
0~250
0~3
05
0
1
0
015
According to the
actual model
According to the
actual model
Note:means no fault
record
00
*
*
*
001001 is fault
cleared
00
Reserved
Display mode select
Rated voltage of the inverter
0:50Hz 1:60Hz
Factory Set
*
*
TECORP Electronics
TECORP Electronics
220
220
220
55
24
15
8
8
0 0.5 2.5
50
25
50
0 0.5 2.5
380
380
380
110
45
27.5
16
13.5
0 0.5 2.5
50
28
9
0 0.5
50
20
0 0.5
25
50
0 0.5 2.5
50
htigh torque curve
TECORP Electronics
CD011
Factory setting
Set range:0010
Unit:1
Factory setting:00
If the parameter you have set is improper or abnormal. You can
change it into 08 first to return to the factory setting, and then reset it.
But if CD010 is set for 1, you should unlock the parameter first. Related
parameter: CD010.
CD012 Accel.Time 1
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:10.0/25.0
CD013 Decel.Time 1
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:10.0/25.0
CD014
Accel.Time 2
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:50.0
29
TECORP Electronics
CD015
CD016
CD017
CD018
Decel.Time 2
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:50.0
Accel.Time 3
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:50.0
Decel.Time 3
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:50.0
Accel.Time 4
Set range:0.16500.0s
Unit:0.1s
**
Factory setting:50.0
CD019
Decel.Time 4
**
Set range:0.16500.0s
Unit:0.1s
Factory setting:50.0
Accelerating Time means time needed for inverter accelerating from
0Hz to 50Hz (See t1 in the diagram)
Decelerating Time means time needed for inverter decelerating from
50Hz to 0Hz (See t2 in the diagram)
F
50Hz
T
t1
t2
TECORP Electronics
CD020CD030
Reserved
CD031
Output Frequency
Set frequency
Output Current
CD032 Stop method select
Set range01
Unit1
Factory setting0
TECORP Electronics
Unit 1
Factory setting0
Factory setting0
TECORP Electronics
low
large
strong
TECORP Electronics
only be executed when the machine is in the stop state. It will not be
effective when in running. Related setting refers to CD050-CD055.
CD037
Factory setting1
TECORP Electronics
Unit0.01Hz
**
Factory setting0.5
F
CD046
CD045
CD044
Jump point
CD047
CD047
TECORP Electronics
skip points are set. When CD047is set for 0, all the set skip
frequencies are invalid; the actual skip frequency range is twice of the
setting value of CD047.
Shown as above.
CD048 CD049
Reserved
NAME
00
Terminal Invalid
01
Run
02
03
04
05
FOR
REV
STOP
FOR/REV
06
07
08
09
JOG
JOG FOR
JOG REV
Emergency stop
10
RST
11
Reserved
12
Overheat
36
DESCRIPTIONE
Empty terminal, avoid false
operation.
Control the run and stop of the
inverter, and also used to make up
multiple control methods combining
with other terminals.
Forward run.
Reverse run.
Stop.
Forward run, Reverse run shift
switch.
Jog.
Jog forward rotation.
Jog reverse rotation.
The inverter would stop immediately
when there was emergency.
The inverter can be reset when the
fault is cleared.
Using this function to protect heat
TECORP Electronics
Reserved
17
High speed
18
Medium speed
19
Low speed
20
Multi-speed 1
21
Multi-speed 2
22
Multi-speed 3
23
ACCEL/DECEL
time select 1
ACCEL/DECEL
time select 2
UP
DOWN
TECORP Electronics
CD051=04
BUsing RUN.DCM.F/R to start,stop,forward and reverse run and
reverse rotation.
1) Using multi-function terminals FOR and REV.
K
FOR
2) Parameter setting: CD033=1
K
CD050=01
REV
CD051=05
DCM
K2 open for FOR run; K2 closed for REV run.
1
38
TECORP Electronics
RUN SPL
terminal
ON OFF
SPM
SPH
Results
terminal terminal
OFF
OFF
Main speed and the run frequency
are determined by CD000.
ON ON
OFF
OFF
Low speed and the run frequency
are determined by CD080.
ON ON/OFF ON
OFF
Medium speed and the run
frequency are determined by
CD081.
ON ON/OFF ON/OFF ON
High speed and the run frequency
are determined by CD082.
Note1This function is only valid when CD076 is set for1(i.e. in
external control four speed)
2The frequency of low speed, medium speed and high speed
are determined by the second,third,fourth frequencies.
3The acceleration or deceleration time is controlled by the
acceleration or deceleration selection terminals.
4When multiple signals are received, it will have the priority
from the high to the low.
EUP/DOWN terminals
F
Max operation frequency
Set frequency
Up command
Down Command
39
TECORP Electronics
UP
ON
OFF
ON
DOWN
OFF
ON
ON
RESULTS
Frequency up
Frequency down
Neither up nor down
TECORP Electronics
G Counting
C00
C00
cn
t1
t2
Counting Arrival
Counting Reset
TECORP Electronics
TECORP Electronics
CD060
Multi-function output 5
**
Set range:07
Unit:1
Factory setting:1
Function: Analog frequency output terminal, output 0-10V.It can be
Joined together with CD071 for external monitoring if connected to a
Frequency meter with a measuring range of 10V or below.
0: invalid
1: output frequency 2: output current (010V)
3: DC voltage (010V)
4: output voltage (010V)
567:invalid
CD061
Up to desired frequency 1 setting
**
CD062
Up to desired frequency 2 setting
Set range:0.00400.00Hz Unit:0.01Hz
Factory setting:0.00
CD063
Up to frequency setting detection width
**
Set range:0.0010.00Hz Unit:0.01Hz Factory setting:0.50
When the output frequency is in the range of up to frequency setting
detection, the corresponding multi-function output will act. If it is not in
the range, no contact will begin to act.
43
TECORP Electronics
F
Frequency agreed
2*CD063
Frequency agreed
CD064
Counter set
**
Set range065500
Unit1 Factory setting0
The counter takes the multi-function external terminal as its contact
Terminal. When the counting value reaches the set value of CD064, the
corresponding multi-function output contact will act. The counter can go
on for a new counting only after the former numerical value is cleared
Up and the counter gets a reset. The trigger signal can be sent by
Proximity switch and photoelectric switch,etc.
CD065
44
TECORP Electronics
1Negative direction
Bias direction means commands for FOR or REV run. Positive bias
means FOR run; negative bias means REV run; Related setting, refer to
CD070.
CD068
Higher analog frequency set point
Set range0.00400.00 Hz Unit0.01Hz Factory setting50.00
CD069
For example
F
0V
4mA
50Hz
5V
10V
12mA
20mA
settingCD066=50
CD067=1
CD068=50
CD069=0
CD070=1
F
50
0
4mA
10V
20mA
Setting: CD066=50
CD067=0
CD068=0
CD069=0
CD070=1
45
TECORP Electronics
Setting: CD066=10
CD067=1
CD068=40
CD069=0
CD070=1
40
0
4
10v
20mA
10
40
0v
4mA
10
2v
4.8mA
10v
20mA
Setting: CD066=10
CD067=1
CD068=40
CD069=0
CD070=0
TECORP Electronics
CD073~CD075
Reserved
CD076
Main frequency
Multi speed1
Multi speed2
Multi speed3
Multi-function Terminal
Multi Multi Multi
speed 1 speed 2 speed 3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
Result
Main frequency and the frequency are determined
by CD00 or external analog input.
Speed 1 and the frequency are determined by
CD080.
Speed 2 and the frequency are determined by
CD081.
Speed 3 and the frequency are determined by
CD082.
Speed 4 and the frequency are determined by
CD083.
Speed 5 and the frequency are determined by
CD084.
47
TECORP Electronics
OFF
ON
ON
ON
ON
CD086
CD087
CD088
CD086
CD080
48
TECORP Electronics
Note
CD087 CD088
CD089 CD090
49
TECORP Electronics
Unit: 1
Factory setting: 0
50
TECORP Electronics
Manual
HC1-A User
CD081
CD085
CD082
CD000
CD086
CD083
CD087 CD088
CD089
CD094
CD084
CD080
Note
1) When the auto running command is received, the inverter begin to
run at its parameter set value .When every stage changes, the
inverter will first stop and then restart again. The inverter will
automatically stop after running for one circle. Only when a new
running command is received, will the inverter begin to run again.
2) The frequency for different steps is set by CD000, CD080-CD086.
3) The running time for different steps is set by CD087-CD094.
4) The running direction is set by CD078.
CD086
CD084
CD082
CD085
CD083
CD000
CD090
CD000
CD084
CD084
TECORP Electronics
Manual
HC1-A User
PLC Accel./Decel.time
Set range0~65535
Unit1
Factory setting0
TECORP Electronics
Manual
HC1-A User
Set parameter
120+121+125+126=99
CD080
CD081
CD082
CD083
CD084
CD085
CD086
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Unit0.01 Hz
15**
20
25
30
35
40
0.5
TECORP Electronics
Manual
HC1-A User
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Unit0.1S
10.0**
10.0
0.0
0.0
0.0
0.0
0.0
0.0
Reserved
Factory setting1
TECORP Electronics
Manual
HC1-A User
quickly and exceed the rated value level. When this happens, the
inverter will stop accelerating, until the current returns under its rated
value, will the inverter go on to accelerate.
100% current is the motor rated current. If this parameter is set for0,
stall prevention function is invalid.
CD122
Factory setting
0
When the inverter is in constant speed running, because of the
change of load and some other reasons, the current will go up. When the
current exceeds its rated value, the inverter will lower the output
frequency. When the output current returns to its normal range the
inverter will accelerate to its set frequency again.
output frequency
T
55
TECORP Electronics
Manual
HC1-A User
Reserved
Over torque detection level
Set range0200%
Unit1%
Factory setting
0
When the output current exceeds the over torque detection level and
also exceeds half of the over torque detection time (factory setting: 1.0s),
the over torque detection will begin to work, and the corresponding
multi-function contact will act. When it exceeds the set time value, the
inverter will turn into self-protection. But when this parameter is set for
0, the over torque detection will be invalid.
CD126
56
Reserved
Rated voltage
Unit: 0.1V
Factory setting:*
TECORP Electronics
Manual
HC1-A User
Rated current
Unit: 0.1A
Factory setting:*
Motor Poles
Set range0210
Unit:1
Factory setting04
Factory setting1440
Reserved
CD140
DC braking level
Set range0.020.0%
Unit0.1%
Factory setting2.0
TECORP Electronics
Manual
HC1-A User
CD141
DC braking time at starting
Set range0.025.0S
Unit0.1S
Factory setting0.0
CD142
DC braking time at stopping
Set range0.025.0
Unit0.1S
F
CD042
T
CD142
58
Factory setting0.0
TECORP Electronics
Manual
CD143
HC1-A User
Unit0.1S
Factory setting2.0
Factory setting150
0 invalid
no auto restarting after a momentary power loss
1restart by speed search
Related introduction refer to CD143
CD146
Factory setting00
TECORP Electronics
Manual
HC1-A User
voltage, etc, the inverter will have an auto reset and restart itself. If the
starting method is set as normal starting, the inverter will start in the
normal method. If the starting method is set as speed search starting, the
inverter will start in the speed search method. After restarting, if meeting
no new abnormal situation after 60 second, the parameter will return
to its set value again. If meeting new abnormal situations again and
again, and reaching the Number of auto restarting attempt, the inverter
will stop output. Only after reset can the inverter restart again. If CD147
is set for 0, the inverter will not have auto reset and restart function in
abnormal situations.
CD148
Factory setting1
0invalid
1valid
Under the situation of unstable power supply, if the voltage is too
high and the motor is running at a higher voltage than its rated, this will
cause the motor temperature to increase, the insulation to be destroyed,
and output torque to be unstable. The auto voltage regulation function
can keep the output voltage within the rated motor voltage.
When this function is set for 0 there will be fluctuation of the
output voltage.
CD149
Auto energy saving
Set range020%
Unit 1%
Factory setting 0
If this parameter is set for 0, the energy saving function is
invalid. In auto energy saving, it will run at its full voltage when
accelerating or decelerating; when in constant running it will run at the
best voltage value which is auto calculated by the load power and thus
reach the purpose of energy saving.
The Max energy saving rate can
reach30% But for those
have
frequent load changes or are almost
full loaded, this function is not
suitable.
Output voltage
100%
70%
F
60
TECORP Electronics
Manual
HC1-A User
Target Value
**
Set range:0~100.0%
Unit:1%
Factory setting:*
The target value can be set through external voltage signal or the
digital operator.100% target value is corresponding to the frequency
when the analog voltage is 10V.
PID closed-loop control is usually used in the control of processed of
no fast physical quantity changes, such as pressure control, temperature
control,etc.The feedback signal is usually taken from temperature, or
pressure translator etc.When under PID control, the feedback signal
input path is the analog current signal 4-20mA.
PID closed-loop control is valid only when the multi-function inputs
PID are open.
PID Control Diagram:
Target
value
CD150
CD151
+
VVVF
+
CD152
D
61
Feedback
TECORP Electronics
Manual
HC1-A User
Output
Before regulating
Target value
After regulating
Time
2. Decrease the
oscillation
a. decrease the
differential time (D) or
set it for 0
b. decrease the
proportional constant
(P)
CD154
TECORP Electronics
Manual
HC1-A User
Reserved
CD160
Communication identified no
Set range: 00~250
NO.
Factory setting: 00
When the inverter is set to be RS-485 Communication control. The
inverter will be set an individual identified No.
00: no communication function
01~250: inverter individual identified No.
CD161
CD162
Factory setting: 0
2: 8O1 For ASC
5: 8O1 For RTU
63
TECORP Electronics
Manual
HC1-A User
ASCII
30H
31H
32H
33H
34H
35H
36H
37H
ASCII
38H
39H
41H
42H
43H
44H
45H
46H
TECORP Electronics
Manual
HC1-A User
65
TECORP Electronics
Manual
HC1-A User
CNTR format
7
6
Jog REV
Jog
FOR/REN
STOP
REV
FOR
Run
Jog FOR
Start
DC Brake
FOR/REV
joggin
running
FOR/REV
Jog
Run
By speed search
TECORP Electronics
Manual
HC1-A User
FUNC
0 2
30H32H
LEN
0 3
30H33H
DATA
0 0 0 B B 8
30H30H30H42H42H38H
LRC
3 7
33H37H
END
CR LF
0DH0AH
Calculate LRC:
01H+02H+03H+00H+0BH+B8H=C9H,
100H-C9H=37H
so the sent data is following
3AH 30H 31H 30H 32H 30H 33H 30H 30H 30H 42H 42H 38H
33H 37H 0DH 0AH
3.2 RTU mode
QUIET
50ms
ADDR
FUNC
LEN
D(n-1)~D0
CRC
QUIET
50ms
TECORP Electronics
Manual
HC1-A User
be seat first.
7: Example:
Write 30.00Hz to inverter with address 01
command data
ADDR
FUNC
LEN
DATA
CRC
01H
02H
03H
00H 0BH B8H 7FH 0CH
Send data 01H 02H 03H 00H 0BH B8H 7FH 0CH
8: Example 2:
the following is that get CRC value with C language.
The function has two parameters
Unsigned char data the point of data buffer
Unsigned char length number of data buffer
This function will send back the CRC value with unsigned integer
format.
unsigned int crc_chk(unsigned char data unsigned char length)
int j;
unsigned int reg_crc=0xffff;
while(length)
reg_crc^=*data++;
for(j=0;j8;j++=
if(reg_crc&0x01)/*LSB(b0)=1*/
reg_crc=(reg_crc1)^0xa001;
else
reg-crc=reg_crc1;
return reg_crc;
CD163~CD167
CD168
68
Reserved
Unit: 1
Factory setting: 0
TECORP Electronics
Manual
HC1-A User
0: not display
4
1: on display
1
DC
AC
CNT
T
DC bus voltage
Output voltage
Counter
Temperature
This parameter setting can be used to choose different items to be
displayed, such as the counting,DC voltage,AC voltage and inverter
temperature,etc.Its easy for users to monitor running status and the
items are displayed in the order by switching.
Set methodbinary 4 BIT first, then be changed into decimal system.
Related introduction refer to CD078.
CD169
Software edition
Factory setting*
Only for checking and verifying.
CD172
Fault Record 1
CD173
Fault Record 2
CD174
Fault Record 3
CD175
Fault Record 4
Notemeans no fault record.
Factory setting
Factory setting
Factory setting
Factory setting
CD176
Fault cleared
**
Set range0010
Unit:1
Factory setting00
Only 01means fault cleared. Others are not valid.
69
TECORP Electronics
Manual
CD177
HC1-A User
Reserved
CD178
CD179
Manufacture date
Factory setting*
4 3
CD180
Factory setting*
This parameter is a factory setting, only for checking and verifying.
CD181~CD250
Reserved
Note: * means: this setting has several choices and it should be set
according to actual situation or condition.
** Means: this setting can be changed during run mode.
70
TECORP Electronics
Manual
HC1-A User
71
TECORP Electronics
Manual
HC1-A User
TECORP Electronics
Manual
Fault code
E.Fb.S
E.Fb.n
E.Fb.a
E.Fb.d
E.Lu.s
E.Lu.A
E.Lu.n
E.Lu.d
E.OH.S
E.OH.A
E.OH.n
E.OH.d
Content
Fuse break
Solution
Notify your supplier to check.
Low voltage
Inverter overheating
E.OT.A
E.OT.n
E.OT.d
E.bS.A
E.bS.n
E.bS.d
E.bS.S
E.bT.A
E.bT.n
E.bT.d
HC1-A User
Over torque
No feedback of the
auxiliary coil of the
electromagnetic
contactor in the
inverter
Braking transistor in Notify your supplier to check.
fault
73
TECORP Electronics
Manual
Fault code
E.EC.S
E.EC.n
E.EC.d
E.EC.A
E.EE.S
E.EE.n
E.EE.d
HC1-A User
Content
Solution
CPU fault
E2 Prom fault
Er
External Interference Isolate from the interference source
ES
Emergency Stop
In Emergency Stop Status
20
4-20mA wire broken Join the broken wires
Pr
Setting error
Correct the setting
DCb DC braking
In DC braking status
Note:Fault Code Description:
E XX Y
means: status
means: warning information
means: fault
S: in stop status
A: in accelerating status
n: in constant speed status
d: in decelerating status
Code Comparison:
A B C D E F G H O
S
Y
N L T
TECORP Electronics
Manual
HC1-A User
7) Inverter fault.
(2) The parameter can not be set:
1) Unlock the parameter lock function (CD010).
2) The inverter is in running.
3) Abnormal connection of the connectors, abnormal communication
of the digital operator. Cut off the power supply, take down the digital
operator and fit it again.
(3) The motor only rotates in FOR direction.
Reverse run prohibited is selected.
(4) If the direction of the motor rotation is reversed.
The motor output wiring is faulty. Switching two wires among U.V.W
will settle the problem.
(5) If motor deceleration is too long
1) The deceleration time setting is too long.
2) Add braking resistor.
3) Add DC brake.
(6) If the motor overheats.
1) The load is too big. Consider increasing the motor capacity.
2) The ambient temperature is too high. The motor will burn out if it
is run continuously at the rated torque in an environment in which the
maximum ambient operating temperature is exceeded. Lower the
motors ambient operating temperature.
3) The withstand voltage between the motor phases is in sufficient.
When the motor is connected to the inverter output, a surge is
generated because of the on/off of the IGBT in the and inverter.
Normally the maximum surge voltage is three times the inverters input
power supply voltage. Be sure the motor withstand voltage is high than
the maximum surge voltage.
(7) If the inverter produces interference to other devices.
1) Lower the carrier frequency.
2) Add a nose filter on the power supply input side.
3) Add a noise filter on the output side of the inverter.
4) Confirm the inverter and motor in good earth-connection status.
5) Have the wires shielded.
6) Get the main circuit wires and the control circuit wires separated.
75
TECORP Electronics
Manual
HC1-A User
(8) If the inverter detects over current when the output load is fan.
1) Get DC braking valid at starting.
2) If DC braking is already valid, please increase the DC braking
value.
(9) If there is Mechanical Vibration
1) There may be resonance between the mechanical systems
characteristic frequency and the carrier frequency.
2) There may be resonance between a machine characteristic
frequency and the output frequency of the inverter.
To prevent this, either use the jump frequency functions or install
rubber padding on the motor base to reduce vibration.
11. Peripheral devices and specification of options
11.1 Peripheral Devices
Name
Purpose and descriptions
Protect inverter wiring. Always connect a
NFB or Ground fault
breaker to the power supply line to protect
interrupter
inverter wiring. Use a ground fault
interrupter suitable for high frequencies.
Prevent burning when a Braking Resistor
Magnetic contactor
is used. Always attach a surge absorber to
the coil.
Absorb surge from the magnetic contactor
Surge absorber
and control relays.
Isolate the I/O signals of the inverter and
Isolator
is effective to reduce to interference to
other electric devices.
Used to improve the input power factor of
DC Reactor
the inverter.
Used to improve the input power factor of
AC Reactor
the inverter.
Braking resistor ,braking
Consume the regenerative energy of the
resistor unit
motor and reduce deceleration time.
76
TECORP Electronics
Manual
HC1-A User
Currency
(A)
238
291
326
395
494
557
700
800
Inductance
(mH)
0.29
0.24
0.215
0.177
0.142
0.126
0.10
0.08
Model
00D423B
0D7523B
01D523B
02D223B
0D7543B
01D543B
02D243B
03D743B
05D543B
07D543B
001143B
001543B
18D543B
002243B
003043B
003743B
004543B
005543B
Currency (A)
2.5
5
10
15
2.5
3.7
5.5
9
13
18
24
34
38
50
60
75
91
112
Inductance (mA)
4.2
2.1
1.1
0.7
8.4
2.239
2.18
1.85
1.56
1.0
0.52
0.397
0.352
0.26
0.24
0.235
0.17
0.16
77
TECORP Electronics
Manual
HC1-A User
007543B
009043B
011043B
013243B
016043B
018543B
020043B
022043B
030043B
150
180
220
265
300
360
400
560
640
0.12
0.10
0.09
0.08
0.07
0.06
0.05
0.03
0.215
400V
Class
78
Model
Currency (A)
0D7543B
01D543B
02D243B
03D743B
05D543B
07D543B
001143B
001543B
18D543B
002243B
003043B
003743B
004543B
005543B
007543B
009043B
011043B
013243B
016043B
018543B
3.0
3.0
6.3
11
16
18
28
35
40
50
63
80
60
40
35
30
20
16
13
11
Inductance
(uA)
2100
2100
1450
1100
800
650
330
250
200
180
90
80
60
40
35
30
20
16
13
11
TECORP Electronics
Manual
HC1-A User
020043B
022043B
030043B
9
8
6
9
8
6
Specifications of braking
resistor
W
80
200
100
200
300
100
300
70
80
750
300
400
300
250
400
150
500
100
1000
75
1000
50
1500
40
4800
32
4800
27.2
6000
20
9600
16
9600
13.6
12000
20/2
18000
13.6/2
18000
20/3
18000
20/3
24000
20/4
36000
13.6/4
38400
13.6/4
45000
13.6/5
48000
13.6/5
57600
13.6/6
Braking
torque
10%ED
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
Motor
power
(KW)
0.4
0.75
1.5
2.2
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
200
220
300
TECORP Electronics
Manual
HC1-A User
12 Appendices
(1) Mounting Dimensions of inverters
Model
Mounting
Dimensions
B
A
CA UTION
HCI-A
WA RNING
Do not connect ACpower to
output turbi nals( U.V.W)
Dischargi ng ti me legreater
than5 ancones.
Do not Lnspect components
unless Ins ide HARGE
lamp Is turned oft.
HC1A00D423B
HC1A01D523B
HC1A0D7543B
HC1A02D243B
10
unitmm
B
A
F
HCI-A
CAUTION
WARNING
Do not connect AC power to
output turbinals(U.V.W)
Discharging ti me l e greater
than 5 ancones.
Do not Lnspect components
unless Inside HARGE
lamp Is turned oft.
10
HC1A02D223B
HC1A03D743B
unitmm
80
TECORP Electronics
Manual
HC1-A User
B
E
HCI-A
CAUTION
High voltage Inaide
HC1A05D543B
HC1A07D543B
WARNING
Do not connect AC power to
output turbinals(U.V.W)
Discharging time le greater
than 5 ancones.
Do not Lnspect components
unl ess Inside HARGE
lamp Is turned oft.
unitmm
B
A
HCI-A
CA UTIO N
Hig h voltag e Ina ide
HC1A001143B
HC1A004543B
W AR NING
Do n ot conn ect A C pow er t o
ou tpu t t ur bina ls(U .V.W)
Disch ar ging tim e le g re ate r
th an 5 anco nes.
Do n ot Lnsp ect comp one nts
un less I nside H ARG E
lam p I s t ur ned of t.
unitmm
81
TECORP Electronics
Manual
HC1-A User
2Specifications
Model
HC1A00D423B
HC1A0D7523B
HC1A01D523B
HC1A07D543B
HC1A01D543B
HC1A02D243B
HC1A02D223B
HC1A03D743B
HC1A05D543B
HC1A07D543B
HC1A001143B
HC1A001543B
HC1A18D543B
HC1A002243B
HC1A003043B
HC1A003743B
HC1A004543B
HC1A005543B
HPA007543B
HPA009043B
HC1A011043B
HC1A013243B
HC1A016043B
82
116
125
161
170
141
128
140
238
250
157
184
200
306
318
183
182
253
437
457
241
206
277
490
510
241
239
311
490
510
241
250
341
650
670
326
10
10
300
300
450
450
768
768
800
800
350
350
16
16
16
16
500
650
868
900
400
16
16
TECORP Electronics
Manual
HC1-A User
Mounting Dimensions
54.5
58.0
FOR
REV
66.5
13.5
A ROTT
PROG
DISP
SET
RUN
STOP
13.5
HC001
70.0
FWD REV Hz
7.0
2.0
13.0
7.0
unitmm
15.3
128.0
6.3
F/R
129.6
129.0
HC002
6.3
6.2
FWD REV Hz A r/min
75.4
38.0
17.3
16.0
69.0
75.4
6.2
1.5
unitmm
83
TECORP Electronics
Manual
HC1-A User
Main frequency
Max output voltage
Factory
setting
0.00
220/400
CD002
Base frequency
50.00
CD003
Function
Function
code
CD046
CD047
CD048~
CD049
CD050
Factory
setting
Skip frequency 3
0.00
Skip frequency range
0.5
Function
Reserved
Multi-input 1
02
CD004
Medium frequency
2.50
CD051
Multi- input 2
03
CD005
8.0/13.5
CD052
Multi- input 3
10
CD006
CD007
Lowest frequency
Max operating frequency
0.50
50.00
CD053
CD054
Multi- input 4
Multi- input 5
17
18
CD008
50.00
CD055
Multi- input 6
19
CD009
CD010
CD011
0.00
0
00
CD056
CD057
CD058
Multi- output 1
Multi- output 2
Multi- output 3
01
05
02
CD012
Accel.time 1
10.0/25.0
CD059
Multi- output 4
00
CD013
Decel.time 1
10.0/25.0
CD060
Multi- output 5
CD014
Accel.time 2
50.0
CD061
0.00
CD015
Decel.time 2
50.0
CD062
CD016
Accel.time 3
100.0
CD063
CD017
Decel.time 3
100.0
CD064
Counter set
00
CD018
Accel.time 4
200.0
CD065
CD066
CD019
Decel.time 4
CD020~
CD030
200.0
Reserved
CD031
Start mode
CD068
CD032
Stop mode
CD069
CD067
0.00
0.50
0
50.00
0
CD033
CD070
CD034
Frequency command
method select
CD071
100
CD035
Carrier frequency
CD072
Up/down frunction
select
Reserved
CD036
Jog frequency
5.00
CD073~
CD075
CD037
FOR/REV select
CD076
CD038
CD077
CD039~
CD040
Reserved
CD078
84
TECORP Electronics
Manual
Function
code
Function
HC1-A User
Factory
setting
Function
code
Function
Factory
setting
CD041
Starting frequency
0.5
CD079
PLC accel./decel.time
CD042
Stopping frequency
0.5
CD080
Multi-speed2
15.00
CD043
Torque boost
2.0
CD081
Multi-speed3
20.00
CD044
CD045
Skip frequency 1
Skip frequency 2
0.00
0.00
CD082
CD083
25.00
30.00
CD084
Multi-speed6
35.00
CD146
CD085
Multi-speed7
40.00
CD147
CD086
Multi-speed8
0.50
CD148
Multi-speed4
Multi-speed5
Power loss time
allowable
Number of auto
restart attempt
Auto voltage
regulation
CD087
Timer 1
10.0
CD149
CD088
Timer 2
10.0
CD150
100%
CD089
Timer 3
0.0
CD151
5.0
CD090
Timer 4
0.0
CD152
CD091
Timer 5
0.0
CD153
Target value
CD092
Timer 6
0.0
CD154
CD093
Timer 7
0.0
CD155
100%
CD094
Timer 8
0.0
CD156
0%
CD095~
CD119
CD120
CD121
CD122
CD123
CD124
CD157~
CD159
Reserved
Stall prevention select
Stall prevention level
during accel
Stall prevention level
during running
Stall prevention level
during decek
CD160
150
CD161
CD162
150
CD163~
CD167
Reserved
CD168
CD125
CD169
1.0
CD170
CD126
CD127~
CD129
Reserved
CD130
Rated voltage
CD131
0.5
00
1
Reserved
Communication
identified no.
Baud rate of
communication
Communication
agreement
0
1
0
Reserved
Display mode
Rated voltage of the
inverter
Rated current of the
inverter
00
*
*
CD171
Software version
CD172
Fault record 1
Rated current
CD173
Fault record 2
CD132
Motor poles
04
CD174
Fault record 3
CD133
1440
CD175
Fault record 4
85
TECORP Electronics
Manual
Function
code
CD134~
CD139
Function
DC braking level
CD141
CD142
CD143
CD145
86
Factory
setting
Reserved
CD140
CD144
HC1-A User
Function
Factory
setting
CD176
Fault cleared
00
CD177
Reserved
0.0
CD178
0.0
CD179
5.0
CD180
Sequence number
150
CD181~
CD250
Reserved
2.0
Function
code