Profis Anchor 2.5.

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

1
5/16/2015

Specifier's comments:

1 Input data
Anchor type and diameter:

HIT-RE 500 + HIT-V (5.8) M16

Effective embedment depth:

hef,opti = 217 mm (hef,limit = 320 mm)

Material:

5.8

Evaluation Service Report:

ETA 04/0027

Issued I Valid:

6/26/2013 | 5/16/2018

Proof:

Design method Extended ETAG BOND (EOTA TR 029)

Stand-off installation:

eb = 0 mm (no stand-off); t = 16 mm

Anchor plate:

S 355 (St 52); E = 210000.00 N/mm2; fyk = 355.00 N/mm2; gMs = 1.100
lx x ly x t = 350 mm x 350 mm x 16 mm; (Recommended plate thickness: calculated)

Profile:

Pipe; (L x W x T) = 140 mm x 140 mm x 10 mm

Base material:

uncracked concrete, C35/45, fcc = 45.00 N/mm2; h = 500 mm, Temp. short/long: 30/30 C

Installation:

diamond cored hole, Installation condition: Dry

Reinforcement:

no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
with longitudinal edge reinforcement d >= 12

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

2
5/16/2015

2 Load case/Resulting anchor forces


5
y

Load case: Design loads


Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor
Tension force
Shear force
Shear force x
1
1.057
6.474
6.127
2
0.000
7.205
4.791
3
0.000
6.925
1.534
4
10.571
5.693
-1.756
5
29.924
3.800
-3.127
6
40.896
2.118
-1.791
7
36.956
2.900
1.466
8
20.410
4.897
4.756
max. concrete compressive strain:
0.57 []
max. concrete compressive stress:
17.23 [N/mm2]
resulting tension force in (x/y)=(-70/50):
139.813 [kN]
resulting compression force in (x/y)=(112/-76): 145.313 [kN]

6
Shear force y
2.091
5.381
6.752
5.416
2.159
-1.131
-2.502
-1.166

Tension
7

Compression
2

8
1

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN]
40.896

Capacity [kN]
52.667

Utilization bN [%]
78

Status
OK

Combined pullout-concrete cone failure**

139.813

144.941

97

OK

Concrete Breakout Strength**

139.813

154.480

91

OK

139.813

251.511

56

OK

Steel Strength*

Splitting failure**
* anchor having the highest loading

**anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN]
79.000

gM,s
1.500

NRd,s [kN]
52.667

NSd [kN]
40.896

3.2 Combined pullout-concrete cone failure


Ap,N [mm2]
328193

A0p,N [mm2]
129707

2
tRk,ucr,25 [N/mm ]
9.50

scr,Np [mm]
360

ccr,Np [mm]
180

yc
1.061

2
tRk,ucr [N/mm ]
10.08

k
3.200

yg,Np
1.922

yg,Np
1.526

ec1,N [mm]
32

yec1,Np
0.850

ec2,N [mm]
33

yec2,Np
0.844

ys,Np
1.000

N0Rk,p [kN]
109.896

NRk,p [kN]
304.376

gM,p
2.100

NRd,p [kN]
144.941

NSd [kN]
139.813

cmin [mm]

yre,Np
1.000

3.3 Concrete Breakout Strength


Ac,N [mm2]
768004

A0c,N [mm2]
423801

ccr,N [mm]
326

scr,N [mm]
651

ec1,N [mm]
32

yec1,N
0.911

ec2,N [mm]
33

yec2,N
0.907

N0Rk,c [kN]
216.579

gM,c
2.100

NRd,c [kN]
154.480

NSd [kN]
139.813

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

ys,N
1.000

yre,N
1.000

k1
10.100

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

3
5/16/2015

3.4 Splitting failure


Ac,N [mm2]
423842

A0c,N [mm2]
188356

ccr,sp [mm]
217

scr,sp [mm]
434

yh,sp
1.433

ec1,N [mm]
32

yec1,N
0.873

ec2,N [mm]
33

yec2,N
0.867

ys,N
1.000

N0Rk,c [kN]
216.579

gM,sp
2.100

NRd,sp [kN]
251.511

NSd [kN]
139.813

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

yre,N
1.000

k1
10.100

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

4
5/16/2015

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN]
7.205

Steel Strength (without lever arm)*


Steel failure (with lever arm)*
Pryout Strength*
Concrete edge failure in direction **
* anchor having the highest loading

Capacity [kN]
31.200

Utilization bV [%]
24

Status
OK
N/A

N/A

N/A

N/A

7.205

49.007

15

OK

N/A

N/A

N/A

N/A

**anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN]
39.000

VRd,s [kN]
31.200

gM,s
1.250

VSd [kN]
7.205

4.2 Pryout Strength (Bond Strength controls)


Ap,N [mm2]
43381

A0p,N [mm2]
129707

2
tRk,ucr,25 [N/mm ]
9.50

ccr,Np [mm]
180

scr,Np [mm]
360

cmin [mm]

yc
1.061

2
tRk,ucr [N/mm ]
10.08

k
3.200

k-factor
2.000

yg,Np
0.000

yg,Np
1.000

ys,Np
1.000

ec1,V [mm]
0

yec1,Np
1.000

ec2,V [mm]
0

yec2,Np
1.000

yre,Np
1.000

N0Rk,p [kN]
109.896

NRk,p [kN]
137.420

gM,c,p
1.500

VRd,c1 [kN]
49.007

VSd [kN]
7.205

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


bN
0.965

bV
0.231

a
1.000

Utilization bN,V [%]


100

Status
OK

(bN + bV) / 1.2 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk

0.000 [kN]

VSk

5.337 [kN]

dN

0.000 [mm]

dV

0.213 [mm]

dNV

0.213 [mm]

Long term loading:


NSk

0.000 [kN]

dN

0.000 [mm]

VSk

5.337 [kN]

dV

0.320 [mm]

dNV

0.320 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

5
5/16/2015

7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
Characteristic bond resistances depend on short- and long-term temperatures.
Please contact Hilti to check feasibility of HIT-V rod supply.
Edge reinforcement is not required to avoid splitting failure

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

5/16/2015

8 Installation data
Anchor plate, steel: S 355 (St 52); E = 210000.00 N/mm2; fyk = 355.00 N/mm2
Profile: Pipe; 140 x 140 x 10 mm
Hole diameter in the fixture: df = 18 mm
Plate thickness (input): 16 mm
Recommended plate thickness: calculated
Cleaning: Premium cleaning of the drilled hole is required

Anchor type and diameter: HIT-RE 500 + HIT-V (5.8) M16


Installation torque: 0.080 kNm
Hole diameter in the base material: 18 mm
Hole depth in the base material: 217 mm
Minimum thickness of the base material: 253 mm

8.1 Recommended accessories


Drilling
Diamond core rig

Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
y

175

40

175

Setting
Dispenser including cassette and mixer
Torque wrench

94

175

39

39

175

94

40

40

39

94

94

39

40

Coordinates Anchor [mm]


Anchor
1
2
3
4

x
-1
95
135
96

y
-135
-96
-1
95

c-x
-

c+x
-

c-y
-

c+y
-

Anchor
5
6
7
8

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

x
1
-95
-135
-96

y
135
96
1
-95

c-x
-

c+x
-

c-y
-

c+y
-

Profis Anchor 2.5.2

www.hilti.com.sg
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

7
5/16/2015

9 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan