Virtual Instrument Based Fault Classification in Power Transformers Using Artificial Neural Networks
Virtual Instrument Based Fault Classification in Power Transformers Using Artificial Neural Networks
Virtual Instrument Based Fault Classification in Power Transformers Using Artificial Neural Networks
S. Gopalakrishna
I.
INTRODUCTION
Power transformers are a class of very expensive and vital
components of electric power systems. The crucial objective to
mitigate the frequency and duration of unwanted outages
related to power transformer puts a high pointed demand on
power transformer protective relays to operate immaculately
and capriciously. One of the major problems associated with
the power transformer relay is the false tripping during
magnetizing inrush current. It is found that the ratio of second
harmonic to fundamental component is more in the case of
inrush than other faults [1-2]. Considering this ratio, a method
known as harmonic restraint differential protection scheme was
developed to judge whether the current is inrush or due to
internal fault. Traditionally, frequency analysis of the currents
was performed using discrete Fourier transform (DFT). But it
is well known that DFT is not accurate if the current is
contaminated by harmonics that are not integer multiples of the
fundamental, especially when the computation window is very
short and DFT only accounts for frequency analysis and
provides no information in the time domain [3]. DFT assumes
the inrush and fault currents as periodic signal, whereas inrush
and fault currents are non-stationary and non-periodic
containing both high frequency oscillations and localized
impulses superimposed on the power frequency and its
harmonics [4].
CATCON2013
2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems
external fault patterns, the fault resistance is varied from 0.1
to 100 in multiples of 10. To simulate inrush, secondary is
kept open and switching instances are varied.
Switching
circuits
3 power
transformer
Current
sensors
Transmission
line
R-L load
4
Current (A)
3 source
Table II. The wavelet analysis using db6 as the mother wavelet
is performed up to Detail 5 level for the differential current
signals of all the cases to extract the Detail coefficients. The
analysis is carried out for 20 ms during 0.1 s to 0.12 s.
Current
sensors
Differential
measurement
Display
Phase A
Phase B
Phase C
2
0
-2
-4
0
Transformer
(Y-Y connected)
Transmission Line
R-L Load
(Y connected)
Current transformers
( connected)
Current (A)
Rating
230 kV, 50Hz,
source resistance 0.8929
source inductance 16.58 mH
450 MVA, 230 kV/500 kV, 50 Hz
Winding resistance 0.02 pu
Winding reactance 0.08 pu
(for both Secondary and Primary)
Saturable core with no residual flux
100 Km
Resistance 0.01273 10-3 /m,
Inductance 0.933710-6 H/m
Capacitance 12.0410-6 F/m
0.2
Phase A
Phase B
Phase C
2
0
-2
0
0.05
0.1
Time (s)
0.15
0.2
20
Current (A)
Power Supply
(Y connected)
0.15
3 Component
0.1
Time (s)
0.05
10
Phase A
Phase B
Phase C
-10
-20
0
0.05
0.1
Time (s)
0.15
0.2
Current (A)
10
Phase A
Phase B
Phase C
-10
0
0.05
0.1
Time (s)
0.15
0.2
Current (A)
10
Phase A
Phase B
Phase C
-5
-10
0
0.05
0.1
Time (s)
0.15
0.2
CATCON2013
2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems
2
Current (A)
1
0
-1
0.1
0.105
0.11
Time (s)
0.115
0.12
Current (A)
4
2
0
-2
0.1
0.12
0.14
0.16
Time (s)
0.18
0.2
Current (A)
0.02
0.01
0
-0.01
-0.02
0.1
0.105
0.11
Time (s)
0.115
0.12
Current (A)
0.05
-0.05
0.1
0.105
0.11
Time (s)
0.115
0.12
Current (A)
0.2
0.1
0
TABLE II.
-0.1
0.4
0.2
IV.
0.105
0.11
Time (s)
0.115
0.12
Current (A)
-0.2
0.1
0
-0.2
-0.4
0.1
0.105
0.11
Time (s)
0.115
Frequency band
5 kHz-2.5 kHz
2.5 kHz-1.25 kHz
1.25 kHz-0.625 kHz
0.625 kHz - 0.3125 kHz
0.3125 kHz-0.15625 kHz
0.12
CATCON2013
2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems
used in the ANN is of sigmoid type. The training and testing
data are statistical features obtained for the three phases. The
mean, standard deviation and norm (root mean square value) of
the decomposed Detail coefficients for the three phases are
used as input data as these statistical variables are distinct and
significant as observed from the analysis and acts like principal
components.
10
Current (A)
5
0
-5
-10
0
0.05
0.1
Time (s)
0.15
0.2
0.5
0
-0.5
0.1
0.105
0.11
Time (s)
0.115
0.12
1
0.5
0
-0.5
0.1
TABLE III.
0.105
0.11
Time (s)
0.115
Name of the
event
Normal
Inrush
L-G fault (I)
L-L-G fault (I)
L-L-L-G fault (I)
L-L fault (I)
L-L-L fault (I)
L-L-L-G fault (E)
Over excitation
0.12
0.5
-0.5
0.1
0.105
0.11
Time (s)
0.115
0.12
TABLE IV.
Current (A)
-1
0.105
0.11
Time (s)
0.115
Normal
Inrush
L-G fault (I)
L-L-G fault (I)
L-L-L-G fault (I)
L-L fault (I)
L-L-L fault (I)
L-L-L-G fault (E)
Over excitation
0.12
N9
0
0
0
0
0
0
0
0
1
Name of the
event
0
-0.5
-1
0.1
-2
0.1
N1
1
0
0
0
0
0
0
0
0
0.105
0.11
Time (s)
0.115
The detail analysis of all the cases are carried out for
different mother wavelets and statistical data obtained after the
analysis are used to train and test the ANN. The performance
of ANN for different mother wavelets is given in Table V.
From Table V it is clear that Daubichies mother wavelet when
used for analysis of the transient signals give high efficiency in
discrimination of simulated cases. The Haar wavelet gives the
0.12
CATCON2013
2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems
least efficiency whereas Symlet and Coiflet wavelets
performance are better than Haar but not as good as
Daubichies.
TABLE V.
V. CONCLUSIONS
It is possible to distinguish between inrush currents
and fault currents by analyzing the ripple patterns obtained
from wavelet transforms. ANN with sigmoid activation
function is found to classify better with Detail-3 data. To show
the real time application of this method a virtual instrument in
LabVIEW is developed. The performance of trained ANN is
tested successfully for the classification of various cases. The
classification ability of the ANN in combination with advanced
signal processing technique opens the door for smart relays
power transformer protection with very less operating time and
with desirable accuracy.
Name of the
event
Normal
Inrush
L-G fault (I)
L-L-G fault (I)
L-L-L-G fault (I)
L-L fault (I)
L-L-L fault (I)
L-L-L-G fault (E)
Over excitation
REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[9]
[10]
[11]
[12]
[13]
[14]
CATCON2013