Quick Start

PowerFlex 400 Adjustable


Frequency AC Drive
FRN 4.xx
This Quick Start guide summarizes the basic steps needed to install,
start-up and program the PowerFlex 400 Adjustable Frequency AC
Drive. The information provided Does Not replace the User Manual
and is intended for qualified drive service personnel only.
For detailed PowerFlex 400 information including EMC instructions,
application considerations and related precautions refer to the
PowerFlex 400 User Manual, Publication 22C-UM001 supplied with
the drive or at www.rockwellautomation.com/literature.

General Precautions

ATTENTION: The drive contains high voltage capacitors which take


time to discharge after removal of mains supply. Before working on
drive, ensure isolation of mains supply from line inputs [R, S, T (L1,
L2, L3)]. Wait three minutes for capacitors to discharge to safe voltage
levels. Failure to do so may result in personal injury or death.
A darkened LCD display and LEDs is not an indication that capacitors
have discharged to safe voltage levels.

!
!

ATTENTION: Only qualified personnel familiar with adjustable


frequency AC drives and associated machinery should plan or
implement the installation, start-up and subsequent maintenance of the
system. Failure to comply may result in personal injury and/or
equipment damage.
ATTENTION: This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing or repairing this assembly.
Component damage may result if ESD control procedures are not
followed. If you are not familiar with static control procedures,
reference A-B publication 8000-4.5.2, Guarding Against Electrostatic
Damage or any other applicable ESD protection handbook.

English-2

!
!

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

ATTENTION: An incorrectly applied or installed drive can result in


component damage or a reduction in product life. Wiring or application
errors, such as, undersizing the motor, incorrect or inadequate AC
supply, or excessive ambient temperatures may result in malfunction of
the system.
ATTENTION: The bus regulator function is extremely useful for
preventing nuisance overvoltage faults resulting from aggressive
decelerations, overhauling loads, and eccentric loads. However, it can
also cause either of the following two conditions to occur.
1. Fast positive changes in input voltage or imbalanced input voltages
can cause uncommanded positive speed changes;
2. Actual deceleration times can be longer than commanded
deceleration times
However, a Stall Fault is generated if the drive remains in this state
for 1 minute. If this condition is unacceptable, the bus regulator must be
disabled (see parameter A187).

Mounting Considerations

Mount the drive upright on a flat, vertical and level surface.


Frame
C
D
E
F

Screw Size
M5 (#10-24)
M8 (5/16 in.)
M8 (5/16 in.)
M10 (3/8 in.)

Screw Torque
2.45-2.94 N-m (22-26 lb.-in.)
6.0-7.4 N-m (53.2-65.0 lb.-in.)
8.8-10.8 N-m (78.0-95.3 lb.-in.)
19.6-23.5 N-m (173.6-208.3 lb.-in.)

Protect the cooling fan by avoiding dust or metallic particles.


Do not expose to a corrosive atmosphere.
Protect from moisture and direct sunlight.

Maximum Surrounding Air Temperature


Frame

Enclosure Rating

IP 20/UL Open-Type

-10 to 45C (14 to 113F) Figure 1: Option A

IP 30/NEMA 1/UL Type 1(1)

-10 to 45C (14 to 113F) Figure 1: Option B

IP 20/UL Open-Type

-10 to 50C (14 to 122F) Figure 1: Option B

IP 30/NEMA 1/UL Type 1

-10 to 45C (14 to 113F) Figure 2:

D, E, F
(1)

Temperature Range

Minimum Mounting
Clearances

Frame C drives require installation of the PowerFlex 400 IP 30/NEMA 1/UL Type 1
option kit to achieve this rating.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-3

Minimum Mounting Clearances


Figure 1: Frame C Mounting Clearances
25 mm
(1.0 in.)
120 mm
(4.7 in.)

120 mm
(4.7 in.)

Mounting Option A
No clearance required
between drives.
Mounting Option B

120 mm
(4.7 in.)

120 mm
(4.7 in.)

Figure 2: Frames D, E and F Mounting Clearances

Frame D & E

Frame F
250 mm
(9.8 in.)

150 mm
(6.0 in.)

50 mm
(2.0 in.)

50 mm
(2.0 in.)

50 mm
(2.0 in.)

150 mm
(6.0 in.)

150 mm
(6.0 in.)

General Grounding Requirements


L1
R

L2
S

L3
T

Required
Input Fusing
Required Branch
Circuit Disconnect

PE

50 mm
(2.0 in.)

PE

T1
U

T2
V

T3
W

English-4

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Ungrounded Distribution Systems

ATTENTION: PowerFlex 400 drives contain protective MOVs that


are referenced to ground. These devices must be disconnected if the
drive is installed on an ungrounded or resistive grounded distribution
system.
Phase to Ground MOV Removal

Frame C

Frame E & F

R/L1
S/L2
T/L3
1

Important:
Tighten screw after
jumper removal.
Note: Frame D drives do not contain a MOV to ground connection and
are suitable for operation in both grounded and ungrounded distribution
systems without modification.

CE Conformity
Refer to the PowerFlex 400 User Manual supplied with the drive for
details on how to comply with the Low Voltage (LV) and
Electromagnetic Compatibility (EMC) Directives.
EMC Line Filters
240V 50/60 Hz 3-Phase
kW
2.2
4.0
5.5
7.5
11
15
18.5
22
30
37

HP
3.0
5.0
7.5
10
15
20
25
30
40
50

480V 50/60 Hz 3-Phase


Catalog
Number
22-RF034-CS
22-RF034-CS
22-RF034-CS
22-RF034-CS
22-RFD070
22-RFD100
22-RFD100
22-RFD150
22-RFD150
22-RFD180

kW
2.2
4.0
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110

HP
3.0
5.0
7.5
10
15
20
25
30
40
50
60
75
100
125
150

Catalog
Number
22-RF018-CS
22-RF018-CS
22-RF018-CS
22-RF018-CS
22-RF026-CS
22-RFD036
22-RFD050
22-RFD050
22-RFD070
22-RFD100
22-RFD100
22-RFD150
22-RFD180
Consult Factory
Consult Factory

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-5

Specifications, Fuses and Circuit Breakers


Drive Ratings
Output Ratings Input Ratings
Catalog
Number

Power
Dissipation

Branch Circuit Protection

Amps
140M Motor
Fuses Protectors

Voltage
kW (HP) 50C Range kVA Amps (1)

(2) (3)

Min.
Enclosure
Volume(4) IP20 Open
Contactors (in.3)
Watts

200 - 240V AC 3-Phase Input, 0 - 230V 3-Phase Output


22C-B012N103 2.2 (3.0)

12

180-265 6.5

15.5

20

140M-F8E-C16 100-C23

5098

22C-B017N103 3.7 (5.0)

17.5

180-265 8.8

21

30

140M-F8E-C25 100-C37

5098

146
207

22C-B024N103 5.5 (7.5)

24

180-265 10.9 26.1

35

140M-F8E-C32 100-C37

5098

266

22C-B033N103 7.5 (10)

33

180-265 14.4 34.6

45

140M-F8E-C45 100-C45

5098

359

22C-B049A103 11 (15)

49

180-265 21.3 51

70

100-C60

488

22C-B065A103 15 (20)

65

180-265 28.3 68

90

100-C85

650

22C-B075A103 18.5 (25) 75

180-265 32.5 78

100

100-D95

734

22C-B090A103 22 (30)

81

180-265 38.3 92

125

100-D110

778

22C-B120A103 30 (40)

120

180-265 51.6 124

175

100-D180

1055

22C-B145A103 37 (50)

130

180-265 62.4 150

200

100-D180

1200

380 - 480V AC 3-Phase Input, 0 - 460V 3-Phase Output


22C-D6P0N103 2.2 (3.0)

340-528 6.3

7.5

10

140M-D8E-C10 100-C09

5098

105

22C-D010N103 4.0 (5.0)

10.5

340-528 10.9 13

20

140M-D8E-C16 100-C16

5098

171

22C-D012N103 5.5 (7.5)

12

340-528 11.9 14.2

20

140M-D8E-C16 100-C23

5098

200

22C-D017N103 7.5 (10)

17

340-528 15.3 18.4

25

140M-D8E-C20 100-C23

5098

267

22C-D022N103 11 (15)

22

340-528 19.2 23

30

140M-F8E-C32 100-C30

5098

329

22C-D030N103 15 (20)

27

340-528 25.8 31

40

140M-F8E-C32 100-C37

5098

435

22C-D038A103 18.5 (25) 38

340-528 33.3 40

50

140M-F8E-C45 100-C60

9086

606

22C-D045A103 22 (30)

45.5

340-528 39.1 47

60

100-C60

738

22C-D060A103 30 (40)

54

340-528 53.3 64

80

100-C85

664

22C-D072A103 37 (50)

72

340-528 60.7 73

100

100-C85

1019

22C-D088A103 45 (60)

88

340-528 74.9 90

125

100-D110

1245

22C-D105A103 55 (75)

105

340-528 89

107

150

100-D140

1487

22C-D142A103 75 (100)

128

340-528 124.8 150

200

100-D180

2043

22C-D170A103 90 (125)

170

340-528 142

170

250

100-D250

2617

22C-D208A103 110 (150) 208

340-528 167

200

250

100-D250

3601

(1)
(2)
(3)

(4)

Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M
Motor Protection Circuit Breakers Application Ratings.
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.

English-6

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Category
Specification
Agency
UL
Certification
C
US

Listed to UL508C and CAN/CSA-22.2


Listed to UL508C for plenums
Certified to AS/NZS, 1997 Group 1, Class A

Protection

Electrical
Control
Control
Inputs

Control
Outputs

Marked for all applicable European Directives


EMC Directive (89/336)
EN 61800-3, EN 50081-1, EN 50082-2
Low Voltage Directive (73/23/EEC)
EN 50178, EN 60204
The drive is also designed to meet the appropriate portions of the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and
Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
Bus Overvoltage Trip:
200-240V AC Input: 405V DC bus voltage (equivalent to 290V AC
incoming line)
380-460V AC Input: 810V DC bus voltage (equivalent to 575V AC
incoming line)
Bus Undervoltage Trip:
200-240V AC Input: 210V DC bus voltage (equivalent to 150V AC
incoming line)
380-480V AC Input: 390V DC bus voltage (equivalent to 275V AC
incoming line)
Power Ride-Thru:
100 milliseconds
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical
Electronic Motor Overload
Provides class 10 motor overload protection according to NEC
Protection:
article 430 and motor over-temperature protection according to
NEC article 430.126 (A) (2). UL 508C File 29572.
Overcurrent:
180% hardware limit, 220% instantaneous fault
Ground Fault Trip:
Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output
Efficiency:
97.5% at rated amps, nominal line voltage
Output Frequency:
0-320 Hz (programmable)
Digital: Quantity:
(3) Semi-programmable
(4) Programmable
Type
Source Mode (SRC): 18-24V = ON, 0-6V = OFF
Sink Mode (SNK): 0-6V = ON, 18-24V = OFF
Analog: Quantity:
(1) Isolated, 10 to 10V or 4-20mA
(1) Non-isolated, 0 to 10V or 4-20mA
Specification
10-bit
Resolution:
0 to 10V DC Analog: 100k ohm input impedance
250 ohm input impedance
4-20mA Analog:
1-10k ohm, 2 Watt minimum
External Pot:
Relay: Quantity:
(2) Programmable Form C
Specification
Resistive Rating:
3.0A at 30V DC, 3.0A at 125V, 3.0A at 240V AC
Inductive Rating:
0.5A at 30V DC, 0.5A at 125V, 0.5A at 240V AC
(6) Optional Programmable Form A (Drive Frames D, E & F Only)
Optional Quantity:
Relay Specification
Card:
Resistive Rating:
0.1A at 30V DC Class II circuits, 3.0A at 125V,
3.0A at 240V AC
0.1A at 30V DC Class II circuits, 3.0A at 125V
Inductive Rating:
3.0A at 240V AC
(1) Programmable
Opto: Quantity:
Specification:
30V DC, 50mA Non-inductive
Analog: Quantity:
(2) Non-Isolated, 0-10V or 4-20mA
Specification
Resolution:
10-bit
0 to 10V DC Analog: 1k ohm minimum
4-20mA Analog:
525 ohm maximum

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-7

Power Wiring
Figure 3: Power Terminal Blocks
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P2

P1

DC DC+ BR+ BR

R/L1 S/L2 T/L3

R/L1S/L2T/L3

P1 P2 DC

T/L3 P1 P2
DC

Terminal (1)
R/L1, S/L2, T/L3
U/T1
V/T2
W/T3

P2, P1

DC, DC+
P2, DC
BR+, BR
(1)

U/T1 V/T2

P2 DC U/T1 V/T2 W/T3

U/T1V/T2W/T3

R/L1 S/L2 T/L3

R/L1 S/L2

P1

P1

P2

DC U/T1 V/T2 W/T3

W/T3

Description
3-Phase Input
To Motor U/T1
To Motor V/T2
=
To Motor W/T3
DC Bus Inductor Connection

Switch any two motor


leads to change
forward direction.

Drives are shipped with a jumper between Terminals


P2 and P1. Remove this jumper only when a DC Bus
Inductor will be connected. Drive will not power up
without a jumper or inductor connected.
DC Bus Connection (Frame C Drives)
DC Bus Connection (Frame D, E, and F Drives)
Not Used
Safety Ground - PE

Important: Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.

English-8

PowerFlex 400 Adjustable Frequency AC Drive Quick Start


Power Terminal Block Specifications
Frame

Maximum Wire Size (1) Minimum Wire Size (1) Recommended


Torque

8.4 mm2 (8 AWG)

33.6 mm

2 (2 AWG)

1.3 mm2 (16 AWG)

2.9 N-m (26 lb.-in.)

8.4 mm2 (8 AWG)

5.1 N-m (45 lb.-in.)

3.5 mm2 (12 AWG)

5.6 N-m (49.5 lb.-in.)

480V
33.6 mm2 (2 AWG)
37-45 kW
(50-60 HP)

240V
107.2 mm2 (4/0 AWG) 53.5 mm2 (1/0 AWG)
30-37 kW
(40-50 HP)
480V
55-75 kW
(75-100 HP)

19.5 N-m (173 lb.-in.)

152.5 mm2 (300 MCM) 85.0 mm2 (3/0 AWG)

19.5 N-m (173 lb.-in.)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations. If national or local codes require sizes outside this range, lugs may
be used.

Important: Frame C, D, and F drives utilize a finger guard over the


power wiring terminals. Replace the finger guard when
wiring is complete.
Refer to the PowerFlex 400 User Manual for maximum power cable
length recommendations.
Input Power Conditions
Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line


reactance)

Install Line Reactor(1)


or Isolation Transformer

Line has power factor correction capacitors

Install Line Reactor(1)


or Isolation Transformer

Line has frequent power interruptions


Line has intermittent noise spikes in excess of
6000V (lightning)
Phase to ground voltage exceeds 125% of
normal line to line voltage
Ungrounded distribution system
(1)

Remove MOV jumper to ground


(Frame C, E & F drives only)
or Install Isolation Transformer with
grounded secondary if necessary

Refer to the PowerFlex 400 User Manual for accessory ordering information.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-9

I/O Wiring Recommendations


Wire Type(s)

Description

Minimum
Insulation Rating

Belden 8760/9460
(or equiv.)

0.8 mm2 (18AWG), twisted pair, 100%


shield with drain. (1)

Belden 8770
(or equiv.)

0.8 mm2 (18AWG), 3 conductor, shielded for


remote pot only.

300V
60 degrees C
(140 degrees F)

(1)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

I/O Terminal Block Specifications


Frame

Maximum Wire Size (2) Minimum Wire Size (2) Torque

C, D, E, F

1.3 mm2 (16 AWG)

(2)

0.13 mm2 (26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Refer to the PowerFlex 400 User Manual for maximum control cable
length recommendations.

English-10

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Control Terminal Block


1 of 7 Digital Input Circuits

Typical
Typical
Stop/
(1)(4) SRC Wiring SNK Wiring
Function Loss

01

Start/Run FWD

02
Enable
Jumper

(4)

ENBL

Direction/Run REV

03
SNK

SRC

Digital Common

04

Digital Input 1

05

SNK

Digital Input 2

06
SRC

Digital Input 3

07

Digital Input 4

08

Digital Common

09
#1 Relay N.O.
#1 Relay Common
#1 Relay N.C.

Opto Common

10
R1

+24V

+24V DC Source

11

R2
Earth Referenced (5)
Frames D & E

R3

+10V

+10V DC Source

12

0-10V
#2 Relay N.O.
#2 Relay Common
#2 Relay N.C.

Analog Input 1 (AI1)

13

0-20mA
R4

Analog Common 1

14
0-10V

R5

Analog Output 1 (AO1)

15

R6
Isolated

0-10V
0-20mA

Analog Input 2 (AI2)

17

Analog Common 2

18

(1)

AO1

AO2

AI1

AI2

10V 20MA

10V 20MA

10V 20MA

(3)

Common

24V

RS485 Shield

20

10V 20MA

(6)

Opto Output

19

30V DC
50mA
Non-inductive

Pot must be
1-10k ohm
2 Watt Min.

Analog Output 2 (AO2)

16

0-20mA

(2)

RS485
(DSI)

Important: I/O Terminal 01 is always a coast to stop input


except when P036 [Start Source] is set to option 1 3-Wire or
6 2-W Lvl/Enbl. In three wire control, I/O Terminal 01 is
controlled by P037 [Stop Mode]. All other stop sources are
controlled by P037 [Stop Mode].
Important: The drive is shipped with a jumper installed
between I/O Terminals 01 and 11. Remove this jumper when
using I/O Terminal 01 as a stop or enable input.

P036 [Start Source]

Stop

Keypad

Per P037

I/O Terminal 01 Stop


Coast

3-Wire

Per P037

Per P037(4)

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast

(2)

Two wire control shown. For three wire control use a momentary input
on I/O Terminal 02 to command a
start. If reverse is enabled by A166, use a maintained input
for I/O Terminal 03 to change direction.

(3)

When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as
shown, to prevent damage to the output.

(4)

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing a
coast to stop without software interpretation.

(5)

Most I/O terminals labeled Common are not referenced to the safety ground (PE) terminal and are designed to
greatly reduce common mode interference. On Frame D and E drives, Analog Common 1 is referenced to
ground.

(6)

Common for Analog Input 2 (AI2). Electronically isolated from digital I/O and opto output. Not to be used with
Analog Input 1 (AI1), Analog Output 1 (AO1) or Analog Output 2 (AO2). With Analog Input 2, provides one fully
isolated analog input channel.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-11

Control I/O Terminal Designations


No. Signal

Default

Description

01

Stop (1) /
Function Loss

Coast

02

Start/Run FWD

03

Direction/Run REV

Rev Disabled

04

Digital Common

05
06
07
08
09

Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Common

Purge (2)
Local
Clear Fault
Comm Port

10

Opto Common

11

+24V DC

12

+10V DC

13

Analog Input 1

0-10V

14

Analog Common 1

15

Analog Output 1

OutFreq 0-10

16

Analog Output 2

OutCurr 0-10

17

Analog Input 2

0-10V

18

Analog Common 2

19

Opto Output

At Frequency

Factory installed jumper or a normally closed input must


be present for the drive to start.
Program with P036 [Start Source].
HAND Mode: Command comes from Integral Keypad.
AUTO Mode: I/O Terminal 02 is active.
Program with P036 [Start Source].
To enable reverse operation, program with A166
[Reverse Disable].
Program with P036 [Start Source].
For digital inputs. Tied to I/O Terminal 09.
Electronically isolated with digital inputs from analog I/O
and opto output.
Program with T051 [Digital In1 Sel].
Program with T052 [Digital In2 Sel].
Program with T053 [Digital In3 Sel].
Program with T054 [Digital In4 Sel].
For digital inputs. Tied to I/O Terminal 04.
Electronically isolated with digital inputs from analog I/O
and opto output.
For opto-coupled outputs. Electronically isolated with
opto output from analog I/O and digital inputs.
Drive supplied power for digital inputs.
Referenced to Digital Common. Max. Output: 100mA.
Drive supplied power for 0-10V external potentiometer.
Referenced to Analog Common. Max. Output: 15mA.
External 0-10V (unipolar), 0-20mA or 4-20mA input
supply or potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI1 DIP Switch to 20mA.
Program with T069 [Analog In 1 Sel].
Input Impedance: 100k ohm (Voltage Mode)
250 ohm (Current Mode)
Common for Analog Input 1 and Analog Output 1 and 2.
Electrically isolated from digital I/O and opto output.
Default analog output is 0-10V.
For current (mA) value, set AO1 DIP Switch to 20mA.
Program with T082 [Analog Out1 Sel].
Maximum Load: 4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
Default analog output is 0-10V.
For a current (mA) value, set AO2 DIP Switch to 20mA.
Program with T085 [Analog Out2 Sel].
Maximum Load: 4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
Optically isolated external 0-10V (unipolar), 10V
(bipolar), 0-20mA or 4-20mA input supply or
potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI2 DIP Switch to 20mA.
Program with T073 [Analog In 2 Sel].
Input Impedance: 100k ohm (Voltage Mode)
250 ohm (Current Mode)
For Analog Input 2. Electronically isolated from digital I/O
and opto output. With Analog Input 2, provides one fully
isolated analog input channel.
Program with T065 [Opto Out Sel].

20

RS485 (DSI) Shield

(1)
(2)

Param.
P036 (1)

P036, P037

P036, P037,
A166

T051
T052
T053
T054

P038
T069, T070,
T071, T072

P038,
T051-T054,
A152

T082, T084,
T085, T086,
T087

T073, T074,
T075, T076

T065, T066,
T068

Terminal connected to Safety Ground - PE when using


the RS485 (DSI) Communication Port.

See Footnotes (1) and (4) on previous page.


See the User Manual for Important information regarding Stop commands and the [Digital Inx Sel] Purge option.

English-12

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Relay Terminal Designations and DIP Switches


No. Signal

Default

Description

Param.

R1
R2
R3
R4
R5
R6

Ready/Fault

Ready/Fault
Motor Running

Motor Running

Normally open contact for No. 1 output relay.


Common for output relay.
Normally closed contact for No. 1 output relay.
Normally open contact for No. 2 output relay.
Common for output relay.
Normally closed contact for No. 2 output relay.

T055

Selection DIP Switches:


Analog Input (AI1 & AI2)
Analog Output (AO1 & AO2)

0-10V

Sink/Source DIP Switch

Source (SRC)

Sets analog output to either voltage or current.


Settings must match: AI1 & T069 [Analog In 1 Sel]
AI2 & T073 [Analog In 2 Sel]
AO1 & T082 [Analog Out1 Sel]
AO2 & T085 [Analog Out2 Sel]
Inputs can be wired as Sink (SNK) or Source (SRC) via DIP
Switch setting.

#1 Relay N.O.
#1 Relay Common
#1 Relay N.C.
#2 Relay N.O.
#2 Relay Common
#2 Relay N.C.

T055
T060
T060

Figure 4: User Installed Auxiliary Relay Card (Frames D, E, & F Only)

3A 3B 4A 4B 5A
5B
6A 6B 7A 7B 8A
8B

Important: If using auxiliary motor control, ensure that wiring and parameter
configuration are correct before wiring contactor outputs. All relays
on the Auxiliary Relay Card will energize on power-up by default.
Failure to verify proper wiring and parameter configuration can result
in improper motor operation or drive damage. Refer to Appendix D
for more details.
User Installed Relay Board Terminal Designations
No. Signal

Default

Description

Param.

3A
3B
4A
4B
5A
5B
6A
6B
7A
7B
8A
8B

Ready/Fault

Ready/Fault

Ready/Fault

Ready/Fault

Ready/Fault

Ready/Fault

Normally open contact for Number 3 Output Relay


Common for Number 3 Output Relay
Normally open contact for Number 4 Output Relay
Common for Number 4 Output Relay
Normally open contact for Number 5 Output Relay
Common for Number 5 Output Relay
Normally open contact for Number 6 Output Relay
Common for Number 6 Output Relay
Normally open contact for Number 7 Output Relay
Common for Number 7 Output Relay
Normally open contact for Number 8 Output Relay
Common for Number 8 Output Relay

R221

#3 Relay N.O.
#3 Relay Common
#4 Relay N.O.
#4 Relay Common
#5 Relay N.O.
#5 Relay Common
#6 Relay N.O.
#6 Relay Common
#7 Relay N.O.
#7 Relay Common
#8 Relay N.O.
#8 Relay Common

R224
R227
R230
R233
R236

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-13

Prepare For Drive Start-Up

ATTENTION: Power must be applied to the drive to perform the


following start-up procedures. Some of the voltages present are at
incoming line potential. To avoid electric shock hazard or damage to
equipment, only qualified service personnel should perform the
following procedure. Thoroughly read and understand the procedure
before beginning. If an event does not occur while performing this
procedure, Do Not Proceed. Remove All Power including user
supplied control voltages. User supplied voltages may exist even when
main AC power is not applied to the drive. Correct the malfunction
before continuing.

Before Applying Power to the Drive

1. Confirm that all inputs are connected to the correct terminals and are
secure.

2. Verify that AC line power at the disconnect device is within the rated
value of the drive.

3. Verify that any digital control power is 24 volts.


4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to
match your control wiring scheme.
Important: The default control scheme is Source (SRC). The Stop
terminal is jumpered (I/O Terminals 01 and 11) to allow
starting from the keypad. If the control scheme is changed
to Sink (SNK), the jumper must be removed from I/O
Terminals 01 and 11 and installed between I/O Terminals
01 and 04.

5. Verify that the Stop input is present or the drive will not start.
Important: If I/O Terminal 01 is used as a stop input, the jumper
between I/O Terminals 01 and 11 must be removed.

6. Verify that the Analog I/O DIP Switches are set to 10 volts.
Applying Power to the Drive

7. Apply AC power and control voltages to the drive.


8. Familiarize yourself with the integral keypad features before setting
any Program Group parameters.

Start, Stop, Direction and Speed Control


Factory default parameter values allow the drive to be controlled from
the integral keypad. No programming is required to start, stop, and
control speed directly from the integral keypad.
If a fault appears on power up, refer to page 25 for an explanation of the
fault code. For complete troubleshooting information, refer to the
PowerFlex 400 User Manual supplied with the drive.

English-14

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Intergral Keypad

Operator Keys
Key

Name
Escape
Select
Up Arrow
Down Arrow

Scroll through groups and parameters.


Increase/decrease the value of a flashing digit.

Enter

Advance one step in programming menu.


Save a change to a parameter value.

Digital Speed
Increment and
Decrement Arrows
Run/Start & Hand (1)

Used to control speed of drive. Default is active.


Control is activated by parameter P038 [Speed Reference] or
P042 [Auto Mode].
Used to start the drive. Default is Hand mode as controlled by
parameter P042 [Auto Mode].
Control is activated by parameter P036 [Start Source] or
P042 [Auto Mode].
Used to select Auto control mode.
Controlled by parameter P042 [Auto Mode].

Auto (1)

Stop/Off

(1)

Description
Back one step in programming menu.
Cancel a change to a parameter value and exit Program
Mode.
Advance one step in programming menu.
Select a digit when viewing parameter value.

Used to stop the drive or clear a fault.


This key is always active.
Controlled by parameter P037 [Stop Mode].

Important: Certain digital input settings can override drive operation. Refer to the PowerFlex 400
User Manual for details.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-15

LED Status Indicators


LED

LED State
Program Status Steady Red

Description
Indicates parameter value can be changed.
Selected digit will flash.

Fault Status

Flashing Red

Indicates that the drive is faulted.

Speed Status

Steady Green

Indicates that the digital speed control keys are


enabled.

Hand Status

Steady Green

Indicates that the Run/Start key is enabled.

Auto Status

Steady Yellow

Indicates that the drive is in Auto mode.

LCD Display

No. Description

Parameter Name
Run/Stop Status:
= Stopped /
= Running
flashes to indicate that the drive is stopping, but is still decelerating.
flashes when DC Injection is commanded.
Direction Indication: The Direction Arrow
indicates the commanded direction of
rotation. If the Arrow is flashing, the drive has been commanded to change direction, but is still
decelerating.
Sleep Mode Indication:
flashes to indicate that the drive is in sleep mode.
Parameter Group and Number:
= Basic Display
= Basic Program
= Terminal Block
= Communications
= Advanced Program
= Aux Relay Card
= Advanced Display

Fault Indication and Fault Number


Fault Name

English-16

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Keypad Hand-Off-Auto Functions


Parameter P042 [Auto Mode] defines the operation mode of the control
keys on the integral keypad. Hand-Off-Auto is the default operation
mode for PowerFlex 400 drives. For detailed information on other
operation modes, refer to the PowerFlex 400 User Manual supplied with
the drive.

Hand-Off-Auto Mode
In HAND mode:
Control keys operate as Hand-Off-Auto.
Start command and speed reference come from the integral keypad
Start/Hand and Digital Speed Increment and Decrement keys.
Auto key switches control from HAND mode to AUTO mode in a
bumpless transfer as long as there is an active Run command.
In AUTO mode:
Auto key LED is illuminated.
Start command is defined by P036 [Start Source].
Speed Reference command is defined by P038 [Speed Reference].
Start/Hand key switches control to the integral keypad in a bumpless
transfer and switches the speed reference to the integral keypad.
Stop key stops the drive and the drive switches to HAND mode.

Key

Table 4.A P042 [Auto Mode] = 1 Hnd-Off-Auto (Default)


T051-T054 [Digital Inx Sel] 2 Auto Mode or 3 Local
HAND Mode
AUTO Mode
LED Key Function
LED Key Function
On Starts drive.
On Changes to HAND Mode and Starts
drive.
Runs according to Speed Increment/
Runs according to Speed Increment/
Decrement keys.
Decrement keys.
On Changes speed.

Off Not active.


Keys are only active if P038 [Speed
Source] = 0 Drive Pot.

Off Changes to AUTO Mode.

On Not active.

N/A Stops drive.

N/A Changes to HAND Mode and Stops


drive.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-17

Viewing and Editing Parameters


The following is an example of basic integral keypad and display functions. This example provides basic
navigation instructions and illustrates how to program the first Basic Program Group parameter.
Step
Key(s)
1. When power is applied, the last user-selected
Basic Display Group parameter number is
displayed with flashing characters. The display
then defaults to that parameters current value.
(Example shows the value of b001 [Output
Freq] with the drive stopped.)
2. Press the Up Arrow or Down Arrow to scroll
through the Basic Display Group parameters.
(Only in Display Groups)

Example Displays

or

3. Press Esc once to display the Basic Display


Group parameter number shown on power-up.
The parameter number will flash.
4. Press Esc again to enter the group menu. The
group menu letter will flash.
5. Press the Up Arrow or Down Arrow to scroll
through the group menu (b, P, T, C, A and d).

or

6. Press Enter or Sel to enter a group. The right


digit of the last viewed parameter in that group
will flash.

or

7. Press the Up Arrow or Down Arrow to scroll


through the parameters that are in the group.

or

8. Press Enter or Sel to view the value of a


parameter. If you do not want to edit the value,
press Esc to return to the parameter number.

or

9. Press Enter or Sel to enter program mode to


edit the parameter value. The right digit will
flash and the Program LED will illuminate if the
parameter can be edited.

or

10. If desired, press Sel to move from digit to digit


or bit to bit. The digit or bit that you can change
will flash.
11. Press the Up Arrow or Down Arrow to change
the parameter value.
12. Press Esc to cancel a change. The digit will
stop flashing, the previous value is restored and
the Program LED will turn off.
Or
Press Enter to save a change. The digit will stop
flashing and the Program LED will turn off.
13. Press Esc to return to the parameter list.
Continue to press Esc to back out of the
programming menu.
If pressing Esc does not change the display,
then b001 [Output Freq] is displayed. Press
Enter or Sel to enter the last group menu
viewed.

or

English-18

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Basic Display Group Parameters


The Basic Program Group contains the most commonly changed parameters.
No.

Parameter

Min/Max

Display/Options

b001 [Output Freq]

0.00/[Maximum Freq]

0.01 Hz

b002 [Commanded Freq]

0.00/[Maximum Freq]

0.01 Hz

b003 [Output Current]

0.0/(Drive Amps 2)

0.1 Amps

b004 [Output Voltage]

0/510

1 VAC

b005 [DC Bus Voltage]

0/820

1 VDC

b006 [Drive Status]

0/1 (1 = Condition True)

Bit 4
Decelerating

b007 [Fault 1 Code]

0/122

b008 [Process Display]

0.00/9999.99

0.01

b010 [Output Power]

0.0/999.9 kW

0.1 kW

b011 [Elapsed MWh]

0/3276.7 MWh

0.1 MWh

b012 [Elapsed Run Time]

0/9999 Hrs

1 = 10 Hrs

b013 [Torque Current]

0.0/(Drive Amps 2)

0.1 Amps

b014 [Drive Temp]

0/120 degC

1 degC

b015 [Elapsed kWh]

0.0/100.0 kWh

0.1 kWh

Bit 3
Accelerating

Bit 2
Forward

Bit 1
Running

Smart Start-Up with Basic Program Group


The PowerFlex 400 is designed so that start up is simple and efficient. The Program Group
contains the most commonly used parameters.
= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

20/Drive Rated Volts

1 VAC

Based on Drive Rating

Set to the motor nameplate rated volts.


P032 [Motor NP Hertz]
15/320 Hz

1 Hz

60 Hz

Set to the motor nameplate rated frequency.


P033 [Motor OL Current] 0.0/(Drive Amps 2)

0.1 Amps

Based on Drive Rating

Set to the maximum allowable motor current.


P034 [Minimum Freq]
0.0/320.0 Hz

0.1 Hz

0.0 Hz

P035 [Maximum Freq]


0.0/320.0 Hz
Sets the highest frequency the drive will output.

0.1 Hz

60.0 Hz

P036 [Start Source]

0 = Keypad
1 = 3-Wire
2 = 2-Wire
3 = 2-W Lvl Sens
4 = 2-W Hi Speed
5 = Comm Port
6 = 2-W Lvl/Enbl

0 = Ramp, CF(1)
1 = Coast, CF(1)
2 = DC Brake, CF(1)
3 = DCBrkAuto,CF(1)
4 = Ramp
5 = Coast
6 = DC Brake
7 = DC BrakeAuto
(1)
Stop input also clears active fault.

P031 [Motor NP Volts]

Sets the lowest frequency the drive will output


continuously.

0/6

Sets the control scheme used to start the drive


when in Auto/Remote mode.

P037 [Stop Mode]

0/7

Active stop mode for all stop sources [e.g. keypad,


run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to
stop input except when P036 [Start Source] is set
for 3-Wire control. When in three wire control, I/O
Terminal 01 is controlled by P037 [Stop Mode].

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-19

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

P038 [Speed Reference]

0/5

P039 [Accel Time 1]

0.00/600.00 Secs

Display/Options

0 = Drive Keypad
1 = InternalFreq
Sets the source of the speed reference to the drive. 2 = Analog In 1
Important: When T051 T054 [Digital Inx Sel] is 3 = Analog In 2
set to option 1, 2, 3, 4, 5, 8, 14, 15, 16 or 17 and 4 = Preset Freq
the digital input is active, or if A152 [PID Ref Sel] is 5 = Comm Port
not set to option 0, the speed reference
commanded by this parameter will be overridden.
Refer to Chapter 1 of the PowerFlex 400 User
Manual for details.

Default
2

0.01 Secs

20.00 Secs

0.01 Secs

20.00 Secs

0 = Ready/Idle
1 = Factory Rset

Sets the rate of accel for all speed increases.


P040 [Decel Time 1]

0.00/600.00 Secs

Sets the rate of decel for all speed decreases.


P041 [Reset To Defalts]
0/1
Resets all parameter values to factory defaults.

P042 [Auto Mode]


0/3
0 = No Function
Determines the operation of the Auto key on the 1 = Hnd-Off-Auto
2 = Local/Remote
integral keypad.
3 = Auto/Manual
P043 [Motor OL Ret]
0/1
0 = Disabled
Enables/disables the Motor Overload Retention 1 = Enabled
function.

0 = Disabled

Terminal Block Group Parameters


No.

Parameter

Min/Max

Display/Options

T051 [Digital In1 Sel]


I/O Terminal 05
T052 [Digital In2 Sel]
I/O Terminal 06
T053 [Digital In3 Sel]
I/O Terminal 07
T054 [Digital In4 Sel]
I/O Terminal 08

0/36

0 = Not Used
1 = Purge
2 = Auto Mode
3 = Local
4 = Comm Port
5 = PID Disable
6 = PID Hold
7 = PID Reset
8 = Preset Freq
9 = Aux Fault
10 = Clear Fault
11 = RampStop,CF
12 = CoastStop,CF
13 = DCInjStop,CF

T055 [Relay Out1 Sel]


T060 [Relay Out2 Sel]

0/23

0 = Ready/Fault
1 = At Frequency
2 = MotorRunning
3 = Hand Active
4 = Motor Overld
5 = Ramp Reg
6 = Above Freq
7 = Above Cur
8 = Above DCVolt

T056
T058
T059
T061

0.0/9999
0.0/600.0 Secs
0.0/600.0 Secs
0.0/9999

0.1
0.1 Secs
0.1 Secs
0.1

0.0
0.0 Secs
0.0 Secs
0.0

0.1 Secs

0.0 Secs

[Relay Out1 Level]


[Relay 1 On Time]
[Relay 1 Off Time]
[Relay Out2 Level]
T060 Setting
6
7
8
9
10
12

T061 Min/Max
0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1

T063 [Relay 2 On Time]

0.0/600.0 Secs

Default
14 = Anlg1 InCtrl
15 = Anlg2 InCtrl
16 = MOP Up
17 = MOP Down
18 = Acc & Dec 2
19 = Current Lmt2
20 = Force DC
21 = Mtr I-Lock 1
22 = Mtr I-Lock 2
23 = Mtr I-Lock 3
24 = Mtr I-Lock 4
25 = Cmd Reverse
31 = Logic In 1
32 = Logic In 2
36 = Damper Input
9 = Above Anlg 2
10 = Above PF Ang
11 = Anlg In Loss
12 = ParamControl
13 = Retries Exst
14 = NonRec Fault
15 = Reverse
16 = Logic In 1
17 = Logic In 2
23 = Aux Motor

1
3
10
4

0
2

English-20
No.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start


Min/Max

Display/Options

Default

T064 [Relay 2 Off Time]


T065 [Opto Out Sel]

Parameter

0.0/600.0 Secs
0/17

0.0 Secs
1

T066 [Opto Out Level]

0.0/9999

0.1 Secs
0 = Ready/Fault
1 = At Frequency
2 = MotorRunning
3 = Hand Active
4 = Motor Overld
5 = Ramp Reg
6 = Above Freq
7 = Above Cur
8 = Above DCVolt
0.1

T065 Setting
6
7
8
9
10
12

0.0

T066 Min/Max
0/400 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1

T068 [Opto Out Logic]


T068 Option
0
1

0/1

Opto Out Logic


NO (Normally Open)
NC (Normally Closed)

T069 [Analog In 1 Sel]


T069 Option
0
1
2
4
5
6

9 = Above Anlg 2
10 = Above PF Anlg
11 = Anlg In Loss
12 = ParamControl
13 = Retries Exst
14 = NonRec Fault
15 = Reverse
16 = Logic In 1
17 = Logic In 2

0/6

Setting
Current Mode
Current Mode
Voltage Mode - Unipolar
Current Mode (Square Root)
Current Mode (Square Root)
Voltage Mode - Unipolar (Square Root)

1
Input Range
0-20 mA
4-20 mA
0-10V
0-20 mA
4-20 mA
0-10V

2
DIP Switch AI1 Setting
0-10V
0-10V
0-10V
0-10V
0-10V
0-20 mA

T070 [Analog In 1 Lo]


T074 [Analog In 2 Lo]

0.0/100.0%

0.1%

0.0%

T071
T075
T072
T076

0.0/100.0%

0.1%

100.0%

0/6

0 = Disabled
1 = Fault (F29)
2 = Stop

0/7

[Analog In 1 Hi]
[Analog in 2 Hi]
[Analog In 1 Loss]
[Analog In 2 Loss]

T073 [Analog In 2 Sel]


T073 Option
0
1
2
3
4
5
6
7

Setting
Current Mode
Current Mode
Voltage Mode - Unipolar
Voltage Mode - Bipolar
Current Mode (Square Root)
Current Mode (Square Root)
Voltage Mode - Unipolar (Square Root)
Voltage Mode - Bipolar (Square Root)

T077 [Sleep-Wake Sel]

0/3

T078
T079
T080
T081

0.0/100.0%
0.0/600.0 Secs
0.0/100.0%
0.0/600.0 Secs

[Sleep Level]
[Sleep Time]
[Wake Level]
[Wake Time]

Input Range
0-20 mA
4-20 mA
0-10V
-10 to +10V
0-20 mA
4-20 mA
0-10V
-10 to +10V

0 = Disabled
1 = Analog In 1
0.1%
0.1 Secs
0.1%
0.1 Secs

3 = Zero Ref
4 = Min Freq Ref
5 = Max Freq Ref
6 = Int Freq Ref

2
DIP Switch AI1 Setting
20 mA
20 mA
10V
10V
20 mA
20 mA
10V
10V

2 = Analog In 2
3 = Command Freq

0
10.0%
0.0 Secs
15.0%
0.0 Secs

PowerFlex 400 Adjustable Frequency AC Drive Quick Start


No.

Parameter

T082 [Analog Out1 Sel]


T085 [Analog Out2 Sel]

T083 [Analog Out1 High]


T086 [Analog Out2 High]
T083 Setting
50%
90%

Min/Max

Display/Options

Default

0/20

0
1

Output
Range
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
4-20 mA
4-20 mA
4-20 mA
4-20 mA
4-20 mA
4-20 mA
4-20 mA

Setting
0 OutFreq 0-10
1 OutCurr 0-10
2 OutTorq 0-10
3 OutVolt 0-10
4 OutPowr 0-10
5 Setpnt 0-10
6 TstData 0-10
7 OutFreq 0-20
8 OutCurr 0-20
9 OutTorq 0-20
10 OutVolt 0-20
11 OutPowr 0-20
12 Setpnt 0-20
13 TstData 0-20
14 OutFreq 4-20
15 OutCurr 4-20
16 OutTorq 4-20
17 OutVolt 4-20
18 OutPowr 4-20
19 Setpnt 4-20
20 TstData 4-20

Min. Output
Value
0V = 0 Hz
0V = 0 Amps
0V = 0 Amps
0V = 0 Volts
0V = 0 kW
0V = 0.0%
0V = 0000
0 mA = 0 Hz
0 mA = 0 Amps
0 mA = 0 Amps
0 mA = 0 Volts
0 mA = 0 kW
0 mA = 0.0%
0 mA = 0000
4 mA = 0 Hz
4 mA = 0 Amps
4 mA = 0 Amps
4 mA = 0 Volts
4 mA = 0 kW
4 mA = 0.0%
4 mA = 0000

0/800%

T082 Setting
1 OutCurr 0-10
11 OutPowr 0-20

T084 [Anlg Out1 Setpt]


T087 [Anlg Out2 Setpt]
T088 [Anlg Loss Delay]

English-21

Max. Output Value


[Maximum Frequency]
200% Drive Rated FLA
200% Drive Rated FLA
120% Drive Rated Output V
200% Drive Rated Power
100.0% Setting
65535 (Hex FFFF)
[Maximum Frequency]
200% Drive Rated FLA
200% Drive Rated FLA
120% Drive Rated Output V
200% Drive Rated Power
100.0% Setting
65535 (Hex FFFF)
[Maximum Frequency]
200% Drive Rated FLA
200% Drive Rated FLA
120% Drive Rated Output V
200% Drive Rated Power
100.0% Setting
65535 (Hex FFFF)

Filter
None
Filter A
Filter A
None
Filter A
None
None
None
Filter A
Filter A
None
Filter A
None
None
None
Filter A
Filter A
None
Filter A
None
None

DIP Switch
AO1
10V
10V
10V
10V
10V
10V
10V
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA
20 mA

Related
Parameter
b001
b003
b013
b004
b010
T084
A196
b001
b003
b013
b004
b010
T084
A196
b001
b003
b013
b004
b010
T084
A196

1%

100%

T082 Max. Output Value


5V for 200% Drive Rated Output Current
18 mA for 200% Drive Rated Power

0.0/100.0%

0.1%

0.0%

0.0/20.0 Secs

0.1 Secs

0.0 Secs

Communications Group Parameters


No.

Parameter

C101 [Language]

C102

C103

C104
C105

C106
C107
C108

Min/Max

Display/Options

1 = English
2 = Franais
3 = Espaol
4 = Italiano
5 = Deutsch
[Comm Format]
0/9
0 = RTU 8-N-1
1 = RTU 8-E-1
Power to drive must be cycled before any
2 = RTU 8-O-1
changes will affect drive operation.
3 = RTU 8-N-2
4 = RTU 8-E-2
[Comm Data Rate]
0/5
0 = 1200
1 = 2400
2 = 4800
[Comm Node Addr] 1/247
1
[Comm Loss Action] 0/5
0 = Fault
1 = Coast Stop
2 = Stop
[Comm Loss Time] 0.1/60.0 Secs
0.1 Secs
[Comm Write Mode] 0/1
0 = Save
[Start Source 2]
0/6
0 = Keypad
Sets the control scheme used to start the drive 1 = 3-Wire
2
= 2-Wire
when in Auto/Remote mode.

C109 [Speed Ref 2]

1/10

0/5

0 = Drive Keypad
1 = InternalFreq
2 = Analog In 1

Default
6 = Reserved
7 = Portugus
8 = Reserved
9 = Reserved
10 = Nederlands
5 = RTU 8-O-2
6 = MetaSys N2
7 = P1 8-N-1
8 = P1 8-E-1
9 = P1 8-O-1
3 = 9600
4 = 19.2K
5 = 38.4K
3 = Continu Last
4 = Run Preset 0
5 = Kypd Inc/Dec
1 = RAM Only
3 = 2-W Lvl Sens
4 = 2-W Hi Speed
5 = Comm Port
6 = 2-W Lvl/Enbl
3 = Analog In 2
4 = Preset Freq
5 = Comm Port

100
0

5.0 Secs
0
3

English-22

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Advanced Program Group Parameters


No.

Parameter

Min/Max

Display/Options

Default

A141
A142
A143
A144
A145
A146
A147
A148
A149
A150
A151
A152

[Purge Frequency]
[Internal Freq]
[Preset Freq 0]
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
[Accel Time 2]
[Decel Time 2]
[S Curve %]
[PID Trim Hi]
[PID Trim Lo]
[PID Ref Sel]

0.0/320.0 Hz
0.00/320.00 Hz
0.0/320.0 Hz

0.1 Hz
0.01 Hz
0.1 Hz

0.00/600.00 Secs
0.00/600.00 Secs
0/100%
0.0/320.0 Hz
0.0/320.0 Hz
0/8

0.01 Secs
0.01 Secs
1%
0.1 Hz
0.1 Hz
0 = PID Disabled
1 = PID Setpoint
2 = Analog In 1
3 = Analog In 2

5.0 Hz
60.00 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.00 Secs
30.00 Secs
20%
60.0 Hz
0.0 Hz
0

A153 [PID Feedback Sel]


A154
A155
A156
A157
A158
A159
A160
A163
A164
A165
A166
A167
A168
A169
A170

A171

0/2

4 = Comm Port
5 = Setpnt, Trim
6 = A-In 1, Trim
7 = A-In 2, Trim
8 = Comm, Trim
2 = Comm Port

0 = Analog In 1
0
1 = Analog In 2
[PID Prop Gain]
0.00/99.99
0.01
1.00
[PID Integ Time]
0.0/999.9 Secs
0.1 Secs
2.0 Secs
[PID Diff Rate]
0.00/99.99 (1/Secs)
0.01 (1/Secs)
0.00 (1/Secs)
[PID Setpoint]
0.0/100.0%
0.1%
0.0%
[PID Deadband]
0.0/10.0%
0.1%
0.0%
[PID Preload]
0.0/320.0 Hz
0.1 Hz
0.0%
[Process Factor]
0.1/999.9
0.1
30.0
[Auto Rstrt Tries]
0/9
1
0
[Auto Rstrt Delay]
0.0/160.0 Secs
0.1 Secs
1.0 Secs
[Start At PowerUp]
0/1
0 = Disabled
1 = Enabled
0
[Reverse Disable]
0/1
0 = Rev Enabled
1 = Rev Disabled
1
[Flying Start En]
0/1
0 = Disabled
1 = Enabled
0
[PWM Frequency]
2.0/8.0, 10.0 kHz
0.1 kHz
4.0 kHz
[PWM Mode]
0/1
0 = Space Vector
1 = 2-Phase
1
[Boost Select]
0/15
Settings in % of base voltage.
4
Only active when A125 [Torque Perf Mode] is 0 = Custom V/Hz
set to 0 V/Hz.
Variable Torque Constant Torque
1 = 30.0, VT
5 = 0.0, no IR
10 = 10.0, CT
2 = 35.0, VT
6 = 0.0
11 = 12.5, CT
3 = 40.0, VT
7 = 2.5, CT
12 = 15.0, CT
4 = 45.0, VT
8 = 5.0, CT
13 = 17.5, CT
9 = 7.5, CT
14 = 20.0, CT
15 = Kepco
1.1%
2.5%
[Start Boost]
0.0/25.0%

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to 0.
A172 [Break Voltage]
0.1%
0.0/100.0%
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to 0.
A173 [Break Frequency]
0.1 Hz
0.0/320.0 Hz
A174
A175
A176
A177
A178
A179
A180
A181

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to 0.
[Maximum Voltage] 20/Rated Volts
1 VAC
[Slip Hertz @ FLA] 0.0/10.0 Hz
0.1 Hz
[DC Brake Time]
0.0/99.9 Secs
0.1 Secs
[DC Brake Level]
0.0/(Drive Amps 1.5) 0.1 Amps
[DC Brk Time@Strt] 0.0/99.9 Secs
0.1 Secs
[Current Limit 1]
0.0/(Drive Amps 1.5) 0.1 Amps
[Current Limit 2]
[Motor OL Select]
0/2
0 = No Derate
1 = Min Derate
2 = Max Derate

25.0%
15.0 Hz
Rated Volts
2.0 Hz
0.0 Secs
Amps 0.05
0.0 Secs
Amps 1.1
0

PowerFlex 400 Adjustable Frequency AC Drive Quick Start


No.

Parameter

A182 [Drive OL Mode]

Min/Max

Display/Options

A195 [Reset Meters]

0 = Disabled
1 = Reduce CLim
0.0/(Drive Amps 1.8) 0.1 Amps
0.0/Drive Amps
0.1 Amps
0/9999 Secs
1 Secs
0/5
0 = 60 Seconds
1 = 120 Seconds
2 = 240 Seconds
0/1
0 = Disabled
0/320 Hz
1 Hz
0.0/30.0 Hz
0.1 Hz
0/320 Hz
1 Hz
0.0/30.0 Hz
0.1 Hz
0/320 Hz
1 Hz
0.0/30.0 Hz
0.1 Hz
0/3
0 = Disabled
1 = Electrical
0/2
0 = Ready/Idle

A196 [Testpoint Sel]


A197 [Fault Clear]

1024/65535
0/2

1
0 = Ready/Idle

A198 [Program Lock]

0/3

A199 [Motor NP Poles]


A200 [Motor NP FLA]

2/40
0.1/(Drive Amps 2)

0 = Unlocked
1 = Locked (All)
1
0.1 Amps

A183
A184
A185
A186

[SW Current Trip]


[Load Loss Level]
[Load Loss Time]
[Stall Fault Time]

A187
A188
A189
A190
A191
A192
A193
A194

[Bus Reg Mode]


[Skip Frequency 1]
[Skip Freq Band 1]
[Skip Frequency 2]
[Skip Freq Band 2]
[Skip Frequency 3]
[Skip Freq Band 3]
[Compensation]

English-23

0/3

Default
2 = Reduce PWM
3 = Both-PWM 1st

3 = 360 Seconds
4 = 480 Seconds
5 = Flt Disabled
1 = Enabled

2 = Mechanical
3 = Both
1 = Reset MWh
2 = Reset Time
1 = Reset Fault
2 = Clear Buffer

3
0.0 (Disabled)
0.0 (Disabled)
0 (Disabled)
0

1
0 Hz
0.0 Hz
0 Hz
0.0 Hz
0 Hz
0.0 Hz
3
0
1024
0

2 = Locked (Not Network) 0


3 = Locked (P035, A170)
4
Rated Amps

Aux Relay Card Group Parameters


No.

Parameter

Min/Max

Display/Options

R221
R224
R227
R230
R233
R236

[Relay Out3 Sel]


[Relay Out4 Sel]
[Relay Out5 Sel]
[Relay Out6 Sel]
[Relay Out7 Sel]
[Relay Out8 Sel]

0/23

0 = Ready/Fault
1 = At Frequency
2 = MotorRunning
3 = Hand Active
4 = Motor Overld
5 = Ramp Reg
6 = Above Freq
7 = Above Cur
8 = Above DCVolt

R222
R225
R228
R231
R234
R237

[Relay Out3 Level]


[Relay Out4 Level]
[Relay Out5 Level]
[Relay Out6 Level]
[Relay Out7 Level]
[Relay Out8 Level]

0.0/9999 Hz

0.1

[Relay OutX Select] Setting


6
7
8
9
10
12

Default
9 = Above Anlg 2
10 = Above PF Ang
11 = Anlg In Loss
12 = ParamControl
13 = Retries Exst
14 = NonRec Fault
15 = Reverse
16 = Logic In 1
17 = Logic In 2
23 = Aux Motor

0.0

[Relay OutX Level] Min/Max


0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1

R239 [Aux Motor Mode]


R240 [Aux Motor Qty]

0/1
1/6

R241 [Aux 1 Start Freq]


R244 [Aux 2 Start Freq]
R247 [Aux 3 Start Freq]

0.0/320.0 Hz

0 = Disabled
1 = 1 Aux Mtr
2 = 2 Aux Mtr
3 = 3 Aux Mtr
0.1 Hz

1 = Enabled
4 = 1 Mtr + Swap
5 = 2 Mtr + Swap
6 = 3 Mtr + Swap

0
1

50.0 Hz

English-24

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

No.

Parameter

Min/Max

Display/Options

Default

R242
R245
R248
R243
R246
R249
R250
R251
R252
R253
R254

[Aux 1 Stop Freq]


[Aux 2 Stop Freq]
[Aux 3 Stop Freq]
[Aux 1 Ref Add]
[Aux 2 Ref Add]
[Aux 3 Ref Add]
[Aux Start Delay]
[Aux Stop Delay]
[Aux Prog Delay]
[Aux AutoSwap Tme]
[Aux AutoSwap Lvl]

0.0/320.0 Hz

0.1 Hz

25.0 Hz

0.0/100.0%

0.1%

0.0%

0.0/999.9 Secs
0.0/999.9 Secs
0.00/60.00 Secs
0.0/999.9 Hrs
0.0/100.0%

0.1 Secs
0.1 Secs
0.01 Secs
0.1 Hrs
0.1%

5.0 Secs
3.0 Secs
0.50 Secs
0.0 Hr
50.0%

Advanced Display Group Parameters


No.

Min/Max

Display/Options

d301 [Control Source]

Parameter

0/99

Digit 0: Start Command


0 = Keypad
1 = Terminal Block
2 = Communications

d302 [Control In Status]

0/1
(1 = Condition True)

Display Digit (Right to Left)


0
1
2
3
4
5
6

I/O Terminal
02
03
01
05
06
07
08

Control Input
Start/FWD In
Dir/Rev In
Stop Input
Digital In 1
Digital In 2
Digital In 3
Digital In 4

d303 [Comm Status]

0/1
(1 = Condition True)

d304
d305
d306
d307
d308
d309
d310
d312
d314
d311
d313
d315
d316
d317
d318
d319
d320
d321
d322
d323
d324
d325
d326
d327

[PID Setpnt Displ]


[Analog In 1]
[Analog In 2]
[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
[Fault 1 Time-hr]
[Fault 2 Time-hr]
[Fault 3 Time-hr]
[Fault 1 Time-min]
[Fault 2 Time-min]
[Fault 3 Time-min]
[Elapsed Time-hr]
[Elapsed Time-min]
[Output Powr Fctr]
[Testpoint Data]
[Control SW Ver]
[Drive Type]
[Output Speed]
[Output RPM]
[Fault Frequency]
[Fault Current]
[Fault Bus Volts]
[Status @ Fault]

Default
Digit 1: Speed Command Read Only
0 = Local Keypad Pot
1 = A142
2 = Analog Input 1
3 = Analog Input 2
4 = A143-146
5 = Communications
Read Only

Read Only

0.0/100.0%
0.0/120.0%

Digit 0: Received Good Message Packet


Digit 1: Transmitting Message
Digit 2: DSI Peripheral Connected
Digit 3: Received Bad Message Packet
0.1%
0.1%

0/122

Read Only

0/9999 Hrs

1 Hrs

Read Only

0.0/60.0 Min

0.1 Min

Read Only

0/32767
1 Hr
0.0/60.0 Min
0.1 Min
0.0/180.0 deg
0.1 deg
0/FFFF
1 Hex
1.00/99.99
0.01
Used by Rockwell Automation field service personnel.
0.0/100.0%
0.1%
0/24000 RPM
1 RPM
0.00/320.00 Hz
0.01 Hz
0.0/(Drive Amps 2) 0.1 Amps
0/820 VDC
1 VDC
0/1
1

0.0%
0.0%

Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-25

Fault Codes
To clear a fault, press the Stop key, cycle power or set A100 [Fault Clear] to 1 or
2.
No.

Fault

Description

F2
F3
F4
F5

Auxiliary Input(1)
Power Loss
UnderVoltage(1)
OverVoltage(1)

F6

Motor Stalled(1)

F7

Motor Overload(1)

F8

Heatsink OvrTmp(1)

F12

HW OverCurrent

Check remote wiring.


Monitor the incoming AC line for low voltage or line power interruption.
Monitor the incoming AC line for low voltage or line power interruption.
Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be
caused by motor regeneration. Extend the decel time or install a dynamic brake chopper.
Increase [Accel Time x] or reduce load so drive output current does not exceed the current set
by parameter A089 [Current Limit].
An excessive motor load exists. Reduce load so drive output current does not exceed the
current set by parameter P033 [Motor OL Current].
Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded 40C
(104F) for IP 30/NEMA 1/UL Type 1 installations or 50C (122F) for Open type installations.
Check fan.
Check programming. Check for excess load, improper DC boost setting, DC brake volts set too
high or other causes of excess current.
Check the motor and external wiring to the drive output terminals for a grounded condition.
Check for load loss (i.e., a broken belt).
An analog input is configured to fault on signal loss. A signal loss has occurred.
Correct the cause of the fault and manually clear.
Check the wiring between the drive and motor. Check motor for grounded phase.
Replace drive if fault cannot be cleared.

F13
F15
F29
F33
F38
F39
F40
F41
F42
F43
F48

Ground Fault
Load Loss
Analog Input Loss(1)
Auto Rstrt Tries
Phase U to Gnd
Phase V to Gnd
Phase W to Gnd
Phase UV Short
Check the motor and drive output terminal wiring for a shorted condition.
Replace drive if fault cannot be cleared.
Phase UW Short
Phase VW Short
Params Defaulted
The drive was commanded to write default values to EEPROM. Clear the fault or cycle power to
the drive. Program the drive parameters as needed.
(1)
Check load requirements and A098 [SW Current Trip] setting.
F63 SW OverCurrent
F64 Drive Overload
Reduce load or extend Accel Time.
F70 Power Unit
Cycle power. Replace drive if fault cannot be cleared.
F71 Net Loss
The communication network has faulted.
F81 Comm Loss
If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port
expander, adapters or complete drive as required. Check connection. An adapter was
intentionally disconnected. Turn off using C105 [Comm Loss Action].
F94 Function Loss
Close input to terminal 01 and re-start the drive.
F100 Parameter Checksum Restore factory defaults.
F122 I/O Board Fail
Cycle power. Replace drive if fault cannot be cleared.
(1)

Auto-Reset/Run type fault. Configure with parameters A092 and A093.

For a complete listing of Faults and Alarms, refer to the PowerFlex 400
User Manual.

English-26

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Dimensions
PowerFlex 400 Frames
Output Power
kW
2.2-7.5
11-15
18.5-22
30-37
45-75
90-110

Frame Size
208-240V AC Input
C
D
D
E

HP
3-10
15-20
25-30
40-50
60-100
125-150

400-480V AC Input
C
C
D
E
E
F

Figure 5: PowerFlex 400 Frames C-F


IP20/66 (NEMA Type 1/4X/12)
A
D

Flange Mount
244
(9.61)

300
(11.81)

325
(12.8)

24.5
(0.96)

105.8
(4.17)

138.2
(5.44)

Dimensions are in millimeters and (inches).


Frame
C
D
E
F
(1)

A
130.0 (5.1)
250.0 (9.84)
370.0 (14.57)
425.0 (16.73)

B
260.0 (10.2)
436.2 (17.17)
605.5 (23.84)
850.0 (33.46)

C
180.0 (7.1)
206.1 (8.11)
259.2 (10.21)
264.0 (10.39)

D
116.0 (4.57)
226.0 (8.90)
335.0 (13.19)
381.0 (15.00)

E
246.0 (9.7)
383.4 (15.09)
567.4 (22.34)
647.5 (25.49)

F
5.8 (0.23)
9.0 (0.35)
8.5 (0.33)
13.0 (0.51)

Weights include HIM and Standard I/O.


EMC Line Filters
Figure 6: Catalog Numbers: 22-RF018-CS, 22-RF018-CL, 22-RF026-CS,
22-RF026-CL, 22-RF026-CL, 22-RF034-CS
32
(1.26)

17
(0.67)

130
90 (5.12)
(3.54)

60
(2.36)

297
(11.69)

309
(12.17)
297
(11.69)

30
(1.18)

5.5 (0.22)

Weight (1)
kg (lbs.)
4.33 (9.5)
14.0 (30.9)
51.2 (112.9)
88.0 (194.0)

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-27

Figure 7: Catalog Numbers: 22-RFD036, 22-RFD050, 22-RFD070, 22-RFD100,


22-RFD150, 22-RFD180
A
D

C
F

B
E

Catalog
Number

22-RFD036

74 (2.91)

272 (10.71) 161 (6.34)

60 (2.36)

258 (10.16) 7.5 (0.30)

22-RFD050

93 (3.66)

312 (12.28) 190 (7.48)

79 (3.11)

298 (11.73) 13.5 (0.53) 7 (0.28)

22-RFD070

93 (3.66)

312 (12.28) 190 (7.48)

79 (3.11)

298 (11.73) 13.5 (0.53) 7 (0.28)

22-RFD100

93 (3.66)

312 (12.28) 190 (7.48)

79 (3.11)

298 (11.73) 13.5 (0.53) 7 (0.28)

22-RFD150

126 (4.96)

312 (12.28) 224 (8.82)

112 (4.41)

298 (11.73) 19.5 (0.77) 7 (0.28)

22-RFD180

126 (4.96)

312 (12.28) 224 (8.82)

112 (4.41)

298 (11.73) 27 (1.06)

Dimensions are in millimeters and (inches).

Figure 8: Catalog Numbers: 22-RFD330


235
(9.25)
65
65
(2.56) (2.56)

386
120
(15.20) (4.72)
306
(12.05)

40
15
68
(1.57) (0.59) (2.68)

55
(2.17)
12
(2.56)

120
(4.72)

10.5
(2.56)

25
(0.98)

G
7 (0.28)

7 (0.28)

www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846

Publication 22C-QS001B-EN-P June 2013


Supersedes February 2006

Copyright 2013 Rockwell Automation, Inc. All rights reserved.