S2255053 Function Moveable Contact
S2255053 Function Moveable Contact
S2255053 Function Moveable Contact
Service Information
Contents
General 1
Parts Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Tools Required 1
Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Information 2
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 3
GENERAL
The purpose of this replacement kit is to provide the parts
and installation instructions for replacing the main movable
contacts on a QD5 Quick Drive Tap Changer.
PARTS SUPPLIED
Item
Part Number
Description
5740785B33
Qty
1
Tools Required
Description
Qty
3/8 inch drive - 3/4 inch (19 mm) deep well socket
3/8 inch drive - 7/16 inch (11 mm) deep well socket
Pliers
S225-50-53
Additional Information
These instructions cannot cover all details or variations
in the equipment, procedures, or process described nor
provide directions for meeting every possible contingency
during installation, operation, or maintenance. For
additional information, contact your representative.
Standards
ISO 9001:2000 Certified Quality Management System
Product Information
Introduction
The QD5 Main Movable Contact Replacement Kit and
installation instructions from Cooper Power Systems gives
customers the ability and guidance to replace the QD5
Main Movable Contact during maintenance cycles when
contact erosion has occurred to the point of needing
replacement.
SAFETY
FOR LIFE
SAFETY
FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around
high-voltage lines and equipment and support our Safety For Life mission.
SAFETY Information
The instructions in this manual are not intended as a
subs titute for proper training or adequate experience
in the safe operation of the equipment described.
Only competent technicians, who are familiar with this
equipment should install, operate and service it.
A competent technician has these qualifications:
n Is thoroughly familiar with these instructions.
n Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
n Is trained and authorized to energize, de-energize, clear,
and ground power distribution equipment.
n Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield, hard
hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe
installation and operation of this equipment, be sure to
read and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that
apply to this equipment. Additional statements, related to
specific tasks and procedures, are located throughout the
manual.
DANGER:
WARNING:
DANGER:
WARNING:
CAUTION:
2
2
WARNING:
WARNING:
S225-50-53
SAFETY
FOR LIFE
Installation Procedure
1. The QD5 should be secured to a bench before starting
the replacement procedure if the tap changer has been
removed from the unit.
2. The QD5 should be in the neutral position before
starting the replacement procedure. Refer to Figure
1. If the QD5 is not in the neutral position, turn the
shaft on the back of the motor shaft using a 3/8 inch
(10 mm) socket on a ratchet until the QD5 is in the
neutral position.
Remove
These Two
Bolts
Actuator
Finger
Figure 3.
Actuator Finger.
Contacts in
the Neutral
Position
Figure 1.
Neutral Position.
Flats on the
Main Shaft
Figure 4.
Main Shaft.
Molded
Panel
Neutral
Stationary
Contact
First Raise
Stationary
Contact
Removed
Main Shaft
Figure 2.
Stationary Contact.
Figure 5.
Fastening Nut for Main Shaft.
3
Movable Contact
Panel
Washer
Geneva Gear
Hub
Figure 6.
Shaft Positioning.
Figure 8.
Removal of Shaft.
Washer
Button Contacts
Figure 7.
Washer.
Figure 9.
Removal of Main Contacts.
S225-50-53
SAFETY
FOR LIFE
Button Head
Screw
Figure 10.
Movable Contact Removal from Insulating Arm and Rings.
Movable Contacts
on Stationary Neutral
Contact
Figure 12.
Installation of Movable Contacts and of Rings.
Figure 11.
Removal of Contacts.
Small Blade
Screwdriver
Button Contact
Shunt
Figure 15.
Ring and P Contacts.
Button Contact
Spring
14. Insert the threaded end of the main shaft through the
back of the molded panel, then through the movable
contact panel until the threads of the shaft are just
protruding out of the movable contact panel. Slide the
washer onto the main shaft and position it against the
movable contact panel. Refer to Figure 16.
Figure 13.
Installing Rings into P1 and P2.
Figure 16.
Installing Main Shaft.
Figure 14.
Installing Ring into P2 Contact.
S225-50-53
SAFETY
FOR LIFE
Viewing Hole in
the Steel Panel
Geneva Section
Geneva Pin
Main Shaft
Figure 19.
Viewing Hole for Geneva and Reversing Actuator.
Geneva Section
Figure 17.
Aligning Geneva Gear.
E-Clip
Washer
Figure 18.
Locating of E-Clip.
Reversing Neutral
Stationary Contact
SAFETY