Best Practice Guide For Passive Fire Protection
Best Practice Guide For Passive Fire Protection
Best Practice Guide For Passive Fire Protection
ASFP President:
Commissioner Brian Robinson CBE, QSFM, FIFireE
Association House, 99 West Street, Farnham,
Surrey GU9 7EN
www.asfp.org.uk
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Brian Wilson
Minister of State for Energy and Construction
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
CONTENTS
1 INTRODUCTION 2
1.1 Overview 2
1.2 Introduction to fire protection and Passive Fire Protection (PFP) 2
1.3 Why guidance is needed 3
1.4 The fire process 4
1.5 Design response 6
1.6 Extreme events 6
1.7 Statutory obligations, regulations, standards and accreditation 6
1.8 Other influencers 11
4 DESIGNERS 18
4.1 Who are the designers? 18
4.2 Designers and the Fire Strategy 18
4.3 Extreme events 19
4.4 Duties and responsibilities 19
4.5 Relationship between specialists 20
4.6 Understanding and applying standards 20
ii
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
iii
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
12 CEILINGS 52
18 GLOSSARY 66
iv
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The main objective of the project was to determine if problems existed in the specification and installation of
PFP systems in buildings and to analyse the reasons behind any problems, with the intention of producing
effective and feasible guidance on the use of PFP. The guidance is also intended to have the additional
benefit of providing Building Control Bodies and Fire Safety Officers with summarised, accessible, and
meaningful information that will enable them to more accurately assess the appropriateness of the passive
fire protection systems intended for the building.
The work follows the report of the Construction Task Force, chaired by Sir John Egan in 1998, and fits into
the ‘Rethinking Construction’ initiative and its three simple principles, Client leadership, integrated teams
throughout the delivery chain and respect for people. The objectives of this initiative are to achieve radical
improvements in the design, quality, sustainability, and customer satisfaction of UK construction by assisting
best practice and so providing improved life safety and best value.
The Best Practice recommendations in this Guidance are shown highlighted in this manner.
The following matrix is intended to help individual professionals find their way through this document.
D C Mf A Mg 1
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
1 INTRODUCTION
1.1 OVERVIEW
This guidance document is intended to assist all involved in the design, construction, administration,
management or inspection of buildings or structures to establish ‘Best Practice’ in the provision of Passive
PFP Section 9 Fire Protection (PFP) measures.
While primarily concerned with the safety of life and reduction of injury, PFP also provides protection for the
building fabric, contents, business operations, heritage, and the environment, by reducing fire severity.
This subject is too large and the range of materials and building elements too complex for all the details of
their correct specification, installation and use to be included in one publication. It is intended to provide a
reference document that contains basic details and direct the user to detailed sources of information on
areas of concern. Only by applying due diligences at all stages of the process is it possible that these
measures are likely to provide the expected performance.
Recommendations for fire resistance are expressed in terms of time and the ability of dividing elements
such as walls or floors to contain fire and/or maintain insulation values. Load bearing elements are
required to maintain their capacity and/or integrity for the basic framework of the building, and include
any element or service that provides an opening or passes through the walls, floors, or fire separating
elements. It is vital that these protection measures are correctly designed, specified and installed if the
building is to behave as expected should fire break out. By their nature they are ‘passive’ until there is a
fire and only then will their fire performance in-situ be demonstrated. The occupants of a building will
attend to their daily business, visitors will shop, be entertained, or enjoy recreation without any
knowledge of the PFP measures that will protect them in fire. However, it is essential that these measures
will work if an emergency occurs.
This natural fire resistance may be enhanced by the use of added materials or components that are known
by the collective term PFP. These are called passive because they do not need any special energisation or
command signal to operate, (although some systems such as dampers and certain types of doors may be
designed to operate from such methods).
PFP includes:
" Cavity barriers
" Ceiling systems
" Compartment walls
2 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
" Fire doors and furniture (eg self-closing devices, latches etc)
" Fire fighting shafts and stairwells
" Fire-resisting air transfer grilles (mechanical or intumescent)
" Fire-resisting dampers (mechanical or intumescent) used in horizontal or vertical air distribution ducts
" Fire-resisting ductwork
" Fire-resisting glazing
" Fire-resisting service ducts and shafts
" Fire-resisting walls and partitions
" Floors
" Hinged or pivoted fire doorsets (timber or steel)
" Industrial fire shutters (rolling or folding)
" Linear gap seals
" Penetration seals for pipes, cables and other services
" Structural frame fire protection
" Suspended ceilings
" Membrane ceilings (horizontal partitions)
" The building envelope, eg fire-resisting external walls, curtain walls etc.
Other elements of the building may also have a role in PFP.
Active systems all need to be actuated by a signal. Detectors will operate from heat, smoke, CO, CO2 etc.
The signal from a detector will be needed to operate any of the systems listed above. Alternatively, or in
addition, these systems will usually be operable by manual triggering, eg from a control room.
Because active systems actually do something when a fire is detected, and fires are rare and unexpected in
normal buildings, they need to be regularly tested and maintained. Apart from these comments this
guidance document will only occasionally mention Active Fire Protection.
Egan[1] The Egan report, published in 1998[1] and the earlier Latham report[2] identified the confrontational and
Latham[2] competitive situation that exists in the construction industry and the need for improvements in training and
skill levels. Research has shown that these comments have particular relevance when considering the life
safety requirements that are embodied in the installation of fire protective materials. This work has been
undertaken as part of the ‘Best Practice Programme’ of research and innovation[3] set up by Government
D C Mf A Mg 3
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
following these reports. The research has included reviewing manufacturers’ information, fire investigation
reports, inspectors’ findings, extensive industry consultation and detailed examinations of buildings.
Furthermore, the move within regulatory guidance from prescriptive rules to performance-based designs and
risk assessment during occupation put greater responsibility for safety onto construction companies and
building owners or occupiers. These notes are intended to help all concerned understand their responsibility
and fulfil the requirements.
Egan[1] The ‘Rethinking Construction’ research[1] with clients brought the following conclusion that is central to
this research:
‘Using price competition as the main criteria for selection encourages contractors to submit low
tenders to win the contract. Once contractors have secured contracts they strive to increase
profitability by applying pressure on their subcontractors to further reduce prices...’
Additionally, the initiative identified six key guidelines that are fully in line with this document and the
research findings.
1 Traditional processes of selection should be radically changed because they do not lead to best value.
2 An integrated team which includes the client, should be formed before design and maintained
throughout delivery.
3 Contracts should lead to mutual benefit for all parties and be based on a target and whole life
cost approach.
4 Suppliers should be selected by Best Value and not by lowest price; this can be achieved within EC
and central government procurement guidelines.
5 Performance measurement should be used to underpin continuous improvement within the
working process.
6 Culture and processes should be changed so that collaborative rather than confrontational working
is achieved.
These are considered to be particularly relevant in the context of PFP because of the life safety implications
which are unseen until a fire emergency arises.
4 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
A fire needs three elements; heat, fuel and air. If a fuel, a combustible material, is heated enough it will give
off volatile gases, which may ignite. If the heat from these burning gases is enough, it will cause more gases
to be given off and so the fire will grow.
A fire starts when a source of heat is brought into contact with something ignitable. Because a material is
combustible does not mean it will ignite easily. But the item ignited (eg paper) may be in contact with other
combustible materials (eg furnishings). Once a fire has started, extra heat is produced by the first item and
this can cause other items to burn. So a fire can grow very quickly, and this speed of growth is enhanced by
being in a room which can contain the heat. Fires indoors grow more quickly than fires in the open. How
the fire then develops depends on the quantity and density of combustible materials in the room or
compartment.
As the fire gets bigger, a third factor becomes important; the amount of air available. In a small room, with
all doors and windows closed, the fire will use up the air quite quickly and may go out. But in a larger room,
or where doors or windows are open, the fire will grow. The fire gets so hot that volatiles are produced
more quickly than the air can reach them. These volatiles leave through the various openings to burn outside
a compartment. Once this stage is reached the fire is very dangerous since it can spread very quickly. The
development of a fire depends on the source of ignition, quantity and layout of the material to burn, and
the air supply.
As well as heat, the fire produces products of combustion which include smoke. This is often the first killer
since it is produced in large quantities by most fires and it can spread a long way from the fire. It can be
blinding, irritant and toxic. As well as being dangerous in itself, even quite dilute smoke can hinder escape.
It is also thought that some toxic gases can affect the decision-making ability.
Some fires start off as smouldering hot spots. These fires do not grow very quickly and do not produce very
much heat, but can produce very toxic smoke. Smouldering fires may suddenly turn into real flaming fires
and grow very rapidly. They are particularly dangerous to people who are asleep.
Explosions are different from fires. Here the fuel will be mixed with air or have oxygen as part of its own
chemical composition and so the growth of the fire is very rapid; so rapid that a pressure wave may be
produced. Buildings are not normally designed to cope with explosions and neither are most PFP systems,
unless specifically called for at the design stage.
D C Mf A Mg 5
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
There can be different risks in different occupancies. Not only will the content and use of the building affect
how the fire starts and develops, but the function of the building will determine the type of people present.
People who are familiar with a building will find the exit routes more easily than those who are new to the
building, and when people are sleeping they are likely to take longer to react to an emergency than those
awake. Similarly, people who are mentally confused (for whatever reason) will be at particular risk. Partially
occupied buildings can present a problem to occupants if a fire breaks out in the unoccupied part.
In addition, facilities can be provided to assist the fire service in their efforts to extinguish or control the fire
and rescue trapped occupants.
In designing a building the designer must specify PFP materials and constructions that will limit the growth
of fire and smoke in a number of ways. These specifications will usually relate to a defined test method. (See
Section 6).
The protection requirements for such events are, at the time of writing, under review. However, materials are
available which, properly designed and implemented, could provide protection, or, at least, some protection,
against these consequential fires. This may entail significant weight and/or cost implications.
The requirement for a PFP system that must withstand a defined extreme event needs to be defined very
early in any building project.
6 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
An owner or developer has a statutory duty to notify the authorities at the following stages of a development.
" Commencement " Drains open
" Excavations " Drains on completion
" Concrete Foundations " Completion
" DPC " Occupation
" Oversite concrete/DPM
The details of inspections carried out at these specific stages (as well the level of general inspections
undertaken throughout the construction phase), are decided by the Building Control Surveyor. If an
‘Approved Inspector’ is handling the project then the approach to the regulations may be slightly
Approved different[7,8] and a developer must ensure that he understands these differences. Since there is no Statutory
[7,8]
Inspectors Duty for the building control body to inspect fire protection measures, other checks may be needed (see later).
Approved Documents for these Regulations set out recommended acceptance criteria for a wide range of
inter-related technical provisions. The needs of one provision may sometimes conflict with the needs of
[9]
AD B another and designers must be able to satisfy each provision without contravening another by doing so. Fire
TS Scot[10] protection guidance for England and Wales is contained in Approved Document B (Fire Safety) of the
TB NI [11]
Building Regulations[9], in Scotland in the Building Standards (Scotland) Regulations 1990 Technical Standards
Part D[10], and in Northern Ireland in the Northern Ireland Building Regulations, 1994 Technical Booklet E[11],
AD 7 [12]
see also the AD to Regulation 7: Materials and Workmanship[12].
See Section 8.2 Approved Document B (AD B) is broken down into building types or purpose groups and provides ‘deemed to
satisfy’ data and sources of data on the fire performance of many common construction materials and
elements of the building. Compliance with the recommendations contained within AD B will (except in unusual
circumstances) satisfy the requirements of the Building Regulations. There is however a general move by
designers away from the ‘prescriptive’ method of AD B towards performance or output-based specification.
AD B makes provision for projects as a whole or in part to be ‘fire safety engineered’ to provide alternative
solutions to those contained in the AD B. This allows the developer and his designer more freedom to innovate
in both design and functional areas. BS 7974:2001 Application of fire safety engineering principles to the
BS 7974 [13]
design of buildings – Code of practice provides guidance on the use of fire safety engineering[13].
In general the fire safety specification for a building to satisfy the regulations will only be concerned with
life safety. However there are other issues that may need to be addressed by the fire protection system.
These include; building fabric, business interruption, contents, heritage, functionality and/or
environmental protection. The building manager must be made aware where these additional criteria,
if any, have been considered.
D C Mf A Mg 7
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
FS (WP) Regs[14] Designers and Building managers will need to be aware of the Fire Safety (Workplace) Regulations[13].
The location and maintenance of the PFP within the building should form part of the risk assessment
carried out for the building under these regulations. Managers need to be aware that there may be liability
issues in the failure to comply with some regulations (eg as a criminal act). There may also be requirements
imposed by insurers.
Building managers need to be aware of the overall Fire Strategy for the building and the influences on
the fire safety measures that are contained within it.
CPD[15] These might include any Fire Safety Engineering guides or codes that apply, CE marking (see The
Construction Products Directive and the classification of products[15], applicable British Standards, Industry
CDM [16]
Standards or documentation appropriate to the Construction (Design and Management) Regulations[16].
FP Act[17] Where appropriate (eg to premises designated under the Fire Precautions Act[17]), the building will be issued
with a Building Control completion certificate.
It needs to be ensured that any future modifications to the building do not negate the effectiveness of
the system to which the certificate applies. There is also a need to be aware that the fire safety systems
within the building may interact with other systems, services or engineering facilities. The use or
maintenance of such systems should not be allowed to affect the PFP and must be considered in the
occupiers risk assessment.
The design of the PFP should take account of building life cycle issues with regard to management,
maintenance, suitability for repair and change of use.
BS 476[18] The long established test standards called for in AD B are set down in BS476, parts 3 to 11 covering
‘Reaction to Fire Tests’ and parts 20 to 24 cover ‘Fire Resistance Tests’[18]. The performance requirements are
proven by these tests and Test Reports issued by the fire test laboratory, which must carry NAMAS approval.
It is not possible to test many products in all possible uses or configurations and so Assessment Reports are
prepared to show the range of performance of the product. These are usually produced by the testing
laboratory concerned but may be produced by any suitable qualified fire specialist. Guidance on the
contents and use of such assessments is contained in the PFPF publication ‘Guide to Undertaking
PFPF[19] Assessment Reports in Lieu of Fire Tests’[19].
At the completion of the above process products are not routinely issued with a ‘Fire Certificate’, just the
test or and/or assessment reports. Fire Certification of products is purely voluntary on the part of
manufacturers. (See Section 13 for details of available schemes).
Only products which can be shown to have a fire performance that satisfies the relevant test standard(s)
should be put into the market-place. Relevant documents must be available to the user and
enforcement authorities.
8 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
In accordance with CPD, product classifications will be expressed as Euroclasses. Fire tests will be carried out
in accordance with the new European Standards, implemented as British Standards (BS EN), see Section 16
and below.
The attestation of a fire protective product against the EN product standard will usually require the
involvement of a certification body which will be responsible for checking the manufacturer’s factory
production control and selecting samples for tests. For the fire performance new European ‘reaction to fire’
BS EN 13501 [21]
and ‘fire resistance’ classification systems have been agreed (BS EN 13501[21]). These, in turn, will call up the
BS EN 1363[22] new European fire test methods (BS ENs eg BS EN 1363[22] – Fire resistance tests, BS EN 1634[23] Fire doors
BS EN 1634 [23]
and shutters), which will replace the various parts of BS 476[18] Fire tests on building materials and
BS 476[18] constructions that are currently in use.
Once test data have been obtained against a European test method this will then be acceptable across the
EU, so current systems of testing to national fire test standards will be a thing of the past. A manufacturer
can demonstrate that his/her product has undergone the relevant attestation procedures by CE marking the
product. (Whilst CE marking is not mandatory in the UK the expectation is that manufacturers of mandated
products will want CE marking in order to provide presumption of conformity, parity with competitors and
enhanced market confidence).
The fire classification (reaction to fire and/or fire resistance) will have to be clearly indicated on the
CE marking label.
For each product there will be a transition period of 1 – 2 years during which time a manufacturer can
demonstrate compliance by tests to either the British Standards (BS) or the European Standards (BS EN).
However CE marking can only be applied to those products conforming to the appropriate BS EN or which
have a European Technical Approval (ETA) issued against an ETAG. This can only be done by carrying out
tests to the BS EN standards. Test results cannot be transposed from British Standard tests to European tests
as the new tests and classification systems are different.
D C Mf A Mg 9
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Wherever possible, fire protection products should carry a relevant quality marking.
All fire protection products and systems should be supported by a relevant fire test report
and/or assessment. Although there is little restriction on the scope of use of the data, more reputable
manufacturers or suppliers will always indicate any limitations which may apply.
There are no formalised BS test procedures for fire-stopping in a linear manner or for fire protection at
service penetrations through compartment walls; only ad hoc test evidence is available under existing
BS 476 methods. BS EN standards will in future provide suitable test procedures based upon European
Technical Agreement guidelines (ETAGs).
10 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
AD B advises that fire protection materials and systems may be more reliable if supplied and/or installed
under Third Party Accreditation schemes.
Whilst European legislation does not directly cover installation, installers have an obligation to maintain the
performance of products and systems incorporated into the works so as to maintain compliance with the
Essential Requirements of the CPD.
Schemes are available for certification of installers (see Section 13) and an appropriate scheme should be
selected by the Main Contractor unless the client has already specified a scheme. The scheme should include:
" Verification of the skills and training of management, designers and estimators
" Suitable materials to be used in accordance with approved details
" Operatives and supervisors to be trained and certificated
" Random inspection of sites to monitor the quality of work
" Provision of a ‘Certificate of Conformity’ for completed work
" Provision of an audit trail
" UKAS accreditation for the scheme
Insurers may have higher requirements than Building Regulations to minimise the damage to the property and
to the business itself. In addition, the compartment area may require enhanced fire resistance to the walls and
roof within the ‘protected zone’ on each side of the compartment wall. Details are contained in the LPC
LPC [24]
Guide for the Fire Protection of Buildings, published by the Fire Protection Association, London[24].
The insurance requirements are described in the LPC Design Guide for the Fire Protection of Buildings
2000[24] and individual insurers should be contacted for advice.
1.8.2 Litigation
The use of ‘best practice’ guidance, can play a significant role where litigation is involved, for example
following a fire. The guidance here offers the opportunity for designers, builders and managers to
demonstrate, and document, their professionalism.
D C Mf A Mg 11
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
For anything more than simple designs the architectural team will seek assistance from specialists such as
structural or environmental engineers and quantity surveyors to produce a ‘Bill of Quantities’ and
specification for the project.
The next stage in this process is for construction companies to tender for the work and be appointed as the
‘Main Contractor’. Specialist sub-contractors will be sought for ‘packages’ of work and during construction
the whole project will be supervised by the design team, led by the architect who has the overall
responsibility for ensuring that the building satisfies the brief originally agreed with the client.
This system sees the contractor responsible for designing all aspects of the project to meet the performance
requirements of the client within the agreed budget.
Public Private Partnerships place risks with the party best placed to manage them. The private sector
partner puts its own capital at risk, encouraging innovation and the effective management of risks, which
helps to deliver projects on time and on budget through the lifetime of the project. Public Private
Partnerships are intended to offer better services, delivered more efficiently and thus providing better value
for money for the taxpayer.
12 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Public Private Partnerships are not a single model applied to every circumstance but rather offer a tailored
approach to the particular circumstances of public services. The Private Finance Initiative (PFI) has been the
main vehicle for delivering successful PPPs. PFI projects can only go ahead where they demonstrate clear
value for money against a ‘traditional’ procurement. This involves a comparison between the PFI proposal
and a Public Sector Comparator which estimates the costs of a ‘traditional’ procurement in which separate
arrangements will exist for the construction, maintenance and operation of a service.
Within the concept of the ‘Private Finance Initiative’ government departments and local authorities seek
companies who will provide a facility that may be a building or some other construction such as a road or
a bridge at their own expense. The cost will be met by the Main Contractor drawing funds from either the
users or the authority for the use of the facility over an agreed period of time.
In this way it is intended that the original design will meet the requirements of the client in functional terms
but will also have to be capable of being maintained over a long period within projected income limits if the
Main Contractor is to meet his cost and profit objectives from the construction and use of the facility over
the agreed period.
Where the fire strategy and compartmentation for the project has been designed and approved by
others (architects and design consultants, building control bodies, etc) the Main Contractor should ensure this
information is correctly converted into scope documents, drawings and specifications for the work.
Careful attention should be paid to the interface arrangements between the trades.
For example, it may be appropriate to include, in the PFP package, the installation of Z-bars, brackets, and
other attachments to the steel that are not part of the PFP system. The PFP Contractor can then pre-install
these items before fire protection is applied and so minimise subsequent damage. Alternatively, a similar
result may be obtained by appropriate programming of the other trades concerned.
If it is inevitable that following trades will have to remove small areas of fire protection, this should be
properly addressed in the contracts of those trades to ensure that excessive damage is not caused and
proper reinstatement of the PFP executed.
D C Mf A Mg 13
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
A developer may be the client, or a person or company who develops facilities for others to operate or own.
He/she will take responsibility for ensuring that the building meets the legal requirements but may not, in
the long term, retain ownership of the facility.
Where a developer passes ownership on to others, then they accept the responsibility for the fire
safety of the building (subject to the terms of any contract or agreement) and must ensure
compliance with all regulatory requirements at handover.
The team must be selected from qualified persons or companies and in this particular guidance the aim
is to explain how their ability to supply or install fire protection materials should be judged for best results.
Any safety objectives that go beyond life safety (ie building fabric, contents, business interruption,
heritage or environment) must be agreed with the client and specified at an early stage.
The ‘Best Practice’ in PFP will be achieved by setting out the requirements at the start of the project,
stating that that all PFP measures should, wherever possible, be installed by third party accredited installers.
This will ensure that expert companies select these life safety measures in accordance with the design
requirements whether they are laid down by the design team against the guidance contained in AD B and
Guidance [9,10,11]
its equivalent Scotland/Northern Ireland guidance[9,10,11] or to fire safety engineered designs[13].
[13]
BS 7974
The principle construction companies will be required to seek quotations from qualified contractors who in
turn will select materials from manufacturers who have adequate test evidence for their products.
At the end of the installation process Certificates of Conformity must be provided which show exactly
what has been installed and provide an audit trail for the work. This will also provide valuable information
to support the client’s acceptance of the responsibility to assess the risks in the operation of the building.
14 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The specialist contractors are required to provide full details of all materials used, their location and
purpose, for the CDM File. If an accredited installer has been used for the PFP work as recommended, this
will include a copy of a Certificate of Conformity.
Overall this is known as the CDM Regulations Safety Plan and must be handed over on completion of
the building.
The handover must also include details of the Fire Strategy that has been established for the building.
This should be considered alongside the CDM File as the building is commissioned.
The occupier will install his/her own equipment and processes. If these require mechanical fixing, wiring,
ductwork or any other services that pass around or through the building he must understand the impact on
the fire safety measures incorporated in the structure.
During this process should any of the fire protection be affected by, eg breaches of fire separating
elements or removal of structural protection, then these must be restored to their original condition.
FS (WP) Regs[14] A Risk Assessment is required by virtue of the Fire Safety (Workplace) Regulations[14] as soon as the building
is in use. This must consider if the fire safety measures provided and the fire strategy adopted are adequate
for the purposes for which the building is being used. Without the CDM File and the Strategy details this
risk assessment cannot be undertaken adequately and a failure to do so is a criminal offence under the
Workplace Regulations.
It must be assumed that the Fire Inspector may never visit the building. The occupier has responsibility for fire safety.
Advice on building handover can be found in BRE Digest 474 ‘HOBO protocol; Handover of Office Building
HOBO[25] Operations[25].
The fire safety manual is an essential part of any successful building operation. It is strongly recommended
that a manual be compiled by the designer for the occupier.
The manual needs to set out the basis on which the means of escape were planned and the type of
management organisation envisaged for running the building, also the consequential staff responsibilities.
It needs to explain the operation of all the mechanical and electrical systems and to give information on
routine testing and maintenance requirements. The fire safety manual must be available for inspection or
tests by auditors and enforcers, and for operational purposes by the fire brigade.
D C Mf A Mg 15
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
CDM[16] Depending on circumstances the manual may need to be separate from the CDM Regulations Safety Plan[16]
FPA [17]
and/or the Fire Precautions Act[17] requirements, in which case the information from these should be
duplicated in the manual. The actual form of the manual will depend on the type of occupancy involved.
Contents
The fire safety manual should include the following items:
" fire safety policy statement
" fire safety specification for the building
" a description of the passive fire safety measures
" a description of the active fire safety measures
" integration of active and passive fire safety measures
" planned inspection, maintenance and testing schedules
" CDM Regulations information
" copies of all certificates and licences
" maintenance requirements and records
" a log of the contractor’s and/or workman’s attendance
" changes to building structure
" information relating to regulatory requirements (eg Fire Prevention Certificate,
Building Regulations approvals)
" detail routine inspection and maintenance activities, with frequencies and routine test measures
" contain documentation from contractors and manufacturers (including any instructions, guarantees
and test certificates) and spare parts
" contain as-built drawings and specifications and equipment operating parameters and record
BS 1635 23 [26]
drawings in accordance with BS 1635 23[26] for all fire protection measures, both active and passive,
incorporated into the building.
The manual will form part of the information package that will contribute to the risk assessment
required under the Fire Precautions (Workplace) Regulations.
The responsible person is the employer, where there is one, and where there is not it will be the
person responsible for the activity undertaken on the premises which might give rise to a risk to
those present. It includes;
a the employer in relation to any workplace which is to any extent under his control;
b in relation to any premises where there is no employer –
i the person (whether the occupier or owner of the premises or not) who has the overall
management of the premises; or
ii where there is no one with overall management responsibility, the occupier of the premises; or
iii where neither (i) or (ii) apply, the owner of the premises
16 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Such work may necessitate bringing in a specialist for apparently minor jobs but this is preferable to allowing
any fire incident to cause unexpected damage and possibly injury.
Where the design involved Fire Safety Engineering the structure may contain features that differ from those
suggested in AD B and its equivalent Scotland/Northern Ireland guidance. Any changes in the operation or
occupation of the building can therefore have a more critical impact on the Fire Safety Strategy.
Example
An example of the changes that can have an unexpected impact on the fire safety strategy and
risk assessment is that escape distances and routes may have been calculated for the originally
proposed occupancy levels or layout. Changes in the number and type of personnel in a particular
location may negate the calculations used for the original design. Such changes may have an
impact on the passive fire protection provided for escape routes and compartments.
The responsible person must be aware of any critical areas, particularly if Fire Safety Engineering was a part
of the design process, as the calculations may limit the freedom of the occupier to make changes. This latter
point is particularly critical when a building changes ownership.
Where the occupier is responsible for part of a building, eg as the tenant of premises within a shopping
mall or large office complex the safety of those that work in or visit this part of the building must be
considered.
This may involve them in using common parts of the complex for escape in the event of fire. The safety
of these areas for access/egress should also be considered in the Risk Assessment and maintenance.
Liaison with other tenants and the building management is essential in this matter. In such premises a
Fire Safety Manual as recommended above should be in place and available to all occupiers.
D C Mf A Mg 17
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
4 DESIGNERS
4.1 WHO ARE THE DESIGNERS?
The most prominent designer in a project will be the project architect but the role and responsibilities will
vary with the procurement option chosen for the project (see Section 2). The designer of the fire protection
measures may be the architect or one of many specialists involved in sectors of the building.
In considering the list of PFP measures contained in the introduction to this document (see Section 2) it will
be realised that the design may be the result of contributions from anyone involved in producing part of
the specification of the building. Architects, structural engineers, mechanical and electrical specialists,
and sub-contractors may all have a responsibility for fire protection measures, as well as fire engineers.
Designers should be aware that the recommendations in AD B provide only a ‘life safety’ standard and they
BS 5588 24[27]
may need or wish to adopt a higher ‘best practice’ standard eg via BS 5588 24[27] series, or the LPC Design
LPC[24] Guide for the Fire Protection of Buildings[24].
The fire safety objectives (life safety, building fabric, contents, business interruption, heritage or
environment) must be specified at an early stage.
Many designers are not yet familiar with fire safety engineering and rely on normal (building) regulation
guidance, Standards and manufacturers’ claims when setting the fire rating and fire resistance for
construction elements, fire compartments, travel distances and means of escape. AD B of the Building
Regulations is broken down into building types or purpose groups and experience gained from previous
designs will inform the designer on these issues. AD B of the Building Regulations also provides ‘deemed to
satisfy’ data and sources of data on the fire rating of many common construction materials. With this
information the designer will know whether additional protection is required.
The basic fire strategy for a project should be decided at the outset of the design process. If this
recommendation is adopted, then the activities of all sectors of the process may be co-ordinated.
There is a general move by designers away from prescriptive towards performance or output-based
specification. This has been driven by, amongst other issues, the need to broaden the choice of supplier and,
in particular, the increasing complexity of buildings leading to the emergence of the specialist (sub)
contractor and supplier. As a result the final selection of a product that satisfies the performance
specification often rests with the main contractor.
Typically the supply and fix of fire protection products is by specialists. The designer will provide the
specialist with the performance requirement for the product or service such as ‘provide one hour fire
protection to all structural steel columns’. The specialist will then select a suitable material, given the
circumstances from the range of board, cementitious spray or intumescent coatings available on the
market. He/she will take into account site conditions, cost requirements, aesthetic requirements, access,
building operating conditions and many other variables. A total reliance on pure cost may not be the best
18 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
solution for service in the long-term use of the building and there is a need for a complete ‘brief’ to the
contractors if expensive problems are to be avoided.
The contractual relationship between the designer, main contractor and specialist will influence the
process for passing the specification to the specialist. However both the designer and main contractor
will anticipate the responsibility for achieving the performance being placed with the specialist best suited
for this role, and so careful scrutiny of the specialist's qualifications is essential.
Not all structures will need protection in the first place. This will depend on building types, permitted use
and the risk to occupants, bystanders, spread of fire beyond the boundary and fire and rescue personnel.
The protection requirements for such events are, at the time or writing, under review. However, materials are
available which, properly designed and implemented, could provide protection, or, at least, some protection,
against these consequential fires. It needs to be recognised that there may be significant weight and/or cost
implications from such protection.
The requirement for a passive fire protection system that must withstand a defined extreme event needs
to be specified very early in any building project.
It is the duty of everyone involved in the specification or design of an element of the building to be
aware of the fire strategy and to ensure that any element with which they are concerned complies with
the agreed strategy. Clear instructions must be given and wherever possible fire rating requirements
should be shown on drawings and in written specifications.
The consideration of fire rating or fire protection after the design of an element has otherwise been
completed may add considerable extra cost. An example of this is the design of the steel framework of a
building where the careful use of slightly varying steel member sizes or types can reduce the amount of
added fire protection required to provide the stability times for the building.
Contractors who are bidding for specialist work will require extra payments for additional fire safety
materials. Best value will not be achieved if such additions are carried out piecemeal.
All the various elements of the building must interact correctly if the maximum level of fire safety required
is to be achieved. Designers that are unsure of the reaction with other elements from this standpoint
should consult the fire strategy plans for guidance.
D C Mf A Mg 19
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Steel should be supplied prepared and painted with an appropriate priming system for selected fire
protection materials and the timing of the contract for the application/fitting of this protection is
then critical.
To apply the protection too soon can result in damage that has to be made good, whilst leaving the steel in
primer too long could result in corrosion and/or delays to other fitting out trades.
The steel designer should consider the added protection as noted above and plans can then be made for
the incorporation of the whole process in the programme.
Similarly, there will be many individual cable, pipe and ductwork penetrations within a service duct or above
suspended ceilings, for example. It is wasteful to have each penetration sealed by the tradesman concerned
only to have a later trade destroy the work as they fit their particular service.
These individual trades should be trained to fit fire-rated penetration sealing systems, or have sufficient
experience to price the fire protection work correctly. A far better job will result, often at lower overall
cost if the Mechanical and Electrical designer recognises the areas where untrained or inexperienced
trades may be working and prepares the specification accordingly to allow specialist contractors to price
for the work.
It should be part of the overall planning that the fire strategy is included as part of the work programme.
The designers of all sections of any building must ensure that they are familiar with the fire safety
standards that apply not only to their speciality but also to any other sectors that are likely to
interact. Guidance on the various standards and codes of practice are contained in the reference section
(Section 16) of this document.
20 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Main Contractors should select sub-contractors who carry Third Party Accreditation wherever possible (see
Section 13). As a very minimum, site labour involved in activities concerned with fire protection should hold
a CSCS (Construction Skills Certification Scheme) blue card in PFP installation (Section 17) for the work being
undertaken.
Sub-contractor workers must be properly supervised and their work individually inspected as the CSCS
card scheme does not cover supervision and inspection directly.
As the objective of PFP material installation is to protect the life of the building occupants the work
should not be allocated to contractors for whom it is an add-on function.
It may be desirable to group as much as possible of such work under one contract and the detailed
sections where PFP is required are set out in Section 1.
By placing this work with specialists, and with careful programming, it is possible to ensure that the correct
materials are specified and installed, and damage and rework can be avoided. Other trades will then be free
to perform their own speciality.
D C Mf A Mg 21
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
" Ensure that the PFP Contractor is not required to carry out difficult or dirty work above or adjacent to
sensitive equipment or materials
" Ensure that barriers, segregated areas, screens and protection are installed correctly
" Plan work by other trades to be carried out in advance where possible to minimise subsequent damage
" Ensure hoists, cranes etc are available for the delivery of materials and to move equipment
" Allow the PFP Contractor sufficient time to complete the work before the area is handed over to other
trades
A final round of inspection is recommended before areas are handed over for closing up, or access is
finally removed. The re-inspection will check for damage that may have occurred after the work was
originally approved. If there is only a limited amount of damage it is sometimes convenient to carry out the
final inspection jointly with all concerned parties, and with a repair team in attendance to carry out minor
repairs on the spot.
A systematic approach to quality checks and inspection will take the following form:
" The PFP operative will carry out a self check and rectify any defects. For structural fire protection
this check may not be recorded, but for fire seals the PFP operative should affix a label giving
details of the seal type, date of installation and the name of the operative.
" The Contractor’s supervisor (or quality checker) will check the work, using an agreed check list and
record sheet. For fire seals, the supervisor will countersign the label.
" If the Contractor’s supervisor finds the installation is satisfactory, the PFP Contractor will ask the
inspection agency to inspect the work. This refers to an inspection agency (see Section 10.2) rather
than a third party accreditation organisation as discussed in Sections 13 and 10.3.
" Following the inspection by the inspection agency the PFP Contractor will offer the work for the
Main Contractor to check. Depending on project specific arrangements, the Main Contractor may
invite the Architect and/or the enforcing authority (eg Building Control) to inspect.
" The formality with which this process is followed depends on the scale of the project and the
working relationships. Some of the steps above can be taken simultaneously provided there is a
consistently good standard of work being offered.
It must be borne in mind that the occupier must produce a risk assessment once control of the building is
handed over, and should it be found that fire protection measures are inadequate or badly installed he/she
will have a legal claim against the construction company. The occupier cannot assume that the building, at
hand over, is safe and must not wait for a Fire Inspector to check the premises. Under the Fire Safety
[14]
FS (WP) Regs (Workplace) Regulations[14] full responsibility for these matters rests with the occupier and criminal sanctions
apply if the duty is not fulfilled. The contractual responsibility must be accepted and due care taken to
ensure compliance with the accepted design.
22 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Materials may be supplied either direct to the contractor or through distributors. In some specialist cases,
eg certain types of fire doors or fire rated ductwork, the manufacturer may also be the installer. The
manufacturers of materials and material systems will usually offer advice on the selection of a suitable
material and methods of application.
Product literature must show the correct use of the materials and the range of their test evidence,
together with any certification that may exist for the product to allow designers or contractors to select
the correct product for his/her needs. Vague usage claims should be questioned as the product test evidence
may limit the extended application of the product and result in an unsafe application if not made clear.
Suppliers may also offer advice on the selection of suitable materials and methods of application provided
that they have been adequately trained by a suitable authority to do so.
Suppliers must be able to provide clients with product literature which shows the correct use of the materials
and the range of their test evidence, together with any certification that may exist for the product to allow
designers or contractors to select the correct product for his/her needs. It is recommended that clients contact the
manufacturers direct for confirmation that the materials or systems are correctly installed. As above for
manufacturers, vague usage claims from suppliers who are not the manufacturers of a product must be
treated with caution and verified.
Some manufacturers will provide site advisory personnel, at no extra cost, to ensure that queries and/or
inappropriate use of their materials is minimised and ultimately eradicated. The personnel may carry out
checks on the materials, application, installation, thickness and all aspects of the work to ensure that this is
in line with their test evidence.
D C Mf A Mg 23
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
This direct advice from the manufacturing company is commended since it should provide both designer
and contractors with reassurance concerning the correct use of the products.
The attestation of a fire protective product against the Technical Specification (Harmonised European Product
Standard or European Technical Approval Guideline,) for critical, regulated products such as PFP, will require
the involvement of a certification body which will be responsible for inspecting and auditing the
manufacturer’s factory production control, selecting samples and conducting type tests. For the fire
performance new European reaction to fire and fire resistance classification systems have been agreed
BS EN 13501 [21]
(BS EN 13501 Parts 1 and 2[20]). These, in turn, will call up the new European fire test methods which will
BS 476[18] replace the various parts of BS 476[18]. A full list of BS ENs is given in Section 16.
Once test data classification and attestation has been obtained against a European test method, providing all
the requirements of the technical specification have been followed, they will then be acceptable across the
EU, so current systems of testing to individual national fire test standards will be a thing of the past.
CE marking, or at least compliance with Construction Product Regulations, is applicable to products and
systems which are the subject of Regulation. For PFP the method of attesting conformity involves
certification of products by an independent third party certification body. The fire classification (reaction to
fire and/or fire resistance) will have to be clearly indicated on the CE marking label.
For each product there will be a transition period of 1–2 years during which a manufacturer can demonstrate
compliance by either the BS route or BS EN route. But after the end of this transitional period, compliance can
only be demonstrated against the BS ENs, and this can only be done by carrying out tests. Test results cannot
be transposed from BS to BS EN as the new tests are substantially different. (See Section 1.7.4).
24 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
As stated in AD B (Use of Guidance; Materials and Workmanship - Independent certification schemes and
Appendix A), the membership of a Third Party Certification scheme will give the user reassurance that this
requirement is being met even before the EU system is in regular use in the UK.
From AD B
‘Use of Guidance; Materials and Workmanship – Independent certification schemes: There
are many UK product certification schemes. Such schemes certify compliance with the
requirements of a recognised document which is appropriate to the purpose for which the
material is to be used. Materials which are not so certified may still conform to a relevant
standard. Many certification bodies which approve such schemes are accredited by UKAS.
Since the fire performance of a product, component or structure is dependent upon satisfactory
site installation and maintenance, independent schemes of certification and registration of
installers and maintenance firms of such will provide confidence in the appropriate standard of
workmanship being provided.’
The manufacturer will make the classification documents for the product available to specifiers, users and
any appropriate authority. Product data sheets and product safety information are available to assist the user
in complying with the requirements of CDM regulations.
It is essential to ensure that all advice given is accurate and practical. It is recommended that the
manufacturer be encouraged to provide as much information as possible to ensure that the materials are
correctly used.
D C Mf A Mg 25
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Also with authority to enforce regulations, during the occupation stage, is the Fire Authority for the
geographical location and in certain buildings (at the time of writing this guidance document) a Fire
Certificate will be required for designated premises. Even where this is the case the occupier should note
that this does not negate the responsibility to produce a risk assessment under the Fire Precautions
FS (WP) Regs[14] (Workplace) Regulations[14]. The enforcement responsibility passes to the Fire Authority who are responsible
for ensuring compliance with the Fire Protection Regulations once the building is handed over.
It is recognised that, other than during construction and major change, inspections by the building control
bodies or enforcers may be infrequent and/or superficial. But there is always the possibility that an inspector
may probe further. The potential is therefore present for an unforeseen loss of use of a building, or an
element of a building, if deemed unsafe. Additionally, in an ever more protective culture, the risk of
prosecution for breaches of regulation is a real prospect.
Through the development or adoption of maintenance strategies for passive fire protection building
owners and users can mitigate all manner of such tangible risks.
26 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Within the document, buildings are split according to type with the following main sectors:
" Residential (Domestic), Flats or Dwelling Houses " Assembly and Recreation
" Residential, Institution or Other " Industrial
" Office " Storage and Other Non-residential
" Shop and Commercial including Car Parks
By demonstrating compliance with AD B a developer is ‘deemed to have satisfied’ the Building Regulations
although alternatives are available through Fire Safety Engineering of the whole or parts of the construction. The
periods of loadbearing capacity, integrity and/or insulation may be provided by using materials that themselves
have the required characteristics, or comply by the addition of ‘Built-in fire protection’ using PFP materials.
Fire Safety Engineering is the application of scientific and engineering principles, rules (Codes), and expert
judgement, based on an understanding of the phenomena and effects of fire and of the reaction and behaviour
of people to fire, to protect people, property and the environment from the destructive effects of fire.
Built-in fire protection is also important to ensure that the fire resistance of purpose-made shafts is provided
and usefully maintained. These shafts may contain building services or fuel lines within buildings.
A protected shaft is defined as ‘a shaft which enables persons, air or objects to pass from one
compartment to another, and which is enclosed in fire-resisting construction’.
D C Mf A Mg 27
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
It is therefore recommended that only a limited and controlled number of parties be authorised to change
the specification and that any changes to the specification be carefully monitored and recorded.
BS 5950[30] Alternative Fire Safety Engineered design solutions may be found in BS 5950 Part 8[30}.
Invariably, paint or spray on systems will need to ensure that the steel surface is suitably prepared and
primed for the material being applied, the steel temperature at the time of the PFP application should be
3oC above the Dew Point to assist good adhesion and avoid surface moisture which could adversely affect
the adhesion of the applied coat. Such systems will usually follow the profile of the steel member, but
‘boxed’ systems are available for some cementitious sprays reinforced by wire mesh.
Intumescent systems are thin by comparison with other sprayed protection systems. The film thickness required
will be advised by the manufacturer and will vary with the material, function and size of the steel section
requiring treatment. Accurate definition and measurement of the required thickness is vital to provide the
performance specified. A top coat may be required either for long term protection or for a decorative finish.
By contrast most board protection systems are usually applied in a ‘boxed’ form and use less surface area
as a result.
28 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Only approved and tested fixing systems are acceptable for boards. The form of the joints needs particular
attention to avoid gaps. Some joints require fire-resisting glues/adhesives to achieve the required fire
performance.
Where these fire protection systems abutt profiled decking used in the floor construction the fire protection
period/system type will dictate whether the re-entrant profiles need fire stopping or not. Where such profiles
are used above a fire rated partition or wall they will require fire stopping
Good practice developed by the Steel Construction Institute and the ASFP has offered the designer a
choice of solutions to this problem and details are contained in ‘Fire Protection for Structural Steel in
ASFP[29] Buildings’ from the ASFP[29].
Concrete frames generally do not require PFP because they are designed to achieve a specified fire resistance
period. In certain circumstances spalling may be an issue and PFP required. Only products intended for this
application, and which have been demonstrated to provide the necessary protection should be used.
For timber frame buildings, the structural frame fire protection, if needed, will often be provided by
a board system, for example, plaster board. Most manufacturers of these products provide guidance
on their installation and use. See Section 17.
Fire-resisting doorsets may be of timber or metal construction and hinged, pivoted, sliding or mechanised
including roller shutters. They must be installed in accordance with the details contained in the test
report provided by the manufacturer or as required by Third Party Certification. All installations must be
properly maintained.
In order that fire-resisting doors fulfil their mechanical and movement functions, movement gaps in the ‘fit’
with the door frame are essential. These gaps have specially selected sealing strips fitted adjacent to the
movement spaces which will expand in fire conditions to seal the movement gap.
It is important that the doors and hardware are maintained in good condition including sealing strips,
hinges, latches and vision panels if fitted. Each product should be tested to the appropriate BS or
[36]
BS 4787 BS EN Standard, with timber doorsets complying with the door-to-frame gap tolerances of
BS 8214[37] BS 4787-1:1980[36]. For maintenance requirements refer to BS 8214:1990[37].
Fire-resisting doors are not effective unless they are closed. Self-closing devices ensure that fire-resisting
doors re-close each time they are opened.
When the door relies only on the self-closing device, it is important to ensure that the closing force is
set to the value at which it was tested, during the fire resistance test, with the minimum closing force,
BS EN 1154 [38]
power size 3 as required in BS EN 1154:1997[38]. Fire-resisting doors may also incorporate latch systems,
which enable the door to be held closed in lieu of the door closing device.
D C Mf A Mg 29
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Fire-resisting doors, frames, self-closing devices and latch systems are all fire tested as a specified set to
achieve the stated fire performance - the matched set of components is essential to the fire performance.
Substitute components must be avoided, unless permitted as alternatives by means of assessments. or
within the third party certification of the product. It should be noted that hardware does not carry its
own fire test report but is recorded in the fire test report as contributing to the successful performance
of the doorset in the fire resistance test.
DSMA[31] For further information on industrial and metal doors, consult the Door and Shutter Manufacturers’ Association
ASDMA[32] (DSMA) code of practice[31] or the ASDMA[32]. Information on timber fire-resisting doors is available from the
IFSA [33]
British Woodworking Federation (BWF)[38]. For information on intumescent seals, contact the Intumescent Fire
BWF[38] Seals Association (IFSA)[33] and for timber doors, contact TRADA[39}. See Section 17 for all contact details.
[39]
TRADA
For further information on the selection of door fittings reference should be made to the Building Hardware
BHIF [34]
Industry Federation (BHIF) Code of practice – Hardware for timber fire and escape doors[34].
BS 5499[40] Attention is drawn to the revision of BS 5499 safety signs including fire safety signs. Part 5:2002 Graphical
symbols and signs[40] – Safety signs including fire safety signs – Signs with specific safety meanings for
signage required on fire-resisting doorsets and emergency/panic exit doors.
It may have one or more leaves, and the term includes a cover or other form of protection to an
opening in a fire-resisting wall or floor, or in a structure surrounding a protected shaft.
Rolling shutters across means of escape should only be released by a heat sensor in the immediate vicinity
of the door, and not initiated by smoke detectors or a fire alarm system, unless the shutter is also intended
to partially descend to form part of a smoke reservoir.
LPC[24] (See ‘LPC Design Guide for Fire Protection of Buildings, 2000’[24] and DSMA guidance[31].)
[31]
DSMA
The allowable size of a compartment will vary with the height and use of a building, the fire load contained
in the building, and the ability of fire-fighters to intervene effectively. In some cases, the availability of a
dependable sprinkler system may allow larger compartment sizes, but it should be recognised that sprinkler
systems require adequate water pressures and regular maintenance practices to ensure reliable performance.
30 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Any compartment wall below a service void should run continuously up through the void to prevent the
spread of fire through the void. Where the void is a roof void, the wall should reach roof level or pass
through the roof to a specified height to prevent spread of fire across the roof. The junctions of
compartment walls or floors with each other, with external walls or roofs must provide continuity of the
expected fire-resisting performance.
Any element (including structural elements) passing through compartment walls or floors should have
associated fire-stopping at the point of penetration and the aperture should be kept as small as practicable.
The design should ensure that the failure of a penetrating structure because of fire in one compartment
will not cause failure in the adjacent compartment. The same comment applies to the passage of building
services, and special provisions are required for protected shafts.
Most guidance documents to building regulations provide recommendations for allowable compartment
sizes and guidance on junctions with other walls and roofs. It should be noted that resilient fire-stopping
systems are recommended where compartment walls meet roofs, and double skinned roof sheeting should
incorporate bands of material of limited combustibility centred over each compartment wall.
Insurers may have higher requirements than building regulations to minimise the damage to the property
and to the business itself. In addition, the compartment wall may require enhanced fire resistance to the
walls and roof within the ‘protected zone’ on each side of the compartment wall. Details are contained in
the LPC Guide for the Fire Protection of Buildings, published by the Fire Protection Association, London.
The junctions of fire walls or fire separating elements with each other, with external walls or roofs must
provide continuity of the expected fire-resisting performance. Any element passing through a fire wall or
fire separating element should have associated fire-stopping at the point of penetration and the aperture
should be kept as small as practicable. The design should ensure that the failure of a penetrating element
will not cause failure of the fire wall or fire separating element or vice versa.
9.7 FLOORS
Floors may be formed of timber, concrete, steel or composite steel/concrete systems. The fire resistance of a
floor will depend on the material from which it is formed, the properties of that material in fire, on the
materials essential to the stability of the floor, and on the means by which these materials or products are
fixed together.
Timber floors will char, the wood will be progressively but predictably consumed by fire. The timber
thickness is critical to the performance in fire and therefore must be correctly specified.
Concrete floors contain entrapped moisture. They may well be reinforced with steel. In fire, the entrapped
moisture will heat up and turn to steam. The steam pressure will increase and try to find relief by escaping from
D C Mf A Mg 31
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
the concrete. The escape mechanism can be violent and large pieces of concrete can be removed – ‘explosive
spalling’. Any steel reinforcement in the concrete will be initially protected by the concrete, until spalling exposes
the steel and it will substantially expand to threaten the viability of use as a floor. The extent of concrete cover
over reinforcement is therefore critical to the fire resistance available and must be correctly specified.
Composite floors perform differently in fire, because the metal base will conduct heat from fire laterally. The
metal face will attempt to expand. The rate of temperature increase in the critical parts of the floor may be
lessened compared to concrete alone. The composite floor will also be fixed through shear connectors to the
supporting steel structure. Steam formed in the concrete may force out the metal decking to distort it and
cause gaps and subsequent failure. The steel reinforcement will transfer the load and the heat from fire. The
composite structure may ultimately deform under the heat and sag under the load of the concrete.
The fire performance of all floors can be enhanced through the use of added passive fire protection systems.
These PFP systems act to insulate the timber, concrete, or steel from the effects of fire for given periods of
time. The protecting mechanism depends on the characteristics of the PFP system and careful design based
on fire test evidence is essential.
Manufacturer’s test evidence must be understood and incorporated into the specification to ensure that the
anticipated performance is achieved.
The choice of PFP can also be important if the performance is not to be negated by deformation of the floor
system. Some PFP materials will deform better than others, which may fracture under deformation in fire.
9.8 CEILINGS
Fire-resisting ceilings can form a critical component of the fire resistance of a building and should be
specified to fully satisfy the manufacturers' instructions. See Section 12.
Cavity barriers require special attention from the designer. By their very nature they are often hidden once
installed and are therefore difficult to inspect after installation, handover and subsequently through the
life of the building. However the barrier will not become effective until it has been covered up and later
inspection, by re-opening the work, could affect its integrity.
The designer should indicate where there is a need for a cavity barrier. Because it is an important element
that is often accidentally missed out during construction, the responsibility for its installation and
performance must be clearly identified. This is all the more important as the cavity barrier may well be
hidden after its installation.
Unless clearly defined, it is possible for an in-appropriate sub-contractor to be given the task of installing
cavity barriers.
32 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The requirements and responsibilities for the provision of cavity barriers must be clearly stated in the
contract(s). Proprietary systems must be designed in accordance with manufacturers instructions.
Guidance[9,10,11] Recommendations on the provision of cavity barriers are given in AD B and its equivalent Scotland/Northern
Ireland guidance. Co-ordination between different trades and contractors is essential particularly when
aligning or joining one cavity barrier system with another.
The insulation and integrity requirements may be different from those required by the compartment walls
and floors of the building. Care should be taken therefore with their use, particularly for large barriers. It
should be noted that barriers in a roof space for example, which are located above the fire separating
divisions must provide the same level of insulation and integrity as the division. The recommended
positioning and spacing of Cavity Barriers is given in regulatory guidance documents.
Like cavity barriers, fire stopping requires special attention from the designer. They are frequently hidden
once installed and are therefore difficult to inspect after installation, handover and subsequently through
the life of the building. The designer may not be able to indicate where there is a need for fire stopping
since it should be fitted wherever needed. Because it is an important element that is often accidentally
missed out during construction, the responsibility for its installation and performance must be clearly
identified. This is all the more important as fire stopping is often hidden after its installation.
Unless clearly defined, it is possible for an inappropriate sub-contractor to be given the task of installing
fire-stopping. For example, where fire-stopping is needed behind a cladding system at floor level, the
responsibility may fall to the floor installer or the cladding contractor. Those who carry out the task must
have the necessary expertise. The requirements and responsibilities for the provision of fire stopping must
be clearly stated in the contract(s). Proprietary systems must be designed in accordance with
AD B[9] manufacturer’s instructions. Recommendations on the provision of fire stopping are given in AD B and
ASFP [29]
the ASFP ‘Red Book’[29].
From AD B
‘Fire-stopping
11.12 In addition to any other provisions in this document for fire-stopping:
a. joints between fire separating elements should be fire-stopped; and
b. all openings for pipes, ducts, conduits or cables to pass through any part of a fire separating
element should be:
i. kept as few in number as possible, and
ii. kept as small as practicable, and
iii. fire-stopped (which in the case of a pipe or duct, should allow thermal movement).’
BRE DAS[41] Advice on preventing fire spread between buildings at roof level is given in BRE Defect Action Sheets 7 and 8[41].
D C Mf A Mg 33
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
If smoke barriers are used, these will not have the same high fire resistance criteria as fire barriers/curtains.
They can only be expected to provide fire integrity, not insulation, and will not provide continuity of the
fire-resisting division. They may be helpful to provide a smoke reservoir as part of a different and separate
fire strategy. Again edge and joint fixing and sealing must be correctly specified.
The use of ductwork to distribute air around a building may threaten the overall expected fire performance,
unless the possibility of fire entering the duct, and/or breaking out of a duct is considered. This is covered in
BS 5588[27] BS 5588:Part 9[27}. Three alternative methods are outlined.
" Fire dampers
" Fire-resisting ducts
" Enclosing in fire-resisting shaft
The possibility of fire entering the duct, and/or breaking out of a duct must be considered. Suitable test
BS 476[18] standards are defined in BS 476 Part 24[18], see below.
34 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
BS 5588[27] The design of fire-resisting ductwork of all types is described in BS 5588 Part 9[27] and this in turn requires
BS 476 [18]
the duct and materials to be tested according to the requirements of BS 476 Part 24[18]. This test Standard
BS EN 1366[42] will be replaced by BS EN 1366-1[42] as the EN fire test standards become available.
The duct should be constructed according to the same fire rating as the fire separating element through
which it originally passes. This is especially important when the duct is intended to remove smoke from a
compartment exposed to fire, or a kitchen extract system where the duct may become lined with ignitable
fatty deposits if poor filtration or maintenance persists. (for this last application, additional insulation
criteria are specified in the test standard).
ASFP[29] Design guidance may be found in the ASFP publication ‘Fire-resisting Ductwork and Dampers’[29].
Where a fire-resisting duct system has been specified, it must be fully tested or independently assessed
to the requirements of BS 476:Part 24 (or BS EN 1366-1). This must include the method of support and
the type of seal used around the ducts where it penetrates a wall or floor whose fire resistance must be
maintained. Also, it should have been tested for both fire outside (duct A) and fire inside (duct B), both in
horizontal and vertical orientations unless the end use conditions are to be restricted.
Types of product used to make steel ductwork fully fire resistant typically include:
" Fire protection boards, typically calcium silicate and vermiculite boards
" Rock fibre mineral wool (not glass fibre mineral wool)
" Sprayed fire protection coatings
" Intumescent coatings
" Hybrid systems, comprising at least two of the above
Care should be taken when utilising any of the above to make steel ducts fire resistant, that adequate test
evidence is available for the particular circumstances, or a valid independent assessment has been obtained.
Materials typically used for self supporting ducts include fire protection boards, typically calcium silicate and
vermiculite boards.
The designer must consider the possibility of fire spread through such a space and specify adequate fire
stopping and fire sealing at all penetration points and possibly fire barriers at floor levels.
9.15 PIPE, CABLE AND SERVICE PENETRATIONS (INCLUDING LINEAR GAP SEALS)
Wherever services penetrate elements of structure, any fire resistance criteria of the element of structure
must be maintained. Any apertures must be kept as small as possible and fire-stopped in such a way that
differential movement of the service and the element of structure will not disturb the fire-stopping (see
Section 9.10). It may be required to extend the fire-stopping along the service to ensure that high
temperatures are not conducted along the service to the side isolated from the fire, to ensure that fire
D C Mf A Mg 35
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
spread is prevented. The exact solution will depend on the system provided and manufacturer’s advice is
essential for compliance with the available test data.
Note - Currently the UK does not have a formal test standard for such service penetrations. Specifiers and users
should scrutinise test data carefully to ensure the relevance of the intended fire protection system. The
European Union is preparing a new standard as prEN 1366-3 for the fire performance of service penetrations,
and prEN 1366-4 for linear fire stopping systems in the gaps between building elements (see page 61).
In certain cases, the vertical penetration of compartment floors may necessitate large apertures to be formed
for the passage of the services. This introduces an additional hazard if the aperture could permit
maintenance staff to fall through it.
Any fire-stopping used to block the aperture should be either capable of maintaining the expected load,
be reinforced or supported adequately, or covered with a load bearing steel plate.
GGF[43] Advice on the latest options available to the designer may be obtained from the Glass and Glazing
LPC [24]
Federation[43]. See Section 17 and the LPC Guide[24].
Recommendations for the construction of external walls are given in guidance to Building Regulations.
BR 135[44] Specific design principles are given in the recently revised BR 135[44], Fire Performance of external thermal
insulation for walls of multi-storey buildings, which also provides a method of assessing the fire performance
BS 8414[45] of these systems using the BS 8414-1:2002[45] test method for external cladding systems.
Built-in fire protection may be formed from a wide range of ordinary (but mostly low-combustibility)
construction products (ie materials not specifically marketed as passive fire protection). Such products
36 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
include brick and block, concrete, cement, plaster board and timber. Such products are used, for example,
to form fire-resisting compartment walls and floors, or to provide cavity barriers, cavity closures or fire
stopping. Cavity barriers in cavity walls, or in roof constructions, may need to be installed as part of the
construction process. Others, such as cavity barriers in roof spaces, may be fitted later.
It is essential that those elements of construction that comprise the built-in fire protection are properly
designed, installed, inspected and maintained. This is particularly important for ordinary (non-specialist)
products since their role as passive fire protection can be overlooked and difficult to inspect.
Guidance[9,10,11] For most buildings, designed using AD B and its equivalent Scotland/Northern Ireland guidance, it is only
necessary to check that the passive fire protection proposed for the building corresponds in both location
and value to that recommended in AD B. However, insurers requirements may also need to be considered.
Where a building has had its fire safety system designed using fire safety engineering then more detailed
analysis may be needed, since, for example, the fire resistance specified might be reduced because
sprinklers are fitted. It is vitally important that where a Fire Engineer is used, he or she is involved in the
project at the earliest possible stage, preferably when the Fire Strategy is being agreed so that all aspects
of his/her proposals are considered before any work is implemented.
It is important for the checker to be satisfied that the PFP offered does meet the recommendations or can
otherwise be justified, and that it is of a type that is appropriate for the actual use of the building, eg a
soft coating may not be appropriate if trolleys are going to impact it.
It is essential that where designs or proposals do not follow the guidance document recommendations the
enforcers should have access to suitably qualified persons to verify the proposals.
D C Mf A Mg 37
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Assuming the fire strategy and compartmentation for the project has been designed and approved by
others (architects and design consultants, building control bodies, etc) the Main Contractor should ensure this
information is correctly converted into scope documents, drawings and specifications for the work. Careful
attention should be paid to the interface arrangements between the trades.
Note: see Relationships between specialists (Section 4.5) and Specialist Installers (Section 5.1.2).
If it is inevitable that following trades will have to remove small areas of fire protection. This should be
properly addressed in the contracts of those trades to ensure that excessive damage is not caused.
The Main Contractor should identify competent contractors for the work concerned. Advice can be
obtained from recognised industry accreditation schemes. See Section 10.3. If a manufacturer’s product has
been specified, advice should be obtained on approved or recommended installers. The scope of work
should include a requirement that the PFP Contractor carry out inspection of work in progress and when
completed. This may include a requirement that the PFP Contractor employs an approved third party
independent inspector, whose reports will be issued to the Main Contractor. The contract should be
awarded only to a contractor whose submittal complies with these tender requirements.
For the work of installing fire seals around penetrations in compartment walls and slabs, traditionally this
has been included in the scope of work for each of the service trade contractors. This traditional approach
can raise problems because of interface problems, and sometimes the seal installation has been left to
untrained personnel.
An alternative approach, which has proved successful, is to remove the penetration and fire seals from the
scope of work of the service trades, and appoint a competent specialist contractor to carry out all this
work throughout the project.
Approved Document B recognises the benefits in confidence and reliability obtained by the use of
Accredited Installers. All Contractor members of the ASFP are Third Party Accredited.
38 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
For most effective use of this system the Main Contractor can ask the PFP Contractor to provide a list of
names of operatives and supervisors, with copies of their certificates. The overall majority should be
certified but a small number in training can be allowed to work under supervision. (See Section 17 for the
available Third Party Accreditation (TPA) schemes).
The designer will usually provide a full specification if masonry or in-situ concrete is chosen as the fire
protecting media. In cases where proprietary spray or panel systems including pre-cast concrete are to be
used, the designer will indicate the required fire rating to the specialist installer who will select the
materials and specification accordingly.
Where steel protection is required the steel must be supplied to site with appropriate and compatible
priming systems applied. This is another example of the need to co-ordinate the activities of all contractors
where PFP is required.
Accredited contractors are trained in the specialist installation to steelwork and the methods required
and will minimise the risk of additional expense that may be incurred when unsatisfactory work is found.
The protection thickness required will vary for the specific steel mass, and the perimeter of steel which
could be exposed to fire, as well as the duration of the protection. Specialist contractors will understand
the requirements and ensure that the correct thickness of material is used.
Invariably, it will be necessary to ensure that for paint or spray on systems, the steel surface is suitable for
the material being applied, the steel temperature at the time of application should be 3oC above the Dew
Point to assist good adhesion and avoid surface moisture. Such systems will usually follow the profile of the
steel member, but ‘boxed’ systems are available for some cementitious sprays reinforced by wire mesh.
Intumescent systems are thin by comparison with other sprayed protection systems. The dry film thickness
required will be advised by the manufacturer and will vary with the material and steel section requiring
treatment. Accurate dry film thickness measurement during inspection is vital. A top coat may be required
either for long term protection or for a decorative finish.
D C Mf A Mg 39
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
By contrast most board protection systems are usually applied in a ‘boxed’ form and use less surface area as a
result. Only tested and approved fixing systems are acceptable. The form of the joints needs particular attention
to avoid gaps. Some joints require fire-resisting glues/adhesives to achieve the required fire performance.
The interfaces between different elements of structure need careful planning for the expected performance
in fire. The ASFP suggests that sample situations are agreed before general work commences, so that all
parties are aware of the issues. Simple steel protection may well be the norm, but more complex areas
will always occur, especially where different trade packages interface – eg Protection of perimeter steel
adjacent to prefabricated cladding, and interfaced by internal fire walls, storey decks and services. The
practice of fire protection of cladding supports varies according to local Bye-Laws, and special solutions
may well be required.
Where these fire protection systems abutt profiled decking the fire protection period/ system type will
dictate whether the re-entrant profiles need fire stopping or not, according to good practice developed
ASFP[29] by the Steel Construction Institute and the ASFP (See ASFP ‘Fire Protection for Structural Steel in Buildings’)[29].
It is recommended that only doors covered by Third Party Certification which includes factory production
control should be used. Suitable schemes are operated by CERTIFIRE, TRADA Q Mark and LPCB. See
Section 17 for contact details. Doorsets should be included on a schedule that will describe the swing,
the size of opening, appearance and required building hardware (ironmongery).
Current practice is that the building hardware (ironmongery) will often be selected by a member of the
project design team and included as a Prime Cost (PC) sum. Certain procedures may follow the alternative
route of selecting catalogue items, usually covered with the caveat of ‘equal and approved’ to preserve the
ideals of fair competition and choice. This route can lead to incompatible specifications which are further
down-graded by the Main Contractor or the purchaser (doorset supplier, sub-contract installer etc).
Confirmation of the fire performance compatibility must be obtained from the door manufacturer and/or the
hardware supplier for all components.
To achieve Best Practice the final building hardware schedule should be prepared by an architectural
ironmonger who has specialist knowledge regarding the overall requirements for functionality and
performance, This route is more likely to result in the desired performance - aesthetics, functional etc.
Attention should be paid to the use of auxiliary items such as electro-magnetic hold-open and swing-free
door closing devices for use where doorsets are required for fire compartmentation but where the door
AD M[46] otherwise creates an inconvenience in day-to-day use, viz under the new DDA requirements with particular
BS 8300 [47]
reference to AD M[46] and BS 8300:2001[47] Design of buildings and their approaches to meet the needs of
disabled people - Code of practice where there are possibilities of conflict between user friendliness and
function in case of fire.
40 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
It should be remembered that from all the PFP products included in any building the doorset with its
hardware is the item which withstands the greatest use and abuse. The door is required to function correctly
at all times, being the most handled product in the circulation area of any building. It is expected to play a
dual role of conventional door for security, privacy, separation, sound reduction and/or air movement control
BUT in the event of a fire it has to perform 100% as a fire barrier.
This can only be achieved if the correct items are fitted at the time of construction and maintained
throughout its whole working life. Any replacement MUST be on a ‘like-for-like’ basis.
BS 8214[37] For maintenance and replacement refer to BS 8214:1990[37] and BHIF Code of practice - Hardware for fire
BHIF[34] and escape doors[34] and ASDMA guidance[32].
[32]
ADSMA
Where specialist metal and/or mechanical fire-resisting doors are used they will usually be fitted by the
manufacturer since specialist skills are required to ensure long term performance and compliance with the
[31]
DSMA[31] test evidence for the installation, using the Code of Practice for Fire Resistant Metal Doorsets, etc
As such, they will require regular testing; apart from this aspect, they will be designed or specified in the
same way as fire doors.
The designer will fully specify the structural performance of load bearing compartment walls. The fire
resistance may be covered by the structural specification, but a specialist will provide details if additional
protection is needed. Partition or non-load bearing walls may also be fully specified, although if a stud
system has been specified, the supplier will be expected to certify that the required performance has
been achieved.
Installation contractors can only provide meaningful certification through independent Third Party Accreditation.
10.8 CEILINGS
Fire-resisting ceilings should be constructed to fully satisfy the manufacturers' instructions and allow for parts
of the ceiling to be removed for maintenance. Light fittings, and other penetrations through the ceiling,
must be appropriate for the type of ceiling. See Section 12.
D C Mf A Mg 41
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The requirements and responsibilities for the provision of cavity barriers must be clearly stated in the
contract(s). Proprietary systems must be installed in accordance with manufacturers instructions.
Guidance[9,10,11] Recommendations on the provision of cavity barriers are given in AD B and its equivalent Scotland/Northern
Ireland guidance. Advice on preventing fire spread between buildings at roof level is given in BRE Defect Action
BRE DAS[41] Sheets 7 and 8[41].
Like cavity barriers, fire stopping requires special attention from the installer. They are frequently hidden once
installed and are therefore difficult to inspect after installation, handover and subsequently through the life
of the building.
The designer may not have been able to indicate where there is a need for fire stopping but it should be
fitted wherever needed. Because it is an important element that is often accidentally missed out during
construction, the responsibility for its installation and performance must be clearly identified. This is all the
more important as fire stopping is often hidden after its installation.
Unless clearly defined, it is possible for an in-appropriate sub-contractor to be given the task of installing
fire-stopping. For example, where fire-stopping is needed behind a cladding system at floor level, the
responsibility may fall to the floor installer or the cladding contractor. Who ever carries out the task must
have the necessary expertise.
Guidance[9,10,11] The requirements and responsibilities for the provision of fire stopping must be clearly stated in the
contract(s). Proprietary systems must be designed in accordance with manufacturers instructions.
Recommendations on the provision of fire stopping are given in AD B and its equivalent Scotland/Northern
ASFP [29]
Ireland guidance and The ASFP Red Book[29].
42 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
2 Self-supporting duct systems constructed entirely from fire protection boards eg calcium silicate and
vermiculite boards.
Fire dampers with fusible links (or those designed to be operated when smoke is detected) are designed to
be installed in the line of the cavity barrier, fire wall or compartment wall/floor through which the ductwork
passes. If they are not in the line of the fire division, then fire can by-pass the damper system.
The damper assembly should be independently supported so that failure of the duct will not cause failure/
collapse or disturbance of the damper mechanism in the line of the wall. Ducts also need to be
adequately supported so that no undue load is applied to the damper due to distortion of the duct. This
can prevent the damper from closing properly or not at all. It is also important that the damper has been
tested (or assessed) for the particular type of wall or floor in which it is to be installed.
ASFP[29] Readers are referred to the ASFP publication ‘Fire-resisting Ductwork and Dampers’[29].
If the shaft is independent of the structure, eg non-load-bearing, the designer, probably the architect - will
provide a performance based specification, tempered by aesthetics or other non-fire related issues.
D C Mf A Mg 43
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
It is essential that both the designer and the specialist contractor are fully conversant with the fire
protection requirements. It is recommended that suitably accredited contractors are used for such work.
Fire-resisting glazing systems must be suitable for the required application and installed in accordance with
the manufacturer’s instructions.
Providing a balance for these criteria involves co-ordination of all the design disciplines and many sub-
contractors. Because of this wide ranging criteria that the building envelope has to satisfy, the lead designer
will usually need to take on the role of co-ordinator and provide detailed designs and prescriptive
specifications for most of the system although applied fire protection will be subject to a performance
specification.
Design consultants and contractors need to appreciate the implications of selecting materials that increase
the fire load. The amount of combustible material that is permitted will depend on building height, size, use
and distance from the boundary.
Built-in fire protection may be formed from a wide range of ordinary (but mostly low-combustibility)
construction products (ie materials not specifically marketed as passive fire protection). Such products
include brick and block, concrete, cement, plaster board and timber. Such products are used, for example, to
form fire-resisting compartment walls and floors, or to provide cavity barriers, cavity closures or fire stopping.
Cavity barriers, in cavity walls, or in roof constructions, may need to be installed as part of the construction
process. Others, such as cavity barriers in roof spaces, may be fitted later.
It is essential that those elements of construction that comprise the built-in fire protection are properly
designed, installed, inspected and maintained. This is particularly important for ordinary (non-specialist)
products since their role as passive fire protection can be overlooked and difficult to inspect.
44 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
All the design disciplines and key personnel in the supply chain involved in the project should be properly
informed of the PFP philosophy so that they avoid compromising agreed principles. Co-ordination of
designers and suppliers along with supervision of the works is essential. Procurement routes – design led,
design and build or PFI and responsibilities for the performance of the fire protection systems – need to
be established at the outset of the project.
Therefore the manufacturer and the distributor, who are often relied upon by the specialist contractor for
technical advice, play a significant role in the procurement chain.
Both the manufacturer and the distributor have a duty to ensure that the materials supplied conform to
the specified requirements and have the required test evidence to demonstrate this compliance.
This document has stressed the importance of using accredited specialists throughout and such specialists
will understand the test and certification requirements for products in their field of expertise. The placing of
contracts that include PFP in the scope with contractors inexperienced in such matters places a greater
burden on the suppliers. Ordering by untrained staff will be vague and lack detail and suppliers must accept
responsibility for the materials that are provided as the life safety of the occupants and users of the building
may be put at risk by the use of the wrong materials, probably wrongly installed. Documentation giving the
scope of test evidence and full installation information in an unambiguous manner is essential with all
limitations of application clearly defined.
This latter supply problem is most prevalent when the PFP element is a minor part of work that may be of a
skilled nature in another field and it is recommended grouping all PFP work into specialist contracts to avoid
such problems.
D C Mf A Mg 45
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Approved Document B recognises the benefits in confidence and reliability obtained by the use of
Accredited Installers for such materials and all ASFP Contractor members are Third Party Accredited.
Contractors who are trained in the specialist installation methods required, should be used to minimise
the risk of additional expense that may be incurred when unsatisfactory work is found.
The interfaces between different elements of structure need careful planning for the expected performance
in fire. The ASFP suggests that sample situations are agreed before general work commences, so that all
parties are aware of the issues. Simple steel protection may well be the norm, but more complex areas
will always occur, especially where different trade packages interface, eg protection of perimeter steel
adjacent to prefabricated cladding, and interfaced by internal fire walls, storey decks and services. The
practice of fire protection of cladding supports varies according to local Bye-Laws, and special solutions
may be required.
Quality checks and inspections are mentioned in other sections of this document.
To summarise this topic specifically in terms of procurement for ASFP related services, (see Section 17)
the Main Contractor should include in the PFP Contract:
" Suitable scope of work and specification, which should define the type and frequency of checks
required
" Contractor to provide a Quality Plan or other documents describing the procedures and resources
for quality assurance including site testing and inspection
" For PFP to structural steel, contractor to employ an approved independent inspection agency to carry
out tests and inspections to verify the work is complete and in accordance with the specification
" For fire seals, contractor shall affix a suitable permanent label to every seal giving a reference number,
type of seal, name of the operative who installed it, date of installation, name of supervisor who
subsequently inspected, and date of supervisor’s inspection. The contractor shall also maintain a
summary record of this information in the form of marked-up drawing or similar. The Main Contractor
retains the right to inspect all work. PFP contractor to provide access when requested for inspection
by the Main Contractor and building control bodies.
Wherever products are specified by name for a contract it is the usual practice to include the option of ‘or
other approved’ in some form in the specification. The subsequent substitution of alternatives requires
careful control, as the primary reason for such a change will almost certainly be a reduction of cost. Where
alternatives are being offered expert knowledge of such matters as test evidence, scope of application,
installation skill requirements, ease of maintenance and other related points is required to approve the
alternative being offered.
When such products are accepted within the contracting chain the responsibility for the ‘in use’
performance rests with those accepting the substitution and the decision should not be taken lightly where
life safety matters such as PFP are concerned. This responsibility for changes to the design specification starts
with the Main Contractor and applies down the contractual chain through sub-contractors and suppliers of
materials in all sectors of PFP work.
46 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
FS (WP) Regs[14] Building managers will need to be aware of the Fire Safety (Workplace) Regulations[14]. The provision
and maintenance of the PFP within the building should form part of the risk assessment
carried out under these regulations for the building. Managers need to be aware that there may be
liability issues in the failure to comply with regulations (eg as a criminal act). Where PFP systems have to
be removed or have become damaged for other purposes, they must be made-good as soon as possible.
Where appropriate (eg to premises designated under the Fire Precautions Act), the building will be issued
with a Building Control completion certificate.
It is essential to ensure that future modifications to the building do not negate the effectiveness of the
system to which the certificate applies. Managers also need to be aware of the other regulations and
guidance that may have influenced the design of the building.
These might include any Fire Safety Engineering decisions taken within the design that may restrict the
BS 5950[30] adaptability in use, for example if BS 5950 Part 8[30] had been used in the structural design.
CDM[16] The Construction Design and Management Regulations (CDM)[16] require all concerned in the process from
design inception to completion of the building to prepare a file (the CDM file) containing details of all the
work done and materials used where safety is concerned. The CDM file can be an invaluable source of
information on all aspects of fire safety work in the construction of the building that may be used by the
occupant when preparing maintenance plans, modifications to the building or Fire Risk Assessments as
required by the Fire Precautions (Workplace) Regulations.
In general the fire safety specification for a building will primarily be concerned with life safety. However
there are other issues that may need to be addressed by the fire strategy and these include; business
interruption, contents, heritage, functionality and/or environmental protection.
The building manager must be aware where these additional criteria have been considered.
Ideally, where the operation and maintenance data for a building is available and the ‘as-built’ products
can readily be procured, any changes and repairs should be carried out with the materials originally
specified. Suitably skilled, experienced and accredited personnel must carry out such works in accordance
with the manufacturer’s recommendations.
Again it is important to emphasise the role played by basic construction materials and systems in PFP.
Maintenance of PFP cannot be achieved without the integrity of the building construction being included.
Best practice in the construction, use and maintenance of walls, floors and the building envelope must be
the goal to optimise the life cycle of the asset.
D C Mf A Mg 47
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The use of materials that are susceptible to damage, eg through impact and/or dampness in
inappropriate locations, will greatly reduce the life of the PFP. Worse still, whilst the evidence of damage
may be quite obvious when impact has occurred, the detrimental effects of moisture on some types of
unsealed intumescent products may not become apparent until they fail under fire conditions.
Materials that are subject to deterioration during the life of the building must be identified and be subject
to a suitable maintenance procedure to extend the life of the PFP.
Notwithstanding these reservations, most modern passive fire protection materials are durable and, if
properly maintained, are more than capable of delivering a sustained level of fire resistance throughout the
life of a building (say 40 years).
The primary concern in the maintenance of PFP should be focussed on the control of change
(alterations/breaches) and the quality and efficacy of repair.
It is a requirement of building regulations and Insurers’ Rules as well as good practice, that breaches
created by the penetration of services be made good to the extent that the fire-resisting performance of
the penetrated element is fully restored in terms of their load-bearing capacity, integrity and insulation.
Modern commercial and public buildings are dynamic environments in which change may be endemic.
Building services are the principal cause of breaches in this scenario and because of their frequency and
obscure locations often give rise to the greatest uncontrolled risk of fire spread.
Therefore, planning of breaches and their recovery are of prime importance in controlling the risk.
The planned duration of new service installations or modifications should also be assessed for risk and
consideration given to the deployment of temporary penetration seals.
Care must be taken in selecting an appropriately rated penetration repair solution, compatible with the
original installation and substrate and suited to the type, configuration and number of penetrating
services. This care should be extended to the delivery and verification of the solution by an accredited
specialist. If the labelling system recommended in Section 10.18 above is used repair and maintenance
of penetrations will be facilitated.
11.4 PERMITS
The need for control of hot work processes is widely recognised and it is common practice to forbid such
activities without the deployment of controlling ‘hot work’ procedures and permit systems.
48 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Often these permits will be highly restrictive, limiting activities, and durations and stipulating protective measures
to be taken before, during and even for some time after the activity. Contrast this with the introduction of new
services, facilitated by the creation of multiple breaches in fire-resisting elements or the removal of structural
protection within the construction. Whilst there is apparently much less immediate risk of starting a fire, there is
potential for the circumvention of fire-resisting elements in such a way as to greatly increase the risk to both life
and property through the spread of fire and smoke or the premature weakening of the structural frame.
Accordingly, where it is impractical to plan and control such work through conventional methods,
consideration should be given to the operation of ‘cold work’ procedures and permit systems to control
and record access to, and activity within, areas of a building.
Understanding the design concept of fire-resisting compartmentation as well as the contradictory nature
of our need for more open and highly serviced buildings gives experienced facilities management
professionals the ability to recognise the inherent risks. Thus they can successfully plan and control
change without placing occupants and buildings at risk. Having access to the fire strategy documents
and the CDM file will materially assist in the performance of this function.
Trained in the behaviour of fire, smoke and people they will often have a superior understanding of the
nature of the risk from uncontrolled breaches in fire-resisting elements. They are a powerful force in auditing
the condition of the building and can provide early warning of unplanned activity and breaches and, as with
CDM [16]
Facility managers they should have access to the CDM file[16].
Additionally, they will have a role in the provision of training and guidance to personnel, building management
and contractors. They will probably ensure that both active and passive fire protection measures in the building
design are delivered at hand-over and are maintained to the required standard throughout the life of the building.
It is strongly recommended that a ‘fire safety manager’ be appointed for the building. The Fire Safety
Manager should have overall responsibility (and powers and resources) for all issues relating to fire safety,
and liaise with the other engineering professionals looking after the building.
D C Mf A Mg 49
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
This policy statement should contain a description of the levels of passive fire protection required throughout
the building including recommendations for structural protection, compartmentation, protected shafts,
firefighting shafts, cavities/voids and their respective protective barriers, and fire-resisting doorsets, etc.
An important aspect of the fire safety specification is the link between active and passive fire safety
measures employed throughout the building. The extent to which this linkage applies should be taken into
account within the fire safety specification.
Location and access: The fire safety manual should be kept in a secure and fireproof container on the site
(but preferably not within the building), readily accessible to fire officers attending an incident.
Maintenance, review and testing of fire safety manual: The fire safety manual needs to be reviewed
and its procedures tested annually, or whenever alterations are made to the building, in accordance with a
documented procedure. The review should include the following:
" All plant and equipment interface controls, to ensure that all equipment is in working order
and that maintenance procedures are being followed
" Record documents, as-built drawings and specifications of the fire protection measures;
and records should be kept of reviews and of the changes made
" Managers will need to be aware of the changes that create a need to review the risk assessment
[14]
FS (WP) Regs under the Workplace Regulations[14], which will include reference to the PFP.
11.9 MONITORING
The regular review and measurement of breach activity must be carried out. This can produce
beneficial information in respect of ownership, planned and unplanned activity, frequency, type, periodicity,
cost and other statistical data. It can potentially demonstrate compliance in the control and management of
the passive fire protection element of fire safety in the work place. The frequency of monitoring activity will
be dictated by the building’s risk profile. Buildings with hazardous contents, high occupancy levels or high
rates of change are examples of a higher risk category. The period between monitoring activities should not,
of course, be allowed to exceed any Statutory or Health and Safety Executive guidance minimum.
50 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
It is important to ensure that all activities within the building that might affect the PFP are monitored and,
responded to, where necessary.
11.10 RECORDING
Information as to identity, location, design, performance, installation, type, age, etc, is also highly
beneficial in repairing and maintaining passive fire protection. The creation of maintenance records can
range from simple identification tags to more elaborate databases of information tailored to both client
and regulatory requirements. These records should be created and maintained in addition to the ‘as built’
records which form part of the building’s Health and Safety File and Fire Safety Manual. Additionally, records
of monitoring activities must be maintained in order to demonstrate compliance.
Management need to be aware of the importance of PFP on a range of factors that affect the successful
operation of the building.
Through the development or adoption of maintenance strategies for passive fire protection building
owners and users can mitigate all manner of such tangible risks.
D C Mf A Mg 51
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
12 CEILINGS
Fire-resisting ceilings can form a critical component of the fire resistance of a building. Ceilings are generally
constructed of gypsum, mineral wool or calcium silicate-based products supported on a steel framework.
Three of their more common uses is a) to protect a structure above, such as a timber floor or structural
steelwork, b) to separate building services from the space below, or c) to form one side of a smoke plenum.
Whatever type is selected, it should have documented test evidence to show that it meets the appropriate
level of fire resistance for the relevant application, and should be designed, specified and constructed to fully
satisfy the manufacturers' instructions. Light fittings, and other penetrations through the ceiling, must also
have the same demonstrated standard of fire resistance, and be appropriate for the type of ceiling.
The ceiling design and fitting must allow for those occasions when any parts of the ceiling system need to
be removed for maintenance, access, etc. Management procedures should be put in place for those
occasions when any parts of the ceiling system is removed for maintenance, access, etc and the ceiling must
be restored to its original condition.
Third Part Accreditation for products varies according to the terms of individual schemes, but essentially
includes verification of the test evidence and scope of application or use of the product, and a regular audit
of the factory QA system to ensure that the product as supplied to the contractor is to the same design or
formulation as the original test samples.
Third Party Accreditation for installers is a process whereby the contracting company is seen to employ
appropriately trained staff to design and install the required PFP system. Their work is independently audited
by site inspections from the 3rd party organisation and a full record system is required as part of the scheme.
The use of such accreditation is recognised in the Building Regulations, Approved Document B (Use of
Guidance; Independent certification schemes). The use of accredited installers will reduce the incidence of PFP
materials being installed by unskilled or unscrupulous contractors and/or the use of unsuitable materials and
reduce essential work and re-work considerably. Upon completion, a Certificate of Conformity is issued to the
main contractor for each contract. These autonomous schemes raise the perceived profile of the supply and
installation chain and provide the client with a new level of comfort regarding the quality of the PFP.
Where the designer has elected to use Fire Safety Engineering techniques for all or part of the works, quality
of installation may be more important, because prescriptive requirements tend to be all encompassing and
slightly conservative, whereas fire safety engineering calculations or recommendations may be more exact in
their requirements, and any deficiency then becomes critical. Some clients will no longer accept the use of
non-accredited installers. This is to be applauded and endorses the suggested use of accredited agencies in
government guidance.
In July 2001, the ASFP endorsed the requirement for all contractor/installer members to be third party
accredited as a formal requirement for membership of the Association, in order that Manufacturing
members can rely on fair use and representation of their products as intended.
52 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Fire compartment sizes and overall fire resistance of the structure and other key elements and travel
distances will therefore probably have been decided by the architect with reference to AD B, past experience
and discussions with the local Building Inspector. This often means that the opportunities for effective fire
engineering may have been lost. At Stage D, details of the materials for the structure, external cladding and
roofing may only be developed by the designer in sufficient detail to satisfy the planning authorities. Design
and specifications of fire stopping, actual passive and active fire protection systems etc will generally be left
until some way through Stage F.
B Strategic Briefing Preparation of Strategic Brief by, or on behalf of, the Client confirming key
requirements and constraints. Identification of procedures, organisational structure and
range of Consultants and others to be engaged for the Project
C Outline proposals Commence development of Strategic Brief into full Project Brief. Preparation of Outline
Proposals and estimate of cost. Review of procurement route.
D Detailed proposals Complete development of the Project Brief. Preparation of Detailed Proposals.
Application for full Development Control approval.
E Final proposals Preparation of final proposals for the Project sufficient for co-ordination of all
components and elements of the Project.
F Production information F1: Preparation of production information in sufficient detail to enable a tender or
tenders to be obtained. Application for statutory approvals.
F2: Preparation of further production information required under the building contract.
G Tender documentation Preparation and collation of tender documentation in sufficient detail to enable a
tender or tenders to be obtained for the construction of the Project.
H Tender action Identification and evaluation of potential Contractors and/or Specialists for the
construction of the Project. Obtaining and appraising tenders and submission of
recommendations to the Client.
J Mobilisation Letting the building contract, appointing the contractor. Issuing of production
information to the contractor. Arranging site handover to the contractor.
K Construction to Practical Administration of the building contract up to and including practical completion.
Completion Provision to the Contractor of further Information as and when reasonably required.
D C Mf A Mg 53
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Guidance[9,10,11] Building Regulations In England and Wales The Building Regulations 2000
(SI 2000/2531)
Fire Precautions Legislation In designated buildings The Fire Precautions Act 1971
Hotels, Factories, Offices,
Shops, Railway Premises.
54 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Approved Document B interprets the requirements of the Building Regulations and states that the stability
criterion will be satisfied if ‘the load bearing elements of the structure of the building are capable of
withstanding the effects of fire for an appropriate period without loss of stability’.
The Approved Document contains detailed provisions for the maintenance of structural stability in fire. These
are intended to provide guidance for some of the most common building situations. Guidance on
‘appropriate periods’ for different building occupancies are given. However these fire resistance periods are
not mandatory. The Approved Document also states that: ‘There is no obligation to adopt any particular
solution contained in an Approved Document if you prefer to meet the relevant requirement in some other
way. However, should a contravention of a requirement be alleged then, if you have followed the guidance in
the relevant Approved Documents, that will be evidence tending to show that you have complied with the
regulations. If you have not followed the guidance then that will be evidence tending to show that you have
not complied. It will then be for you to demonstrate by other means that you have satisfied the requirement’.
The Approved Document goes on to suggest ‘other means’ to demonstrate compliance by stating that:
‘A fire safety engineering approach that takes into account the total fire safety package can provide an
alternative approach to fire safety. It may be the only viable way to achieve a satisfactory standard of fire
safety in some large and complex buildings’.
The Approved Document lists the parameters that should be included in such a fire safety study. Reference [9].
15.3 SCOTLAND
In Scotland approval must be gained before building. In Scotland compliance is required with the Technical
Standards of the Building Regulations; one cannot build at risk.
Fire resistance requirements are contained in Regulation 12 to the Building Standard (Scotland) Regulations
which state that ‘every building shall be so constructed that, for a reasonable period, in the event of a fire,.
its stability is maintained.’
The measures which should be followed to ensure that this regulation is met are contained in Part D2 of the
Technical Standards: Structural Fire Precautions. Many of the provisions outlined in Part D are designated as
functional standards, which contain references to deemed to satisfy standards. These may be descriptive or
refer to documents such as British Standards. Alternative design strategies can be adopted.
D C Mf A Mg 55
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
The third of these statements is taken to mean that it is not necessary to follow the requirements of the
technical standard if it can be proven that an alternative method meets the provision of the functional
standard.
A relaxation of the requirements given in Technical Standard D is possible where alternative methods of fire
protection can be shown to give equivalent levels of safety to those required in the standard. In such
situations the local Building Control Officer, often assisted by the Scottish Development Office, may request
compensatory features. Reference [10].
In Northern Ireland new Building Regulations came into force in November 1994. The fire safety
requirements for these regulations are supported by Technical Booklet E which contains provisions regarding
structural fire resistance, compartmentation, etc. similar to those in the Approved Document for England
and Wales.
Unlike the provisions of the Approved Document which are for guidance, the use of which is regarded as
evidence tending to show that the requirements of the Building Regulations have been met, the provisions
of Technical Booklet E are deemed to satisfy those requirements. Where the provisions of the Technical
Booklet are not followed then the onus falls on the designer to show that the requirements of the
regulations can be met by other means. Reference [11].
56 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
1 Egan Sir John Egan. Rethinking Construction: The report of the Construction Task Force on the scope
for improving quality and efficiency in UK construction. ODPM, 16 July 1998
2 Latham Sir Michael Latham. ‘Constructing the Team’. Final Report of the Government/Industry Review
of Procurement and Contractural Arrangements in the UK Construction Industry HMSO Department of
the Environment (1994)
4 The Building Regulations 1991, S.I. 1991 No. 2768 plus amendments. (SI 2000/2531)
7 Statutory Instrument 2000 No. 2532 The Building (Approved Inspectors etc.) Regulations 2000
8 Statutory Instrument 2002 No. 2872, The Building (Approved Inspectors etc.) (Amendment)
Regulations 2002
9 The Building Regulations 1991 Approved Document B Fire Safety. HMSO 2000 (including the Building
Regulations 2000 Amendments to Approved Document B (Fire Safety) coming into effect March 2003)
10 The Building Standards (Scotland) Regulations 1990 Technical Standards Part D (as amended
September 2001)
12 The Building Regulations 2000: Materials and Workmanship. Approved Document to support
Regulation 7, 1999 edition, amended 2000
13 BS 7974, Code of Practice on the Application of Fire Safety Engineering Principles to the Design of
Buildings Draft for Public Comment, BSI 2000. (Note: partially supersedes Fire safety engineering in
buildings, British Standard Draft for Development, DD 240, 1997).
16 Statutory Instrument 1994 No. 3140: Construction (Design and Management) Regulations 1994
D C Mf A Mg 57
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
BS 476-11:1982 Fire tests on building materials and structures. Method for assessing the heat emission
from building materials
BS 476-12:1991 Fire tests on building materials and structures. Method of test for ignitability of
products by direct flame impingement
BS 476-13:1987, ISO 5657:1986 Fire tests on building materials and structures.
Method of measuring the ignitability of products subjected to thermal irradiance
BS 476-15:1993, ISO 5660-1:1993 Fire tests on building materials and structures. Method for
measuring the rate of heat release of products
BS 476-20:1987 Fire tests on building materials and structures. Method for determination of the fire
resistance of elements of construction (general principles)
BS 476-21:1987 Fire tests on building materials and structures. Methods for determination of the fire
resistance of loadbearing elements of construction
BS 476-22:1987 Fire tests on building materials and structures. Methods for determination of the fire
resistance of non-loadbearing elements of construction
BS 476-23:1987 Fire tests on building materials and structures. Methods for determination of the
contribution of components to the fire resistance of a structure
BS 476-24:1987, ISO 6944:1985 Fire tests on building materials and structures. Method for
determination of the fire resistance of ventilation ducts
BS 476-31.1:1983 Fire tests on building materials and structures. Methods for measuring smoke
penetration through doorsets and shutter assemblies. Method of measurement under ambient
temperature conditions
BS 476-32:1989 Fire tests on building materials and structures. Guide to full scale fire tests within
buildings
BS 476-33:1993, ISO 9705:1993 Fire tests on building materials and structures. Full-scale room test for
surface products
19 Guide to Undertaking Assessments in Lieu of Fire Tests The Passive Fire Protection Federation (PFPF)
20 Statutory Instrument 1991 No. 1620: The Construction Products Regulations 1991
23 BS EN 1634-1:2000 Fire resistance tests for door and shutter assemblies. Fire doors and shutters
BS EN 1634-3:2001 Fire resistance tests for door and shutter assemblies. Smoke control doors and
shutters
24 Design Guide for the Fire Protection of Buildings 2000. LPC FPA, London
25 BRE Digest 474. Advice on building handover ‘HOBO protocol; Handover of Office Building Operations’,
BRE Watford WD25 9XX
58 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
26 BS 1635:1990 Recommendations for graphic symbols and abbreviations for fire protection drawings
27 BS 5588-1:1990 Fire precautions in the design, construction and use of buildings. Code of practice for
residential buildings
BS 5588-4:1998 Fire precautions in the design, construction and use of buildings. Code of practice for
smoke control using pressure differentials
BS 5588-5:1991 Fire precautions in the design, construction and use of buildings. Code of practice for
firefighting stairs and lifts
BS 5588-6:1991 Fire precautions in the design, construction and use of buildings. Code of practice for
places of assembly
BS 5588-7:1997 Fire precautions in the design, construction and use of buildings. Code of practice for
the incorporation of atria in buildings
BS 5588-8:1999 Fire precautions in the design, construction and use of buildings. Code of practice for
means of escape for disabled people
BS 5588-9:1999 Fire precautions in the design, construction and use of buildings. Code of practice for
ventilation and air conditioning ductwork
BS 5588-10:1991 Fire precautions in the design, construction and use of buildings. Code of practice for
shopping complexes
BS 5588-11:1997 Fire precautions in the design, construction and use of buildings. Code of practice for
shops, offices, industrial, storage and other similar buildings
30 BS 5950-8;1990 Structural use of steelwork in building. Code of practice for fire resistant design
D C Mf A Mg 59
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
35 The British Woodworking Federation, BWF Guide No.12 – Guide to selection of fire-resisting doors.
36 BS 4847: Pt 1: 1980 Internal and external wood doorsets, door leaves and frames. Pt 1 – specification
for dimensional requirements
37 BS 8214:1990 Code of practice for fire door assemblies with non-metallic leaves
38 BS EN 1154:1997 Building hardware. Controlled door closing devices. Requirements and test methods
39 TRADA: Timber Fire-resisting Doorsets: maintaining performance under the new European test standard
40 BS 5499-1:2002 Graphical symbols and signs. Safety signs, including fire safety signs. Specification for
geometric shapes, colours and layout
BS 5499-2:1986 Fire safety signs, notices and graphic symbols. Specification for self-luminous fire
safety signs
BS 5499-3:1990 Fire safety signs, notices and graphic symbols. Specification for internally-illuminated
fire safety signs
BS 5499-4:2000 Safety signs, including fire safety signs. Code of practice for escape route signing
BS 5499-5:2002 Graphical symbols and signs. Safety signs, including fire safety signs. Signs with
specific safety meanings
BS 5499-6:2002 Graphical symbols and signs. Safety signs, including fire safety signs. Creation and
design of graphical symbols for use in safety signs. Requirements
BS 5499-11:2002 Graphical symbols and signs. Safety signs, including fire safety signs. Water safety signs
43 Glass and Glazing Federation: Glass and Glazing datasheet 2.8: Fire Resistant Glazing
44 BR 135 Cladding
BRE Report Fire performance of external thermal insulation for walls of multi-storey buildings
(BR 135, 1988, revised 2003)
45 BS 8414-1:2002 Fire performance of external cladding systems. Test methods for non-loadbearing
external cladding systems applied to the face of a building
47 BS 8300:2001 Design of buildings and their approaches to meet the needs of disabled people. Code
of practice
60 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
D C Mf A Mg 61
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
62 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
D C Mf A Mg 63
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
PRODUCT TESTING, RESEARCH, PRODUCT AND INSTALLER CERTIFICATION AND FIRE SAFETY
ENGINEERING
BMTRADA Ltd (for Trada Q Mark)
Chiltern International Fire Ltd.
Stocking Lane, Hughenden Valley, High Wycombe, Buckinghamshire HP14 4ND
T: 01494 563091 F: 01494 565487 W: www.chilternfire.co.uk
E: info@chilternfire.co.uk
BRE Certification (Incorporating the Loss Prevention Council (LPC) for LPCB Certification) FRS
Building Research Establishment, Garston, Watford, WD25 9XX UK
T: 01923 664960 F: 01923 664910 W: www.bre.co.uk/frs
E: shippm@bre.co.uk
64 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Some of the organisations listed above have a number of interests. This listing is only a guide and full details
can be found on the appropriate website.
D C Mf A Mg 65
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
18 GLOSSARY
Air transfer grille: A device which allows the passage of ventilation air in normal conditions through a fire
door, wall or partition; but, closes automatically to prevent the passage of fire in a fire condition for a
stipulated time period.
Automatic fire and smoke damper: A device which allows the passage of ventilation air in normal
conditions through a duct, fire wall or partition; but closes automatically to prevent the passage of smoke
and fire in a fire condition for a stipulated period of time. Response to smoke is typically achieved by linking
to the automatic fire detection system.
Building hardware (ironmongery): Fittings designed for incorporation in a fire-resisting doorset and
which contribute to ensure that the fire-resisting door (when closed) resists the passage of fire and/or
gaseous products of combustion. Such fittings include hinges, pivots, door closing devices, latches, locks,
and door furniture (lever handles, knobs).
Cavity barrier: A construction provided to close a concealed space against the penetration of smoke and
flame or to restrict the movement of smoke or flame within such a space, for a stipulated time period.
Combustibility (BS 476-4): This assesses whether a material will burn and add to a fire when subjected to
an existing fire. Spread of flame (BS 476-7) this assesses whether the fire will spread over the surface of the
material (especially wall linings).
Compartment (fire): A building or part of a building, comprising one or more rooms, spaces or storeys,
constructed to prevent the spread of fire to or from another part of the same building, or an adjoining
building. The basis of compartmentation is to subdivide buildings into areas of manageable risk, to provide
adequate means of escape, and to provide fire separation for adjoining buildings.
Drywall: A generic term used to describe a range of metal and timber framed assemblies clad with gypsum
plasterboard and other board materials for standard dry lining, partitions and ceilings which involve little or
no wet operations.
European Technical Approval (ETA): Favourable technical assessment of the fitness for use of a product
for an intended use, based on the fulfilment of the Essential Requirements for building works for which the
product is used (article 8, 9 and 4.2 of the CPD). An ETA can be issued on the basis of a Guideline (article
9.1 of the CPD) or without guideline (article 9.2 of the CPD)
European Technical Approval Guideline (ETAG): Document used as the basis for preparing ETAs, which
contains specific requirements for the products within the meaning of the Essential Requirements, the test
procedures, the methods of assessing and judging the results of the tests, the inspection and conformity
procedures, written by EOTA (the European Organisation for Technical Approvals) on the base of a mandate
received from the Commission (article 9.1 and 11 of the CPD)
Fire damper: A device which allows the passage of ventilation air in normal conditions through a duct,
wall or partition; but, closes automatically to prevent the passage of fire in a fire condition for a stipulated
time period.
Fire door (assembly): A door or shutter, provided for the passage of persons, air or objects, which
together with its frame and furniture as installed in a building, is intended, when closed, to resist the
passage of fire and/or gaseous products of combustion, and is capable of meeting specified performance
criteria to those ends. (BS 5599-11 and AD B)
66 D C Mf A Mg
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Fire-resisting (fire resistance): The ability of a component or construction of a building to satisfy for
a stated period of time some or all of the appropriate criteria specified in the relevant part of BS 476
(AD B and BS 5588-11)
Fire-resisting composite panel: A fully bonded steel faced panel with mineral fibre or other non
combustible core which is used for cladding external walls of steel building structures to form a separating
element from one building to another; and, for high risk areas within buildings to form a separating
element. It is designed to restrict the spread of fire from the compartment or building of origin for a
stipulated period of time.
Fire-resisting doorset: A complete installed door assembly comprising door frame, door leaves, other
panels, building hardware, seals and any glazing that, when closed, is intended to resist the passage of fire
and smoke in accordance with specified performance criteria. (ASDMA guide)
Fire-resisting ductwork: Ventilation or extraction ductwork designed to contain fire and the products of
combustion in a manner that does not allow passage to other parts of the building from the compartment
of origin for a stipulated time period.
Fire-resisting glass: A glass that demonstrates its ability to meet the defined heating and pressure
conditions specified in EN 1363-1 Fire resistance Test (or any other National or International fire resistance
test method). Typically, the glass will be clear, textured, toughened, laminated or wired and may
incorporate special features such as coatings or laminations that enable the glass to achieve a particular
fire performance in terms of integrity and insulation. Each glass may have a unique chemical composition
and its fire test performance may be dependant on or affected by the pane size, aspect ratio, edge cover,
glazing method and type of frame and its fixing. Other fire performance parameters may be requested by
the test sponsor to classify the glass according to EN 13501-2, such as the measurement of radiation as
defined in EN 1363-2.
Fire-resisting glazed screen: Glazed structure or window incorporating fire-resisting glass and designed to
resist the spread of fire and the gaseous products of combustion for a stipulated period of time.
Fire-resisting luminaire: Lighting structure or fitting for suspended ceilings designed to resist the spread of
fire and the products of combustion for a stipulated period of time. It is required to be tested for integrity
when fitted to an individual manufacturer’s suspended ceiling.
Fire-resisting partition: An internal non load bearing vertical dividing structure designed to resist the
spread of fire, heat, and the products of combustion for a stipulated period of time. Such a partition can
include a glazed section or a fire door.
Fire-resisting suspended ceiling: A suspended ceiling designed to contribute to the overall fire
resistance of a floor assembly or to prevent the collapse of steel beams supporting a floor or roof,
for a stipulated period of time. It may also provide fire resistance as a membrane in the same way as a
partition.
Fire Safety Engineering is the application of scientific and engineering principles, rules [Codes], and
expert judgement, based on an understanding of the phenomena and effects of fire and of the reaction
and behaviour of people to fire, to protect people, property and the environment from the destructive
effects of fire.
Fire separating element: A compartment wall, compartment floor, cavity barrier and construction
enclosing a protected escape route and/or a place of special fire hazard. (AD B).
D C Mf A Mg 67
E N S U R I N G B E ST P R A C TI C E F O R PA S S IVE F I R E P R OTE C TI O N I N B U I LD I N G S
Fire Shutters. These can be collectively defined with fire-resisting doors as ‘a door, or shutter, provided for
the passage of persons, air or objects, which together with its frame and furniture as installed in a
building, is intended (when closed) to resist the passage of fire and/or gaseous products of combustion,
and is capable of meeting specified performance criteria to those ends’. A door or shutter across means of
escape should only be released by a heat sensor in the immediate vicinity of the door, and not initiated by
smoke detectors or a fire alarm system, unless the shutter is also intended to partially descend to form
part of a smoke reservoir.
Fire-stopping: Sealing products that take up imperfections of fit or design tolerance between the
fire-resisting fixed elements of a building to restrict the passage of fire and smoke. They continue to take
up the imperfections of fit at all times and have the same fire rating as the fixed elements of which they
form a part. In reaction to a fire condition they swell, spread or deform to achieve their performance.
Fusible link: Device installed local to the door or shutter which will fracture at a specified temperature to
release a door closing mechanism. (This originates from prEN 14600 for fire doors)
Penetration seal: Products that maintain the integrity and insulation of fire-resisting separating elements
where services pass through the element. They are designed to allow for any movement and to close any
opening that may be expected to occur in a fire situation. For the purpose of this study penetration seals
have been included under fire-stopping products.
Protected Shaft. A protected shaft is defined as ‘ a shaft which enables persons, air or objects to pass
from one compartment to another, and which is enclosed in fire-resisting construction’.
Reaction to fire tests assess a number of properties and materials: Ignitability (BS 476-5, 12, 13) this
assesses whether a material is likely to catch fire.
Reaction to fire: This is the extent to which a product burns and contributes to the development of a fire.
Resistance to Fire: The ability of a product to prevent the spread of flame and/or smoke, and, where
relevant to maintain mechanical stability. Resistance to fire tests to assess the ability of a product when
used in specific circumstances to perform in a particular manner are defined in BS 576 parts 20 to 24.
Responsible person is the employer, where there is one, and where there is not it will be the person
responsible for the activity undertaken on the premises which might give rise to a risk to those present. It
includes;
a the employer in relation to any workplace which is to any extent under his control;
b in relation to any premises where there is no employer –
i the person (whether the occupier or owner of the premises or not) who has the overall
management of the premises; or
ii where there is no one with overall management responsibility, the occupier of the premises; or
iii where neither (i) or (ii) apply, the owner of the premises
Structural fire protection: Products used to insulate the structural frame of a building or other
construction to allow it to retain its required load bearing strength or limit the core temperature for a
stipulated period of time. The time periods may be stipulated in Building Regulations, IMO Regulations,
Safety Case studies or Safety designs according to the type of structure involved.
68 D C Mf A Mg
ACKNOWLEDGMENTS
The following individuals and organisations have participated in the development of this guidance.
This Guidance is the outcome of a three year ‘Partners in Innovation’ project, which was partly funded by
ODPM and DTI. The contribution of ODPM and DTI is gratefully acknowledged.
This document has been produced by the ASFP as part of a PII let by the Department of Trade and Industry
(DTI)/Office of the Deputy Prime Minister (ODPM). Any views expressed in it are not necessarily those of
the DTI or the ODPM.
Cover photographs courtesy of Pilkington Pyrostop, Leigh Paints, Fire Protection Ltd, Nullifine Ltd
Price £25
ASFP Association House, 99 West Street, Farnham, Surrey GU9 7EN Web: www.asfp.org.uk
ISBN 1 870409 19 1