Inverse Modeling To Estimate The Effective Leakage Area in Buildings
Inverse Modeling To Estimate The Effective Leakage Area in Buildings
Inverse Modeling To Estimate The Effective Leakage Area in Buildings
ABSTRACT
Infiltration plays a significant role in the energy
consumption of buildings. Estimating infiltration rates
can provide insights into building energy consumption
patterns. Both Effective Leakage Area (ELA) and Air
Change rate per Hour (ACH) can be used to describe
the air infiltration rate in the building. This paper
presents an approach using the ELA as the major
parameter to model infiltration in existing buildings
The conventional way to estimate the aggregated ELA
value of a building is through a blower-door test, which
is rather expensive in practice. This study introduces a
lower cost alternative to estimate the ELA using inverse
modeling approach .
INTRODUCTION
Infiltration can lead to many negative effects in
commercial buildings in the U.S. Unexpected and
uncontrolled high air change rates can reduce the
thermal comfort and indoor air quality (IAQ), interfere
the operation of mechanical ventilation systems, and
cause moisture damage in building envelopes and mold
growth on internal surfaces and increase total building
energy consumption. Studies have shown that
infiltration is responsible for 33% of the total heating
energy use in U. S. office buildings (Emmerich 2005).
Therefore, controlling air leakage in buildings as part of
retrofits can achieve significant energy savings.
Building energy simulation tools can provide insights
into the infiltration impact on the total energy
consumption using a reasonable estimation of air
infiltration rates. There are two main ways to estimate
air infiltration rates: determining the Effective Leakage
Area (ELA) or determining the Air Change rate per
Hour (ACH). This paper proposes an inverse modeling
approach (also referred as calibration) to estimate the
ELA. This approach integrates a multi-zone airflow
model in CONTAM (CONTAM 2013) with a building
energy model in EnergyPlus (EnergyPlus 2013). We
first calculate dynamic infiltration rates in CONTAM
with different ELA estimations as inputs. Then we use
these calculated dynamic infiltration rates as inputs to
BACKGROUD
1. Blower-door test approach
The air leakage through the building envelope can be
measured with a pressurization test, which is commonly
called a blower-door test (ASHRAE 2009). In this
method, a large fan or blower is mounted in a door or
window inducing a roughly uniform large pressure
difference across the building shell (ASTM Standards
E779 and E1827; Canadian General Standards Board
(CGSB) Standard 149.10; ISO Standard 9972). The
airflow required to maintain this pressure difference is
the infiltration rate under this applied pressure
difference. Consequently, the result of a pressurization
test is combinations of different pressure differences
and corresponding airflow (infiltration) rate. Equation 1
shows the formula to calculate the total leakage area.
where
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
323
+
2
where
{ } { }
where
building height, m;
reference height of one-story building, 2.5m.
Table 1 Stack Coefficient Cs
Stack Coefficient
House Height
one
two
three
0.000145 0.00029 0.000435
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
324
(http://www.eebhub.org/projects-list/navy-yard-buildin
g-101)
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
325
)(
+ |
+
)[
|+
Here
is the CONTAM simulation result
(2
33 values), we set
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
326
is a vector of n predictions
is the vector of the true values
In this case study,
is the real measured data of boiler
gas consumption, is the predicted boiler
consumption from the EnergyPlus model.
Table 5 lists the measurement results from the blowerdoor test. Based on the whole building depressurization
test conducted by Camroden Associates, Inc, we
derived the power law of the whole building:
23
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
327
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
328
ACKNOWLEDGMENT
This work is partially funded by Energy Efficient
Buildings Hub, sponsored by the Department of Energy
under Award Number DE-EE0004261.
REFERENCES
ASHRAE
(2009).
Fundamentals.
Chapter16 American Society of Heating,
Camroden Associates, Inc 2012. Report on the
building envelope air tightness and pressure
relationship mapping, report submitted to
Philadelphia Industrial Development Corporation
CONTAM
http://www.bfrl.nist.gov/IAQanalysis/CONTAM/
Design Builder 2005
http://www.designbuilder.co.uk/
Emmerich, S.J., Persily, A.K. 2005. Impact of
Infiltration on Heating and Cooling Loads in U.S.
Office Buildings. AIVC Conference.
EnergyPlus
http://apps1.eere.energy.gov/buildings/energyplus/
Gowri, K., D. Winiarski, and R. Jarnagin. (2009).
Infiltration modeling guidelines for commercial
building energy analysis. PNNL #18898. Richland,
WA: Pacific Northwest National Laboratory.
M.C. Kennedy, A. OHagan, (2001). Bayesian
calibration of computer models, Journal of the
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
329
2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission
in either print or digital form is not permitted without ASHRAEs prior written permission.
330