VL Molded Case Circuit Breakers

Trip Unit Overview


Selection

mation menus. With precise control


over the circuit beaker functions and
access to system status, diagnostics,
and information, these trip units allow
for unsurpassed flexibility in circuit
coordination.

The interchangeability of the VL circuit


breaker trip units allow for easy conversion from any of 3 types of protection.
They are thermal-magnetic, electronic,
or electronic with a built-in LCD display.
The thermal-magnetic trip unit features
an adjustable magnetic trip setting. The
electronic trip units are microprocessor
based true RMS sensing devices and
are available with a variety of adjustable
trip settings, configurations, and infor-

An example of coordination is the out


of the box Ground Fault function on the
Model 545 trip units. The pick-up and
time delay settings are fixed for each

frame and do not overlap with the settings on the other frames. Therefore,
when VL breakers are used together in
a system the GF protection is automatically coordinated. The user also has the
ability to program a custom coordination scheme with the high level of
adjustability available on the Model
576 trip units.

VL Trip Units
Trip Unit Functions

Model 525

Model 545

Model 576

ThermalMagnetic

Electronic
LI

Electronic
LIG

Electronic
LSI

Electronic
LSIG

Electronic with LCD


LSI

Electronic with LCD


LSIG

Continuous Current
Setting (Ir)

Fixed

Long Time Delay (tr)

Fixed

Fixed

Instantaneous
Overcurrent Setting (Ii)

Fixed

Fixed

Short Time Pick-up (Isd)

(ON/OFF)

(ON/OFF)

Short Time Delay (tsd)


Short Time l t Pick-up
2

Ground Fault Pick-up (lg)


Ground Fault Delay (tg)
Alarm & Status LEDs
Built-in Display (LCD)
Pre-Trip Alarm
Last trip information
Zone Selective
Communications

Fixed
Fixed

Fixed
Fixed

Adjustable setting.
This feature is included.
fixed Non-Adjustable setting.
Feature is not included.
Requires the trip unit to be connected to a PC (via a COMPRO or COMMOD communications module) for access or programming.

Continuous Amps Rating (Ir)


This setting is the continuous current
that the breaker will carry without tripping. It can be set up to 100% of the trip
units nominal rating (In).
Long Time Delay (tr)
Sometimes referred to as the overload
position, this function controls the breakers pause-in-tripping time. It allows
low level, temporary inrush currents
such as those encountered when starting a motor to pass without tripping. The
time delay begins when the current
reaches 6 x Ir.
Instantaneous Pick-up (Ii)
This function sets the breaker to trip
instantaneously during high fault conditions. On Model 545 trip units this setSiemens Industry, Inc.
Industrial Controls Catalog

ting is fixed on LSI and LSIG trip units


and adjustable on LI and LIG trip units.
These features are fully adjustable on
Model 576 trip units.
Short Time Pick-Up (lsd)
This function controls the level of fault
current the breaker will carry for a short
time without tripping, thus allowing
downstream devices to clear short circuits ahead of up-stream protection.
It may be defeated (turned-off) on
Model 576 trip units.
Short Time Delay (tsd)
This controls the interval of time the
breaker will remain closed against a fault
(at the Short Time Pick-up current level)
without tripping. The time delay may be
set at fixed points or at short time intervals based on l2t curves. This function is

used with the Short Time Pick-up to


achieve selectivity and better system
coordination.
Ground Fault Pick-Up (Ig)
This setting controls the level of ground
fault current that will cause the breaker
to trip. Model 545 Electronic Trip Units
act on the residual current to sense
ground current. The Model 576
Electronic Trip Unit is programmable
and allows the user to select either
the residual current method or direct
detection (via a separate current transformer) to detect ground current.
Ground Fault Time Delay (tg)
This controls the interval of time the
breaker will remain closed after a ground
fault is detected (at the Ground Fault
Pick-up current level) without tripping.
17/15

VL Molded Case Circuit Breakers

General Information
Selection

Thermal-Magnetic trip units, Model 525, combine the inverse time element design for low level overloads, and instantaneous
magnetic action for short circuit protection. The standard unit has preset overload protection and an adjustable instantaneous trip
setting, with 6 set points. Thermal-Magnetic trip units are available throughout the VL family, from 15 to 1600A.

Type/Tipo CLT3

Ii

M4-PAN-TORX

M4-PAN-TORX

I n = 600A
3850
3300
2750

4400

40 C

4950

TM ~

5500

Trip Unit/Disparador 525

Cat. No. CLT3B600

Electronic Trip Units


Electronic trip units are available through
the VL family, from 60A (which can be
set as low as 30A) up through 1600A .
They are also available in four trip
configurations (LI, LIG, LSI, LSIG) and
features can include a built-in LCD
display.
On the Model 545 Electronic Trip Unit a
flashing LED confirms that the

microprocessor in operating and another


indicates an overload condition. For
ease-of-use and to insure proper
coordination, the set points for the
continuous current are shown on the
face of these trip units in amps.

displays, no secondary or auxiliary voltage is required as long as the breaker is


energized and a minimal load current is
present. These trip units can also indicate the last trip status (date, time,
amps) when theyre connected to a PC
via one of our communications modules.

On the Model 576, the LCD version, the


current in each phase is continuously
shown on the display. Unlike many

Typical Trip Unit Labeling and Adjustment Positions


Model 545 Electronic Trip Unit
with LSIG trip functions

Model 576 Electronic Trip Unit


has an LCD display

17/16

Siemens Industry, Inc.


Industrial Controls Catalog