Xgard Manual
Xgard Manual
Xgard Manual
Gas Detectors
Installation, operating
and maintenance
instructions
M07249
May 2004
Safety information
Xgard gas detectors must be installed, operated and maintained in
strict accordance with these instructions, warnings, label information,
and within the limitations stated.
The lid on flameproof versions of Xgard must be kept tightly closed
until power to the detector is isolated otherwise ignition of a flammable
atmosphere can occur. Before removing the cover for maintenance or
calibration purposes, ensure the surrounding atmosphere is free of
flammable gases or vapours.
Xgard detectors are designed to detect gases or vapours in air, and
not inert or oxygen deficient atmospheres. Xgard oxygen detectors
can measure in oxygen deficient atmospheres.
Electrochemical cells used in toxic and oxygen versions of Xgard
contain small volumes of corrosive electrolyte. Care should be
observed when replacing cells to ensure that the electrolyte does not
come into contact with skin or eyes.
Maintenance and calibration operations must only be performed by
qualified service personnel.
Only genuine Crowcon replacement parts must be used, substitute
components may invalidate the certification and warranty of the
detector.
Xgard detectors must be protected from extreme vibration, and direct
sunlight in hot environments as this may cause the temperature of the
detector to rise above its specified limits and cause premature failure.
This equipment must not be used in a Carbon Disulphide atmosphere.
Safety information
Zone 1:
Zone 2:
Notes:
In North America Divisions are used to categorise risk where:
Division 1 is equivalent to Zone 0 or 1
Division 2 is equivalent to Zone 2
Under European ATEX rules hazardous area equipment has been
re-defined under equipment categories where:
Equipment Category 1 is suitable for Zone 0
Equipment Category 2 is suitable for Zone 1
Equipment Category 3 is suitable for Zone 2
Overview
Product overview
Xgard are a family of gas detectors for monitoring a very wide range of
toxic and flammable gases and oxygen. Xgard are available as either
Intrinsically Safe (Exia) or Flameproof (Exd) detectors, dependant upon
sensor type and customer preference. Intrinsically Safe versions are
suitable for use in Zone 0, 1 or 2 hazardous areas when used with a
suitable Zener barrier or galvanic isolator. Flameproof versions are
suitable for use in Zone 1 or 2 hazardous areas.
Please refer to the certification label on the detector junction box to
identify the type of certification that relates to the product supplied.
Hazardous area definitions are shown in the Hazardous area
classifications section on page 3.
Note: if no certification label is fitted to the junction box, the
detector is not certified for use in hazardous areas.
Overview
Each type of Xgard detector is identified by a label fitted on the junction
box body. Please quote the model number, gas range and sensor type
when contacting Crowcon for advice or spares.
This manual covers all versions of Xgard, care should be taken to ensure
that the correct section is referenced according to the type of detector
used. The Xgard detector type is detailed on the product label. The
Xgard range is as shown:
Type 1: Intrinsically safe toxic and oxygen gas detector
Type 2: Flameproof toxic and oxygen gas detector
Type 3: Flameproof flammable gas detector
Type 4: Flameproof high temperature flammable gas detector
Type 5: Flameproof flammable gas detector with 4-20mA output
Type 6: Flameproof thermal conductivity type gas detector
Type 7: Flameproof Sulphistor hydrogen sulphide gas detector
Product description
Xgard comprises of a universal assembly to accommodate the full range
of toxic, flammable and oxygen gas sensors. The assembly comprises
five main parts; the junction box, junction box lid, amplifier/terminal PCB,
sensor PCB and sensor retainer. These are shown in exploded form in
Diagram 3.
A cover is fitted over the amplifier PCB to provide protection when the
junction box is opened. This cover is designed to allow access to all
cable terminals, test points and potentiometers without the need for
removal. The modular sensor retainer is supplied without an insert for I.S.
versions, and with a sinter assembly for Flameproof versions.
The junction box is manufactured from marine grade aluminium with a
durable polyester coating (stainless steel option is available), and is used
for both Flameproof and Intrinsically Safe versions. The junction box is
supplied with 1 x M20, M25, 12" or 34"NPT cable gland entry, on the right
hand side for customer use. The junction box is suitable for fixing on the
wall or ceiling using M6 fixings. Cable gland adaptors are available if
required (see Spare parts and accessories section).
Overview
Slots to suit M6
or 1/4 fixings for
ceiling mount
36 Slot
CRS
155.5 Overall
166.3 Overall
Height 111
146 CRS
Overview
Certification label
Enclosure lid
PCB cover
Lid O-ring seal
Enclosure
base
Sensor Housing
Assy
Sensor retainer
O-ring seal
Sensor retainer
Table of contents
Type 1 - Intrinsically safe toxic and oxygen gas detector . . . . . . . .9
1. Introduction ......................................................................................9
2. Installation ......................................................................................10
3. Operation........................................................................................13
4. Specification...................................................................................16
Type 2 - Flameproof toxic and oxygen gas detector . . . . . . . . . . .17
1. Introduction ....................................................................................17
2. Installation ......................................................................................18
3. Operation........................................................................................21
4. Specification...................................................................................24
Type 3 - Flameproof flammable gas detector . . . . . . . . . . . . . . . .25
1. Introduction ....................................................................................25
2. Installation ......................................................................................26
3. Operation........................................................................................29
4. Specification...................................................................................32
Type 4 - Flameproof high temperature flammable gas detector . .33
1. Introduction ....................................................................................33
2. Installation ......................................................................................34
3. Operation........................................................................................37
4. Specification...................................................................................40
Type 5 - Flameproof flammable gas detector with 4-20mA output .41
1. Introduction ....................................................................................41
2. Installation ......................................................................................42
3. Operation........................................................................................45
4. Specification...................................................................................49
Type 6 - Flameproof thermal conductivity type gas detector . . . .50
1. Introduction ....................................................................................50
2. Installation ......................................................................................51
3. Operation........................................................................................54
4. Specification...................................................................................58
Type 7 - Flameproof Sulphistor hydrogen sulphide gas detector .59
1. Introduction ....................................................................................59
2. Installation ......................................................................................60
3. Operation........................................................................................63
4. Specification...................................................................................68
Spare parts and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Appendix: Sensor limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
8
1. Introduction
Xgard Type 1
Earth
Test
points
Set zero
Run
2. Installation
Xgard Type 1
WARNING
This detector is designed for use in Zone 0, Zone 1 and Zone 2
hazardous areas, and is certified
II 1 G EEx ia IIC T4 when
used with a suitable Zener barrier or galvanic isolator.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level and Crowcon recommend the use of a collector
cone (Part No. C01051) and accessory adaptor (Part No. M04666).
To detect heavier than air gases, detectors should be mounted at low
level.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a Spray Deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Mounting of oxygen detectors requires knowledge of the gas
displacing the oxygen. For example, carbon dioxide is heavier than air
and collects in low lying areas. It will displace oxygen and so
detectors should be placed at low level.
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, ammonia is normally
lighter than air, but if released from a cooling system, the gas may fall
rather than rise.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
10
2. Installation
Xgard Type 1
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Resistance
Max. Distance
(Ohms per km)
(km)
Awg Cable
Loop
1.0
1.5
2.5
17
15
13
18.1
12.1
7.4
36.2
24.2
14.8
9.4
14
23
0.35
0.5
0.85
2. Installation
Xgard Type 1
Control Panel
SIG
I.S. Earth
HAZARDOUS AREA
SAFE AREA
2
1
4
MTL
3 715+ / 728+
SIG
I.S. Earth
Control Panel
KF D2-CR-Exl.30200
3 Pepperl & Fuchs 7
8
1
1211
24V dc
Supply
SIG
Earth
SAFE AREA
HAZARDOUS AREA
1
2
MTL
5041
1314
11
12
24V dc
Supply
12
SIG
Earth
3. Operation
Xgard Type 1
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
160
x Gas
Range
+ 40 = mV setting
13
3. Operation
160
x 150
250
Xgard Type 1
+ 40 = 136 mV
3. Operation
Xgard Type 1
15
4. Specification
Junction box material
Xgard Type 1
Dimensions
Weight
Operating voltage
830 V dc
Output
Fault signal
< 3mA
16
Humidity
Degree of protection
Explosion protection
Intrinsically Safe
Approval code
ATEX
II 1 G EEx ia IIC T4
Tamb = -40 to 55C
UL Class I, Division 1, Groups A, B, C & D
ATEX Baseefa04ATEX0115
Standards
Zones
Gas groups
EMC
EN50270
1. Introduction
Xgard Type 2
Earth
Test
points
Set zero
Run
2. Installation
Xgard Type 2
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T6.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level and Crowcon recommend the use of a collector
cone (Part No. C01051) and accessory adaptor (Part No. M04666).
To detect heavier than air gases, detectors should be mounted at low
level.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a Spray Deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Mounting of oxygen detectors requires knowledge of the gas
displacing the oxygen. For example, carbon dioxide is heavier than air
and collects in low lying areas. It will displace oxygen and so
detectors should be placed at low level.
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, ammonia is normally
lighter than air, but if released from a cooling system, the gas may fall
rather than rise.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
18
2. Installation
Xgard Type 2
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
1.0
17
18.1
36.2
9.4
1.5
15
12.1
24.2
14
2.5
13
7.4
14.8
23
2. Installation
Xgard Type 2
Control Panel
SIG
Earth
8-30v dc
4-20mA
(Source)
20
3. Operation
Xgard Type 2
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
160
x Gas
Range
+ 40 = mV setting
160
x 150
250
+ 40 = 136 mV
21
3. Operation
Xgard Type 2
3. Operation
Xgard Type 2
23
4. Specification
Junction box material
Xgard Type 2
Dimensions
Weight
Operating voltage
830 V dc
Output
Fault signal
< 3mA
24
Humidity
Degree of protection
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T6
Tamb = -40 to 50C
UL Class I, Division 1, Groups B, C & D
ATEX Baseefa04ATEX0024X
Standards
Zones
Gas groups
EMC
EN50270
1. Introduction
Xgard Type 3
Earth
2. Installation
Xgard Type 3
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T6 for
operation up to 50C (122F),
II 2 G EExd IIC T4 for
operation up to 80C (176F). Installation must be in
accordance with the recognised standards of the appropriate
authority in the country concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level and Crowcon recommend the use of a collector
cone (Part No. C01051) and accessory adaptor (Part No. M04666).
To detect heavier than air gases, detectors should be mounted at low
level.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a Spray Deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, butane is normally
heavier than air, but if released from a process which is at an elevated
temperature and/or pressure, the gas may rise rather than fall.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
26
2. Installation
Xgard Type 3
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Pellistor
Type
Bridge Volts
(Vdc)
Comment
S011251/S
300P
2.0
S011509/S
VQ21T
2.0
S011506/S
VQ8
2.5
S011712/S
VQ25
2.0
For halogens
S011487/S
VQ41
2.0
S011489/S
VQ41
2.0
For Ammonia
27
2. Installation
Xgard Type 3
Resistance
(Ohms per km)
Cable
Loop
mm2 Awg
Max. Distance
Max. Distance
(km)
(km)
2.0 volt pellistors 2.5 volt pellistors
1.0
17
18.1
36.2
1.47
1.42
1.5
15
12.1
24.2
2.2
2.13
2.5
13
7.4
14.8
3.6
3.5
SIG
Control Panel
SIG
Earth
See table 3 for sensor voltage settings
3. Operation
Xgard Type 3
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
3.1
Commissioning procedure
1. Open the junction box of the detector by unscrewing the lid in an anticlockwise direction (having loosened the retaining grub-screw first).
2. Check that all electrical connections have been made and are correct
as per Diagram 9.
3. Measure the voltage across the + and - terminals and adjust
according to the type of pellistor fitted (see Table 3).
4. Leave the detector to stabilise for at least 1 hour.
5. Balance the WB circuit at the control panel if necessary. Refer to the
control equipment instruction manual.
Zeroing the detector
6. Ensure you are clean air. Adjust the control equipment to read zero.
Calibrating the detector
7. Apply calibration gas (concentration should be 50% LEL) to the
detector at a flow rate of 0.5 - 1 litre/minute via a flow adaptor (Part
No. C03005). Contact Crowcon for the supply of calibration gas.
8. Allow the gas reading to stabilise (usually 30 to 60 seconds) and
adjust the control equipment to read 50% LEL.
9. Remove the gas and allow the sensor to completely settle before rechecking the zero setting.
10.Close the junction box of the detector ensuring that the lid is securely
tightened, and the grub-screw is secured.
11.The detector is now operational.
29
3. Operation
Xgard Type 3
30
3. Operation
Xgard Type 3
31
4. Specification
Junction box material
Xgard Type 3
Dimensions
Weight
Electrical output
3-wire mV bridge.
Typically 12-15mV per % LEL CH4
32
Humidity
Degree of protection
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T6
Tamb = -40 to 50C
ATEX
II 2 G EExd IIC T4
Tamb = -40 to +80C
UL Class I, Division 1, Groups B, C & D
ATEX Baseefa04ATEX0024X
Standards
Zones
Gas groups
EMC
EN50270
1. Introduction
Xgard Type 4
Earth
+++SIG
-- SIG
SIG
Red
Black
White
196 Overall
146
166.3 Overall
Height 111
2. Installation
Xgard Type 4
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T3.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level.
To detect heavier than air gases, detectors should be mounted at low
level.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding.
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, butane is normally
heavier than air, but if released from a process which is at an elevated
temperature and/or pressure, the gas may rise rather than fall.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
34
2. Installation
Xgard Type 4
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Comment
C01883
VQ21T
2.0
Poison resistant
C01884
VQ41
2.0
Fuel vapours/ammonia
35
2. Installation
Xgard Type 4
Awg
17
15
13
Resistance
(Ohms per km)
Cable
Loop
18.1
36.2
12.1
24.2
7.4
14.8
Max. Distance
Max. Distance
(km)
(km)
2.0 volt pellistors 2.5 volt pellistors
1.47
1.42
2.2
2.13
3.6
3.5
Control Panel
SIG
Earth
SIG
3. Operation
Xgard Type 4
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
3.1
Commissioning procedure
1. Open the junction box of the detector by unscrewing the lid in an anticlockwise direction (having loosened the retaining grub-screw first).
2. Check that all electrical connections have been made and are correct
as per Diagram 11.
3. Measure the voltage across the + and - terminals and adjust
according to the type of pellistor fitted (see Table 5).
4. Leave the detector to stabilise for at least 1 hour.
5. Balance the WB circuit at the control panel if necessary. Refer to the
control equipment instruction manual.
Zeroing the detector
6. Ensure you are clean air. Adjust the control equipment to read zero.
Calibrating the detector
7. Apply calibration gas (concentration should be 50% LEL) to the
detector at a flow rate of 0.5 - 1 litre/minute via a flow adaptor (Part
No. C01886). Contact Crowcon for the supply of calibration gas.
8. Allow the gas reading to stabilise (usually 30 to 60 seconds) and
adjust the control equipment to read 50% LEL.
9. Remove the gas and allow the sensor to completely settle before rechecking the zero setting.
10.Close the junction box of the detector ensuring that the lid is securely
tightened, and the grub-screw is secured.
11.The detector is now operational.
37
3. Operation
Xgard Type 4
38
3. Operation
Xgard Type 4
39
4. Specification
Junction box material
Xgard Type 4
Dimensions
Weight
Electrical output
3-wire mV bridge.
Typically 10mV per % LEL CH4 (Minimum)
40
Humidity
Degree of protection
IP54
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T3
Tamb -20C to +150C
FM Class I, Division 1, Groups B, C & D
Baseefa04ATEX0024X
BAS01ATEX2110X
Standards
Junction Box
VQ600H detector
Zones
Gas groups
EMC
EN50270
1. Introduction
Xgard Type 5
Earth
TP2
Sink
TP4
Test
points
VR3
TP3
Srce
TP1
2. Installation
Xgard Type 5
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T6.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level and Crowcon recommend the use of a collector
cone (Part No. C01051) and accessory adaptor (Part No. M04666).
To detect heavier than air gases, detectors should be mounted at low
level.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a Spray Deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, butane is normally
heavier than air, but if released from a process which is at an elevated
temperature and/or pressure, the gas may rise rather than fall.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
42
2. Installation
Xgard Type 5
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Max. Distance
(km)
2.2
3.3
5.4
43
2. Installation
Xgard Type 5
SIG
Control Panel
SIG
Earth
10-30v dc
4-20mA
(Sink or Source)
44
3. Operation
Xgard Type 5
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
3.1
Commissioning procedure
1. Open the junction box of the detector by unscrewing the lid in an anticlockwise direction (having loosened the retaining grub-screw first).
2. Check that all electrical connections have been made and are correct,
as shown in Diagram 13.
3. Measure the voltage across the + and - terminals and check a
minimum supply of 10V d.c. is present.
4. Leave the detector to stabilise for at least 1 hour.
5. Before calibration of the detector can commence, the pellistors must
be balanced. To do this remove the PCB cover, and connect a digital
volt meter (DVM) to the test points marked TP3 and TP4 on the
amplifier PCB, as shown in Diagram 12). The DVM should be set to the
dc mV range, and the potentiometer marked VR3 should be adjusted
until the DVM reads 0.00mV. The PCB cover can now be replaced.
6. To zero the detector, reconnect the DVM to the test points marked
TP1 and TP2 on the amplifier PCB, as shown in Diagram 12.
Note: At the test points, Zero will read 40 mV = 4 mA.
Full scale deflection (100% LEL) will read 200 mV = 20 mA. There is a
current clamp of 25mA on the 4-20mA output.
Zeroing the detector
7. Ensure you are clean air. Adjust the ZERO pot on the amplifier
(which is accessible via a hole in the PCB cover) until the DVM reads
40 mV. Check that the control equipment display reads zero.
Calibrating the detector
8. Apply calibration gas (concentration should be 50% LEL) to the
detector at a flow rate of 0.5 - 1 litre/minute via a flow adaptor (Part
No. C03005). Contact Crowcon for the supply of calibration gas.
9. Allow the gas reading to stabilise (usually 30 to 60 seconds) and
adjust the CAL pot until the DVM reads the appropriate reading (ie
120mV = 12mA = 50% LEL). If the concentration of the calibration gas
used is not 50% LEL, the following formula can be used to calculate
the reading:
45
3. Operation
160
x Gas
Range
Xgard Type 5
+ 40 = mV setting
160
x 25
100
+ 40 = 80 mV
46
3. Operation
Xgard Type 5
47
3. Operation
Xgard Type 5
Pellistor
Type
Bridge Volts
(Vdc)
Comment
S011251/S
300P
2.0
S011509/S
VQ21T
2.0
S011506/S
VQ8
2.5
S011712/S
VQ25
2.0
For halogens
S011487/S
VQ41
2.0
S011489/S
VQ41
2.0
For Ammonia
48
4. Specification
Junction box material
Xgard Type 5
Dimensions
Weight
Operating voltage
10-30V dc
Current consumption
Output
Fault signal
< 3mA
Maximum cable
loop resistance
Degree of protection
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T6
Tamb -40C to 50C
ATEX
II 2 G EExd IIC T4
Tamb -40C to 80C
UL Class I, Division 1, Groups B, C & D
Baseefa04ATEX0024X
Standards
Zones
Gas groups
EMC
EN50270
49
1. Introduction
Xgard Type 6
TP2
Sink
TP4
Test
points
VR3
TP3
Srce
TP1
2. Installation
Xgard Type 6
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T6.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
The detector should be mounted where the gas to be detected is most
likely to be present. The following points should be noted when locating
gas detectors:
To detect gases which are lighter than air, detectors should be
mounted at high level and Crowcon recommend the use of a collector
cone (Part No. C01051) and accessory adaptor (Part No. M04666).
To detect heavier than air gases, detectors should be mounted at low
level.
If the detector is to be used to monitor gas in a sample line rather
than ambient conditions, a flow adaptor is available for 6mm (1/4") o/d
pipe (Part No. C01339). Crowcon recommend a flow rate of 0.5 - 1
litre/minute, and the sample gas must be suitably filtered to remove
dust and moisture.
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a Spray Deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. For example, butane is normally
heavier than air, but if released from a process which is at an elevated
temperature and/or pressure, the gas may rise rather than fall.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
51
2. Installation
Xgard Type 6
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Resistance
Cable
18.1
12.1
7.4
Max. Distance
(km)
2.2
3.3
5.4
52
2. Installation
Xgard Type 6
SIG
Control Panel
SIG
Earth
10-30v dc
4-20mA
(Sink or Source)
53
3. Operation
Xgard Type 6
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
3.1
Commissioning procedure
1. Open the junction box of the detector by unscrewing the lid in an anticlockwise direction (having loosened the retaining grub-screw first).
2. Check that all electrical connections have been made and are correct
as per Diagram 15.
3. Measure the voltage across the + and - terminals and check a
minimum supply of 10V d.c. is present.
4. Leave the detector to stabilise for at least 1 hour.
5. Before calibration of the detector can commence, the thermal
conductivity sensor must be balanced. To do this remove the PCB
cover, and connect a digital volt meter (DVM) to the test points marked
TP3 and TP4 on the amplifier PCB, as shown in Diagram 14. The
DVM should be set to the dc mV range.
Check the detector label for details of the background gas. This is
normally air, carbon dioxide, nitrogen or argon. Apply a sample of the
background gas (100% volume concentration) to the sensor at a flow
rate of 0.5 1 litre/minute via a flow adaptor (Part No. C03005). If the
background gas is air, the sensor may simply be exposed to ambient
clean air. The potentiometer marked VR3 should be adjusted until the
DVM reads 0.00mV. The PCB cover can now be replaced.
6. Reconnect the DVM to the test points marked TP1 and TP2 on the
amplifier PCB, as shown in Diagram 14.
Note: At the test points, Zero will read 40 mV = 4 mA.
Full scale deflection will read 200 mV = 20 mA. There is a current
clamp of 25mA on the 4-20mA output.
Zeroing the detector
7. Check the detector label for details of the background gas. This is
normally air, carbon dioxide, nitrogen or argon. Apply a sample of the
background gas (100% volume concentration) to the sensor at a flow
rate of 0.5 1 litre/minute via a flow adaptor (Part No. C03005). If the
background gas is air, the sensor may simply be exposed to ambient
clean air. Adjust the ZERO pot on the amplifier (which is accessible
via a hole in the PCB cover) until the DVM reads 40 mV. Check that the
54
3. Operation
Xgard Type 6
160
x Gas
Range
+ 40 = mV setting
Where the Range is the maximum value of the target gas, and Gas is
the concentration of the target gas in the calibration mixture.
Example: calibrating a detector to measure 0-100% volume methane in
carbon dioxide, using 60% CH4 / 40% CO2 calibration gas:
160
x 60
100
+ 40 = 136 mV
55
3. Operation
Xgard Type 6
56
3. Operation
Xgard Type 6
57
4. Specification
Junction box material
Xgard Type 6
Dimensions
Weight
Operating voltage
10-30V dc
Current consumption
Output
Fault signal
< 3mA
Maximum cable
loop resistance
58
Humidity
Degree of protection
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T6
Tamb -40C to 50C
ATEX
II 2 G EExd IIC T4
Tamb -40C to 80C
UL Class I, Division 1, Groups B, C & D
Baseefa04ATEX0024X
Standards
Zones
Gas groups
EMC
EN50270
1. Introduction
Xgard Type 7
Sink
Test
Point
Inhibit
2mA
4mA
Norm
Srce
Diagram 16: Xgard Type 7 PCB layout (Shown with PCB cover removed).
59
2. Installation
Xgard Type 7
WARNING
This detector is designed for use in Zone 1 and Zone 2
hazardous areas, and is certified
II 2 G EExd IIC T6.
Installation must be in accordance with the recognised
standards of the appropriate authority in the country
concerned.
For further information please contact Crowcon. Prior to
carrying out any installation work ensure local regulations and
site procedures are followed.
2.1 Location
Hydrogen sulphide is a highly toxic gas with a density slightly greater
than air, and will therefore tend to settle low down in still air conditions.
However, it also diffuses readily into air and does not behave like a
vapour such as propane which will form pools. Since the toxic risk from
hydrogen sulphide is by ingestion through the mouth and nose, it is
recommended that detectors are mounted at head height.
The following points should also be noted when locating Xgard Type 7:
When locating detectors consider the possible damage caused by
natural events e.g. rain or flooding. For detectors mounted outdoors
Crowcon recommend the use of a spray deflector (Part No. C01052)
and accessory adaptor (Part No. M04666).
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced
air currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. Gas released from a process which
is at an elevated temperature or pressure may rise rather than fall.
The placement of sensors should be determined following advice of
experts having specialist knowledge of gas dispersion, the plant
processing equipment as well as safety and engineering issues. The
agreement reached on the locations of sensors should be recorded.
Crowcon would be pleased to assist in the selection and siting of gas
detectors.
60
2. Installation
Xgard Type 7
2.2 Mounting
Xgard should be installed at the designated location with the sensor
pointing down. This ensures that dust or water will not collect on the
sensor and stop gas entering the cell. The mounting detail is shown in
Diagram 2. Care should be taken when installing the detector to avoid
damaging the painted surface of the junction box and sensor retainer.
Max. Distance
(km)
0.6
0.9
1.5
Table 10: maximum cable distances for typical cables (4-20mA and mV
bridge versions)
61
2. Installation
Xgard Type 7
SIG
Control Panel
SIG
Earth
24v dc (nominal)
4-20mA
(Sink or Source)
SIG
Control Panel
SENSE
Earth
DI 4-11
DI-850
DI-860
DI-800UN
Set detector voltage
to 6.5V dc
62
3. Operation
Xgard Type 7
WARNING
Prior to carrying out any work ensure local regulations and
site procedures are followed. Never attempt to open the
detector or junction box when flammable gas is present.
Ensure that the associated control panel is inhibited so as to
prevent false alarms.
3.1a
Commissioning procedure
4-20mA Version
Note: the amplifier PCB for this version is fitted with inhibit links (see
Diagram 16) to clamp the output signal to either 2mA or 4mA. With
the movable link in the NORM position the 4-20mA output signal
tracks the gas reading. It is recommended that the link be set to
either the 2mA or 4mA position before applying power to the
detector, to prevent false alarms on the control equipment during
commissioning. The link MUST be reset to the NORM position when
calibration is completed.
1. Open the junction box of the detector by unscrewing the lid in an anticlockwise direction (having loosened the retaining grub-screw first).
2. Check that all electrical connections have been made and are correct
as per Diagram 17.
3. Measure the voltage across the + and - terminals and check a
minimum supply of 10V dc is present.
4. Leave the sensor to stabilise for at least 24 hours before attempting to
zero or calibrate.
5. Connect a digital volt meter (DVM) to the test points on the amplifier
PCB, as shown in Diagram 16.
Note: At the test points, Zero will read 40 mV = 4 mA.
Full scale deflection (100ppm gas) will read 200 mV = 20 mA. There
is a current clamp of 27mA on the 4-20mA output.
Zeroing the detector
6. Ensure the detector is in clean air with no H2S present. Adjust the
ZERO pot on the amplifier (which is accessible via a hole in the PCB
cover) until the DVM reads 40 mV. Check that the control equipment
display reads zero.
Calibrating the detector
7. Apply calibration gas (which should be 25ppm H2S in air) to the
detector at a flow rate of 0.5 - 1 litre/minute via a flow adaptor (Part
No. C03005). Contact Crowcon for the supply of calibration gas.
63
3. Operation
Xgard Type 7
160
x Gas
Range
+ 40 = mV setting
Where the Range is the full scale gas level (ie 100ppm), and Gas is the
concentration in the calibration mixture.
Example: calibrating using 50ppm H2S in air calibration gas:
160
x 50
100
+ 40 = 120 mV
3.1b
Commissioning procedure
mV Bridge Version
64
3. Operation
Xgard Type 7
65
3. Operation
Xgard Type 7
66
3. Operation
Xgard Type 7
67
4. Specification
Junction box material
Xgard Type 7
Dimensions
Weight
Operating voltage
mA version: 10-30V dc
mV version: 6.5V dc +/- 0.2V dc
Current consumption
Output
Maximum cable
loop resistance
(mA version)
Maximum cable
loop resistance
(mV version)
68
Humidity
Degree of protection
Explosion protection
Flameproof
Approval code
ATEX
II 2 G EExd IIC T6
Tamb = -40 to 50C
ATEX
II 2 G EExd IIC T4
Tamb = -40 to +80C
UL Class I, Division 1, Groups B, C & D
4. Specification
Safety certificate no.
Xgard Type 7
Baseefa04ATEX0024X
Standards
Zones
Gas groups
EMC
EN50270
69
Number
Xgard Type
M02125
All Types
M02281
All Types
Calibration adaptor
C03005
All Types*
Calibration cap
C01886
Type 4 only
Accessory adaptor
M04666
All Types*
Weatherproof cap
C01442
All Types*
Collector cone
C01051
All Types*
Spray deflector
C01052
All Types*
C01339
All Types*
M01844
All Types
Sensor retainer
M01840
Type 1 only
M01814
Types 2-7
M04828
All Types
M04829
All Types
S011328
Types 1 and 2
S011240
Types 1 and 2
S011477
Type 3
Type 4
S011242
Types 5 and 6
S011244
Type 7
S011467
Type 7
PCB Cover
M04770
All Types
Type 1
Type 1
Galvanic isolator
Type 1
* Except Type 4
70
C03322
Accessory adaptor
Spray deflector
Weatherproof cap
Flow adaptor
Collector cone
71
72
Warranty
This equipment leaves our works fully tested and calibrated. If, within a period of one
year from the date of purchase, it is proved to be defective by reason of faulty
workmanship or material we undertake, at our option, either to repair or replace it, free
of charge, subject to the conditions below.
1
3
4
If the purchaser wishes to make any claim for repair or replacement under this
guarantee, he shall contact our Customer Care department and obtain a claim
number using the contact information detailed below. The purchaser should then
return the complete instrument to us at his risk, adequately packed and carriage
paid, and include a note of the complaint along with the allotted claim number.
The guarantee will be rendered invalid if the instrument is found to have been
altered, modified, dismantled, or tampered with.
We accept no liability for consequential or indirect loss or damage howsoever
arising (including any loss or damage arising out of the use of the instrument) and
all liability in respect of any third party is expressly excluded.
The guarantee does not cover the accuracy of calibration after the system has
been put into use.
The guarantee does not include the cosmetic finish of the product, and is
dependant upon installation and maintenance of the product in accordance with
the procedures set out in the Installation, Operating and Maintenance Instructions.
Our liability in respect of defective equipment shall be limited to the obligations
set out in the guarantee and any further warranty, condition or statement, express
or implied statutory or otherwise as to the merchantable quality of our equipment
or its fitness for any particular purpose is excluded except as prohibited by
statute. This guarantee shall not affect a customers statutory rights.
Detectors that are returned to Crowcon as faulty, and are subsequently found to
be fault-free may be subject to a small handling charge to cover inspection and
return shipping costs.
Crowcon Detection Instruments Ltd,
2 Blacklands Way,
Abingdon Business Park,
Abingdon,
Oxfordshire
OX14 1DY
Tel: +44 (0)1235 557700
Fax:+44 (0)1235 557749
Email:
crowcon@crowcon.com
Website:
http://www.crowcon.com
Customer Care
Tel
+44 (0) 1235 557741
Fax
+44 (0) 1235 557722
Email
warranty@crowcon.com
Service Department
Tel
+44 (0) 1235 557711
Fax
+44 (0) 1235 557732
Email
service@crowcon.com
73
UK Office
USA Office
2 Blacklands Way,
Abingdon Business Park,
Abingdon,
Oxfordshire OX14 1DY, UK
Tel:
+44 (0)1235 557700
Fax:
+44 (0)1235 557749
email: sales@crowcon.com
internet: http://www.crowcon.com
Rotterdam Office
Singapore Office
Vlambloem 129
3068JG, Rotterdam
Netherlands
Tel:
+31 10 421 1232
Fax:
+31 10 421 0542
email: crowcon@crowcon.net
internet: http://www.crowcon.com
1180
Issue 1 05/04