The document discusses Siemens 3WL IEC circuit breakers, their specifications, and accessories.

3WL air circuit breakers are used as incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers for switching and protecting motors, capacitors, generators, transformers, busbars and cables.

3WL circuit breakers comply with IEC 60947-2 and are climate-proof according to IEC 60068-2-30.

IEC WL Circuit Breakers

2014 Selection Guide

www.usa.siemens.com/3WLIEC

Siemens 3WL IEC Breakers 2014


2

Introduction

8
9
16
23
30
37
44

3WL air circuit breakers/


non-automatic air circuit breakers
up to 6300 A (AC), IEC
Introduction
3-pole, fixed-mounted versions
3-pole, withdrawable versions
4-pole, fixed-mounted versions
4-pole, withdrawable versions
Options
Accessories and spare parts

66
67
69

3WL non-automatic air circuit


breakers up to 4000 A (DC)
3- and 4-pole,
fixed-mounted versions
3- and 4-pole, withdrawable versions
Accessories and spare parts

Ch. 12 3KC ATC5300


transfer control devices

For further technical


product information:
Configuration Manual
IEC WL Technical Guide 2014
Xerox Code: xxxxxxxxxxxxxx
Service & Support Portal
www.siemens.com/lowvoltage/productsupport
Product List:
Technical specifications
Entry List:
Certificates / Characteristics /
Download / FAQ / Manuals /
Updates

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


Introduction

Overview
Standards

9 ... 36 As incoming-feeder, distribution, tie,


IEC 60947-2,
and outgoing-feeder circuit breakers in climate-proof according to IEC 60068-2-30
electrical installations.

Used in

Industry

3WL air circuit breakers/


non-automatic air circuit breakers
up to 6300 A (AC), IEC

Applications/
Individual components

Residential
buildings

Page

Non-residential
buildings

Devices

--

--

For switching and protecting motors,


capacitors, generators, transformers,
busbars and cables.
3WL non-automatic air circuit
breakers up to 4000 A (DC)

66 ... 68 As incoming-feeder, distribution, tie,


IEC 60947-2,
and outgoing-feeder circuit breakers in climate-proof according to IEC 60068-2-30
electrical installations.
For switching and protecting motors,
capacitors, generators, transformers,
busbars and cables.

Protective device with device holder 51


and optional measurement function
(ETU)

Electronic Trip Unit with protection func- As for circuit breakers


tions LI, LSI, LSING and LSIN(G), with
or without measurement function Plus

--

Rating Plugs

51

For rated currents In from 250 A to


As for circuit breakers
6300 A. The maximum rated current of
the circuit breaker must not be exceeded.

--

Ground-fault modules

51

With alarm and tripping

As for circuit breakers

--

Displays

51

4-line displays for ETU45B

As for circuit breakers

--

Current transformers
for N conductor protection

51

Internal transformers for N conductors, As for circuit breakers


external transformers for N conductors

--

EMC filters

51

Common-mode interference suppressor As for circuit breakers


filters

--

More accessories
for Electronic Trip Units

52

Sealable and lockable covers,


As for circuit breakers
automatic reset of the reclosing lockout,
remote reset solenoid,
retrofittable internal CubicleBUS wiring,
retrofittable internal wiring for connection of external N and G transformers

--

Locking devices

52

Interlocking set for mechanical ON/OFF, As for circuit breakers


locking devices against unauthorized
closing in operator panels/for
withdrawable circuit breakers,
locking devices for operating
mechanism handle with padlock,
locking devices to prevent movement
of the withdrawable circuit breakers,
interlocking systems

--

Locking mechanisms

53

To prevent movement of the withAs for circuit breakers


drawable circuit breakers into disconnected position, to prevent opening of
the cabinet door in ON position,
to prevent opening of the cabinet door,
to prevent movement with the cabinet
door open

--

Interlocks

54

Mutual mechanical interlocking,


couplings on the circuit breaker
(with ring) for mutual interlocking,
Bowden wire

--

= 3 2 0 0 A

N S E 0 _ 0 0 9 9 2 b
G F M

5 1
g T R IP

A L A R M

A L A R M

T R IP
C

O F F

J g (s )
.5

B
D

.4
.3
.2
.1

A T 4 5 B
1 2 Jg
.1
.2
.3
.4
.5

N S E 0 _ 0 1 0 2 7 a

N S E 0 _ 0 1 6 0 9

N S E 0 _ 0 0 9 9 0 a

F 7

N S E 0 _ 0 0 9 9 9 a

NSE0_00982

NSE0_00987

NSE0_00989

Siemens 3WL IEC Breakers 2014

As for circuit breakers

Air Circuit Breakers

Test devices

Applications/
Individual components

Standards

Used in

Industry

Transfer control devices


3KC ATC5300

Page

Residential
buildings

Devices

Non-residential
buildings

Introduction

Ch. 12

The transfer control device, equipped with two


motor-driven circuit breakers, serves as a transfer
system that automatically or manually switches
between two power supply systems in low-voltage
power distribution applications.

IEC 60947-6-1
DIN VDE 0660-114

Manual tester Release 2 for Electronic Trip Units,


function testers

As for circuit breakers

--

For shunt releases

As for circuit breakers

--

54

Capacitor storage devices 54

UL 508
CSA 22.2 No. 14

Indicators, control
elements

55

Ready-to-close signaling switches,


signaling switches, tripped signaling switches,
operating cycles counters,
stored energy status signaling switches,
position signaling switches for guide frames,
electric ON buttons,
motor shutdown switches,
EMERGENCY-STOP buttons

As for circuit breakers

--

Auxiliary conductor
connections

56

Male connectors for circuit breakers,


extension for 1000 V male connector versions,
male connectors and extension for 1000 V,
auxiliary supply connectors for circuit breakers
or guide frames,
coding kits,
sliding contacts for guide frames,
blanking blocks for circuit breakers

As for circuit breakers

--

Auxiliary releases

57

Closing solenoids/shunt releases,


undervoltage releases

As for circuit breakers

--

Operating mechanisms

57

Motorized operating mechanism

As for circuit breakers

--

N S E 0 _ 0 1 2 6 9

N S E 0 _ 0 0 9 9 5 a

Auxiliary contacts

57

Auxiliary switch blocks

As for circuit breakers

--

Door sealing frames,


hoods, shutters

58

Door sealing frames, IP55 protective covers,


shutters

As for circuit breakers

--

Arc chutes

58

Arc chutes, arc chute covers

As for circuit breakers

--

Coding for withdrawable


version

58

By customer, for 36 coding variants

As for circuit breakers

--

Grounding connection

59

Grounding connection between the guide frame


and the withdrawable circuit breaker,
contacting modules for withdrawable
circuit breakers

As for circuit breakers

--

Support brackets

59

For mounting fixed-mounted circuit breakers on


vertical plane

As for circuit breakers

--

CubicleBUS modules

59

Digital and analog input and output modules,


Zone Selective Interlocking modules

As for circuit breakers

--

Parameterization systems 59

Breaker Data Adapter (BDA), BDA Plus,


Connection cables for BDA Plus,
powerconfig parameterization software

As for circuit breakers

--

Accessories for
communications

60

Factory-fitted cables for CubicleBUS modules,


voltage transformers

As for circuit breakers

--

Retrofitting and spare


parts

60

PROFIBUS retrofit kits,


COM15 PROFIBUS modules,
COM16 MODBUS modules,
MODBUS IEC retrofit kits,
Breaker Status Sensor (BSS),
measurement function Plus

As for circuit breakers

--

Front-accessible main connections with double


As for circuit breakers
or single hole, rear vertical main connections, rear
horizontal main connections, circuit connecting
flanges, supports for front and DIN connecting bars

--

NSE0 01018a

Device

PROFIBUS DP

CubicleBus

NSE-01025

Main conductor connec61, 62


tions, fixed-mounted, main
conductor connections,
withdrawable

NSE-01010

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


Introduction

Size I

Size III

Size II

Air circuit breakers


3WL air circuit breakers/non-automatic air circuit breakers 3WL non-automaticair circuit breakers
up to 6300 A (AC), IEC
up to 4000 A (DC)
Size
Rated current In

Number of poles

I, II, III

II

630, 800, 1000, 1250,


1600, 2000, 2500, 3200, 4000,
5000, 6300

1000, 2000, 4000

3-pole, 4-pole

3-pole, 4-pole

... 690/1000/1150
--

-... 1000

Rated operational
voltage Ue

V AC
V DC

Rated ultimate
short-circuit breaking
capacity at 500 V AC

Size I

Size II

Size III

kA

55/66/85

66/80/100

100/150 (3-pole),
130 (4-pole)

30/25/20
(at 300/600/1000 V DC)

Operating
cycles

Up to 20000

15000

10000

15000

Mounting position

30 30

30 30

NSE0_00062a

NSE0_00061a

Degree of protection
With cover
Without cover
(with door sealing frame)
Dimensions
3-/4-pole
T

Fixedmounted

IP55
IP41

W mm

320/410

460/590

704/914

460/590

H mm

434

434

434

434

D mm

291

291

291

291

465.5
471

465.5
471

465.5
471

465.5
471

ETU15B1)

ETU25B

ETU27B

ETU45B

ETU76B

Overload protection

Short-time delayed
short-circuit protection

--

Instantaneous
short-circuit protection

Neutral conductor protection

--

--

Ground-fault protection

--

--

Zone Selective Interlocking

--

--

--

LCD, 4-line

--

--

--

--

LCD, graphic

--

--

--

--

Communication

--

--

--

Measurement function Plus

--

--

--

Selectable parameter sets

--

--

--

--

Parameters freely programmable

--

--

--

--

CubicleBUS

--

--

--

Rating Plug

NSE0_01111a

NSE0_01108a

Type

NSE0_01106a

NSE0_01107a

NSS0_00535

NSE0_00062a

NSE0_00061a

IP55
IP41

Withdrawable H mm
D mm

30 30

30 30

NSE0_01109a

Endurance

Electronic Trip Units for 3WL circuit breakers

Standard
-- Not available
Optional
1)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


Introduction
Breaking capacity
Size

II

Type

3WL11

3WL12

Breaking capacity

III
3WL13

C
3-pole

C
4-pole

Short-circuit breaking capacity


Rated operational voltage Ue
up to 415 V AC
Icu
Ics
Icm

kA
kA
kA

55
55
121

66
66
145

85
85
187

66
66
145

80
80
176

100
100
220

100
100
220

150
150
330

130
130
286

kA
kA
kA

55
55
121

66
66
145

85
85
187

66
66
145

80
80
176

100
100
220

100
100
220

150
150
330

130
130
286

kA
kA
kA

42
42
88

50
50
105

66
66
145

50
50
105

75
75
165

85
85
187

85
85
187

150
150
330

130
130
286

----

----

509)
509)
1059)

----

----

50
50
105

50
50
105

704)
704)
1544)

704)
704)
1544)

55
42
29.5
24

66
50
35
29

75
66
46
44

66
55
39
32

80
66
46
44

100
80
651)/702)
501)/652)

100
100
80
65

100
100
80
65

100
100
80
65

55
42
--

66
50
--

75
66
509)

66
50
--

80
75
--

100
85
504)

100
85
504)

100
100
704)

100
100
704)

Rated operational voltage Ue


up to 500 V AC
Icu
Ics
Icm
Rated operational voltage Ue
up to 690 V AC
Icu
Ics
Icm
Rated operational voltage Ue
up to 1000 V/1150 V AC
kA
kA
kA

Icu
Ics
Icm

Rated short-time withstand current

Icw3)
0.5 s
1s
2s
3s

kA
kA
kA
kA

Short-circuit breaking capacity Icc


of the non-automatic air circuit
breakers
Up to 500 V AC
Up to 690 V AC
Up to 1000 V /1150 V AC

kA
kA
kA

Size

II

Type

3WL12

Breaking capacity

DC

DC

Short-circuit breaking capacity


Up to 220 V DC
Up to 300 V DC
Up to 600 V DC
Up to 1000 V DC

Icc
Icc
Icc
Icc

kA
kA
kA
kA

35
30
25
20

Rated short-time withstand current Icw


0.5 s
1s
2s
3s

kA
kA
kA
kA

-355)/306)/257)/208)
---

Circuit breaker with ECO breaking capacity N

Abbreviations*
(functions)

English long text

Explanation

Long Time Delay

Overload protection

Short Time Delay

Short-circuit protection
(short-time delayed)

Circuit breaker with standard breaking capacity S

Circuit breaker with high breaking capacity H

Circuit breakers with very high breaking capacity C

DC

Non-automatic air circuit breakers with DC breaking capacity

Instantaneous

Short-circuit protection
(instantaneous)

These breaking capacities are indicated in the corresponding tables


by the symbols shown on orange backgrounds.

Neutral Protection

Neutral conductor
protection

Ground Fault

Ground-fault protection

Note:
For further technical specifications see
IEC WL Technical Guide 2014

* Designations according to IEC 60947-2, Appendix K.


4)

1)

Size II with In max 2500 A.

Rated operational voltage Ue = 1150 V.

5)

2)

At Ue = 220 V DC.

Size II with In max = 3200 A and In max = 4000 A.

6)

3)

At Ue = 300 V DC.

At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.

7)

At Ue = 600 V DC.

8)

At Ue = 1000 V DC.

9)

Values also apply to 690 V + 20 % version with Z-option "A16".

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


Introduction
3WL air circuit breakers:
Superior individual products integrated into uniform power distribution systems - up to and including industry-specific industrial and infrastructure solutions

6
7

8
5

9
1
25

21

10

19
22

11

23
12

24

18

13

14
20

16
15

Guide frame (pages 45 to 50)

Operating cycles counters (pages 39 and 55)

Main circuit connection front, flange, horizontal, vertical


(pages 42, 61 and 62)

Breaker status sensor (BSS) (pages 40 and 60)

Position signaling switch (pages 40 and 55)

Protective device with device holder, Electronic Trip Unit (ETU)


(page 51)

Grounding connection, leading (page 59)

Remote reset solenoid (pages 39 and 52)

Shutters (pages 40 and 58)

Breaker data adapter (BDA Plus) (page 59)

COM15 PROFIBUS module or COM16 MODBUS module


(pages 40 and 60)

Ground-fault protection module (page 51)

External CubicleBUS modules (page 59)

Rating plug (pages 38 and 51)

Closing coil, auxiliary release (pages 37, 39 and 57)

Measurement function module (pages 40 and 51)

Auxiliary conductor plug-in system (pages 41 and 56)

Air circuit breaker (pages 9 to 36)

Auxiliary switch block (pages 37 and 57)


Door sealing frame (pages 39 and 58)
Interlocking set for mechanical ON/OFF (page 52)
Transparent panel, function insert (page 52)
EMERGENCY-STOP pushbutton, key operated (page 55)
Motorized operating mechanism (pages 39 and 57)

Four-line display (page 51)

Siemens 3WL IEC Breakers 2014

NSE0_01887d

17

Air Circuit Breakers


Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit)

18

Ethernet

16
17

PROFIBUS

11

19

12

13

14

15

from Release 2
CubicleBUS

7
1

9
3

10

NSE0_01105l

3VL molded case circuit breakers

11 Zone Selective Interlocking modules

Electronic Trip Unit LCD

12 Digital output module with relay contacts

Electronic Trip Unit

13 Digital output module with relay contacts, configurable

COM20 Release 2 PROFIBUS module1) including ZSI

14 Analog output modules

BDA Plus with Ethernet interface

15 Digital input module

3WL air circuit breakers

16 powerconfig as of V2.3

COM15 PROFIBUS module2)

17 PLC, e. g. SIMATIC S7

Breaker status sensor (BSS)

18 e. g. powermanager or SIMATIC powerrate

Electronic Trip Unit

19 7KM PAC measuring devices

10 Measurement function Plus


1)
2)

For a MODBUS-RTU connection the COM21 module is required.


For a MODBUS-RTU connection the COM16 module is required.

Features
Coordinated communication concept using the PROFIBUS DP
or MODBUS, ranging from 16 A to 6300 A with 3VL molded
case circuit breakers and 3WL air circuit breakers
The high level of modularity of circuit breakers and accessories
allows easy retrofitting of all communication components
Significant additional benefits for the switchgear due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the 3WL

Communication:
For air circuit breakers with optional communication function
(ETU45B or ETU76B Electronic Trip Unit)
see pages 9 to 36.
For accessories see pages 59 and 60.

Innovative software products for parameterization, operation,


monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
Complete integration of the circuit breakers into the Totally Integrated Power and Totally Integrated Automation solutions

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Introduction

Benefits
Low space requirements
The 3WL air circuit breakers require very little space. Size I
devices (up to 2000 A) fit into a 400 mm wide switchgear panel.
Size III devices (up to 6300 A) are the smallest of their kind.
Size III devices with the construction width of 704mm, fit into an
800mm wide switchgear panel.
Modular design
The following components can be exchanged or retrofitted at a
later stage to allow the circuit breaker to adapt to new changes
in requirements:
Auxiliary Releases
Motorized Operating Mechanisms
Electronic Trip Units
Current Transformers
Auxiliary Circuit Signaling Switches
Automatic Reset Devices
Interlocks
Engagement Operating Mechanisms
The main contact elements can all be replaced in order to increase the endurance of the circuit breaker.
Retrofittable modules for Electronic Trip Units
Modularity is one of the main features of the new 3WL circuit
breakers.
Special LCDs, ground-fault modules, rating plugs and communication modules for the Electronic Trip Units are available for
fast and easy retrofitting and adaptation to changing requirements.
Communication/measurement functions
The use of modern communication-capable circuit breakers
opens up completely new possibilities in terms of start-up,
parameterization, diagnostics, maintenance and operation. This
allows many different ways of reducing costs and improving

productivity in industrial plants, buildings and infrastructure


projects to be achieved:
Fast and reliable parameterization
Timely information and response can prevent plant
stoppages
Effective diagnostics management
Measured values are the basis for efficient load management,
for drawing up power demand profiles and for allocating
energy to cost centers
Preventive maintenance reduces the risk of expensive plant
downtimes
Measurement function with a very wide range of measured
values, such as current, voltage, energy, power etc.
Can be used in 1000 V AC and 690 V IT networks

Application
As incoming-feeder, distribution, tie, and outgoing-feeder
circuit breakers in electrical installations.
For switching and protecting motors, capacitors, generators,
transformers, busbars and cables.
When connected to an electronic I&C system, the air circuit
breakers offer a wide range of options for monitoring network
events.
A complete family of Siemens circuit breakers cover applications between 16 A and 6300 A with molded case and air circuit
breakers.
The AC devices are available as circuit breakers and non-automatic air circuit breakers. DC devices are only available as nonautomatic air circuit breakers.
Standards
3WL circuit breakers comply with:
IEC 60947-2
IEC 60947-2 Annex F / CISPR 11/22 Class B
Climate-proof according to IEC 60068-2-30.

Conductor cross-sections
Size
Type

I
Up to
3WL11 10
A 1000
A 1000
A 1000

3WL11 12 3WL11 16

II
3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20

1250
1250
1210

1600
1600
14902)

2000
1930
1780

800
800
800

1000
1000
1000

1250
1250
1250

1600
1600
1600

2000
2000
2000

Permissible load
for withdrawable
versions
at rear horizontal
main connections

Up to 55 C (Cu bare)
Up to 60 C
(Cu bare)1)
Up to 70 C
(Cu black painted)1)

Main conductor
minimum
cross-sections

Copper bars,
bare

Unit(s) 1
mm2 60 10

2
40 10

2
50 10

3
50 10

1
50 10

1
60 10

2
40 10

2
50 10

3
50 10

Copper bars,
painted black

Unit(s) 1
mm2 60 10

2
40 10

2
50 10

3
50 10

1
50 10

1
60 10

2
40 10

2
50 10

3
50 10

Size

II

Type

3WL12 25 3WL12 32 3WL12 403) 3WL13 40 3WL13 50 3WL13 633)

Permissible load
for withdrawable
versions at rear
horizontal main
connections

Up to 55 C (Cu bare)
Up to 60 C (Cu
bare)1)
Up to 70 C
(Cu black painted)1)

Main conductor
minimum
cross-sections

Copper bars,
bare
Copper bars,
painted black

III
3200
3020
2870

39504)
3810
3600

4000
4000
4000

5000
5000
5000

5920
5810
5500

Unit(s) 2
mm2 100 10

3
100 10

4
120 10

4x
100 x 10

6x
100 x 10

6x
120 x 10

Unit(s) 2
mm2 100 10

3
100 10

4
100 105)

4
100 10

6
100 10

6
120 10

A 2500
A 2500
A 2280

1)

ETU76B with graphics display can be used up to max. 55 C.

2)

At breaking capacity H: 1600 A up to 70 C

3)

With rear vertical connections

4)

Size II, 3-pole, in fixed-mounted version

5)

Minimum main conductor cross-sections for 4-pole withdrawable circuit


breakers: 4 120 mm 10 mm

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions

Selection and ordering data


Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@32-@@@@
3WL1108-2@@32-@@@@
3WL1110-2@@32-@@@@
3WL1112-2@@32-@@@@
3WL1116-2@@32-@@@@
3WL1120-2@@32-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@32-@@@@
3WL1210-2@@32-@@@@
3WL1212-2@@32-@@@@
3WL1216-2@@32-@@@@
3WL1220-2@@32-@@@@
3WL1225-2@@32-@@@@
3WL1232-2@@32-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@31-@@@@
3WL1108-2@@31-@@@@
3WL1110-2@@31-@@@@
3WL1112-2@@31-@@@@
3WL1116-2@@31-@@@@
3WL1120-2@@31-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

66

3WL1208-2@@31-@@@@
3WL1210-2@@31-@@@@
3WL1212-2@@31-@@@@
3WL1216-2@@31-@@@@
3WL1220-2@@31-@@@@
3WL1225-2@@31-@@@@
3WL1232-2@@31-@@@@
3WL1240-2@@31-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary switch
2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

2)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking
capacity Icu = Ics

DT

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


I

630
800
1000
1250
1600

630
800
1000
1250
1600

55

3WL1106-2@@33-@@@@
3WL1108-2@@33-@@@@
3WL1110-2@@33-@@@@
3WL1112-2@@33-@@@@
3WL1116-2@@33-@@@@

1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103

43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@33-@@@@
3WL1210-2@@33-@@@@
3WL1212-2@@33-@@@@
3WL1216-2@@33-@@@@
3WL1220-2@@33-@@@@
3WL1225-2@@33-@@@@
3WL1232-2@@33-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@34-@@@@
3WL1108-2@@34-@@@@
3WL1110-2@@34-@@@@
3WL1112-2@@34-@@@@
3WL1116-2@@34-@@@@
3WL1120-2@@34-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@34-@@@@
3WL1210-2@@34-@@@@
3WL1212-2@@34-@@@@
3WL1216-2@@34-@@@@
3WL1220-2@@34-@@@@
3WL1225-2@@34-@@@@
3WL1232-2@@34-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

3)

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary switch
2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

10

Siemens 3WL IEC Breakers 2014

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@32-@@@@
3WL1108-3@@32-@@@@
3WL1110-3@@32-@@@@
3WL1112-3@@32-@@@@
3WL1116-3@@32-@@@@
3WL1120-3@@32-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@32-@@@@
3WL1210-3@@32-@@@@
3WL1212-3@@32-@@@@
3WL1216-3@@32-@@@@
3WL1220-3@@32-@@@@
3WL1225-3@@32-@@@@
3WL1232-3@@32-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@31-@@@@
3WL1108-3@@31-@@@@
3WL1110-3@@31-@@@@
3WL1112-3@@31-@@@@
3WL1116-3@@31-@@@@
3WL1120-3@@31-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

80

3WL1208-3@@31-@@@@
3WL1210-3@@31-@@@@
3WL1212-3@@31-@@@@
3WL1216-3@@31-@@@@
3WL1220-3@@31-@@@@
3WL1225-3@@31-@@@@
3WL1232-3@@31-@@@@
3WL1240-3@@31-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

2)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

11

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


I

630
800
1000
1250
1600

630
800
1000
1250
1600

66

3WL1106-3@@33-@@@@
3WL1108-3@@33-@@@@
3WL1110-3@@33-@@@@
3WL1112-3@@33-@@@@
3WL1116-3@@33-@@@@

1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103

43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@33-@@@@
3WL1210-3@@33-@@@@
3WL1212-3@@33-@@@@
3WL1216-3@@33-@@@@
3WL1220-3@@33-@@@@
3WL1225-3@@33-@@@@
3WL1232-3@@33-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@34-@@@@
3WL1108-3@@34-@@@@
3WL1110-3@@34-@@@@
3WL1112-3@@34-@@@@
3WL1116-3@@34-@@@@
3WL1120-3@@34-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@34-@@@@
3WL1210-3@@34-@@@@
3WL1212-3@@34-@@@@
3WL1216-3@@34-@@@@
3WL1220-3@@34-@@@@
3WL1225-3@@34-@@@@
3WL1232-3@@34-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

12

Siemens 3WL IEC Breakers 2014

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
Basic price SET, M)
per PU

PS*/
P. unit

PG

Weight
per PU
approx.
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@32-@@@@
3WL1108-4@@32-@@@@
3WL1110-4@@32-@@@@
3WL1112-4@@32-@@@@
3WL1116-4@@32-@@@@
3WL1120-4@@32-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@32-@@@@
3WL1210-4@@32-@@@@
3WL1212-4@@32-@@@@
3WL1216-4@@32-@@@@
3WL1220-4@@32-@@@@
3WL1225-4@@32-@@@@
3WL1232-4@@32-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

III

4000
5000

4000
5000

100

3WL1340-4@@32-@@@@
3WL1350-4@@32-@@@@

1
1

1 unit
1 unit

103
103

82.000
82.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@31-@@@@
3WL1108-4@@31-@@@@
3WL1110-4@@31-@@@@
3WL1112-4@@31-@@@@
3WL1116-4@@31-@@@@
3WL1120-4@@31-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

100

3WL1208-4@@31-@@@@
3WL1210-4@@31-@@@@
3WL1212-4@@31-@@@@
3WL1216-4@@31-@@@@
3WL1220-4@@31-@@@@
3WL1225-4@@31-@@@@
3WL1232-4@@31-@@@@
3WL1240-4@@31-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000
85.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@31-@@@@
3WL1350-4@@31-@@@@
3WL1363-4@@31-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

82.000
82.000
90.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without ground-fault prot.

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

3)

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

13

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@33-@@@@
3WL1210-4@@33-@@@@
3WL1212-4@@33-@@@@
3WL1216-4@@33-@@@@
3WL1220-4@@33-@@@@
3WL1225-4@@33-@@@@
3WL1232-4@@33-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

III

4000

4000

100

3WL1340-4@@33-@@@@

1 unit

103

82.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@34-@@@@
3WL1108-4@@34-@@@@
3WL1110-4@@34-@@@@
3WL1112-4@@34-@@@@
3WL1116-4@@34-@@@@
3WL1120-4@@34-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

43.000
43.000
43.000
43.000
43.000
43.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@34-@@@@
3WL1210-4@@34-@@@@
3WL1212-4@@34-@@@@
3WL1216-4@@34-@@@@
3WL1220-4@@34-@@@@
3WL1225-4@@34-@@@@
3WL1232-4@@34-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

56.000
56.000
56.000
56.000
56.000
59.000
64.000

III

4000

4000

100

3WL1340-4@@34-@@@@

1 unit

103

82.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

3)

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

14

Siemens 3WL IEC Breakers 2014

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 150 kA at 500 V,


very high breaking capacity C
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


III

4000
5000

4000
5000

150

3WL1340-5@@32-@@@@
3WL1350-5@@32-@@@@

1
1

1 unit
1 unit

103
103

82.000
82.000

150

3WL1340-5@@31-@@@@
3WL1350-5@@31-@@@@
3WL1363-5@@31-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

82.000
82.000
90.000

Vertical main circuit connection


III

4000
5000
6300

4000
5000
6300

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING3)5)

EG

ETU45B: Protection functions


LSING3)5) with 4-line display

FG

ETU76B: Protection functions LSING3)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

2)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

4)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

5)

ETU45B and ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

15

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions

Selection and ordering data


Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@35-@@@@
3WL1108-2@@35-@@@@
3WL1110-2@@35-@@@@
3WL1112-2@@35-@@@@
3WL1116-2@@35-@@@@
3WL1120-2@@35-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

45.000
45.000
45.000
45.000
45.000
45.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@35-@@@@
3WL1210-2@@35-@@@@
3WL1212-2@@35-@@@@
3WL1216-2@@35-@@@@
3WL1220-2@@35-@@@@
3WL1225-2@@35-@@@@
3WL1232-2@@35-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

60.000
60.000
60.000
60.000
60.000
63.000
68.000
70.000
70.000
70.000
70.000
70.000
70.000

Without guide frames2)


(for guide frames, see page 45 to 50)

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@36-@@@@
3WL1108-2@@36-@@@@
3WL1110-2@@36-@@@@
3WL1112-2@@36-@@@@
3WL1116-2@@36-@@@@
3WL1120-2@@36-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@36-@@@@
3WL1210-2@@36-@@@@
3WL1212-2@@36-@@@@
3WL1216-2@@36-@@@@
3WL1220-2@@36-@@@@
3WL1225-2@@36-@@@@
3WL1232-2@@36-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

4)

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

16

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@37-@@@@
3WL1108-2@@37-@@@@
3WL1110-2@@37-@@@@
3WL1112-2@@37-@@@@
3WL1116-2@@37-@@@@
3WL1120-2@@37-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

66

3WL1208-2@@37-@@@@
3WL1210-2@@37-@@@@
3WL1212-2@@37-@@@@
3WL1216-2@@37-@@@@
3WL1220-2@@37-@@@@
3WL1225-2@@37-@@@@
3WL1232-2@@37-@@@@
3WL1240-2@@37-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000
103 121.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@38-@@@@
3WL1108-2@@38-@@@@
3WL1110-2@@38-@@@@
3WL1112-2@@38-@@@@
3WL1116-2@@38-@@@@
3WL1120-2@@38-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@38-@@@@
3WL1210-2@@38-@@@@
3WL1212-2@@38-@@@@
3WL1216-2@@38-@@@@
3WL1220-2@@38-@@@@
3WL1225-2@@38-@@@@
3WL1232-2@@38-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

17

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 45 to 50)
I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@35-@@@@
3WL1108-3@@35-@@@@
3WL1110-3@@35-@@@@
3WL1112-3@@35-@@@@
3WL1116-3@@35-@@@@
3WL1120-3@@35-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

45.000
45.000
45.000
45.000
45.000
45.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@35-@@@@
3WL1210-3@@35-@@@@
3WL1212-3@@35-@@@@
3WL1216-3@@35-@@@@
3WL1220-3@@35-@@@@
3WL1225-3@@35-@@@@
3WL1232-3@@35-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

60.000
60.000
60.000
60.000
60.000
63.000
68.000
70.000
70.000
70.000
70.000
70.000
70.000

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@36-@@@@
3WL1108-3@@36-@@@@
3WL1110-3@@36-@@@@
3WL1112-3@@36-@@@@
3WL1116-3@@36-@@@@
3WL1120-3@@36-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@36-@@@@
3WL1210-3@@36-@@@@
3WL1212-3@@36-@@@@
3WL1216-3@@36-@@@@
3WL1220-3@@36-@@@@
3WL1225-3@@36-@@@@
3WL1232-3@@36-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

18

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@37-@@@@
3WL1108-3@@37-@@@@
3WL1110-3@@37-@@@@
3WL1112-3@@37-@@@@
3WL1116-3@@37-@@@@
3WL1120-3@@37-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

80

3WL1208-3@@37-@@@@
3WL1210-3@@37-@@@@
3WL1212-3@@37-@@@@
3WL1216-3@@37-@@@@
3WL1220-3@@37-@@@@
3WL1225-3@@37-@@@@
3WL1232-3@@37-@@@@
3WL1240-3@@37-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000
103 121.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@38-@@@@
3WL1108-3@@38-@@@@
3WL1110-3@@38-@@@@
3WL1112-3@@38-@@@@
3WL1116-3@@38-@@@@
3WL1120-3@@38-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@38-@@@@
3WL1210-3@@38-@@@@
3WL1212-3@@38-@@@@
3WL1216-3@@38-@@@@
3WL1220-3@@38-@@@@
3WL1225-3@@38-@@@@
3WL1232-3@@38-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
91.000
103
91.000
103
91.000
103
91.000
103
91.000
103 102.000
103 113.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

4)

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

19

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Max. rated circuit
breaker current
In max.

Rated current1)
In

kA

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@35-@@@@
3WL1108-4@@35-@@@@
3WL1110-4@@35-@@@@
3WL1112-4@@35-@@@@
3WL1116-4@@35-@@@@
3WL1120-4@@35-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

45.000
45.000
45.000
45.000
45.000
45.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@35-@@@@
3WL1210-4@@35-@@@@
3WL1212-4@@35-@@@@
3WL1216-4@@35-@@@@
3WL1220-4@@35-@@@@
3WL1225-4@@35-@@@@
3WL1232-4@@35-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

60.000
60.000
60.000
60.000
60.000
63.000
68.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@35-@@@@
3WL1350-4@@35-@@@@
3WL1363-4@@35-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

88.000
88.000
96.000

Size

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

Without guide frames2)


(for guide frames, see page 45 to 50)

PU
(UNIT,
Basic price SET, M)
per PU

PS*/
P. unit

PG

Weight
per PU
approx.
kg

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@36-@@@@
3WL1108-4@@36-@@@@
3WL1110-4@@36-@@@@
3WL1112-4@@36-@@@@
3WL1116-4@@36-@@@@
3WL1120-4@@36-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@36-@@@@
3WL1210-4@@36-@@@@
3WL1212-4@@36-@@@@
3WL1216-4@@36-@@@@
3WL1220-4@@36-@@@@
3WL1225-4@@36-@@@@
3WL1232-4@@36-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

91.000
91.000
91.000
91.000
91.000
102.000
113.000

III

4000
5000

4000
5000

100

3WL1340-4@@36-@@@@
3WL1350-4@@36-@@@@

1
1

1 unit
1 unit

103
103

148.000
148.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without ground-fault prot.

AA

None

ETU15B: Protection functions LI7)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

Versions with ground-fault protect.

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

20

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

7)

ETU15B cannot be used with 3WL circuit breakers, size III.


* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
Basic price SET, M)
per PU

PS*/
P. unit

PG

Weight
per PU
approx.
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@37-@@@@
3WL1108-4@@37-@@@@
3WL1110-4@@37-@@@@
3WL1112-4@@37-@@@@
3WL1116-4@@37-@@@@
3WL1120-4@@37-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

100

3WL1208-4@@37-@@@@
3WL1210-4@@37-@@@@
3WL1212-4@@37-@@@@
3WL1216-4@@37-@@@@
3WL1220-4@@37-@@@@
3WL1225-4@@37-@@@@
3WL1232-4@@37-@@@@
3WL1240-4@@37-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

91.000
91.000
91.000
91.000
91.000
102.000
113.000
121.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@37-@@@@
3WL1350-4@@37-@@@@
3WL1363-4@@37-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

148.000
148.000
166.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@38-@@@@
3WL1108-4@@38-@@@@
3WL1110-4@@38-@@@@
3WL1112-4@@38-@@@@
3WL1116-4@@38-@@@@
3WL1120-4@@38-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

70.000
70.000
70.000
70.000
70.000
70.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@38-@@@@
3WL1210-4@@38-@@@@
3WL1212-4@@38-@@@@
3WL1216-4@@38-@@@@
3WL1220-4@@38-@@@@
3WL1225-4@@38-@@@@
3WL1232-4@@38-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

91.000
91.000
91.000
91.000
91.000
102.000
113.000

III

4000

4000

100

3WL1340-4@@38-@@@@

1 unit

103

148.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI7)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

4)

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

7)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

21

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
3-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 150 kA at 500 V,


very high breaking capacity C
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 45 to 50)
III

4000
5000
6300

4000
5000
6300

150

3WL1340-5@@35-@@@@
3WL1350-5@@35-@@@@
3WL1363-5@@35-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

88.000
88.000
96.000

3WL1340-5@@36-@@@@
3WL1350-5@@36-@@@@

1
1

1 unit
1 unit

103 148.000
103 148.000

3WL1340-5@@37-@@@@
3WL1350-5@@37-@@@@
3WL1363-5@@37-@@@@

1
1
1

1 unit
1 unit
1 unit

103 148.000
103 148.000
103 166.000

With guide frames, horizontal main circuit connection


III

4000
5000

4000
5000

150

With guide frames, vertical main circuit connection


III

4000
5000
6300

4000
5000
6300

150

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

LSIN4)

NB

ETU27B: Protection functions LSING5)

DG

ETU45B: Protection functions LSING4)6)

EG

ETU45B: Protection functions


LSING4)6) with 4-line display

FG

ETU76B: Protection functions LSING4)6) with graphics display

NG

ETU76B: Protection functions


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

22

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51.

5)

Current transformers for protection of the N conductor are to be ordered


separately, see page 51.

6)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions

Selection and ordering data


Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@42-@@@@
3WL1108-2@@42-@@@@
3WL1110-2@@42-@@@@
3WL1112-2@@42-@@@@
3WL1116-2@@42-@@@@
3WL1120-2@@42-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@42-@@@@
3WL1210-2@@42-@@@@
3WL1212-2@@42-@@@@
3WL1216-2@@42-@@@@
3WL1220-2@@42-@@@@
3WL1225-2@@42-@@@@
3WL1232-2@@42-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@41-@@@@
3WL1108-2@@41-@@@@
3WL1110-2@@41-@@@@
3WL1112-2@@41-@@@@
3WL1116-2@@41-@@@@
3WL1120-2@@41-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

66

3WL1208-2@@41-@@@@
3WL1210-2@@41-@@@@
3WL1212-2@@41-@@@@
3WL1216-2@@41-@@@@
3WL1220-2@@41-@@@@
3WL1225-2@@41-@@@@
3WL1232-2@@41-@@@@
3WL1240-2@@41-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

75.000
75.000
75.000
75.000
67.000
71.000
77.000
103.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

23

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


I

630
800
1000
1250
1600

630
800
1000
1250
1600

55

3WL1106-2@@43-@@@@
3WL1108-2@@43-@@@@
3WL1110-2@@43-@@@@
3WL1112-2@@43-@@@@
3WL1116-2@@43-@@@@

1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103

50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@43-@@@@
3WL1210-2@@43-@@@@
3WL1212-2@@43-@@@@
3WL1216-2@@43-@@@@
3WL1220-2@@43-@@@@
3WL1225-2@@43-@@@@
3WL1232-2@@43-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@44-@@@@
3WL1108-2@@44-@@@@
3WL1110-2@@44-@@@@
3WL1112-2@@44-@@@@
3WL1116-2@@44-@@@@
3WL1120-2@@44-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@44-@@@@
3WL1210-2@@44-@@@@
3WL1212-2@@44-@@@@
3WL1216-2@@44-@@@@
3WL1220-2@@44-@@@@
3WL1225-2@@44-@@@@
3WL1232-2@@44-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

24

Siemens 3WL IEC Breakers 2014

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@42-@@@@
3WL1108-3@@42-@@@@
3WL1110-3@@42-@@@@
3WL1112-3@@42-@@@@
3WL1116-3@@42-@@@@
3WL1120-3@@42-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@42-@@@@
3WL1210-3@@42-@@@@
3WL1212-3@@42-@@@@
3WL1216-3@@42-@@@@
3WL1220-3@@42-@@@@
3WL1225-3@@42-@@@@
3WL1232-3@@42-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000
50.000
50.000
50.000
50.000
50.000
50.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@41-@@@@
3WL1108-3@@41-@@@@
3WL1110-3@@41-@@@@
3WL1112-3@@41-@@@@
3WL1116-3@@41-@@@@
3WL1120-3@@41-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

80

3WL1208-3@@41-@@@@
3WL1210-3@@41-@@@@
3WL1212-3@@41-@@@@
3WL1216-3@@41-@@@@
3WL1220-3@@41-@@@@
3WL1225-3@@41-@@@@
3WL1232-3@@41-@@@@
3WL1240-3@@41-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103 67.000
103 67.000
103 67.000
103 67.000
103 67.000
103 71.000
103 77.000
103 103.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

25

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


I

630
800
1000
1250
1600

630
800
1000
1250
1600

66

3WL1106-3@@43-@@@@
3WL1108-3@@43-@@@@
3WL1110-3@@43-@@@@
3WL1112-3@@43-@@@@
3WL1116-3@@43-@@@@

1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103

50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@43-@@@@
3WL1210-3@@43-@@@@
3WL1212-3@@43-@@@@
3WL1216-3@@43-@@@@
3WL1220-3@@43-@@@@
3WL1225-3@@43-@@@@
3WL1232-3@@43-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@44-@@@@
3WL1108-3@@44-@@@@
3WL1110-3@@44-@@@@
3WL1112-3@@44-@@@@
3WL1116-3@@44-@@@@
3WL1120-3@@44-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@44-@@@@
3WL1210-3@@44-@@@@
3WL1212-3@@44-@@@@
3WL1216-3@@44-@@@@
3WL1220-3@@44-@@@@
3WL1225-3@@44-@@@@
3WL1232-3@@44-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

3)

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

26

Siemens 3WL IEC Breakers 2014

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@42-@@@@
3WL1108-4@@42-@@@@
3WL1110-4@@42-@@@@
3WL1112-4@@42-@@@@
3WL1116-4@@42-@@@@
3WL1120-4@@42-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@42-@@@@
3WL1210-4@@42-@@@@
3WL1212-4@@42-@@@@
3WL1216-4@@42-@@@@
3WL1220-4@@42-@@@@
3WL1225-4@@42-@@@@
3WL1232-4@@42-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

III

4000
5000

4000
5000

100

3WL1340-4@@42-@@@@
3WL1350-4@@42-@@@@

1
1

1 unit
1 unit

103
103

99.000
99.000

Vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@41-@@@@
3WL1108-4@@41-@@@@
3WL1110-4@@41-@@@@
3WL1112-4@@41-@@@@
3WL1116-4@@41-@@@@
3WL1120-4@@41-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

100

3WL1208-4@@41-@@@@
3WL1210-4@@41-@@@@
3WL1212-4@@41-@@@@
3WL1216-4@@41-@@@@
3WL1220-4@@41-@@@@
3WL1225-4@@41-@@@@
3WL1232-4@@41-@@@@
3WL1240-4@@41-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000
103.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@41-@@@@
3WL1350-4@@41-@@@@
3WL1363-4@@41-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

99.000
99.000
108.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without ground-fault prot.

AA

None

ETU15B: Protection functions LI5)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with ground-fault prot.

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

5)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 3WL IEC Breakers 2014

27

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Front main circuit connection, single hole


II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@43-@@@@
3WL1210-4@@43-@@@@
3WL1212-4@@43-@@@@
3WL1216-4@@43-@@@@
3WL1220-4@@43-@@@@
3WL1225-4@@43-@@@@
3WL1232-4@@43-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

III

4000

4000

100

3WL1340-4@@43-@@@@

1 unit

103

99.000

Front main circuit connection, double hole


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@44-@@@@
3WL1108-4@@44-@@@@
3WL1110-4@@44-@@@@
3WL1112-4@@44-@@@@
3WL1116-4@@44-@@@@
3WL1120-4@@44-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

50.000
50.000
50.000
50.000
50.000
50.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@44-@@@@
3WL1210-4@@44-@@@@
3WL1212-4@@44-@@@@
3WL1216-4@@44-@@@@
3WL1220-4@@44-@@@@
3WL1225-4@@44-@@@@
3WL1232-4@@44-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

67.000
67.000
67.000
67.000
67.000
71.000
77.000

III

4000

4000

100

3WL1340-4@@44-@@@@

1 unit

103

99.000

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI5)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary switch
2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

5)

ETU15B cannot be used with 3WL circuit breakers, size III.

28

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, fixed-mounted versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 130 kA at 500 V,


very high breaking capacity C
Article No.

PU
PS*/
(UNIT, P. unit
SET, M)

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Horizontal main circuit connection


III

4000
5000

4000
5000

130

3WL1340-5@@42-@@@@
3WL1350-5@@42-@@@@

1
1

1 unit
1 unit

103
103

99.000
99.000

130

3WL1340-5@@41-@@@@
3WL1350-5@@41-@@@@
3WL1363-5@@41-@@@@

1
1
1

1 unit
1 unit
1 unit

103 99.000
103 99.000
103 108.000

Vertical main circuit connection


III

4000
5000
6300

4000
5000
6300

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN3)

EB

ETU45B: Protection functions LSIN3)


with 4-line display

FB

ETU76B: Protection functions LSIN3)


with graphics display

NB

ETU27B: Protection functions LSING3)

DG

ETU45B: Protection functions LSING3)4)

EG

ETU45B: Protection functions


LSING3)4) with 4-line display

FG

ETU76B: Protection functions LSING3)4) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

3)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

4)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

29

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions

Selection and ordering data


Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 45 to 50)
I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@45-@@@@
3WL1108-2@@45-@@@@
3WL1110-2@@45-@@@@
3WL1112-2@@45-@@@@
3WL1116-2@@45-@@@@
3WL1120-2@@45-@@@@

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@45-@@@@
3WL1210-2@@45-@@@@
3WL1212-2@@45-@@@@
3WL1216-2@@45-@@@@
3WL1220-2@@45-@@@@
3WL1225-2@@45-@@@@
3WL1232-2@@45-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

54.000
54.000
54.000
54.000
54.000
54.000

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

75.000
75.000
75.000
75.000
72.000
76.000
82.000

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@46-@@@@
3WL1108-2@@46-@@@@
3WL1110-2@@46-@@@@
3WL1112-2@@46-@@@@
3WL1116-2@@46-@@@@
3WL1120-2@@46-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@46-@@@@
3WL1210-2@@46-@@@@
3WL1212-2@@46-@@@@
3WL1216-2@@46-@@@@
3WL1220-2@@46-@@@@
3WL1225-2@@46-@@@@
3WL1232-2@@46-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

30

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for
N conductors can be ordered by adding the supplement "Z" and the order
code "F23", see page 40.

5)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 55/66 kA at 500 V,


ECO breaking capacity N
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@47-@@@@
3WL1108-2@@47-@@@@
3WL1110-2@@47-@@@@
3WL1112-2@@47-@@@@
3WL1116-2@@47-@@@@
3WL1120-2@@47-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

66

3WL1208-2@@47-@@@@
3WL1210-2@@47-@@@@
3WL1212-2@@47-@@@@
3WL1216-2@@47-@@@@
3WL1220-2@@47-@@@@
3WL1225-2@@47-@@@@
3WL1232-2@@47-@@@@
3WL1240-2@@47-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

55

3WL1106-2@@48-@@@@
3WL1108-2@@48-@@@@
3WL1110-2@@48-@@@@
3WL1112-2@@48-@@@@
3WL1116-2@@48-@@@@
3WL1120-2@@48-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

66

3WL1208-2@@48-@@@@
3WL1210-2@@48-@@@@
3WL1212-2@@48-@@@@
3WL1216-2@@48-@@@@
3WL1220-2@@48-@@@@
3WL1225-2@@48-@@@@
3WL1232-2@@48-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for
N conductors can be ordered by adding the supplement "Z" and the order
code "F23", see page 40.

5)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

31

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 45 to 50)
I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@45-@@@@
3WL1108-3@@45-@@@@
3WL1110-3@@45-@@@@
3WL1112-3@@45-@@@@
3WL1116-3@@45-@@@@
3WL1120-3@@45-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

54.000
54.000
54.000
54.000
54.000
54.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@45-@@@@
3WL1210-3@@45-@@@@
3WL1212-3@@45-@@@@
3WL1216-3@@45-@@@@
3WL1220-3@@45-@@@@
3WL1225-3@@45-@@@@
3WL1232-3@@45-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

72.000
72.000
72.000
72.000
72.000
76.000
82.000

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@46-@@@@
3WL1108-3@@46-@@@@
3WL1110-3@@46-@@@@
3WL1112-3@@46-@@@@
3WL1116-3@@46-@@@@
3WL1120-3@@46-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@46-@@@@
3WL1210-3@@46-@@@@
3WL1212-3@@46-@@@@
3WL1216-3@@46-@@@@
3WL1220-3@@46-@@@@
3WL1225-3@@46-@@@@
3WL1232-3@@46-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

LSIN4)

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

ETU76B: Protection functions


with graphics display
Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

32

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for
N conductors can be ordered by adding the supplement "Z" and the order
code "F23", see page 40.

5)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 66/80 kA at 500 V,


standard breaking capacity S
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@47-@@@@
3WL1108-3@@47-@@@@
3WL1110-3@@47-@@@@
3WL1112-3@@47-@@@@
3WL1116-3@@47-@@@@
3WL1120-3@@47-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

80

3WL1208-3@@47-@@@@
3WL1210-3@@47-@@@@
3WL1212-3@@47-@@@@
3WL1216-3@@47-@@@@
3WL1220-3@@47-@@@@
3WL1225-3@@47-@@@@
3WL1232-3@@47-@@@@
3WL1240-3@@47-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

66

3WL1106-3@@48-@@@@
3WL1108-3@@48-@@@@
3WL1110-3@@48-@@@@
3WL1112-3@@48-@@@@
3WL1116-3@@48-@@@@
3WL1120-3@@48-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

80

3WL1208-3@@48-@@@@
3WL1210-3@@48-@@@@
3WL1212-3@@48-@@@@
3WL1216-3@@48-@@@@
3WL1220-3@@48-@@@@
3WL1225-3@@48-@@@@
3WL1232-3@@48-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU15B: Protection functions LI

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

* You can order this quantity or a multiple thereof.

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for
N conductors can be ordered by adding the supplement "Z" and the order
code "F23", see page 40.

5)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

Siemens 3WL IEC Breakers 2014

33

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 45 to 50)
I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@45-@@@@
3WL1108-4@@45-@@@@
3WL1110-4@@45-@@@@
3WL1112-4@@45-@@@@
3WL1116-4@@45-@@@@
3WL1120-4@@45-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

54.000
54.000
54.000
54.000
54.000
54.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@45-@@@@
3WL1210-4@@45-@@@@
3WL1212-4@@45-@@@@
3WL1216-4@@45-@@@@
3WL1220-4@@45-@@@@
3WL1225-4@@45-@@@@
3WL1232-4@@45-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

72.000
72.000
72.000
72.000
72.000
76.000
82.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@45-@@@@
3WL1350-4@@45-@@@@
3WL1363-4@@45-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

106.000
106.000
108.000

With guide frames, horizontal main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@46-@@@@
3WL1108-4@@46-@@@@
3WL1110-4@@46-@@@@
3WL1112-4@@46-@@@@
3WL1116-4@@46-@@@@
3WL1120-4@@46-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@46-@@@@
3WL1210-4@@46-@@@@
3WL1212-4@@46-@@@@
3WL1216-4@@46-@@@@
3WL1220-4@@46-@@@@
3WL1225-4@@46-@@@@
3WL1232-4@@46-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

III

4000
5000

4000
5000

100

3WL1340-4@@46-@@@@
3WL1350-4@@46-@@@@

1
1

1 unit
1 unit

103
103

190.000
190.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without ground-fault prot.

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

4)

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

ETU76B: Protection functions LSIN


with graphics display
Versions with ground-fault prot.

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
4)

Z options which are installed on the guide frame are not available.

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

5)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)
3)

34

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 85/100 kA at 500 V,


high breaking capacity H
Article No.

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

With guide frames, vertical main circuit connection


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@47-@@@@
3WL1108-4@@47-@@@@
3WL1110-4@@47-@@@@
3WL1112-4@@47-@@@@
3WL1116-4@@47-@@@@
3WL1120-4@@47-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200
4000

800
1000
1250
1600
2000
2500
3200
4000

100

3WL1208-4@@47-@@@@
3WL1210-4@@47-@@@@
3WL1212-4@@47-@@@@
3WL1216-4@@47-@@@@
3WL1220-4@@47-@@@@
3WL1225-4@@47-@@@@
3WL1232-4@@47-@@@@
3WL1240-4@@47-@@@@

1
1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000
146.000

III

4000
5000
6300

4000
5000
6300

100

3WL1340-4@@47-@@@@
3WL1350-4@@47-@@@@
3WL1363-4@@47-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

190.000
190.000
227.000

With guide frames, connecting flanges


I

630
800
1000
1250
1600
2000

630
800
1000
1250
1600
2000

85

3WL1106-4@@48-@@@@
3WL1108-4@@48-@@@@
3WL1110-4@@48-@@@@
3WL1112-4@@48-@@@@
3WL1116-4@@48-@@@@
3WL1120-4@@48-@@@@

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

84.000
84.000
84.000
84.000
84.000
84.000

II

800
1000
1250
1600
2000
2500
3200

800
1000
1250
1600
2000
2500
3200

100

3WL1208-4@@48-@@@@
3WL1210-4@@48-@@@@
3WL1212-4@@48-@@@@
3WL1216-4@@48-@@@@
3WL1220-4@@48-@@@@
3WL1225-4@@48-@@@@
3WL1232-4@@48-@@@@

1
1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103
103

109.000
109.000
109.000
109.000
109.000
123.000
136.000

III

4000

4000

100

3WL1340-4@@48-@@@@

1 unit

103

190.000

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without ground-fault prot.

AA

None

ETU15B: Protection functions LI6)

BB

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
4)

Z options which are installed on the guide frame are not available.

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for N conductors can be ordered by adding
the supplement "Z" and the order code "F23", see page 40.

5)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

6)

ETU15B cannot be used with 3WL circuit breakers, size III.

Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)
3)

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

35

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
4-pole, withdrawable versions
Size

Max. rated circuit


breaker current
In max.

Rated current1)
In

Breaking capacity DT
Icu = Ics

Icu 130 kA at 500 V,


very high breaking capacity C
Article No.

PU
PS*/
(UNIT, P. unit
SET, M)

PG

Weight
per PU
approx.

Basic price
per PU
kg

kA

Without guide frames2)


(for guide frames, see page 1/45 to 50)
III

4000
5000
6300

4000
5000
6300

130

3WL1340-5@@45-@@@@
3WL1350-5@@45-@@@@
3WL1363-5@@45-@@@@

1 1 unit
1 1 unit
1 1 unit

103
103
103

115.000
106.000
108.000

3WL1340-5@@46-@@@@
3WL1350-5@@46-@@@@

1 1 unit
1 1 unit

103
103

190.000
190.000

3WL1340-5@@47-@@@@
3WL1350-5@@47-@@@@
3WL1363-5@@47-@@@@

1 1 unit
1 1 unit
1 1 unit

103
103
103

190.000
190.000
227.000

With guide frames, horizontal main circuit connection


III

4000
5000

4000
5000

130

With guide frames, vertical main circuit connection


III

4000
5000
6300

4000
5000
6300

130

Additional
price

Options
Non-automatic
air circuit breakers3)

Without Electronic Trip Units

Electronic Trip Units

Versions without
ground-fault protection

AA

None

ETU25B: Protection functions LSI

CB

ETU45B: Protection functions LSIN4)

EB

ETU45B: Protection functions LSIN4)


with 4-line display

FB

ETU76B: Protection functions LSIN4)


with graphics display

NB

ETU27B: Protection functions LSING4)

DG

ETU45B: Protection functions LSING4)5)

EG

ETU45B: Protection functions


LSING4)5) with 4-line display

FG

ETU76B: Protection functions LSING4)5) with graphics display

NG

Versions with
ground-fault protection

Operating mechanism,
auxiliary release,
auxiliary switch

Manual operating mechanism with


mechanical closing, without 1st and
2nd auxiliary releases; auxiliary
switch 2 NC + 2 NO

1AA2

None

For further Article No. supplements


see page 1/37
Additional price
1)

The rated current is determined by the rating plug. For the standard
version, the supplied module is equal to the maximum rated current.
If a lower rated current is required, adaptation by order code on page 38.

2)

Z options which are installed on the guide frame are not available.

3)

For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see page 5.

36

Siemens 3WL IEC Breakers 2014

4)

Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 51. The
internal current transformers for
N conductors can be ordered by adding the supplement "Z" and the order
code "F23", see page 40.

5)

ETU45B to ETU76B with ground-fault protection module GFM AT


(alarm and tripping), see page 51.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options

Selection and ordering data


Article No. supplement
3WL1 ... - ..... -

Additional price

????

Operating mechanisms
Manual operating mechanism with mechanical closing

None

Manual operating mechanism with mechanical and electrical closing,


closing coil suitable for uninterrupted duty, 100 % OP
50/60 Hz V AC

V DC

110

110 ... 125

230

220

Manual/motorized operating mechanism with mechanical and electrical closing,


closing coil suitable for uninterrupted duty, 100 % OP
Motor

Closing solenoid

50/60 Hz V AC

V DC

50/60 Hz V AC

V DC

208 ... 240

220 ... 250

230

220

110 ... 127

110 ... 125

110

110 ... 125

--

24

--

24

Note
To order different voltages for motorized operating mechanism and closing solenoid or
closing coil for synchronization purposes:
"1" at the 13th digit of the Article No. and order codes, see page 39.

1st auxiliary release


Type

Condition

Without 1st auxiliary


release

--

Shunt release suitable


for uninterrupted duty,
100 % OP

Operating range
0.85 ... 1.1 Us

Us 50/60 Hz V AC Us V DC
---

None

--

24

--

30

--

48

--

60

110 ... 127

110 ... 125

208 ... 240

220 ... 250

2nd auxiliary release


Type

Condition

Without 2nd auxiliary


release

--

Shunt release suitable


for uninterrupted duty,
100 % OP

Operating range
0.85 ... 1.1 Us

Undervoltage release,
instantaneous
( 80 ms),
short-delay ( 200 ms)

Operating range
0.85 ... 1.1 Us

Undervoltage release, Operating range


can be delayed between 0.85 ... 1.1 Us
0.2 s and 3.2 s

Us 50/60 Hz V AC Us V DC
---

None

--

24

--

30

--

48

--

60

110 ... 127

110 ... 125

208 ... 240

220 ... 250

--

24

--

30

--

48

--

60

110 ... 127

110 ... 125

208 ... 240

220 ... 250

380 ... 415

--

--

48

110 ... 127

110 ... 125

208 ... 240

220 ... 250

380 ... 415

--

Auxiliary switches
1st auxiliary switch block
2 NO + 2 NC

None

4 NO + 4 NC

6 NO + 2 NC

5 NO + 3 NC

1st + 2nd auxiliary switch block

Additional price

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

37

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

Additional price

3WL....-.....-....-Z
??? +...+...

Operating manuals
Printed version

French/Italian

A 1 1

Spanish/Portuguese

A 1 2

Rated voltage 1000 V AC and 690 V IT networks

Additional price
3-pole

Additional price
4-pole

Conditions

Size

Rated current In

Only for circuit breakers with high breaking


capacity H
(8th digit of the Article No. is a "4")
Cannot be combined with "Rated voltage
1150 V AC order code "A15".

I1)

Up to 2000 A

A 0 5

II1)

Up to 2000 A

A 0 5

2500 A

A 0 5

3200 A

A 0 5

4000 A

A 0 5

5000 A

A 0 5

6300 A

A 0 5

III1)2)

Rated voltage 1150 V AC


Conditions

Size

Rated current In

Only for circuit breakers with high breaking


capacity H
(8th digit of the Article No. is a "4")
Cannot be combined with "Rated voltage
1000 V AC order code "A05".

II

Up to 2000 A

A 1 5

2500 A

A 1 5

3200 A

A 1 5

4000 A

A 1 5

A 1 6

A 0 8

A 0 8

A 0 8

Note
For size III select a circuit breaker with very high breaking capacity C, which can be used
as standard up to 1150 V AC.

Rated voltage 690 V AC (+ 20 %)


Conditions

Size

Rated current In

Only for 3WL11 circuit breakers, size I,


with high breaking capacity H
(8th digit of the Article No. is a "4").

Up to 2000 A

Tinned version of the customer's connections on the guide frame3)4)


Conditions

Size

Only for circuit breakers in withdrawable version


I
with horizontal connection or flange connection.
II
The normal delivery time increases to 15 work days.
III

Special packaging (moisture protection)

Additional price

Special packaging for extended technical requirements


Cardboard packaging with water-repellent coating on corrugated cardboard
(moisture protection)

A 6 1

Rating plugs
Conditions

Additional price

Size

Only one module is possible per circuit breaker


I, II
(not in conjunction with Electronic Trip Unit
ETU15B).
As standard the Electronic Trip Units are equipped
with a rating plug which is equal to the maximum
rated current circuit breaker (In max). The rated current of the selected rating plug must be smaller
than In max.
I, II, III

II, III

III

Rated current InA


250

B 0 2

None

315

B 0 3

None

400

B 0 4

None

500

B 0 5

None

630

B 0 6

None

800

B 0 8

None

1000

B 1 0

None

1250

B 1 2

None

1600

B 1 6

None

2000

B 2 0

None

2500

B 2 5

None

3200

B 3 2

None

4000

B 4 0

None

5000

B 5 0

None

6300

B 6 3

None

Additional price
1)

If ordering withdrawable circuit breaker and guide frame separately,


specify order code "A05" for withdrawable circuit breaker and guide frame.

2)

Not necessary for circuit breakers with very high breaking


capacity C as these circuit breakers can be used as standard up to
1150 V AC.

3)

Front connections are tinned as standard.

4)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

38

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

3WL....-.....-....-Z

Additional price

??? +...+...

Indication/operator control elements, door sealing frames


C 0 1

Button with sealing cap

C 1 1

Key operation with lock CES

C 1 2

Storage status signaling switches 2) (S21)

1 NO contact

C 2 0

Ready-to-close signaling switches (S20)

1 NO contact

C 2 2

Signaling switches2)

For the first auxiliary release (S22)

C 2 6

For the second auxiliary release (S23)

C 2 7

S 2 5

S 2 4

T 4 0

5-digit mechanical operating cycles counter1)


Electrical ON button in the operator panel
Possible only for circuit breakers
with closing coil.

2)

Motor shutdown switch in the operator panel3)


EMERGENCY-STOP pushbuttons

Mushroom pushbutton instead of


the mechanical OFF pushbutton

Door sealing frames

Reclosing lockout and remote resets


K 0 1

1. Tripped signaling switch2)4)

1 CO contact

K 0 7

2. Tripped signaling switch2)4)8)

1 NO contact

K 0 6

Type

50/60 Hz V AC

24

K 1 0

48

K 1 1

125

K 1 2

208 ... 250

K 1 3

24 ... 30

M0 1

Automatic reset of the reclosing lockout

Remote reset solenoid for displays and reset -buttons


-including automatic reset of the reclosing
120
lockout
208 ... 250

V DC

Motorized operating mechanisms and closing/opening coils


Type

Conditions

Motorized operating mechanism

Only possible if the


13th digit of the
Article No. = "1"

Motor
50/60 Hz V AC

Type

Conditions

--

48 ... 60

M0 3

110 ... 127

110 ... 125

M0 5

208 ... 240

220 ... 250

M0 6

--

Activation coils
50/60 Hz V AC

Closing coil suitable Only possible if the


for uninterrupted
13th digit of the
duty, 100 % OP
Article No. = "1"

Type

Conditions

Type

Conditions

Opening coils
(shunt release)6)7)

Not suitable for uninterrupted duty, 5% OP,


synchronizable

V DC

--

24

M2 1

--

30

M2 2

--

48

M2 3

--

60

M2 4

110 ... 127

110 ... 125

M2 5

208 ... 240

220 ... 250

M2 6

Activation coils
50/60 Hz V AC

Closing coil5) not


Only possible if the
suitable for uninter- 13th digit of the
rupted duty, 5 % OP, Article No. = "1"
synchronizable

V DC

V DC

--

24

M3 1

--

48

M3 3

110 ... 127

110 ... 125

M3 5

208 ... 240

220 ... 250

M3 6

Activation coils
50/60 Hz V AC

V DC

--

24

M4 1

--

48

M4 3

110 ... 127

110 ... 125

M4 5

208 ... 240

220 ... 250

M4 6

Additional price
1)
2)
3)
4)
5)
6)
7)
8)

Only possible with motorized operating mechanism.


Not possible with communications interface option, order code "F02" or
"F12".
Only for switches with motorized operating mechanism, not possible with
order codes "C11", "C12".
Not available for non-automatic air circuit breakers.
Overexcited, i.e. operating time 50 ms (standard > 80 ms).
Only possible if the 14th position of the Article No. for the circuit breaker is
"A", i.e. "without 1st auxiliary release".
Overexcited, i.e. operating time 50 ms (standard > 80 ms).
Only possible with option "K07".

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

39

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

3WL....-.....-....-Z

Additional
price

??? +...+...

Interlocks, covers, position signaling switches (for fixed-mounted version)


Mutual mechanical interlockings
(interlocking module with Bowden wire 2 m)

S 5 5

For withdrawable circuit breakers with guide


frame

R 5 5

For guide frames

R 5 6

For withdrawable circuit breakers


Number of poles Size

R 5 7

3-pole

R 1 0

II

R 1 0

III

R 1 0

R 1 0

II

R 1 0

III
Number of poles Size

R 1 0

3-pole

R 2 1

II

R 2 1

III

R 2 1

R 2 1

II

R 2 1

III

R 2 1

Fixed-mounted circuit breakers

Interlocks, covers, position signaling switches (for withdrawable version)


Mutual mechanical interlockings
(interlocking module with Bowden wire 2 m)

Arc chute covers


Not available for
- 1000 V version (order code "A05")
- DC version
- 4000 A size II
- 1150 V version (order code "A15")
- 150 kA version, size III

Shutters
2-part
lockable
with padlocks1)

Version

4-pole

4-pole

Connected
position

Test position

Disconnected
position

1 CO

1 CO

1 CO

R 1 5

3 CO

2 CO

1 CO

R 1 6

Breaker status sensor (BSS)

F 0 1

PROFIBUS-DP communications interface2) Including COM15 and breaker status sensor


(BSS)

F 0 2

MODBUS-RTU communications interface2) Including COM16 and breaker status sensor


(BSS)

F 1 2

Measurement function Plus


(without PROFIBUS/MODBUS
communications interface)3)

F 0 5

F 2 3

F 2 3

F 2 3

F 3 1

Position signaling switches for guide


frames

Communication and measurement functions

Overload and short-circuit protection for neutral conductors


Size
Internal current transformer
for N conductor
I
Only possible with 4-pole circuit breakers with
II
ETU27B to ETU76B
III

EMC filters
EMC filters
Common-mode interference suppressor filters
(e.g. in IT networks, caused by frequency converters)
Insertion loss (asymmetric) in the range 40 kHz to 10 MHz >40 dB.

Additional price
1)

Padlocks not included in scope of supply.

2)

If ordering withdrawable circuit breaker and guide frame separately,


specify order code "F02" or "F12" for withdrawable circuit breaker only.

3)

Additional voltage transformers are required for connection of the


measurement function Plus, see page 60.

40

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

3WL....-.....-....-Z

Additional
price

??? +...+...

Locking devices (for fixed-mounted versions and withdrawable versions)


Locking devices against
unauthorized closing,
in the operator panels
The disconnector unit fulfills the requirements
for main circuit breakers according to
EN 60204-1

EMERGENCY-STOP pushbuttons

Version
Made by CES

S 0 1

Made by IKON

S 0 3

Assembly kit FORTRESS or Castell1)

S 0 5

Assembly kit for padlocks2)

S 0 7

Made by Ronis

S 0 8

Made by Profalux

S 0 9

Mushroom pushbutton instead of the mechanical S 2 4


OFF pushbutton

S 3 3

Made by CES

R 6 1

Made by Ronis

R 6 8

Made by Profalux

R 6 0

Made by CES

S 7 1

Made by Profalux

S 7 5

Made by Ronis

S 7 6

S 3 0

R 3 0

To prevent movement with the cabinet door open R 5 0

Locking devices for operating mechanism


handles with padlock2)

Locking devices (for withdrawable version)


Locking devices against unauthorized closing, for withdrawable circuit breakers
The disconnector unit fulfills the requirements
for main circuit breakers acc. to EN 60204-1,
consisting of a lock in the cabinet door, active
in the connected position, function is retained
when circuit breaker is replaced.
Not possible in combination with order code
"R81", "R85" or "R86".

Version

Locking devices to prevent movement of


the withdrawable circuit breakers
Lock for mounting on the circuit breaker

Version

Locking mechanisms (for fixed-mounted versions)


Locking devices
Not possible in combination
with order code "R81", "R85" or "R86".

To prevent opening of the cabinet door


in ON position

Locking devices (for withdrawable version)


Locking devices

Version

Not possible in combination with order code


"R81", "R85" or "R86".

To prevent opening of the cabinet door


in connected position

Locking mechanism to prevent movement


of the withdrawable circuit breakers in disconnected position, consisting of Bowden
wire and lock in the cabinet door
Not possible in combination with order code
"R30", "R50", "R61", "R68" or "R60".

Version
Made by CES

R 8 1

Made by Ronis

R 8 5

Made by Profalux

R 8 6

Fixed-mounted

N 6 1

Withdrawable

P 6 1

Connection methods for auxiliary conductors


(for fixed-mounted and withdrawable versions)
Connections for screwless
terminals (tension spring)

Version

Additional price
1)

Locks must be ordered from the manufacturer.

2)

Padlock not included in the scope of supply.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

41

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

Additional price

3WL....-.....-....-Z
??? +...+...

For withdrawable circuit breakers with guide frames or for guide frames1)
Note

Additional price
3-pole

Additional price
4-pole

To select this connection method the 12th digit of the Article No. for the circuit breaker
must be a "6".
Connection methods for main connections

Size

Rated current In

Top and bottom:2)


accessible from front,
single hole

Up to 1600 A

P 0 0

II

Up to 2000 A

P 0 0

Up to 2500 A

P 0 0

Up to 3200 A

P 0 0

III

Up to 4000 A

P 0 0

Connection methods for main connections

Size

Rated current In

Top and bottom:


accessible from front,
double hole

Up to 2000 A

P 0 1

II

Up to 2000 A

P 0 1

Up to 2500 A

P 0 1

Up to 3200 A

P 0 1

III

Up to 4000 A

P 0 1

Connection methods for main connections

Size

Rated current In

Top:2)
horizontal
Bottom:
accessible from front,
single hole

Up to 1600 A

P 0 7

II

Up to 2000 A

P 0 7

Up to 2500 A

P 0 7

Up to 3200 A

P 0 7

III

Up to 4000 A

P 0 7

Connection methods for main connections

Size

Rated current In

Top:
vertical
Bottom:
horizontal

Up to 2000 A

P 1 8

II

Up to 2000 A

P 1 8

Up to 2500 A

P 1 8

Up to 3200 A

P 1 8

Up to 4000 A

P 1 8

Up to 5000 A

P 1 8

III
Connection methods for main connections

Size

Rated current In

Top:
Connecting flange
Bottom:
horizontal

Up to 2000 A

P 1 9

II

Up to 2000 A

P 1 9

Up to 2500 A

P 1 9

Up to 3200 A

P 1 9

III

Up to 4000 A

P 1 9

Connection methods for main connections

Size

Rated current In

Top:
horizontal
Bottom:
vertical

Up to 2000 A

P 2 3

II

Up to 2000 A

P 2 3

Up to 2500 A

P 2 3

Up to 3200 A

P 2 3

Up to 4000 A

P 2 3

Up to 5000 A

P 2 3

III
Connection methods for main connections

Size

Rated current In

Top:
horizontal
Bottom:
connecting flange

Up to 2000 A

P 2 8

II

Up to 2000 A

P 2 8

Up to 2500 A

P 2 8

Up to 3200 A

P 2 8

Up to 4000 A

P 2 8

III
Additional price
1)

Only horizontal connection and vertical connection are available for circuit
breakers with very high breaking capacity C.

2)

Not for 3WL size I with high breaking capacity H.

42

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Options
Add "-Z" to the complete Article No.
and indicate the appropriate order code(s).

Additional price

3WL....-.....-....-Z
??? +...+...

For fixed-mounted circuit breakers


Note

Additional price
3-pole

Additional price
4-pole

To select this connection method the 12th digit of the Article No. for the circuit breaker
must be a "2".
Connection methods for main connections

Size

Rated current In

Top:1)
horizontal
Bottom:
accessible from front,
single hole

Up to 1600 A

N 1 1

II

Up to 2000 A

N 1 1

Up to 2500 A

N 1 1

Up to 3200 A

N 1 1

III

Up to 4000 A

N 1 1

Connection methods for main connections

Size

Rated current In

Top:
vertical
Bottom:
horizontal

Up to 1600 A

N 2 0

Up to 2000 A

N 2 0

Up to 2000 A

N 2 0

Up to 2500 A

N 2 0

Up to 3200 A

N 2 0

Up to 4000 A

N 2 0

Up to 5000 A

N 2 0

II

III
Connection methods for main connections

Size

Rated current In

Top:
horizontal
Bottom:
vertical

Up to 1600 A

N 2 4

Up to 2000 A

N 2 4

Up to 2000 A

N 2 4

Up to 2500 A

N 2 4

Up to 3200 A

N 2 4

Up to 4000 A

N 2 4

Up to 5000 A

N 2 4

II

III
Additional price
1)

Not for 3WL size I with high breaking capacity H

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

43

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts

Overview
Determination of the number of auxiliary supply connectors required

NSE0_01104

This selection is only required if the guide frame is ordered under a


separate Article No.
X7

X6

X5

X8

The required number of auxiliary supply connectors


depends on:
Operating mechanism type
Electronic Trip Unit with/without current transformer
Type and number of auxiliary releases
Number of auxiliary switches
COM15/COM16 communication interface
Number of auxiliary supply connectors

Terminal

First auxiliary supply connector X6 always required.

X6

b
b1
b2
b3

Operating mechanisms
Manual operating mechanism with stored-energy feature with mechanical closing
Manual operating mechanism with stored-energy feature with mechanical and electrical closing
Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing

0
0
+1

X6
X5

c
c1
c2

c3
c4

Electronic Trip Units


Electronic Trip Units ETU15B, ETU25B, ETU27B
Electronic Trip Units ETU45B, ETU76B (internal CubicleBUS)

Connections for external current transformers for overload protection in the N conductor and ground-fault protection
Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected)
Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected)

X8

X8
X8

d
d1
d2

Auxiliary releases
With/without 1st auxiliary release (shunt release F1)
2nd auxiliary release (shunt release F2, undervoltage release F3, delayable undervoltage release F4)

e
e1
e2

Auxiliary switch blocks


1st auxiliary switch block 2 NO + 2 NC
1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected)

X6
X5

f
f1
f2

Communication modules
Without communication module COM15/COM16
With communication module COM15/COM16
occupies the entire terminal strip X7, making the following options no longer possible:
Tripped signal switch S24
Stored-energy status indication S21
Electrical ON button S10
Signaling switch on first and second auxiliary release S22 + S23

0
+1

X7

g
g1
g2
g3
g4
g5
g6
g7
g8

Optional signals/accessories
Tripped signaling switch S24 (only when f2 not selected)
Stored-energy status indicator S21 (only when f2 not selected, required if g1 not selected)
Electric ON button S10 (only when f2 not selected, required if g1 or g2 not selected)
Signaling switch at first auxiliary release S22 (only when f2 not selected, required if g1, g2 or g3 not selected)
Signaling switch at second auxiliary release S23 (only when f2 not selected, required if g1, g2, g3 or g4 not selected)
Switch on ready-to-close signaling switch S20
Motor shutdown switch S12 (only if motorized operating mechanism selected)
Remote reset solenoid F7 (required if c2 not selected)

+1
+1
+1
+1
+1
0
0
+1

X7
X7
X7
X7
X7
X6
X5
X8

Total number of auxiliary supply connectors

(max. 4)

0
+1

+1
+1
0
+1
0
+1

X6
X5

For ordering the auxiliary supply connectors see at "Accessories and spare parts, Guide frames for AC circuit breakers/non-automatic air circuit breakers", pages 45 to 50 and under "Accessories and spare parts, Auxiliary conductor connections, Auxiliary supply
connectors", page 56.

44

Siemens 3WL IEC Breakers 2014

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts

Selection and ordering data


Guide frames for AC circuit breakers/non-automatic air circuit breakers
Size

Max. rated circuit breaker


current
In max.

Breaking
capacity
Icu = Ics

kA

DT

PU
(UNIT,
Basic price SET, M)
per PU

Guide frames for 3-pole circuit breakers/


non-automatic air circuit breakers
Article No.

PS*/
P. unit

PG

Weight
per PU
approx.
kg

Front main circuit connection, single hole


I

1000
1600

... 66
... 66

3WL9211-1AA@@-@@A1
3WL9211-2AA@@-@@A1

1
1

1 unit
1 unit

103
103

25.000
25.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3AA@@-@@A1
3WL9212-4AA@@-@@A1
3WL9212-5AA@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

31.000
39.000
45.000

III

4000

... 100

3WL9213-6AA@@-@@A1

1 unit

103

60.000

Front main circuit connection, double hole


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1AB@@-@@A1
3WL9211-2AB@@-@@A1
3WL9211-3AB@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

25.000
25.000
25.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3AB@@-@@A1
3WL9212-4AB@@-@@A1
3WL9212-5AB@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

31.000
39.000
45.000

III

4000

... 100

3WL9213-6AB@@-@@A1

1 unit

103

60.000

Horizontal main circuit connection


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1AC@@-@@A1
3WL9211-2AC@@-@@A1
3WL9211-3AC@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

25.000
25.000
25.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3AC@@-@@A1
3WL9212-4AC@@-@@A1
3WL9212-5AC@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

31.000
39.000
45.000

III

4000
5000
4000
5000

... 100
... 100
... 150
... 150

3WL9213-6AC@@-@@A1
3WL9213-7AC@@-@@A1
3WL9213-6AC@@-@@C1
3WL9213-7AC@@-@@C1

1
1
1
1

1 unit
1 unit
1 unit
1 unit

103
103
103
103

60.000
60.000
63.000
63.000

Additional
price

Options
Number of auxiliary
supply connectors

Without

None

1 connector

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors,
see table on page 44.
Type of auxiliary circuit
connections

Position signaling switches

Shutters

Without

None

With screw connection


(SIGUT, standard)

With screwless connection


method (tension spring)

Without

None

Option 1:
Connected position 1 CO,
test position 1 CO,
disconnected position 1 CO

Option 2:
Connected position 3 CO,
test position 2 CO,
disconnected position 1 CO

Without

None

With shutter,
Size I
2-part, lockable Size II

Size III

Additional price
1)
For 3WL circuit breakers size I from 630A to 2000A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

45

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Add "-Z" to the complete Article No. and indicate
the appropriate order code(s).

3WL9 21.-.....-....-Z

Additional
price

@@@

Rated voltage 1000 V AC and 690 V IT networks


Size I (breaking capacity H)

A 0 5

Size II, except 4000 A (breaking capacity H)

A 0 5

Size III, not necessary with circuit breakers with very high breaking
capacity

A 0 5

A 1 5

A 1 6

Size I

A 0 8

Size II

A 0 8

Size III

A 0 8

Rated voltage 1150 V AC


Size II, except 4000 A (breaking capacity H)

Rated voltage 690 V AC (+ 20 %)


Size I (breaking capacity H)

Tinned version of the customer's connections on guide frame1)2)


Only for guide frames with horizontal connection or flange connection

Notes
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see pages 38 to 43.
Additional price
1)

Front connections are tinned as standard.

2)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

46

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Size

Max. rated circuit breaker


current In max.

Breaking capacity
Icu = Ics

kA

Guide frames for 3-pole circuit breakers/


PU
non-automatic air circuit breakers
(UNIT,
SET,
Article No.
Basic price
M)
per PU

DT

PS*/
P.
unit

PG

Weight
per PU
approx.
kg

Vertical main circuit connection


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1AD@@-@@A1
3WL9211-2AD@@-@@A1
3WL9211-3AD@@-@@A1

1 1 unit
1 1 unit
1 1 unit

103
103
103

25.000
25.000
25.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3AD@@-@@A1
3WL9212-4AD@@-@@A1
3WL9212-5AD@@-@@A1

1 1 unit
1 1 unit
1 1 unit

103
103
103

31.000
39.000
45.000

III

4000
5000
6300
4000
5000
6300

... 100
... 100
... 100
... 150
... 150
... 150

3WL9213-6AD@@-@@A1
3WL9213-7AD@@-@@A1
3WL9213-8AD@@-@@A1
3WL9213-6AD@@-@@C1
3WL9213-7AD@@-@@C1
3WL9213-8AD@@-@@C1

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103
103
103
103
103
103

60.000
60.000
70.000
63.000
63.000
74.000

Main circuit connection connecting flanges


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1AE@@-@@A1
3WL9211-2AE@@-@@A1
3WL9211-3AE@@-@@A1

1 1 unit
1 1 unit
1 1 unit

103
103
103

25.000
25.000
25.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3AE@@-@@A1
3WL9212-4AE@@-@@A1
3WL9212-5AE@@-@@A1

1 1 unit
1 1 unit
1 1 unit

103
103
103

31.000
39.000
45.000

III

4000

... 100

3WL9213-6AE@@-@@A1

1 1 unit

103

60.000

Options

Add. price

Number of auxiliary Without


supply connectors 1 connector

None

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors, see table on page 44.
Type of auxiliary
Without
circuit connections With screw connection (SIGUT, standard)
With screwless connection method (tension spring)
Position signaling
switches

Shutters

None

Without

None

Option 1: Connected position 1 CO,


test position 1 CO, disconnected position 1 CO

Option 2: Connected position 3 CO,


test position 2 CO, disconnected position 1 CO

Without

None

With shutter,

Size I

2-part,

Size II

lockable

Size III

Add "-Z" to the complete Article No. and indicate the


appropriate order code(s).

3WL9 21.-.....-....-Z
@@@

Additional
price

Rated voltage 1000 V AC and 690 V IT networks


Size I (breaking capacity H)

A 0 5

Size II, except 4000 A (breaking capacity H)

A 0 5

Size III, not necessary with circuit breakers with very high breaking capacity

A 0 5

A 1 5

A 1 6

Size I

A 0 8

Size II

A 0 8

Size III

A 0 8

Rated voltage 1150 V AC


Size II, except 4000 A (breaking capacity H)

Rated voltage 690 V AC (+ 20 %)


Size I (breaking capacity H)

Tinned version of the customer's connections on guide frame1)2)


Only for guide frames with horizontal connection or flange connection

Notes
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see pages 38 to 43.
Additional price
1)
For 3WL circuit breakers size I from 630A to 2000A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.

* You can order this quantity or a multiple thereof.

2)

Front connections are tinned as standard.

3)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

Siemens 3WL IEC Breakers 2014

47

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Size

Max. rated circuit breaker


current
In max.

Breaking
capacity
Icu = Ics

kA

DT

PU
(UNIT,
Basic price SET, M)
per PU

PS*/
P. unit

Guide frames for 4-pole circuit breakers/


non-automatic air circuit breakers
Article No.

PG

Weight
per PU
approx.
kg

Front main circuit connection, single hole


I

1000
1600

... 66
... 66

3WL9211-1BA@@-@@A1
3WL9211-2BA@@-@@A1

1
1

1 unit
1 unit

103
103

30.000
30.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3BA@@-@@A1
3WL9212-4BA@@-@@A1
3WL9212-5BA@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

37.000
47.000
54.000

III

4000

... 100

3WL9213-6BA@@-@@A1

1 unit

103

84.000

Front main circuit connection, double hole


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1BB@@-@@A1
3WL9211-2BB@@-@@A1
3WL9211-3BB@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

30.000
30.000
30.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3BB@@-@@A1
3WL9212-4BB@@-@@A1
3WL9212-5BB@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

37.000
47.000
54.000

III

4000

... 100

3WL9213-6BB@@-@@A1

1 unit

103

84.000

Horizontal main circuit connection


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1BC@@-@@A1
3WL9211-2BC@@-@@A1
3WL9211-3BC@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

30.000
30.000
30.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3BC@@-@@A1
3WL9212-4BC@@-@@A1
3WL9212-5BC@@-@@A1

1
1
1

1 unit
1 unit
1 unit

103
103
103

37.000
47.000
54.000

III

4000
5000
4000
5000

... 100
... 100
... 130
... 130

3WL9213-6BC@@-@@A1
3WL9213-7BC@@-@@A1
3WL9213-6BC@@-@@C1
3WL9213-7BC@@-@@C1

1
1
1
1

1 unit
1 unit
1 unit
1 unit

103
103
103
103

84.000
84.000
87.000
87.000

Additional
price

Options
Number of auxiliary
supply connectors

Without

None

1 connector

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors,
see table on page 44.
Type of auxiliary circuit
connections

Position signaling switches

Shutters

Without

None

With screw connection


(SIGUT, standard)

With screwless connection


method (tension spring)

Without

None

Option 1:
Connected position 1 CO,
test position 1 CO,
disconnected position 1 CO

Option 2:
Connected position 3 CO,
test position 2 CO,
disconnected position 1 CO

Without
With shutter,
2-part, lockable

None

Size I

Size II

Size III

Additional price
1)
For 3WL circuit breakers size I from 630A to 2000A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.

48

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Add "-Z" to the complete Article No. and indicate
the appropriate order code(s).

3WL9 21.-.....-....-Z
@@@

Additional
price

Rated voltage 1000 V AC and 690 V IT networks


Size I (breaking capacity H)

A 0 5

Size II, except 4000 A (breaking capacity H)

A 0 5

Size III, not necessary with circuit breakers with very high breaking
capacity

A 0 5

A 1 5

A 1 6

Size I

A 0 8

Size II

A 0 8

Size III

A 0 8

Rated voltage 1150 V AC


Size II, except 4000 A (breaking capacity H)

Rated voltage 690 V AC (+ 20 %)


Size I (breaking capacity H)

Tinned version of the customer's connections on guide frame1)2)


Only for guide frames with horizontal connection or flange connection

Notes
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see pages 38 to 43.
Additional price
1)

Front connections are tinned as standard.

2)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

49

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Size

Max. rated circuit breaker


current
In max.

Breaking capacity
Icu = Ics

kA

DT Guide frames for 4-pole circuit breakers/


non-automatic air circuit breakers

PU
PS*/
(UNIT, P. unit
SET,
Basic price
M)
per PU

Article No.

PG

Weight
per PU
approx.
kg

Vertical main circuit connection


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1BD@@-@@A1
3WL9211-2BD@@-@@A1
3WL9211-3BD@@-@@A1

1 1 unit 103
1 1 unit 103
1 1 unit 103

30.000
30.000
30.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3BD@@-@@A1
3WL9212-4BD@@-@@A1
3WL9212-5BD@@-@@A1

1 1 unit 103
1 1 unit 103
1 1 unit 103

37.000
47.000
54.000

III

4000
5000
6300
4000
5000
6300

... 100
... 100
... 100
... 130
... 130
... 130

3WL9213-6BD@@-@@A1
3WL9213-7BD@@-@@A1
3WL9213-8BD@@-@@A1
3WL9213-6BD@@-@@C1
3WL9213-7BD@@-@@C1
3WL9213-8BD@@-@@C1

1
1
1
1
1
1

1 unit
1 unit
1 unit
1 unit
1 unit
1 unit

103 84.000
103 84.000
103 119.000
103 88.000
103 88.000
103 124.000

Main circuit connection connecting flanges


I

1000
1600
20001)

... 66
... 66
... 85

3WL9211-1BE@@-@@A1
3WL9211-2BE@@-@@A1
3WL9211-3BE@@-@@A1

1 1 unit 103
1 1 unit 103
1 1 unit 103

30.000
30.000
30.000

II

2000
2500
3200

... 100
... 100
... 100

3WL9212-3BE@@-@@A1
3WL9212-4BE@@-@@A1
3WL9212-5BE@@-@@A1

1 1 unit 103
1 1 unit 103
1 1 unit 103

37.000
47.000
54.000

III

4000

... 100

3WL9213-6BE@@-@@A1

1 1 unit 103

84.000

Additional
price

Options
Number of auxiliary Without
supply connectors 1 connector

None

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors, see table on page 44.
Type of auxiliary
Without
circuit connections With screw connection (SIGUT, standard)
With screwless connection method (tension spring)
Position signaling
switches

Shutters

None

Without

None

Option 1: Connected position 1 CO,


test position 1 CO, disconnected position 1 CO

Option 2: Connected position 3 CO,


test position 2 CO, disconnected position 1 CO

Without
With shutter, 2-part,
lockable

None

Size I

Size II

Size III

Add "-Z" to the complete Article No. and indicate the


appropriate order code(s).

3WL9 21.-.....-....-Z
@@@

Additional
price

Rated voltage 1000 V AC and 690 V IT networks


Size I (breaking capacity H)

A 0 5

Size II, except 4000 A (breaking capacity H)

A 0 5

Size III, not necessary with circuit breakers with very high breaking capacity

A 0 5

A 1 5

A 1 6

Size I

A 0 8

Size II

A 0 8

Size III

A 0 8

Rated voltage 1150 V AC


Size II, except 4000 A (breaking capacity H)

Rated voltage 690 V AC (+ 20 %)


Size I (breaking capacity H)

Tinned version of the customer's connections on guide frame1)2)


Only for guide frames with horizontal connection or flange connection

Notes
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see pages 38 to 43.
Additional price
1) For 3WL circuit breakers size I from 630A to 2000A with high breaking
capacity H and 3WL circuit breakers size I with rated current In = 2000 A.

50

Siemens 3WL IEC Breakers 2014

2)

Front connections are tinned as standard.

3)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.
* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
Quickship
per PU catalog no. for
items (in limitQuickship items ed quantity).

NSE0_01610b

Protective devices with device holder and


optional measurement function1)

3WL931.-.AA.0-0AA1

Contact factory
for availability

Type

With protection
function

Measurement
function

ETU15B

LI

Without

3WL9311-5AA00-0AA2

ETU25B

LSI

Without

3WL9312-5AA00-0AA2

ETU27B

LSING

Without

3WL9312-7AA00-0AA2

ETU45B
(without display)

LSIN(G)

Without
With measurement
function Plus

3WL9314-5AA00-0AA2
3WL9314-5AA20-0AA2

ETU76B

LSIN(G)

Without
With measurement
function Plus

3WL9317-6AA00-0AA2
3WL9317-6AA20-0AA2

250
315
400
500

3WL9111-0AA51-0AA0
3WL9111-0AA52-0AA0
3WL9111-0AA53-0AA0
3WL9111-0AA54-0AA0

630
800
1000

3WL9111-0AA55-0AA0
3WL9111-0AA56-0AA0
3WL9111-0AA57-0AA0

I, II, III

1250
1600
2000

3WL9111-0AA58-0AA0
3WL9111-0AA61-0AA0
3WL9111-0AA62-0AA0

II, III

2500
3200
4000

3WL9111-0AA63-0AA0
3WL9111-0AA64-0AA0
3WL9111-0AA65-0AA0

III

5000
6300

3WL9111-0AA66-0AA0
3WL9111-0AA67-0AA0

GFM AT 45B (only for ETU45B) alarm and tripping


GFM AT 55B76B (only for ETU76B) alarm and tripping

3WL9111-0AT53-0AA0
3WL9111-0AT56-0AA0

Displays
For ETU45B
4-line

3WL9111-0AT81-0AA0

Rating plugs2)
n

Size

= 3 2 0 0 A

I, II

N S E 0 _ 0 0 9 9 2 b

3WL9111-0AA64-0AA0

G F M

5 1
g T R IP

A L A R M

A L A R M

T R IP
C

O F F

J g (s )
.5

B
D

.4
.3
.2
.1

A T 4 5 B
1 2 Jg
.1
.2
.3

Rated current In (A)

Ground-fault modules3)
Versions

.4
.5

N S E 0 _ 0 1 0 2 7 a

3WL9111-0AT53-0AA0

WLLCD48

N S E 0 _ 0 1 6 0 9

3WL9111-0AT81-0AA0
Internal current transformers for N conductor
Including wiring kit
ETU Release 2

Size

--

I
II
III

3WL9111-0AA11-0AA0
3WL9111-0AA12-0AA0
3WL9111-0AA13-0AA0

3WL9111-0AA2.-0AA0

I
II
III

3WL9111-0AA14-0AA0
3WL9111-0AA15-0AA0
3WL9111-0AA16-0AA0

N S E 0 _ 0 0 9 9 0 a

External current transformers for N conductor


For T5, "Measurement Method" function see Technical Information at www.siemens.com/lowvoltage/product-support.
N S E 0 _ 0 0 9 9 1 a

3WL9111-0AA3.-0AA0

Copper connection pieces

Size

--

I
II
III

3WL9111-0AA21-0AA0
3WL9111-0AA22-0AA0
3WL9111-0AA23-0AA0

I
II
III

3WL9111-0AA31-0AA0
3WL9111-0AA32-0AA0
3WL9111-0AA33-0AA0

WLNCT2
WLNCT3

EMC filters
Common-mode interference suppressor filters
(e.g. in IT networks, caused by frequency converters)
Insertion loss (asymm.) in the range 40 kHz to 10 MHz >40 dB.
Versions
Not for ETU Release 2
Only for ETU Release 2
1)

For replacement in existing circuit breakers please specify the circuit


breaker ID No. when ordering.

2)

With the rating plug selected, the maximum rated current In max of the
circuit breaker must not be exceeded. The following applies In In max.

* You can order this quantity or a multiple thereof.

3WL9111-0AK32-0AA0
3WL9111-0AK34-0AA0
3)

For direct measurement of the ground-fault current, e.g. in the neutral point
of the transformer, a 1,200 A/1 A current transformer, class 1, is required.
The internal load of the 3WL circuit breaker is 0.11 m. If the ground-fault
current is to be determined using the vectorial sum of the phases, a transformer must be installed in the neutral conductor.

Siemens 3WL IEC Breakers 2014

51

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
Quickship
per PU catalog no. for items (in limitQuickship items ed quantity).
Contact factory
for availability

More accessories for Electronic Trip Units


NSE0_00983b

Sealable and lockable covers


Versions

ETU25B

For ETU15B to ETU45B


For ETU76

3WL9111-0AT45-0AA0
3WL9111-0AT46-0AA0

Automatic reset of the reclosing lockout


Spare part for option K01, see "-Z" + order code, page 39.

3WL9111-0AK21-0AA0

WLTUSC55
WLTUSC76

1)

Remote reset coils


For mechanical tripped indicator
Spare part for option K10 to K13,
see "-Z" + order code, page 39.
3WL9111-0AT45-0AA0
F 7

Note
Automatic reset of the reclosing lockout
3WL9111-0AK21-0AA0 also needed.
Versions

N S E 0 _ 0 0 9 9 9 a

3WL9111-0AK0.-0AA0

24 V DC
48 V DC
120 V AC/125 V DC
208-250 V AC/208-250 V DC

3WL9111-0AK03-0AA0
3WL9111-0AK04-0AA0
3WL9111-0AK05-0AA0
3WL9111-0AK06-0AA0

Retrofittable internal CubicleBUS wiring


for connection to terminal X8
For ETU45B and ETU76B
Without male connector2)

3WL9111-0AK30-0AA0

Retrofittable internal wiring for connection of the


external N- and G-transformers to terminal X8
Not for ETU Release 2
Without male connector

3WL9111-0AK31-0AA0

Retrofittable internal wiring for connection of the


external N- and G-transformers to terminal X8
For ETU Release 2
Without male connector

3WL9111-0AK33-0AA0

WLRSET24
WLRSET48
WLRSET120
WLRSET240

Locking devices
Interlocking set for mechanical ON/OFF
consisting of 2 transparent covers each for sealing
or for attaching padlocks4),
Cover with 6.35 mm hole (for tool actuation)
Lock mount for lock for key operation
NSE00980

Versions

3WL9111-0BA22-0AA0

Without lock
Made by CES
Made by IKON

3WL9111-0BA21-0AA0
3WL9111-0BA22-0AA0
3WL9111-0BA24-0AA0

WLLKKT

3WL9111-0BA31-0AA0
3WL9111-0BA33-0AA0
3WL9111-0BA34-0AA0
3WL9111-0BA35-0AA0
3WL9111-0BA36-0AA0
3WL9111-0BA38-0AA0
3WL9111-0BA41-0AA0

WLLKOFFKRK

Locking devices against unauthorized closing,


in the operator panels
The disconnector unit fulfills the requirements for main
circuit breakers acc. to EN 60204-1
Spare part for option S01 to S09, see "-Z" + order code,
page 41.
Versions
NSE00981

3WL9111-0BA31-0AA0

NSE0_00982

3WL9111-0BA53-0AA0

Assembly kit FORTRESS or CASTELL3)


Made by Ronis
Made by KIRK-Key3)
Made by Profalux
Made by CES
Made by IKON
Assembly kit for padlocks4)
Locking devices against unauthorized closing,
for withdrawable circuit breakers
The disconnector unit fulfills the requirements for main
circuit breakers acc. to EN 60204-1
Consisting of lock in the cabinet door, active in
connected position; function is retained when circuit
breaker is replaced
Spare part for option R60, R61, R68,
see "-Z" + order code, page 41.

WLLKNP

Versions

Made by CES
Made by IKON
Made by KIRK-Key3)
Made by Ronis
Made by Profalux

1)

Can only be used in conjunction with "automatic reset of reclosing lockout",


e. g. "Z" + "K01", 3WL9 111-0AK21-0AA0.
2) Required if communication is retrofitted.

52

Siemens 3WL IEC Breakers 2014

3WL9111-0BA51-0AA0
3WL9111-0BA53-0AA0
3WL9111-0BA57-0AA0
3WL9111-0BA58-0AA0
3WL9111-0BA50-0AA0
3)
4)

WLDLPR

Locks, cylinders and keys must be ordered from the manufacturer.


Padlock not included in the scope of supply.

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US cat- Quickship


per PU alog no. for Quick- items (in limitship items
ed quantity).
Contact factory
for availability

Locking devices for operating mechanism handle


with padlock1)
Spare part for option S33, see "-Z" + order code,
page 41.

3WL9111-0BA71-0AA0

WLHANDLC

3WL9111-0BA73-0AA0
3WL9111-0BA75-0AA0
3WL9111-0BA76-0AA0
3WL9111-0BA77-0AA0
3WL9111-0BA80-0AA0

WLLKCLKRK

NSE00984

3WL9111-0BA71-0AA0
Locking devices to prevent movement of the withdrawable circuit breakers
Lock for mounting on the circuit breaker
Spare part for option S71, S75, S76, see "-Z" + order
code, page 41.
NSE0_00986

3WL9111-0BA76-0AA0

Versions

Made by CES
Made by IKON
Made by Profalux
Made by Ronis
Made by KIRK-Key2)

Interlocking systems
Made by CES
2 of the same keys for 3 circuit breakers
Locking device in OFF position
Lock in the operator panel
A maximum of 2 circuit breakers can be switched on

3WL9111-0BA43-0AA0

Locking mechanisms

NSE0_00987

3WL9111-0BA83-0AA0

Locking devices to prevent movement of the withdrawable circuit breakers in disconnected position
Consisting of Bowden wire and lock in the cabinet door
on the circuit breaker
Spare part for option R81, R85, R86, see "-Z" + order
code, page 41. Order code, page 41.
Versions

NSE0_00988

3WL9111-0BB12-0AA0

Made by CES
Made by IKON
Made by Profalux
Made by Ronis

Note
Not possible in combination with "Locking device to prevent opening of the cabinet door" (order code "R30") or
"Locking device to prevent movement with the cabinet
door open"
(order code "R50").
Locking devices to prevent opening of the cabinet
door in ON position
Fixed-mounted
Can be defeated
Spare part for option S30, see "-Z" + order code, page
41.
Locking devices to prevent opening of the cabinet
door
Guide frames
Can be defeated
Spare part for option R30, see "-Z" + order code, page 41.
Note
Not possible in combination with "Locking device to prevent movement of the withdrawable circuit breakers in
disconnected position" (order codes "R81", "R85" or
"R86").
Locking devices to prevent movement with the cabinet door open
Guide frames
Spare part for option R50, see "-Z" + order code, page 41.

3WL9111-0BA81-0AA0
3WL9111-0BA83-0AA0
3WL9111-0BA85-0AA0
3WL9111-0BA86-0AA0

3WL9111-0BB12-0AA0

WLLKOFFDRUL3

3WL9111-0BB13-0AA0

WLDRLC1

3WL9111-0BB15-0AA0

WLDRLC5UL

Note
Not possible in combination with "Locking device to prevent movement of the withdrawable circuit breakers in
disconnected position" (order codes "R81", "R85" or
"R86").
1)
2)

Padlock not included in the scope of supply.


Locks, cylinders and keys must be ordered from the manufacturer.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

53

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US Quickship


per PU catalog no. for items (in limitQuickship
ed quantity).
items

Interlocks

Contact factory
Mutual mechanical interlocking
with 2000 mm Bowden wire
(one required for each circuit breaker)
Type

When
Spare part for
ordered
separately

Fixed-mounted circuit
breakers

--

Option S55, see "-Z" +


order code, page 40.

3WL9111-0BB21-0AA0

WLNTLKF23

Module for with-drawable circuit breakers with guide frame

Option R55, see "-Z" +


order code, page 40.

3WL9111-0BB24-0AA0

WLNTLK

Module for guide frame

Option R56, see "-Z" +


order code, page 40.

3WL9111-0BB22-0AA0

WLNTLKC

Module for with


drawable circuit breaker

Option R57, see "-Z" +


order code, page 40.

3WL9111-0BB23-0AA0

WLNTLKB

--

3WL9111-0BB30-0AA0

WLNTLKB

3WL9112-8AH47-0AA0

WLMOC2

2000 mm
3,000 mm
4,500 mm

3WL9111-0BB45-0AA0
3WL9111-0BB46-0AA0
3WL9111-0BB47-0AA0

WLNTLWIRE2
WLNTLWIRE3
WLNTLWIRE4

Manual tester Release 2 for Electronic Trip Units ETU15B


to ETU76B
For testing the Electronic Trip Unit functions of all 3WL ETUs
(release 1 and release 2)

3WL9111-0AT32-0AA0

Function testers

3WL9111-0AT44-0AA0

NSE0_00989

3WL9111-0BB21-0AA0

for availability

Adapter for size III


Withdrawable circuit
breaker

Couplings on the circuit breaker (with ring)


for mutual interlocking
Can be used in all circuit breakers

NSE0_01886

3WL9112-8HA47-0AA0
Bowden wires
Versions

Test devices

For testing the tripping characteristics for Electronic Trip


Units ETU15B to ETU76B

Capacitor storage devices


Capacitor storage devices
For shunt releases
Storage time 5 min

3WL9111-0BA14-0AA0

Rated control supply voltage/rated operational voltage


50/60 Hz V AC

V DC

220 ... 240

220 ... 250

Note
Rated control supply voltage must match the rated control
supply voltage of the shunt release
Suitable also for 3VL and 3WN circuit breakers

54

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
per PU catalog no. for
Quickship items

Quickship
items (in limited quantity).
Contact factory
for availability

Indicators, control elements


Ready-to-close signaling switches
1 NO contact
Spare part for option C22, see "-Z" + order code, page 39.

3WL9111-0AH01-0AA0

WLRTCS

Signaling switches1) 2)
1st or 2nd auxiliary release
Spare part for option C26 and C27, see "-Z" + order code,
page 39.

3WL9111-0AH02-0AA0

WLUVRC

1st tripped signaling switch1) 2)


1 CO contact
Spare part for option K07, see "-Z" + order code, page 39.

3WL9111-0AH14-0AA0

2nd tripped signaling switch1) 2)3)


1 NO contact
Spare part for option K06, see "-Z" + order code, page 39.

3WL9111-0AH17-0AA0

Operating cycles counters


Mechanical4)
Spare part for option C01, see "-Z" + order code, page 39.

3WL9111-0AH07-0AA0

Stored energy status signaling switches1) 2)


1 NO contact
Spare part for option C20, see "-Z" + order code, page 39.

3WL9111-0AH08-0AA0

N S E 0 _ 0 0 9 9 3 a

3WL9111-0AH01-0AA0

N S E 0 _ 0 0 9 9 4 b

WLSTC

3WL9111-0AH02-0AA0
WLBA

WLNUMCNT

N S E 0 _ 0 0 9 9 5 a

3WL9111-0AH07-0AA0

Position signaling switches for guide frames


Spare part for option R15 and R16, see "-Z" + order code,
page 40.
N S E 0 _ 0 0 9 9 6 a

3WL9111-0AH12-0AA0

Versions
1st block (3 CO contacts)
2nd block (6 CO contacts)

3WL9111-0AH11-0AA0
3WL9111-0AH12-0AA0

WLGSGSW111
WLGSGSW321

3WL9111-0AJ02-0AA0
3WL9111-0AJ03-0AA0
3WL9111-0AJ05-0AA0

WLLECS

Motor shutdown switches 6)


Mounting on operator panel
Spare part for option S25, see "-Z" + order code, page 39.

3WL9111-0AJ06-0AA0

WLMCOSW

EMERGENCY-STOP pushbuttons
Mushroom pushbutton instead of the mechanical
OFF pushbutton
Spare part for option S24, see "-Z" + order code, page 39.

3WL9111-0BA72-0AA0

WLEPEN

Electrical ON buttons1)5)
Button + wiring2)
For operator panel
Spare part for option C11 and C12, see "-Z" + order code,
page 39
N S E 0

0 0 9 9 7 a

3WL9111-0AJ0.-0AA0

Versions
With sealing cap C11
With CES C12 assembly kit
With IKON assembly kit
Note
Possible only for circuit breakers with closing coil.

NSE00985

3WL9111-0BA72-0AA0
1)

Not possible with communications interface option, order code "F02" or "F12".

4)

Only in conjunction with motorized operating mechanism.

2)

X7 auxiliary supply connector required for circuit breakers or guide frames.


If this is not already available, please order additionally
(see pages 44 and 56).

5)

Not possible with motor shutdown switch.

6)

Not possible with electrical ON button.

3)

Can only be used in combination with 1st tripped signaling switch.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

55

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
per PU catalog no. for
Quickship items

Quickship
items (in limited quantity).
Contact factory
for availability

Auxiliary conductor connections


3WL9111-0AB01-0AA0

WLCNMD

Extension for the 1000 V male


connector versions
Male connector must be ordered separately.

3WL9111-0AB02-0AA0

WLCNMDA

Male connectors and extension for 1000 V

3WL9111-0AB10-0AA0

NSE0_00978

Male connectors for circuit breakers

3WL9111-0AB01-0AA0

Auxiliary supply connectors for circuit breakers


or guide frames

N S E 0 _ 0 1 2 6 8

Versions
Screw connection (SIGUT)
Screwless connection method (tension spring)

3WL9111-0AB03-0AA0
3WL9111-0AB04-0AA0

WLGAUXPLUGP
WLGAUXPLUGT

Coding kits
For fixed-mounted versions (X5 to X8)

3WL9111-0AB07-0AA0

WLCODEKITUL

Sliding contact modules for guide frames

3WL9111-0AB08-0AA0

WLGDSCN

One-part sliding contact modules


for guide frames
Screw connection (SIGUT)

3WL9111-0AB18-0AA0

WLGAUXPLUGL

Blanking blocks for circuit breakers

3WL9111-0AB12-0AA0

WLGDAUXPLUG

N S E 0 _ 0 1 2 6 9

3WL9111-0AB03-0AA0

NSE00974

3WL9111-0AB04-0AA0

3WL9111-0AB07-0AA0

7 a
9 7
0 0
0 _
E
N S

NSE0_01586

3WL9111-0AB08-0AA0

3WL9111-0AB18-0AA0

For a complete auxiliary current connection you must order:


Fixed-mounted version:

Withdrawable versions:

56

or

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

Price Equivalent US
per PU catalog no. for
Quickship items

DT Article No.

Quickship
items (in limited quantity).
Contact factory
for availability

Auxiliary releases
Closing coils/shunt releases
Versions

Voltage

100 % OP

24 V DC
30 V DC
48 V DC
60 V DC
110 ... 125 V DC/110 ... 127 V AC
220 ... 250 V DC/208 ... 240 V AC

3WL9111-0AD01-0AA0
3WL9111-0AD02-0AA0
3WL9111-0AD03-0AA0
3WL9111-0AD04-0AA0
3WL9111-0AD05-0AA0
3WL9111-0AD06-0AA0

WLSTCD120
WLSTCD240

24 V DC
48 V DC
110 ... 125 V DC/110 ... 127 V AC
220 ... 250 V DC/208 ... 240 V AC

3WL9111-0AD11-0AA0
3WL9111-0AD12-0AA0
3WL9111-0AD13-0AA0
3WL9111-0AD14-0AA0

WLRCS24
WLRCS48
WLRCS120
WLRCS240

3WL9111-0AE01-0AA0
3WL9111-0AE02-0AA0
3WL9111-0AE03-0AA0
3WL9111-0AE07-0AA0

WLUV24

110 ... 125 V DC/110 ... 127 V AC


220 ... 250 V DC/208 ... 240 V AC
380 ... 415 V AC

3WL9111-0AE04-0AA0
3WL9111-0AE05-0AA0
3WL9111-0AE06-0AA0

WLUV120
WLUV240

48 V DC
110 ... 125 V DC/110 ... 127 V AC
220 ... 250 V DC/208 ... 240 V AC
380 ... 415 V AC

3WL9111-0AE11-0AA0
3WL9111-0AE12-0AA0
3WL9111-0AE13-0AA0
3WL9111-0AE14-0AA0

WLUVD48
WLUVD120
WLUVD240

3WL9111-0AF01-0AA0
3WL9111-0AF02-0AA0
3WL9111-0AF03-0AA0
3WL9111-0AF04-0AA0

WLELCMTR24
WLELCMTR48
WLELCMTR120
WLELCMTR240

3WL9111-0AG01-0AA0
3WL9111-0AG02-0AA0
3WL9111-0AG03-0AA0

WLAS4

3WL9111-0AD06-0AA0
5%

OP1)

WLSTCD24
WLSTCD48

Undervoltage releases
Versions
Instantaneous

NSE01001

3WL9111-0AE0.-0AA0
Delayed

Voltage
24 V DC
30 V DC
48 V DC
60 V DC

WLUV48

NSE01002

3WL9111-0AE1.-0AA0

Operating mechanisms
Motorized operating mechanisms2)
Versions

24 ... 30 V DC
48 ... 60 V DC
110 ... 125 V DC/110 ... 127 V AC
220 ... 250 V DC/208 ... 240 V AC

N S E 0 _ 0 1 0 0 3 a

3WL9111-0AF0.-0AA0

Auxiliary contacts
Auxiliary switch blocks
Versions
2 NO contacts + 2 NC contacts
2 NO contacts
1 NO contact + 1 NC contact

NSE0_01004

3WL9111-0AG03-0AA0
1)

Overexcited, i.e. operating time 50 ms (standard > 80 ms).

2)

X5 auxiliary supply connector required for circuit breakers or guide frames.


If this is not already available, please order additionally
(see pages 44 and 47).

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

57

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
per PU catalog no. for
Quickship items

Quickship
items (in limited quantity).
Contact factory
for availability

Door sealing frames, hoods, shutters


Door sealing frames
Spare part for option T40, see "-Z" + order code,
page 39.

3WL9111-0AP01-0AA0

WLDSF

Protective covers
IP55

3WL9111-0AP02-0AA0

Notes
Cannot be used in conjunction with door sealing
frames
Hood removable and can be opened on both
sides
NSE0_01028a

3WL9111-0AP02-0AA0
Shutters
Spare part for option R21, see "-Z" + order code,
page 40.
Number of poles

Size

3-pole

I
II
III

3WL9111-0AP04-0AA0
3WL9111-0AP06-0AA0
3WL9111-0AP07-0AA0

4-pole

I
II
III

3WL9111-0AP08-0AA0
3WL9111-0AP11-0AA0
3WL9111-0AP12-0AA0

NSE0_01006

3WL9111-0AP0.-0AA0

Arc chutes

NSE0_01007

Arc chutes
Versions

Size

690 V

I
II
III

3WL9111-0AS01-0AA0
3WL9111-0AS02-0AA0
3WL9111-0AS03-0AA0

1000 V / 1150 V

II
III

3WL9111-0AS05-0AA0
3WL9111-0AS06-0AA0

3WL9111-0AS0.-0AA0
Arc chute covers1)
Parts kit for guide frame
Spare part for option R10, see "-Z" + order code,
page 40.
NSE0_01008

Number of poles

Size

3-pole

I
II
III

3WL9111-0AS32-0AA0
3WL9111-0AS36-0AA0
3WL9111-0AS38-0AA0

4-pole

I
II
III

3WL9111-0AS42-0AA0
3WL9111-0AS44-0AA0
3WL9111-0AS46-0AA0

3WL9111-0AS3.-0AA0

Coding for withdrawable version


Coding for withdrawable version
By customer, for 36 coding variants
Versions
Sizes I and II
Size III

3WL9111-0AR12-0AA0
3WL9111-0AR13-0AA0

NSE0_01009

3WL9111-0AR12-0AA0
3WL9111-0AR13-0AA0
1)

Not available for


- 1000 V version (order code "A05"),
- 1150 V version (order code "A15"),
- DC version,
- 4000 A size II,
- circuit breaker with very high breaking capacity C.

58

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

Price Equivalent US
per PU catalog no. for
Quickship
items

DT Article No.

Quickship
items (in limited quantity).
Contact factory
for availability

Grounding connection
Grounding connection between the guide frame
and the withdrawable circuit breaker
For 30 kA ground short-circuit current1)
Contacting modules for guide frame
NSE0 01018a

3WL9111-0BA02-0AA0

Versions
Size I and II2)
Size III

3WL9111-0BA01-0AA0
3WL9111-0BA02-0AA0

WLEF2

Contacting modules for withdrawable circuit


breakers
NSE01019

Number of poles

Size

3-pole

I
II2)
III

3WL9111-0BA05-0AA0
3WL9111-0BA06-0AA0
3WL9111-0BA07-0AA0

4-pole

I
II2)
III

3WL9111-0BA08-0AA0
3WL9111-0BA04-0AA0
3WL9111-0BA10-0AA0

3WL9111-0BA07-0AA0

Support brackets
3WL9111-0BB50-0AA0

NSE-01022

Support brackets
For mounting fixed-mounted circuit breakers on
vertical plane
Only for sizes I and II (1 set = 2 units)

3WL9111-0BB50-0AA0

CubicleBUS modules3)6)
Digital output modules with rotary coding switch,
relay outputs

3WL9111-0AT26-0AA0

WLDGNCUB

Digital output modules, configurable,


relay outputs

3WL9111-0AT20-0AA0

WLRLYCCUB

Digital input modules

3WL9111-0AT27-0AA0

WLRLYCUB

Analog output modules

3WL9111-0AT23-0AA0

WLANLGCUB

Zone Selective Interlocking modules

3WL9111-0AT21-0AA0

WLZSIMD

N S E 0 _ 0 1 0 2 3 a

3WL9111-0AT23-0AA0

Parameterization systems6)

N S E 0 _ 0 1 0 2 4 a

BDA Plus4)5)
Parameterization, operation, monitoring and
diagnostics of 3WL air circuit breakers using
the local interface
Breaker Data Adapter, connection cable to the
3WL air circuit breaker and to the programming
device (e.g. notebook)
Can be run with Internet Explorer
with JAVA2 VM 1.4.0-01 and higher
With Ethernet interface for connection to
Ethernet/Intranet/Internet

3WL9111-0AT33-0AA0

Connection cables for BDA Plus


Connection cable for connection of BDA Plus to
terminal X8 of the 3WL air circuit breaker
Required if neither COM15 nor COM16 nor other
external CubicleBUS modules are available
Length 2 m

3WL9111-0BC21-0AA0

3WL9111-0AT28-0AA0

1)

For 60 kA ground short-circuit current, order 2.

2)

Cannot be used for size II, 4000 A.

3)

Each CubicleBUS module is supplied with a 0.2 m factory-fitted cable to


connect the modules with each other. A longer factory-fitted cable is
required for connection to the circuit breaker.

4)

A 24 V DC power supply unit is required.

5)

Operation under Windows Vista and Windows 7 possible with restrictions.

6)

All communication components, CubicleBUS modules and measurement


functions are available for the ETU45B and ETU76B.

* You can order this quantity or a multiple thereof.

WLBDAPMNT

Siemens 3WL IEC Breakers 2014

59

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US
per PU catalog no. for
Quickship items

Quickship
items (in limited quantity).
Contact
factory for
availability

Accessories for communications3)


Preassembled cables for CubicleBUS modules
Versions
0.2 m long, for connection to 3WL with COM15/COM16
1 m long, for connection to 3WL with COM15/COM16
2 m long, for connection to 3WL with COM15/COM16
2 m long, for connection to 3WL without COM15/COM16
Voltage transformers
3-pole, for 3WL circuit breakers
with measurement function Plus1)
380 ... 690 V/100 V, class 0.5

3WL9111-0BC04-0AA0
3WL9111-0BC02-0AA0
3WL9111-0BC03-0AA0
3WL9111-0BC05-0AA0

WLCBUSCABLE02
WLCBUSCABLE1
WLCBUSCABLE2

3WL9111-0BB68-0AA0

Retrofitting and spare parts3)

PROFIBUS retrofit kits


Retrofit kit for PROFIBUS communications including
COM15, BSS and set of cables for all 3WL air circuit
breakers with ETU45B and ETU76B

3WL9111-0AT12-0AA0

WLCM15RET

COM15 PROFIBUS module


For ETU45B and ETU76B

3WL9111-0AT15-0AA0

WLCM16MD

COM16 MODBUS modules


For ETU45B and ETU76B

3WL9111-0AT17-0AA0

MODBUS IEC retrofit kits


Retrofit kit for MODBUS communications including
COM16, BSS and set of cables for all 3WL air circuit
breakers with ETU45B and ETU76B

3WL9111-0AT18-0AA0

Breaker status sensor (BSS)


For ETU45B and ETU76B

3WL9111-0AT16-0AA0

Measurement function Plus2)


For ETUs Release 2
Voltage transformer required

3WL9111-0AT04-0AA0

Device

PROFIBUS DP

CubicleBus

NSE-01025

3WL9111-0AT15-0AA0

1)

Is required for operation of the measurement function Plus.

2)

A measuring accuracy of 3 % is reached if retrofitted.

3)

All communication components, CubicleBUS modules and measurement


functions are available for the ETU45B and ETU76B.

60

Siemens 3WL IEC Breakers 2014

WLBSS

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US Quickship


per PU catalog no. for items (in limited
Quickship items quantity).
Contact factory
for availability

Main conductor connections, fixed-mounted versions


(essential accessory)
Specified for each connection
Front-accessible main connections,

3WL9111-0AL06-0AA0 single hole at top1)


Size

Rated current In

Up to 1000 A
1250 A to 1600 A

3WL9111-0AL01-0AA0
3WL9111-0AL02-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AL03-0AA0
3WL9111-0AL04-0AA0
3WL9111-0AL05-0AA0

III

Up to 4000 A

3WL9111-0AL06-0AA0

NSE-01010

3WL9111-0AL56-0AA0

Front-accessible main connections,


single hole at bottom1)
Size

Rated current In

Up to 1000 A
1250 A to 1600 A

3WL9111-0AL51-0AA0
3WL9111-0AL52-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AL53-0AA0
3WL9111-0AL54-0AA0
3WL9111-0AL55-0AA0

III

Up to 4000 A

3WL9111-0AL56-0AA0

3WL9111-0AL14-0AA0 Front-accessible main connections according


to DIN 43673, double hole at top

NSE-01011

3WL9111-0AL64-0AA0

Size

Rated current In

Up to 1000 A 1)
1250 A to 2000 A

3WL9111-0AL07-0AA0
3WL9111-0AL08-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AL11-0AA0
3WL9111-0AL12-0AA0
3WL9111-0AL13-0AA0

III

Up to 4000 A

3WL9111-0AL14-0AA0

Front-accessible main connections according


to DIN 43673, double hole at bottom
Size

Rated current In

Up to 1000 A 1)
1250 A to 2000 A

3WL9111-0AL57-0AA0
3WL9111-0AL58-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AL61-0AA0
3WL9111-0AL62-0AA0
3WL9111-0AL63-0AA0

III

Up to 4000 A

3WL9111-0AL64-0AA0

Rear vertical main connections


Size

Rated current In

I2)

Up to 2000 A

3WL9111-0AM01-0AA0

II3)

Up to 3200 A

3WL9111-0AM02-0AA0

III

Up to 6300 A

3WL9111-0AM03-0AA0

3WL9111-0AM03-0AA0
1)

Not for 3WL size I with high breaking capacity H

2)

In the case of vertical connection size I with breaking capacity N and S,


up to 1000 A one 3WL9111-0AM01-0AA0 vertical connection is required,
up to 2000 A or with breaking capacity H
two 3WL9111-0AM01-0AA0 vertical connections are required.

3)

In the case of vertical connection size II, up to 2500 A


one 3WL9111-0AM02-0AA0 vertical connection is required,
up to 3200 A two 3WL9111-0AM02-0AA0
vertical connections are required.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

61

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

DT Article No.

Price Equivalent US Quickship


per PU catalog no. for items (in limitQuickship items ed quantity).
Contact factory
for availability

Main conductor connections, withdrawable versions


(essential accessory)
Specified for each connection
Front-accessible main connections,
single hole at top or at bottom1) 2)
Size

Rated current In

Up to 1000 A
1250 A to 1600 A

3WL9111-0AN01-0AA0
3WL9111-0AN02-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AN03-0AA0
3WL9111-0AN04-0AA0
3WL9111-0AN05-0AA0

III

Up to 4000 A

3WL9111-0AN06-0AA0

NSE-01013

3WL9111-0AN06-0AA0

Front-accessible main connections according


to DIN 43673, double hole at top or at bottom1)

NSE-01014

Size

Rated current In

Up to 1000 A 2)
1250 A to 2000 A

3WL9111-0AN07-0AA0
3WL9111-0AN08-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AN11-0AA0
3WL9111-0AN12-0AA0
3WL9111-0AN13-0AA0

III

Up to 4000 A

3WL9111-0AN14-0AA0

3WL9111-0AN14-0AA0

Supports for front and DIN connecting bars


Number of poles

Size

3-pole for 3 bars

I
II
III

3WL9111-0AN41-0AA0
3WL9111-0AN42-0AA0
3WL9111-0AN43-0AA0

4-pole for 4 bars

I
II
III

3WL9111-0AN44-0AA0
3WL9111-0AN45-0AA0
3WL9111-0AN46-0AA0

NSE-01017

3WL9111-0AN41-0AA0
Rear vertical main connections
NSE-01015

Size

Rated current In

Up to 1000 A 2)
1250 A to 2000 A

3WL9111-0AN15-0AA0
3WL9111-0AN16-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AN17-0AA0
3WL9111-0AN18-0AA0
3WL9111-0AN21-0AA0

III

Up to 5000 A

3WL9111-0AN22-0AA0

Up to 6300 A, 3 busbar connection


pieces for 3-pole circuit breakers

3WL9111-0AN23-0AA0

Up to 6300 A, at top,
4 busbar connection pieces
for 4-pole circuit breakers

3WL9111-0AN20-0AA0

Up to 6300 A, at bottom,
4 busbar connection
pieces for 4-pole circuit breakers

3WL9111-0AN10-0AA0

3WL9111-0AN23-0AA0

Rear horizontal main connections


Size

Rated current In

Up to 1000 A 2)
1250 A to 2000 A

3WL9111-0AN32-0AA0
3WL9111-0AN33-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AN34-0AA0
3WL9111-0AN35-0AA0
3WL9111-0AN36-0AA0

III

Up to 5000 A

3WL9111-0AN37-0AA0

NSE-01016

Connecting flange

3WL9111-0AN24-0AA0

Size

Rated current In

Up to 1000 A 2)
1250 A to 2000 A

3WL9111-0AN24-0AA0
3WL9111-0AN25-0AA0

II

Up to 2000 A
Up to 2500 A
Up to 3200 A

3WL9111-0AN26-0AA0
3WL9111-0AN27-0AA0
3WL9111-0AN28-0AA0

III

Up to 4000 A

3WL9111-0AN31-0AA0

1)

When using front-accessible mains connections (withdrawable circuit


breakers) supports are required.

2)

Not for 3WL size I with high breaking capacity H

62

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Designation

Price Equivalent US Quickship


per PU catalog no. for items (in limitQuickship items ed quantity).

DT Article No.

Contact factory
for availability

Conversion sets
Conversion set for converting fixed-mounted circuit
breakers into withdrawable circuit breakers
Guide frames and sliding contact modules must be
ordered separately.
Number of poles

Size

3-pole

3WL9111-0BC11-0AA0

II

3WL9111-0BC12-0AA0

III

3WL9111-0BC13-0AA0

3WL9111-0BC14-0AA0

II

3WL9111-0BC15-0AA0

III

3WL9111-0BC16-0AA0

4-pole

Main contact elements


Main contact elements

NSE-01021

Size

In max

Up to 1600 A

3WL9111-0AM90
L1Y1)

II

Up to 2500 A

3WL9111-0AM91

II

Up to 4000 A

III

Up to 6300 A

L1Y1)
3WL9111-0AM92
L1Y1)
3WL9111-0AM93
L1Y1)
Notes
The circuit breaker ID No. must be specified when
ordering
Specified for each connection (depending on the number of poles on the circuit breaker, order 3 or 4 units)
Article No. is automatically adapted to the circuit
breaker ID number

1)

Please specify the circuit breaker ID No. in plain text when ordering.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

63

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts
Version

Size

DT Article No.

Price Equivalent US Quickship


per PU catalog no. for items (in limitQuickship items ed quantity).
Contact factory
for availability

Withdrawable short-circuiting, grounding and bridging units


Withdrawable short-circuiting,
grounding and bridging units
Top and bottom system components are short-circuited and
grounded.
Number of poles

Rated current In

Size

3-pole

Up to 1600 A
Up to 3200 A
Up to 6300 A

I
II
III

3WL9111-0BD01-0AA0
3WL9111-0BD03-0AA0
3WL9111-0BD05-0AA0

4-pole

Up to 1600 A
Up to 3200 A
Up to 6300 A

I
II
III

3WL9111-0BD02-0AA0
3WL9111-0BD04-0AA0
3WL9111-0BD06-0AA0

NSE0_01112

NSE0_01119

NSE0_01113

L1 L2 L3

Top system component is short-circuited and grounded,


infeed from bottom

NSE0_01122a

Top and bottom system components are short-circuited and grounded


(as-supplied state)

L1 L2 L3
NSE0_01114

NSE0_01123a

NSE0_01115

Withdrawable bridging unit, infeed and outgoing sides are permanently


connected to each other

64

Siemens 3WL IEC Breakers 2014

L1 L2 L3

L1 L2 L3

NSE0_01121

NSE0_01116

L1 L2 L3

NSE0_01120

L1 L2 L3

NSE0_01117

NSE0_01118

Conversion for the following applications is possible

Bottom system component is short-circuited and grounded,


infeed from top

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Accessories and spare parts

Options
Structure of the Article No.
3WL1

> >> > >>>> > >>>

Example

5th position:

Size

Size II

6th and 7th


positions:

Max. rated circuit


breaker current
In max

In max = 2000 A

8th position:

Breaking capacity
class

High breaking capacity


"H": 100 kA

9th position:

Electronic Trip Units ETU76B with graphics display


...

10th position:

Electronic Trip Unit ... with ground-fault protection


supplement

11thposition:

Number of poles

Three-pole

12th position:

Installation type

Fixed-mounted, main
connections on rear, vertical

13th position:

Operating
mechanisms

Manual operating mechanism


with mechanical closing

14th position:

1st auxiliary release Shunt release


50/60 Hz 110 V AC

15th position:

2nd auxiliary release Without 2nd auxiliary release

16th position:

Auxiliary switches

An important prerequisite for


computer-based order processing is that article numbers must
be structured according to standardized criteria.
They are used as an unambiguous means of communication for
various purposes:

Offer processing
Selection and configuration
Order processing
Orders
Order confirmation
Processing of products for storage
Order processing in supply
locations
Supply and dispatch
Reporting and planning
Service and warranty

The standardized structure ensures that only one Article No.


has to be administered for one
device.

This saves time and effort during


planning, configuring, ordering
and in stock keeping, and consequently above all it saves costs.

2 NO contacts + 2 NC contacts

The example opposite explains


the various positions within an
Article No.

Accessories: with first order (components are already mounted)


3WL1

Example

Additional accessory components can be ordered readymounted.

These supplements are identified by "Z".

>
Communications interface
"Standard" + Breaker Status Sensor (BSS)
+ communication module COM15 for
connection to PROFIBUS DP

"Z" with order code

Even with additional components, one Article No. is sufficient.

Accessories: for retrofitting (components for subsequent fitting)


Example
3WL9

Additional accessories which are


not intended to be ready-mounted in the factory, such as spare
parts for storage, can also be ordered separately from the circuit
breaker.

Interlocking set for mechanical ON/OFF


without lock

Accessories for retrofitting are


identified by the Article No. stem
3WL9.

Documentation
Operating manual
Complete set

German/English

Article No.

3ZX18 12-0WL00-0AN1

PROFIBUS manual
Communication

English

Article No.

A5E0151353

MODBUS manual
Communication

English

Article No.

3ZX10 12-0WL10-1AC1

Delivery time class C

Siemens 3WL IEC Breakers 2014

65

Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
3- and 4-pole, fixed-mounted versions

Selection and ordering data


For general data see page 8.
Size

Max. rated circuit breaker DT


current In max.

3-pole non-automatic
air circuit breakers
Article No.

DC

Price
per PU

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight per
PU approx.
kg

Horizontal main circuit connection


II

1000
2000
40001)

3WL1210-8@@32-@@@@
3WL1220-8@@32-@@@@
3WL1240-8@@32-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

56.000
56.000
64.000

3WL1210-8@@31-@@@@
3WL1220-8@@31-@@@@
3WL1240-8@@31-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

56.000
56.000
85.000

3WL1210-8@@33-@@@@
3WL1220-8@@33-@@@@

1
1

1 unit
1 unit

103
103

56.000
56.000

3WL1210-8@@34-@@@@
3WL1220-8@@34-@@@@

1
1

1 unit
1 unit

103
103

56.000
56.000

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight per
PU approx.

Vertical main circuit connection


II

1000
2000
40001)

Front main circuit connection, single hole


II

1000
2000

Front main circuit connection, double hole


II

1000
2000

Options

Add. price

Non-autom. air circuit breakers2) Without Electro. Trip Units


Operating mechanisms

AA

Manual operating mechanism with mechan. closing

None
1AA2

None

For further Article No. supplements see page 1/37


Size

Max. rated circuit breaker DT


current In max.

4-pole non-automatic
air circuit breakers
Article No.

DC

Price per PU

kg

Horizontal main circuit connection


II

1000
2000
40001)

3WL1210-8@@42-@@@@
3WL1220-8@@42-@@@@
3WL1240-8@@42-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

67.000
67.000
77.000

3WL1210-8@@41-@@@@
3WL1220-8@@41-@@@@
3WL1240-8@@41-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

75.000
75.000
103.000

3WL1210-8@@43-@@@@
3WL1220-8@@43-@@@@

1
1

1 unit
1 unit

103
103

67.000
67.000

3WL1210-8@@44-@@@@
3WL1220-8@@44-@@@@

1
1

1 unit
1 unit

103
103

67.000
67.000

Vertical main circuit connection


II

1000
2000
40001)

Front main circuit connection, single hole


II

1000
2000

Front main circuit connection, double hole


II

1000
2000

Options

Add. price

Non-autom. air circuit breakers2) Without Electron. Trip Units


Operating mechanisms

AA

Manual operating mechanism with mechan. closing

None
1AA2

None

For further Article No. supplements see page 1/37


Add "-Z" to the complete Article No. and indicate
the appropriate order code(s).

Condition
Rated voltage
1000 V DC

Size
II

3WL12.0-8....-....-Z
@@@

Additional price
3-pole

4-pole

Rated current In
Up to 2000 A

A 0 5

Up to 4000 A

A 0 5

Note
For voltages over 600 V use the version for 1000 V DC rated voltage: Order with "-Z" and order code "A05".
All other accessory parts must be ordered by specifying "-Z" and the corresponding order code,
see "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC", "Options",
page 38 onwards.
An external overload and short-circuit protection device is available from the company "mat" for the
3WL non-automatic air circuit breakers.
Available only directly from the company mat Maschinen- und Anlagentechnik
(for address see page 1/68).
Additional price
1)

Provisions to dissipate heat must be made on the line side.

66

Siemens 3WL IEC Breakers 2014

2)

For permissible rated short-time current Icw and short-circuit breaking


capacity Icc for non-automatic air circuit breakers, see page 1/5.
* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
3- and 4-pole, withdrawable versions

Selection and ordering data


Size

Max. rated circuit breaker DT


current In max.

3-pole non-automatic
air circuit breakers
Article No.

DC

Price
per PU

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.

kg

Without guide frames


(for guide frames, see page 69)
II

1000
2000
40001)

3WL1210-8@@35-@@@@
3WL1220-8@@35-@@@@
3WL1240-8@@35-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

60.000
60.000
68.000

3WL1210-8@@36-@@@@
3WL1220-8@@36-@@@@
3WL1240-8@@36-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

91.000
91.000
113.000

1000
2000
40001)

3WL1210-8@@37-@@@@
3WL1220-8@@37-@@@@
3WL1240-8@@37-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

91.000
91.000
121.000

1000
2000
40001)

3WL1210-8@@38-@@@@
3WL1220-8@@38-@@@@
3WL1240-8@@38-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

91.000
91.000
113.000

With guide frames,


horizontal main circuit connection
II

1000
2000
40001)

With guide frames,


vertical main circuit connection
II

With guide frames,


connecting flanges
II

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip


Units

Operating mechanisms

Manual operating mechanism with mechanical


closing

AA

None
1AA2

None

For further Article No. supplements see page 37


Add "-Z" to the complete Article No. and indicate the
appropriate order code(s).

Condition

Size

Rated voltage 1000 V DC

II4)

3WL12.0-8..3.-....-Z

Additional price

@@@

3-pole

Rated current
In
Up to 2000 A

A 0 5

Up to 4000 A

A 0 5

A 0 8

Tinned version of the cus- II


tomer's connections on the
guide frame3)
Only for circuit breakers in
withdrawable version with
horizontal connection or
flange connection.
The normal delivery time
increases to 15 work days.
Note

For voltages over 600 V use the version for 1000 V DC rated voltage: Order with "-Z" and order
code "A05".
All other accessory parts must be ordered by specifying "-Z" and the corresponding order code,
see "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC",
"Options", page 38 onwards.
An external overload and short-circuit protection device is available from the company "mat" for
the 3WL non-automatic air circuit breakers.
Available only directly from the company mat Maschinen- und Anlagentechnik
(for address see page 68).
Additional price
1)

Provisions to dissipate heat must be made on the line side.

2)

For permissible rated short-time current Icw and short-circuit breaking


capacity Icc for non-automatic air circuit breakers, see page 5.

3)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

4)

If ordering withdrawable circuit breaker and guide frame separately, specify order code "A05" for withdrawable circuit breaker and guide frame.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

67

Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
3- and 4-pole, withdrawable versions

Selection and ordering data


Size

Max. rated circuit breaker DT


current
In max.

4-pole non-automatic
air circuit breakers
Article No.

DC

Price
per PU

PU
(UNIT,
SET, M)

PS*/
P. unit

PG

Weight
per PU
approx.
kg

Without guide frames


(for guide frames, see page 69)
II

1000
2000
40001)

3WL1210-8@@45-@@@@
3WL1220-8@@45-@@@@
3WL1240-8@@45-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

75.000
75.000
82.000

3WL1210-8@@46-@@@@
3WL1220-8@@46-@@@@
3WL1240-8@@46-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

109.000
109.000
136.000

1000
2000
40001)

3WL1210-8@@47-@@@@
3WL1220-8@@47-@@@@
3WL1240-8@@47-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

109.000
109.000
146.000

1000
2000
40001)

3WL1210-8@@48-@@@@
3WL1220-8@@48-@@@@
3WL1240-8@@48-@@@@

1
1
1

1 unit
1 unit
1 unit

103
103
103

109.000
109.000
136.000

With guide frames,


horizontal main circuit connection
II

1000
2000
40001)

With guide frames,


vertical main circuit connection
II

With guide frames,


connecting flanges
II

Additional
price

Options
Non-automatic
air circuit breakers2)

Without Electronic Trip


Units

Operating mechanisms

Manual operating mechanism with mechanical


closing

AA

None
1AA2

None

For further Article No. supplements see page 37


Add "-Z" to the complete Article No. and indicate the
appropriate order code(s).

Condition

Size

Rated voltage 1000 V DC

II4)

Additional price

3WL12.0-8..4.-....-Z
@@@

4-pole

Rated current
In
Up to 2000 A

A 0 5

Up to 4000 A

A 0 5

A 0 8

Tinned version of the cus- II


tomer's connections on the
guide frame3)
Only for circuit breakers in
withdrawable version with
horizontal connection or
flange connection.
The normal delivery time
increases to 15 work days.
Note

For voltages over 600 V use the version for 1000 V DC rated voltage: Order with "-Z" and order
code "A05".
All other accessory parts must be ordered by specifying "-Z" and the corresponding order code,
see "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC",
"Options", page 38 onwards.
An external overload and short-circuit protection device is available from the company "mat" for
the 3WL non-automatic air circuit breakers.
Available only directly from the company mat Maschinen- und Anlagentechnik5).
Additional price
1)

Provisions to dissipate heat must be made on the line side.

2)

For permissible rated short-time current Icw and short-circuit breaking


capacity Icc for non-automatic air circuit breakers, see page 5.

3)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

4)

If ordering withdrawable circuit breaker and guide frame separately, specify order code "A05" for withdrawable circuit breaker and guide frame.

68

Siemens 3WL IEC Breakers 2014

5)

mat Maschinen- und Anlagentechnik


Dr. Becker GmbH
Rudolf-Diesel-Strae 22
D-22941 Bargteheide
Tel.: +49 (45 32) 20-2101
Fax: +49 (45 32) 20-2121
E-mail: info@m-a-t.de
Internet: www.m-a-t.de

* You can order this quantity or a multiple thereof.

Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Accessories and spare parts

Selection and ordering data


Guide frames for DC non-automatic air circuit breakers
Size

Max. rated circuit breaker current


In max

DT

Guide frames for 3-pole


non-automatic air circuit breakers
Article No.

PU
(UNIT,
SET,
M)
Price
per PU

PS*/
P. unit

PG

Weight
per PU
approx.
kg

Front main circuit connection, single hole


II

2000

3WL9212-3DA@@-@@A1

1 unit

103

31.000

3WL9212-3DB@@-@@A1

1 unit

103

31.000

3WL9212-3DC@@-@@A1
3WL9212-6DC@@-@@A1

1
1

1 unit
1 unit

103
103

31.000
60.000

3WL9212-3DD@@-@@A1
3WL9212-6DD@@-@@A1

1
1

1 unit
1 unit

103
103

31.000
60.000

3WL9212-3DE@@-@@A1
3WL9212-6DE@@-@@A1

1
1

1 unit
1 unit

103
103

31.000
60.000

Front main circuit connection, double hole


II

2000

Horizontal main circuit connection


II

2000
4000

Vertical main circuit connection


II

2000
4000

Main circuit connection connecting flanges


II

2000
4000

Additional
price
3-pole

Options
No. of aux. supply connectors

Without

None

1 connector

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors,
see table on page 44.
Type of aux. circuit connections Without

Position signaling switches

Shutters

None

With screw connection (SIGUT, standard)

With screwless connection


method (tension spring)

Without

None

Option 1:
Connected position 1 CO,
test position 1 CO,
disconnected position 1 CO

Option 2:
Connected position 3 CO,
test position 2 CO,
disconnected position 1 CO

Without

None

With shutter, 2-part, lockable

Add "-Z" to the complete Article No. and indicate


the appropriate order code(s).

3WL9 212-.....-..A1-Z

Additional
price

@@@

Rated voltage 1000 V DC


Size II

A 0 5

A 0 8

1)

Tinned version of the customer's connections on the guide frame


Only for guide frames with horizontal connection or flange connection
Size II
Notes
For guide frames for 4-pole DC non-automatic air circuit breakers see the following page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC", "Options",
page 38 onwards.
Additional price
1)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

* You can order this quantity or a multiple thereof.

Siemens 3WL IEC Breakers 2014

69

Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Accessories and spare parts
Size

Max. rated circuit breaker current


In max

DT

Guide frames for 4-pole non-automatic


air circuit breakers

PU
(UNIT,
Price SET, M)
per PU

Article No.

PS*/
P. unit

PG

Weight
per PU
approx.

kg

Front main circuit connection, single hole


II

2000

3WL9212-3EA@@-@@A1

1 unit

103

37.000

3WL9212-3EB@@-@@A1

1 unit

103

37.000

3WL9212-3EC@@-@@A1
3WL9212-6EC@@-@@A1

1
1

1 unit
1 unit

103
103

37.000
84.000

3WL9212-3ED@@-@@A1
3WL9212-6ED@@-@@A1

1
1

1 unit
1 unit

103
103

37.000
84.000

3WL9212-3EE@@-@@A1
3WL9212-6EE@@-@@A1

1
1

1 unit
1 unit

103
103

37.000
84.000

Front main circuit connection, double hole


II

2000

Horizontal main circuit connection


II
II

2000
4000

Vertical main circuit connection


II
II

2000
4000

Main circuit connection connecting flanges


II
II

2000
4000

Additional
price
4-pole

Options
No. of aux. supply connectors

Without

None

1 connector

2 connectors

3 connectors

4 connectors

Note
For required number of auxiliary supply connectors, see table on
page 44.
Type of auxiliary circuit
connections

Position signaling switches

Shutters

Without

None

With screw connection (SIGUT, standard)

With screwless connection


method (tension spring)

Without

None

Option 1:
Connected position 1 CO,
test position 1 CO,
disconnected position 1 CO

Option 2:
Connected position 3 CO,
test position 2 CO,
disconnected position 1 CO

Without

None

With shutter, 2-part, lockable

Add "-Z" to the complete Article No. and indicate


the appropriate order code(s).

3WL9 212-.....-..A1-Z

Additional
price

@@@

Rated voltage 1000 V DC


Size II

A 0 5

A 0 8

Tinned version of the customer's connections on the guide frame1)


Only for guide frames with horizontal connection or flange connection
Size II
Notes
For guide frames for 3-pole DC non-automatic air circuit breakers see previous page.
All other accessory parts must be ordered by specifying "Z" and the corresponding order code,
see "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC", "Options",
page 38 onwards.
Additional price
1)

The permissible temperature-rise limits according to IEC 60947-2 are 5 K


lower for a tin surface than for a silver surface.

70

Siemens 3WL IEC Breakers 2014

* You can order this quantity or a multiple thereof.

Siemens Industry, Inc.


5400 Triangle Parkway
Norcross, GA 30092
1-800-241-4453
info.us@siemens.com

www.usa.siemens.com/3WLIEC

Subject to change without prior notice


Order No.: CBSA-IECWL-1214
All rights reserved
Printed in USA
2014 Siemens Industry, Inc.

The information provided in this brochure contains merely general


descriptions or characteristics of performance which in case of
actual use do not always apply as described or which may change
as a result of further development of the products. An obligation
to provide the respective characteristics shall only exist if expressly
agreed in the terms of contract. Availability and technical
specifications are subject to change without notice.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for
their own purposes could violate the rights of the owners.