Merlin Gerin
Merlin Gerin
Merlin Gerin
2008
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Micrologic® Electronic Trip Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Masterpact NT Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Masterpact NW Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Trip Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
INTRODUCTION............................................................................................................................................ 4
CODES AND STANDARDS........................................................................................................................... 4
FEATURES AND BENEFITS ......................................................................................................................... 4
OPERATING CONDITIONS........................................................................................................................... 6
MASTERPACT NW CIRCUIT BREAKER DESIGN ....................................................................................... 7
MASTERPACT NW CRADLE DESIGN ......................................................................................................... 8
MASTERPACT NT CIRCUIT BREAKER AND CRADLE DESIGN ................................................................ 9
RATINGS ..................................................................................................................................................... 10
CORRECTION FACTORS ........................................................................................................................... 11
SHIPPING WEIGHTS .................................................................................................................................. 11
3
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Introduction
The Masterpact NT/NW Universal Power Circuit Breaker is designed and tested to meet IEC 60947-2
and 60947-3 Standards and Certified to ABS-NVR (American Bureau of Shipping–Navel Vessel
Rules). These circuit breakers are specifically designed and tested for shipboard use to protect
electrical systems from damage caused by overloads, short circuits and equipment ground faults. All
Masterpact circuit breakers are designed to open and close a circuit manually, and to open the circuit
automatically at a predetermined overcurrent setting. Masterpact circuit breakers can also:
• Enhance coordination by their adjustability.
• Provide integral ground-fault protection for equipment.
• Provide high interrupting ratings and withstand ratings.
800–1600 A Masterpact NT
Drawout Circuit Breaker • Provide communications.
• Provide power monitoring.
• Provide protective relaying functions.
• Provide zone-selective interlocking (ZSI) which can reduce damage in the event of a fault.
06133469
HA10 12kV
NX 08 Uimp
Ui 1000V
Ue (V)
690
s
50kA/1
50/60Hz
AS NBMA
947-2 UNE
IEC
EN 60947-2BS CEI
VDE
UTE
800–3200 A Masterpact NW Drawout Circuit Breaker 4000–6300 A Masterpact NW Drawout Circuit Breaker
Masterpact circuit breakers are manufactured and tested in accordance with the following standards:
Masterpact circuit breakers are available in Square D®, Merlin Gerin®, or Federal Pioneer® brands.
High Ampere Interrupting Rating (AIR): Masterpact NW circuit breakers have an interrupting rating
of 150 kA at 440 Vac without fuses.
High Short-Time Current Rating: Masterpact NW circuit breakers have exceptional short-time
ratings—up to 100 kA.
100% Rated Circuit Breaker: Masterpact circuit breakers are designed for continuous operation at
100% of their current rating.
Reverse Fed Circuit Breaker: Masterpact circuit breakers can be fed either from the top of the circuit
breaker or from the bottom.
4
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
True Two-Step Stored Energy Mechanism: Masterpact circuit breakers are operated via a stored-
energy mechanism which can be manually or motor charged. The closing time is less than five cycles.
Closing and opening operations can be initiated by remote control or by push buttons on the circuit
breaker front cover. An O–C–O cycle is possible without recharging.
Drawout or Fixed Mount, 3-Pole (P) or 4-Pole (4P) Construction: Masterpact circuit breakers are
available in drawout or fixed mounts, with either 3-pole or 4-pole construction.
Field-installable Trip Units, Sensor Plugs and Accessories: Trip units, sensor plugs and most
accessories are field installable with only the aid of a screwdriver and without adjusting the circuit
breaker. The uniform design of the circuit breaker line allows most accessories to be common for the
whole line.
Reinforced Insulation: Two insulation barriers separate the circuit breaker front from the current path.
Isolation Function by Positive Indication of Contact Status: The mechanical indicator is truly
representative of the status of all the main contacts.
Segregated Compartment: Once the accessory cover has been removed to provide access to the
accessory compartment, the main contacts remain fully isolated. Furthermore, interphase partitioning
allows full insulation between each pole even if the accessory cover has been removed.
Front Connection of Secondary Circuits: All accessory terminals (ring terminals are available as an
option) are located on a connecting block which is accessible from the front in the connected, test and
disconnected positions. This is particularly useful for field inspection and modification.
Anti-Pumping Feature: All Masterpact NT and NW circuit breakers are designed with an anti-pumping
feature that causes an opening order to always takes priority over a closing order. Specifically, if
opening and closing orders occur simultaneously, the charged mechanism discharges without any
movement of the main contacts keeping the circuit breaker in the open (OFF) position.
In the event that opening and closing orders are simultaneously maintained, the standard mechanism
provides an anti-pumping function which continues to keep the main contacts in the open position.
In addition, after fault tripping or opening the circuit breaker intentionally (using the manual or electrical
controls and with the closing coil continuously energized) the circuit breaker cannot be closed until the
power supply to the closing coil is discontinued and then reactivated.
NOTE: When the automatic reset after fault trip (RAR) option is installed, the automatic control system
must take into account the information supplied by the circuit breaker before issuing a new closing
order or before blocking the circuit breaker in the open position. Information on the type of fault, e.g.
overload, short-circuit or ground fault.
Disconnection Through the Front Door: The racking handle and racking mechanism are accessible
through the front door cutout. Disconnecting the circuit breaker is possible without opening the door
and exposing live parts.
Door Escutcheon
Racking Handle
T TEST
Racking Mechanism
Disconnected
Position
5
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Drawout Mechanism: The drawout assembly mechanism allows the circuit breaker to be racked in
four positions (connected, test, disconnected, or withdrawn), as shown in the figure below.
Secondary
06135700
Contacts Stabs
Clusters
T TEST TTEST
06133339
TTEST
Reduced Maintenance: Under normal operating conditions, the circuit breaker does not require
maintenance. However, if maintenance or inspection is necessary, the arc chambers are easily
removed so you may visually inspect the contacts and wear indicator groove (see the figure below for
06133470
how wear is indicated). The operation counter can also indicate when inspections and possible
maintenance should be done.
Arc Chamber
Figure 4: Contact Wear Indicators
Good Worn
Contacts Contacts
Operating Conditions
Masterpact circuit breakers are suited for use at ambient temperatures between -22°F (-30°C) and
140°F (60°C). Masterpact circuit breakers have been tested for operation in shipboard atmospheres.
It is recommended that the equipment be cooled or heated to the proper operating temperature and
kept free of excessive vibration and dust. Operation at temperatures above 122°F (50°C) may require
derating or overbussing the circuit breaker. See the appropriate instruction bulletin and page 9 of this
catalog for additional information.
Masterpact circuit breakers have been tested to meet ABS-NVR Standards.
Masterpact circuit breakers meet IEC 68-2-6 Standards for vibration.
• 2 to 13.2 Hz and amplitude 0.039 in. (1 mm)
• 13.2 to 100 Hz constant acceleration 0.024 oz. (0.7 g.)
6
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
The materials used in Masterpact NT and NW circuit breakers will not support the growth of fungus and
mold.
Masterpact circuit breakers have been tested to the following:
• IEC68-2-30 - Damp heat (temperature +55°C and relative humidity of 95%)
• IEC 68-2-52 level 2 - salt mist
Storage Temperature
Circuit breakers with trip units without LCD displays may be stored in the original packaging at
temperatures between -58°F (-50°C) and 185°F (85°C). For circuit breakers with trip units with LCD
displays, this range is -40°F (-40°C) to 185°F (85°C).
Arc Chamber
Charging Handle
Open/Close Push
Button Cover
Electrical Close (Lockable with Padlock)
Push Button (BPFE)
ET
RES
Padlock Attachment
7
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Pull-Out Handgrip
8
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Terminal Cover
Lifting Handle
Padlock Provision
Position Indicator
Accessory Cover
Charging Handle
Extension Rail Handle
Lifting Tab
Accessory Cover
Charging Handle
Lifting Tab
Fault Trip "Push-to-close" Button
Reset Button
"Push-to-open" Button
Trip Unit
Faceplate
Correction Factors
9
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Ratings
10
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
General Information
Endurance Rating (C/O cycles) Mechanical 12,500 12,500 12,500 12,500 12,500
(with no maintenance) Electrical 440 V 6000 6000 3000 60003 60003
1 For Icw 10 kA is for 0.5 s.
2
SELLIM system
3
1600 A, 3000 cycles
Shipping Weights
Circuit Breaker Circuit Breaker1 (lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg) Pallet Total Weight (lb/kg)
Rating (A) 3P 4P 3P 4P Type 3P 4P (lb/kg) 3P 4P
800 FCF 42/19 55/25 17/8 265/121 320/146
109/50 132/60 97/44 116/53
1000, 1250, 1600, 2000 RCTH or RCTV 17/8 22/10 17/8 240/110 287/131
2500 FCF 42/19 55/25 17/8 310/142 386/176
127/58 165/75 124/57 149/68
3200 RCTH or RCTV 17/8 22/10 17/8 285/131 353/161
4000 127/58 165/75 124/57 149/68 RCTH or RCTV 42/19 55/25 17/8 310/142 386/176
5000, 6300 227/103 295/134 278/126 334/152 RCTH or RCTV 52/24 68/31 39/18 596/271 736/335
1
Fixed circuit breaker weight = total weight – cradle weight.
11
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
12
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
All Masterpact circuit breakers are equipped with the Micrologic trip system to protect power circuits
and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense
current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable
rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault
current protection required in the electrical system. If current exceeds a set value for longer than its set
time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote
indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity
of service and energy management. Micrologic trip units can be changed on-site.
Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic
component used in all Micrologic trip units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are
managed by an independent microprocessor.
Masterpact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit
adjustments set at their lowest settings. Actual settings required for a specific application must be
determined by a qualified consultant or plant engineer. A coordination study is recommended to
provide coordination between all circuit breakers in the distribution system.
Thermal Imaging
The thermal imaging function protects the cables or bus bars from overheating in case of low
amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load,
intermittent ground faults, or subsequent closing after a fault.
Traditional electronic protection does not protect against repetitive faults because the duration of each
overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each
overload involves a temperature rise in the installation, the cumulative effect of which could lead to
overheating of the system.
The thermal imaging function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and,
therefore, the reaction of the trip unit will be closer to the real heating of the power network system.
After tripping, the function will also reduce the time delay when closing the circuit breaker on an
overload.
13
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Power (P) and Harmonic (H) trip unit without 24 Vdc power supply at F1 and F2
The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD
display requires too much current to be powered by current flow through the circuit breaker. The P and
H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between
two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit
breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there
would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.
• Provides fault protection for LSIG functions
• Provides LED trip indication (powered by an onboard battery)
NOTE: Ground-fault push-to-trip button works for testing ground fault if the trip unit is powered by the
voltage power supply. The ground-fault push-to-trip is also functional if a hand-held test kit or full-
function test kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit With 24 Vdc Power Supply at F1 and F2
14
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
The sensing system responds to the flow of current through the circuit breaker. Electronic trip circuit
breakers are limited to ac systems because the electronic trip system uses current transformers to
sense the current.The Micrologic trip unit samples the current waveform to provide true RMS
protection through the 15th harmonic.
This true RMS sensing gives accurate values for the magnitude of a non-sinusoidal waveform.
Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated.
The Micrologic H trip unit provides additional sampling of the waveforms to measure and provide
waveform capture of harmonic distortion to the 31st harmonic.
Masterpact Universal Power Circuit Breakers use Micrologic electronic trip systems to sense overcurrents
and trip the circuit breaker. The Micrologic basic trip unit is standard and all Masterpact circuit breakers can
be equipped with the optional Micrologic trip systems listed below:
• Micrologic Basic Trip Unit (standard).
— 2.0 basic protection (LS0)
— 5.0 selective protection (LSI)
• Micrologic A: Trip Unit with Ammeter.
— 2.0A basic protection (LS0)
— 5.0A selective protection (LSI)
— 6.0A selective protection with ground-fault protection for equipment (LSIG)
• Micrologic P: Trip Unit with Power Metering.
— 5.0P selective protection (LSI)
— 6.0P selective protection with ground-fault protection for equipment (LSIG)
• Micrologic H: Trip Unit with Harmonic Metering.
— 5.0H selective protection (LSI)
— 6.0H selective protection with ground-fault protection for equipment (LSIG)
06135748
t= I n= t= I n= t= I n=
tsd= tr= MAX tsd= tr= MAX tsd= tr= MAX
Isd= s Isd= s Isd= s
Ii= Ir= kA Ii= Ir= kA Ii= Ir= kA
Ig= Ig= Ig=
tg= tg= tg=
40 % 40 % 40 %
Micrologic 2.0 and 5.0 Basic Trip Units Micrologic 2.0A, 5.0A and 6.0A Trip Units
15
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
06133482
06133479
06133480
Micrologic 5.0P and 6.0P Trip Units Micrologic 5.0H and 6.0H Trip Units
16
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
The Micrologic 2.0 and 5.0 trip units protect power circuits.
Protection Settings
06133253 Protection thresholds and delays are set using the rotary switches.
Micrologic 5.0
1—Overload signal (LED) A full-range of long-time settings are available via field-installable
2—Long-time rating plug adjustable rating plugs.
screw
Ir
long time
tr alarm 1 • Overload protection
3—Long-time current setting .7
.8
.9 (s) 4
8
12
.6 .95 2 16
and tripping delay .5 .98 1 20 2 — True RMS long-time protection
24
.4
x In
1 .5
@6 Ir 3
4—Instantaneous pickup short time instantaneous — Thermal imaging: Active thermal imaging before and after tripping
Isd tsd Ii
3
4
5 (s) . 4 . 4 .3 6 8 10
5—Short-time pickup and 2.5 6 .3 .2 4 12 4 • Short-circuit protection.
2 8 .2 .1 3 15
tripping delay 1.5 10 .1 0 2 2 off
x Ir on off
I t x In 5
6—Test connector
setting delay
test — Short-time RMS
6
— Selection of I2t type (ON or OFF) for short-time delay
• Instantaneous protection.
• Neutral protection on four-pole circuit breakers.
Micrologic 5.0 Basic Trip Unit
t Current Setting (A) 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
Ir Tripping Between 1.05 Ir = ln x...
and 1.20 x Ir Other ranges are available by changing rating plug
Ir
Tripping Between 1.05 Ir = ln x...
and 1.20 x Ir Other ranges are available by changing rating plug
tr
Long-Time tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Protection Maximum Time Delay (s)
lsd tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Accuracy: 0 to –20%
tsd tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
li Thermal Imaging 20 minutes before or after tripping
0 I Current Setting (A)
lsd = Ir x... 1.5 2 2.5 3 4 5 6 8 10
Accuracy: ±10%
2
I t OFF 0 0.1 0.2 0.3 0.4
Settings
Short-Time I2t ON 0.1 0.2 0.3 0.4
Protection Maximum Time Delay (s) Min. trip
at 10 x Ir 20 80 140 230 350
time (ms)
tsd
Max. trip
80 140 200 320 500
time (ms)
Instantaneous Current Setting (A)
Ii = In x... 2 3 4 6 8 10 12 15 off
Protection Accuracy: ±10%
17
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
Protection Settings
Protection thresholds and delays are set using the rotary switches. The
06133254
Micrologic 6.0 A
selected values are momentarily displayed in amperes and in seconds.
1
1—Test lamp and reset A full-range of long-time settings are available via field-installable rating
2
2—Indication of tripping Δt= IΔn=
plug.
tsd= tr= MAX
cause Isd=
Ii= Ir=
Ig=
s
kA • Overload protection (true RMS long-time protection).
3—Digital display tg= 3
• Thermal imaging (active thermal imaging before and after tripping).
4—Three-phase bar graph
and ammeter • Short-circuit protection.
5—Navigation buttons
100 %
— Short-time RMS
6—Overload signal (LED) — I2t ON or OFF for short-time delay
4
7—Long-time rating plug
screw
40 % • Instantaneous protection.
8—Long-time current setting 5 • Ground-fault protection for equipment.
and tripping delay
menu
— Residual ground-fault protection for equipment
9—Short-time pickup and
tripping delay — Source ground-return ground-fault protection for equipment
long time
6
10—Instantaneous pickup
Ir
.6
.7
.8
.9
.95
tr
(s)
2
4
8
12
16
alarm
— Modified differential ground-fault protection (MDGF) for
7
.5
.4 1
.98 1
.5
20
24 8 equipment
11—Electronic push-to-trip x In @ 6 Ir
2.5
3
4
5
6
tsd
(s)
.3
.4 .4 .3
.2
Ii
4
6 8 10
12
9 • Neutral protection on four-pole circuit breakers.
tripping delay 2 8 .2 .1 3
1.5
x Ir
10
on
.1 2 0
I t off
2
x In
15
off 10 • ZSI: Zone-selective interlocking (a ZSI terminal block may be used to
setting delay
13—Test connector Ig
E
tg
(s) .4 .4 .3
test
Ammeter Measurements
Micrologic A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x In with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x In. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x In and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4-pole
circuit breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
18
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
t Current Setting (A) 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
06133324
Ir Tripping Between 1.05 Ir = ln x...
and 1.20 x Ir Other ranges are available by changing rating plug
Ir
Tripping Between 1.05 Ir = ln x...
and 1.20 x Ir Other ranges are available by changing rating plug
tr Long-Time tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
Protection Maximum Time Delay (s)
tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
lsd Accuracy: 0 to –20%
tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
tsd
Thermal Imaging 20 minutes before or after tripping
li
Current Setting (A)
lsd = Ir x... 1.5 2 2.5 3 4 5 6 8 10
0 I Accuracy: ±10%
I2t OFF 0 0.1 0.2 0.3 0.4
Settings
Short-Time I2t ON 0.1 0.2 0.3 0.4
Protection Maximum TimeDelay (s) Min. trip
at 10 x Ir 20 80 140 230 350
time (ms)
tsd
Max. trip
80 140 200 320 500
time (ms)
Instantaneous Current Setting (A)
Ii = In x... 2 3 4 6 8 10 12 15 off
Protection Accuracy: ±10%
I2t on
Ground-Fault Pickup (A) ln ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
lg
Accuracy: ±10% 400 A < ln ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2 t off
tg ln > 1200 A 500 640 720 800 880 960 1040 1120 1200
I2t OFF 0 0.1 0.2 0.3 0.4
Settings
0 I Maximum Time Delay (s) I2t ON 0.1 0.2 0.3 0.4
at 10 x Ir Minimum Trip Time (ms) 20 80 140 230 350
tg
Maximum Trip Time (ms) 80 140 200 320 500
19
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Protection Settings
1—Test lamp and indication The adjustable protection functions of the 5.0P and 6.0P trip units
reset
06133255
Micrologic 6.0 P
are identical to those of Micrologic A trip unit (overloads, short
2—Indication of tripping 1
circuits, equipment ground-fault protection); see page 18.
cause 2
These units also feature:
3—High resolution screen I(A)
4—Measurement display Trip • Fine adjustment: Within the range below the rotary switch
5—Maintenance indicators 5000A
setting, fine adjustments of pickups/delays in steps of 1 A/s
3
24s (except for short-time and ground-fault) are possible on the
6—Protection settings
keypad or remotely by the communication network.
7—Navigation buttons 30kA
.6
.7
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm
— OFF
13—Hole for settings .5 .98 1 20
9
lockout pin .4
x In
1 .5 24
@ 6 Ir 10 — 1/2N (1/2 x In)
short time instantaneous
14—Electronic push-to-trip
Isd
3
4
5
tsd
(s) .4 .4 .3
Ii
6 8 10
11 — 1N (1 x In)
2.5 6 .3 .2 4 12
.2 .1 12
15—Ground-fault pickup and
2
1.5 10
8
.1 2 0
3
2
15
off — 2N (2 x In)
x Ir on I t off x In 13
tripping delay setting delay
test
Ig
D
E
F
tg
(s) . 4 .4 .3 14 NOTE: The neutral protection is disabled if the long-time curve is set
16—Test connector .3 .2
C
B
G
H .2 .1 15 to one of the IDMTL protection settings.
.1 2 0
A J
on I t off 16
ground fault
When the cover is closed, the keypad may no longer be used to change the protection settings, but it
still provides access to the displays for measurements, histories, indicators, etc. Depending on the
thresholds and time delays set, the Micrologic P trip unit monitors current, voltage, power, frequency,
and phase sequence. Each threshold overrun may be signalled remotely via the communication
network.
Each threshold overrun may be combined with tripping (protection) or an indication carried out by an
optional M2C/M6C programmable contact (alarm), or both (protection and alarm).
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
• Highest current measured
• Operation counter (both cumulative total and total since last reset)
• Number of test kit connections
• Number of trips in operating mode
• Contact wear (Masterpact NW only)
20
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Load shedding and reconnection parameters can be set according to the power or the current flowing
through the circuit breaker. Load shedding is carried out by a remote computer via the communication
network or by an M2C or M6C programmable contact.
The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal
threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P
and H trip units or remotely using the communication network. These contacts are required to obtain
data from the protective relay functions on Type P and Type H trip units.
I2t on
lg Ground-Fault Pickup (A) ln ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2 t off
Accuracy: ±10% 400 A < ln ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
tg
ln > 1200 A 500 640 720 800 880 960 1040 1120 1200
I2t OFF 0 0.1 0.2 0.3 0.4
MaximumTime Delay (s) Settings
0 I I2t ON 0.1 0.2 0.3 0.4
at 10 x Ir
Minimum Trip Time (ms) 20 80 140 230 350
tg
Maximum Trip Time (ms) 80 140 200 320 500
Table 16: Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
21
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Table 17: Load-Shedding Settings for Current and Power Metering for Micrologic 5.0P and
6.0P Trip Units
Pickup Dropout
The last ten trips and ten alarms are recorded in two separate history files that can be displayed on the
screen (sample displays are shown to the right). The following information is contained in these files:
Trip History
06133262
Trip
• Type of fault history
Vmax
30/06/1999
Alarm History
06133263
Trip
• Type of alarm
03/08/1999
• Date and time of the alarm 11:04:18 am
alarm I1 = 4800 A
I2 = 5600 A
I3 = 4000 A
IN = 200 A
22
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Metering
The Micrologic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh,
VAh, Hz, power factor, and crest factor. The Micrologic P trip unit also calculates demand current and
06133258
50
Current Type of Measurement Unit of Measurement Measurement Source
Metering
IRMS A ØA, ØB, ØC or N
0
Current IAVERAGE A (ØA + ØB + ØC)/3
IPEAK/√2 A ØA, ØB, ØC or N
Iinstant.
max
Voltage
VRMS
VRMS
V
V
(ØA–ØB), (ØB–ØC) and (ØC–ØA)
(ØA–N), (ØB–N) and (ØC–N)
VIMBALANCE % VRMS
IA = 4800 A
IB = 4600 A P, Q and S W, VAR, VA Total
IC = 4000 A Power EP, EQ and ES Wh, VARh, VAh Total
IN = 200 A Power factor Total
Maximum
I = 13 ACurrent
Frequency F Hz 50/60
Demand Metering: The demand is calculated over a fixed or sliding time window that can be
programmed from five to 60 minutes. Depending on the contract signed with the power supplier,
Vinst. specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed
VAB = 460 V
power. Maximum demand values are systematically stored and time stamped.
VBC = 464 V
VCA = 461 V
Type of Measurement Unit of Measurement Measurement Source
VAN = 270 V
VBN = 279 V
Voltage Current IDEMAND A ØA, ØB, ØC or N
VCN = 273 Metering
V
Power P, Q and SDEMAND W, VAR, VA Total
Communication Network
Pinst. Four wire Modbus, RTU, RS485—The communication network may be used to:
P (kW)
2180 • Remotely read parameters for the protection functions
Q (kVAR)
• Transmit all the measurements and calculated values
- 650
• Signal the causes of tripping and alarms
Power
S (kVA)
Metering
2280
• Consult the history files and the maintenance indicator record
In addition, an event log of the last 100 events and a maintenance record, which is stored in the trip
unit memory but not available locally, may be accessed via the communication network.
F (Hz) The Modbus communication system is compatible with Powerlogic® System ManagerTM (SMS) software.
Event Log
60.0
The event log may be accessed by a remote computer via the communication network. All events are
Frequency time stamped and include:
• Trips
• Beginning and end of alarms
Pdemand • Modifications to settings and parameters
P (kW) • Loss of time
2180
• Overrun of wear indicators
Q (kVAR)
- 650
• Test kit connections.
S (kVA)
• Counter resets.
Power
2280
Demand • System faults (thermal self-protection, major fault and minor fault alarms).
23
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Micrologic 6.0 H • In-depth analysis of power quality including calculation of harmonics and the fundamentals.
• Diagnostics aid and event analysis through waveform capture.
• Customized alarm programming to analyze and track down a disturbance on the ac power system.
I (A) • Systematic time stamping of all events and creation of logs.
V (V)
Metering
P (kW)
E (kWh) The Micrologic H trip unit offers all the measurements carried out by the Micrologic P trip unit, with the
addition of phase-by-phase measurements of power and energy as well as calculation of:
Harmonics
• Current and voltage total harmonic distortion (THD, thd).
• Current, voltage and power fundamentals (50/60 Hz).
• Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.
Real-time metering: The value displayed on the screen is refreshed every second. The table below
shows what is measured in real-time metering.
long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
16
.6
.5
.95 2
.98 1 20 Type of Measurement Unit of Measurement Measurement Source
.4 1 .5 24
x In @ 6 Ir
Demand Metering: Similar to the Micrologic P trip unit, demand values are calculated over a fixed or
sliding time window that can be set from five to 60 minutes.
Waveform Capture
Micrologic H trip units can capture and store current and voltage waveforms using digital sampling
techniques similar to those used in oscilloscopes. Using the information available in the captured
waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of
the flow of harmonic power.
Users of Micrologic H trip units can record manually via the keypad the following waveforms:
• The four currents: Ia, Ib, Ic, and IN
• The three phase-to-phase voltages: Vab, Vbc, and Vca
Waveforms may be displayed on the graphic screen of Micrologic H trip units or communicated over a
networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 IN
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
24
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
The instantaneous value of each measurement can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including
circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.
Event Logs
• Setting the display language: System messages can be displayed in six different languages:
— English - US
— English - UK
— French
— German
— Spanish
— Italian
The desired language is selected via the keypad.
• Protection functions: All current-based protection functions require no auxiliary source. Voltage-
based protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
• Accuracy of measurements (including sensors):
— Voltage (V) 1%
— Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current
transformer [CT characterization option])
— Frequency (Hz) 0.1 Hz
— Power (W) and energy (Wh) 2.5%
— The Micrologic H trip unit uses a dedicated metering data chain separate from the protection
data chain so that a greater number of data samples can be used for metering. This increases
the number of samples taken per time period, which in turn gives the H trip unit a higher degree
of metering accuracy.
• Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
• Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.
25
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
The long-time delay switch sets the length of time that the circuit breaker will carry a sustained
.5
x In
short time
@ 6 Ir
instantaneous
Alarm
Isd
3
4
5
tsd
(s) .4 .4 .3
Ii
6 8 10 Indicator
2.5
2
1.5 10
6
8
.3
.2
.1 0
.2
.1
4
3
2
12
15
off
overload before tripping. Delay bands are labeled in seconds of overcurrent at six times the ampere
x Ir on I2t off x In
Ig
D
setting
E
F
tg
(s)
delay
.4 .4 .3
test
rating. For maximum coordination, there are eight delay bands. Long-time delay is an “inverse time”
C G .3 .2
B
A J
H .2
on
.1
I2t
0
.1
off
characteristic in that the delay time decreases as the current increases.
ground fault
Isd
short time
tsd Ii
instantaneous Delay
3
4
5 (s) .4 .4 .3 6 8 10
.3 .2
2.5
2
1.5
x Ir
10
6
8 .2
on
.1 0
.1
I2t off
4
3
2
x In
12
15
off Instantane- short-time pickup range. The delay (based on 10 times the ampere rating Ir) can be adjusted to four
ous Pickup
positions of I2t ramp operation (I2t ON) or five positions of fixed time delays (I2t OFF). I2t ON delay is
setting delay
test
Ig tg
D
E
F (s) .4 .4 .3
C G .3 .2
B
A
ground fault
J
H .2
on
.1 0
.1
I2t off an “inverse time” characteristic in that the delay time decreases as the current increases. Short-time
delay for the 2.0 trip unit is fixed at a delay band of 20 to 80 ms.
Short-Time and
Instantaneous Trip
Functions Instantaneous Trip Function
The instantaneous pickup switch sets the short-circuit current level at which the circuit breaker will trip
with no intentional time delay. The instantaneous current (Ii) is equal to the instantaneous pickup
setting multiplied by the sensor plug amperage (In).
The instantaneous function will override the short-time function if the instantaneous pickup is adjusted
at the same or lower setting than the short-time pickup. In trip units with both adjustable short-time and
instantaneous trip functions, the adjustable instantaneous trip can be disabled by setting
Instantaneous pickup to OFF.
C
D
E
F
G
tg
(s)
.3
.4 .4 .3
.2
test
Delay which exceeds the ground-fault pickup level before tripping. The delay (based on the sensor plug
amperage (In) can be adjusted to four positions of I2t ramp operation (I2t ON) or five positions of fixed
B H .2 .1
A J .1 0
on I2t off
ground fault
time delays (I2t OFF). I2t ON delay is an “inverse time” characteristic in that the delay time decreases
Ground-Fault Trip as the current increases.
Functions
26
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Micrologic® Electronic Trip Systems
Communication Network
Masterpact NW/NT circuit breaker, and Micrologic trip unit information is available via a Modbus network to
Powerlogic® System ManagerTM software (SMS) or other applications for reporting and recording.
Four wire Modbus, RTU, RS485—Types of information available via Modbus communication network:
The Modbus circuit breaker communication feature, standard on the Micrologic P and H trip units and
available for the Micrologic A trip unit, is made up of:
• A Modbus circuit breaker communication module (BCM) installed on the circuit breaker and
supplied with a kit for optional connection to the XF shunt close and MX shunt trip.
• An optional Modbus cradle communication module (CCM) installed adjacent to the breaker cradle.
Cradle position switches are required for breaker position status (connected, test, or disconnected).
The Modbus circuit breaker communication module (BCM) is installed in the circuit breaker and
requires a separate, isolated 24 Vdc power source. The BCM is optically coupled to the Micrologic trip
unit to ensure a high level of isolation between the trip unit and the communication network. The
Modbus BCM provides circuit breaker status via dedicated O/F (open or closed), SDE (fault tripped),
CH (spring charged), and PF (ready-to-close) switches and provides the capability of remotely
controlling the circuit breaker. It also maintains an event log of circuit breaker status containing the
number of times the circuit breaker has experienced each status position with the date and time of the
last transition. This information and the remote control capability are available to a Modbus supervisor
system via a Modbus communication network.
The optional Modbus cradle communication module (CCM) is installed adjacent to the circuit breaker
cradle and is the gateway between the Modbus network and the Modbus BCM. The Modbus CCM
provides circuit breaker cradle status including connected position (CE), disconnected position (CD)
and test position (CT). The CCM monitors the communication parameters of the Modbus BCM and trip
unit when it detects a circuit breaker being racked from the cradle. When the circuit breaker is
reinstalled or a spare circuit breaker is installed and racked into the cradle, the CCM automatically
downloads the address, baud rate, and parity into the BCM. This capability allows a circuit breaker to be
replaced without the need to manually configure the communication parameters in the Modbus BCM.
The CCM maintains an event log of the date and time of the last circuit breaker transition. In order to
aid system communication troubleshooting, the CCM has visual indication of the module’s operating
status by means of two LEDs.
System Manager Software (SMS), used for power systems and energy management, provides the
human-machine interface (HMI) for electrical system information on a PC. SMS displays circuit breaker
and trip unit information in several formats including:
• Screens including real-time readings, breaker status and remote control operation.
• Tables displaying real-time readings, maintenance information and date and time of last operation.
• Waveform captures including harmonic content.
• Tabular displays of event logs and data logs.
• Alarm annunciation and recording.
27
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Section 3—Accessories
28
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Two options are available for remote operation of Masterpact circuit breakers: direct connection or a
communication network.
NOTE: When remote operation features are used, a minimum of four seconds is required for the spring
charging motor (MCH) to completely charge the circuit breaker closing springs prior to actuating the
shunt close (XF) device.
The wiring diagrams for these two options are shown below.
Opening Closing
Spring Ready to
06133264
Order Order
Charged Close
Fault
Open Closed
B3 B2 C2 A2 252 254 82 84 12 14
MCH
MX XF
PF SDE OF1
CH
B1 C1 A1 251 81 11
29
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Terminals
Characteristics MCH
Vac 50/60 Hz 48/60, 100/130, 200/250, 240/277, 380/415, 400/440, 480
Voltage Ratings (Vn)
Vdc 24/30, 48/60, 100/125, 200/250
Operating Threshold 0.85 to 1.1 Vn
Power Consumption 180 VA
Motor Overcurrent 2–3 x In for 0.1 s
Charging Time 4 s maximum on NW, 3 s maximum on NT
Duty Cycle 3 cycles per minute maximum
10,000 cycles for NW < 4000 A
Endurance
5000 cycles for NW ≥ 4000 A
CH Contact 10 A at 240 V
30
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Maximum Wire Length—The inrush currents for these devices are approximately 200 VA. When low
supply voltages (12, 24 or 48 V) are used, the maximum allowable wire length is dependent on the
voltage and the wire size.
Shunt trip (MX1): When energized, the shunt trip instantaneously opens the circuit breaker. The shunt
trip may be energized continuously or intermittently.
Shunt close (XF): Remotely closes the circuit breaker if the spring mechanism is charged. The shunt
close may be energized continuously or intermittently.
Communication versions of the MX1 and XF are available for direct connection via the circuit breaker
communication module (BCM).
Shunt Trip (MX1) and Table 21: Shunt Trip and Shunt Close Characteristics
Shunt Close (XF)
Characteristics MX1 XF Min Max
24 Vac 17 Vac 26 Vac
48 Vac 34 Vac 52 Vac
120 Vac 60 Vac 132 Vac
Vac
240 Vac 168 Vac 264 Vac
50/60 Hz
277 Vac 194 Vac 304 Vac
380 Vac 266 Vac 418 Vac
Voltage Ratings (Vn)
480 Vac 336 Vac 528 Vac
12 Vdc 8 Vdc 13 Vdc
24 Vdc 17 Vdc 26 Vdc
Vdc 48 Vdc 34 Vdc 52 Vdc
125 Vdc 88 Vdc 137 Vdc
250 Vdc 175 Vdc 275 Vdc
Operating Threshold 0.7 to 1.1 Vn 0.85 to 1.1 Vn
Power Consumption (VA or W) Steady-State/Inrush 4.5/200
70 ms ±10 (NW ≤ 4000 A)
50 ms ±10
Circuit Breaker Response Time at Vn1 80 ms ±10 (NW > 4000 A)
(NW and NT)
55 ms (NT)
1
Shunt trip (MX1) and shunt close (XF) circuits must be energized for minimum of 200 ms.
31
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
The undervoltage trip (MN) instantaneously opens the circuit breaker when its supply voltage drops to
a value between 35% and 70% of its rated voltage.
If the undervoltage trip is not energized, it is impossible to close the circuit breaker, either manually or
electrically. An attempt to close the circuit breaker produces no movement of the main contacts.
Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of rated voltage.
MN
C1 1 D1 D1
32
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Remote Order
button carries out electrical closing of the circuit breaker, to Close
taking into account all of the safety functions that are part
of the control/monitoring system of the installation. The A2 A3
33
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
• Following tripping, the remote reset (RES) resets the overcurrent trip switch (SDE) and the
mechanical indicator. (Voltage rating: 110/130 Vac and 200/240 Vac.) RES is not compatible with
an additional overcurrent trip switch (SDE2).
• Automatic reset after fault-trip: Following tripping, a reset of the mechanical indicator (reset button)
is no longer required to enable circuit breaker closing (factory adjustable only).
The rotary-type auxiliary switches are directly driven by the trip mechanism when the minimum
isolation distance between the main circuit breaker contact is reached.
34
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
35
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
The Modbus® circuit breaker communication module (BCM) (standard on the Micrologic P and H trip
units and available for the Micrologic A trip unit) is comprised of a communication module installed on
the circuit breaker with a kit for connection to the shunt close (XF) and shunt trip (MX1) along with a set
of switches.
The Modbus cradle communication module (CCM) is connected to the BCM and cell switches.
Modbus Communication
Network without CCM
CCM
(optional)
2
Terminal
Block
Modbus Communication
Network with CCM
BCM
This module is independent of the trip unit. Installed on the circuit breaker, behind the trip unit, it
receives and transmits information on the communication network. An optical link is used for
communication with the Micrologic A, P, and H trip units. Power requirements: 50 mA, 24 Vdc.
The following may be connected to this module:
• A set of dedicated switches which read the status of the circuit breaker.
• A set of “actuators” (MX/XF) to control the circuit breaker.
Circuit Breaker
Communication
Module (BCM)
36
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Status Indication
ON/OFF Indication
Connected/Disconnected/Test Pos.
Ready-to-Close
Fault Trip
Controls
Opening/Closing
Circuit
Breaker and
Settings Trip Unit
A P H
Reading of Settings on Rotary Switches • • •
Fine Settings in the Range Imposed by the Rotary Switches • •
Setting of Protection and Alarms • •
Customized Alarm Programming •
37
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
The sensor is installed on the neutral conductor for neutral protection and metering and residual
current ground-fault protection for equipment.
NOTE: The rating of the external neutral current transformer must be compatible with the rating of the
circuit breaker.
External Sensor for Source Ground-Return (SGR) and Modified Differential Ground-
External Neutral Current Fault (MDGF) Protection
Transformer (CT)
NOTE: SGR and MDGFare for use on circuit breakers with 1600 A and higher sensors.
For SGR System: The sensor is installed around the connection of the transformer neutral point to
ground and connects to the Micrologic 6.0A, 6.0P or 6.0H trip units. SGR requires a modified
differential ground-fault (MDGF) sensor and MDGF interface module to connect to the trip unit.
For MDGF System: The MDGF sensor is installed on each phase and neutral of each circuit breaker
and connects to the Micrologic trip unit through an MDGF module. See MDGF instruction bulletin
48049-182.
Sensor Plug Sensor plugs (standard) are used to set the sensor rating (In) of the circuit breaker, are field
replaceable and are offered at 50–100% of frame rating.
38
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
These contacts are used with the Micrologic P and H control units, and indicate the type of fault and
instantaneous or delayed threshold overruns (i.e trip unit protection pick-up, current/voltage
unbalance, under/over voltage, reverse power, phase rotation, under/over frequency, and load
shedding). The M2C unit is powered from the control unit’s 24 Vdc source (100 mA consumption); the
M6C unit requires an external 24 Vdc power supply (100 mA consumption).
They are programmed via the control unit using a keypad or via a supervisory station with the COM
communication option. They may be programmed:
M6C Programmable • with instantaneous return to the initial state,
Contact Module
• without return to the initial state,
• with return to the initial state following a delay.
39
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
06133801
During a short-circuit or ground-fault condition on a
ZSI system, the device directly ahead of the fault Z1
B Z2
sends a signal upstream via control wiring to Z3
restrain upstream circuit breakers from tripping and Z4
Z5
then trips with no intentional time delay to clear the
fault. Upstream devices which receive a restraint Fault 2
Upstream Device
Series B Trip Unit
GC-200 Relay
Merlin Gerin
Micrologic
Square D
Square D
Downstream Device
(sends output to RIM)
40
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Cradle Connections
06134457
06134464
Front-Connected
800—3200 A
Flat (FCF)
06134462
06134455
800—3200 A
06134465
06134458
4000 A
Rear-Connected “T”
Vertical (RCTV)
06134460
06134467
5000 A
06134843
06134844
6300 A
06134456
06134463
800—3200 A
06134459
06134466
06134468
5000 A
41
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
06134475
06134478
Front-Connected
800—3200 A
Flat (FCF)
06134474
06134477
800—3200 A
06134479
06134481
4000 A
Rear-Connected
06134485
06134483
5000 A
06134845
06134846
6300 A
06134473
06134476
800—3200 A
06134482
06134480
4000
Rear-Connected
“T” Horizontal
(RCTH)
06134484
06134486
5000 A
42
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
43
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Test Equipment
06133462
44
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Open Position Key Keys may be removed only when locking is effective. The key locks are available in any of the
Lock (NW) following configurations:
• One key lock.
• One key lock mounted on the device plus one identical key lock supplied separately for interlocking
with another device.
• Two different key locks mounted on the circuit breaker for double locking.
Open Position Padlock A locking kit for installation of one or two key locks may be ordered separately.
Provision (NW)
Table 36: Circuit Breaker and Switch Locking Options
Padlock Hasp
The circuit breaker can be locked in the disconnected
position by key interlock (optional) or padlock (standard). 06133464
Test
Door Interlock
The door interlock prevents the compartment door from being opened when the circuit breaker is in the
connected or test position. If the circuit breaker is put into the connected position with the door open,
the door can be closed without disconnecting the circuit breaker. For greater protection, this interlock
06133789
Door Interlock (NW) The racking interlock is optional. It prevents insertion of the racking crank unless the OFF push button
is pressed. Not available for Masterpact NT circuit breakers.
45
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
This option prevents the compartment door from being opened when the circuit breaker is in the closed
position. This kit includes:
A B C
06134189 Kit Contents
(A) Panel Interlocking Plate
(B) Circuit Breaker Interlocking Plate
(C) Interlocking Cables
(D) Bolts with Washers
D (E) Guide-bolt with Washer
G (F) Interlocking Bracket
F (G) Calibration Tray
E
Source changeover interlocks allow mechanical interlocking between two or three circuit breakers
(fixed and drawout).
The cradle rejection feature (standard) ensures that only the properly designated circuit breaker or
switch is matched with the selected cradle assembly.
46
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Accessories
Miscellaneous Accessories
Mechanical Operation Counter (CDM)
06133798
The mechanical operation counter (CDM) registers the total number of operating cycles. One CDM is
0039
9 installed per circuit breaker.
These door escutcheons provide a frame and seal for the circuit breaker.
Seal Seal
06133818
06134065
Escutcheon Escutcheon
The cover is hinged-mounted and locked with a milled head, and is designed to be installed on the
door escutcheon.
47
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
48
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
Fault
Fault
Z4, Z5
Charged
Upstream Downstream
06133796
N A B C
Z3
Z1
Z2
M6C
C12
484
474
182
184
252
254
VN
Q1
Q3
Q2
V1
V2
K2
C2
C3
V3
Z1
Z5
B3
Z2
Z3
Z4
B2
82
D2
A2
A3
84
A
MCH E
I S1 S2 MN MX2 MX1 XF
SDE2 SDE1 CH
Trip Unit
V
RES PF
M2C M6C or
or or
B1
K1
181
D1
C1
251
C11
A1
M3
81
M1
M2
471
T1
T2
T3
T4
F2+
F1–
D NOTE: All diagrams show circuit breaker open, connected and charged.
T1
T2
T3
T4
24 Vdc
C
A—Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B—Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C—For proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D—24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
E—When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
834 824 814 E5 E6 Z5 M1 M2 M3 F2+ V3 484/Q3 184/K2 84 334 324 314 D2/C12 C2 A2 254 B2
832 822 812 E3 E4 Z3 Z4 T3 T4 VN V2 474/Q2 182 82 332 322 312 C13 C3 A3 252 B3
831 821 811 E1 E2 Z1 Z2 T1 T2 F1– V1 471/Q1 181/K1 81 331 321 311 D1/C11 C1 A1 251 B1
or
CE6 CE5 CE4
49
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
Not Connected
06133794
06133795
or Connected Connected
and Open Closed
Open Closed Closed Disconnected Connected Test Position
332
334
324
312
314
812
834
822
824
814
322
832
..2
..8
..6
934
924
914
932
922
912
..4
42
32
22
12
44
24
14
34
EF
OF4 OF3 OF2 OF1 OF . . OF . .
(OF.. + CE)
CD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1
or
CE
831
821
811
321
331
311
911
931
921
..1
..5
41
31
21
11
244 234 224 214 144 134 124 114 44 34 24 14 934 924 914
242 232 222 212 142 132 122 112 42 32 22 12 932 922 912
241 231 221 211 141 131 121 111 41 31 21 11 931 921 911
or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CD6 CD5 CD4 CE9 CE8 C7
248 238 228 218 148 138 128 118 864 854 844 394 384 374
246 236 226 216 146 136 126 116 862 852 842 392 382 372
245 235 225 215 145 135 125 115 861 851 841 391 381 371
1
Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
50
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
Fault
Fault
Power
06134062
Upstream Downstream
Charged
Circuit Breaker Circuit Breaker
N L1 L2 L3
06134061
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
M6C
C12
182
184
252
254
K2
C2
C3
B3
B2
82
D2
A2
A3
84
474
484
Q1
Q2
Q3
VN
V1
V2
V3
Z1
Z2
Z3
Z4
Z5
A
E
MCH
MN MX2 MX1 XF
Q SDE2 SDE1 CH
RES PF
I S1 S2
or
Micrologic or
V
M2C M6C
or
B1
K1
181
D1
C1
251
C11
A1
81
NOTE: All diagrams show circuit breaker open, connected and charged.
471
B
F2+
M1
M2
M3
T1
T2
T3
T4
F1
T1
T2
T3
T4
C
24 Vdc D
A—Do not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
B—Do not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
C—For proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D—24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
E—When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
Remote Operation
D2 / C12 C2 A2 254 B2
C13 C3 A3 252 B3
D1/C11 C1 A1 251 B1
51
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
06134063
06134064
Open Closed Disconnected Test Position
Connected
822
824
812
814
332
334
322
324
312
314
914
912
42
32
22
12
44
24
14
OF4 OF3 34
OF2 OF1
CD2 CD1 CE3 CE2 CE1 CT1
821
811
321
331
311
911
41
31
21
11
CN1 - 440/480 V
9 11
“Spring
Charged“ R
Light
440/480 V
B3 B2
CH
MCH
380V
Spring-Charging Motor 440/480 Vac
(380 Vac Motor + Additional Resistor)
B1
CN2 - 440/480 V
52
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Wiring Diagrams
Alarm Contacts (OF1, OF2, OF3 and OF4 are standard equipment) Cradle Contacts
OF4
OF24: Open/Closed Circuit Breaker or Switch Position Contact CD3 CE3 CT3
OF3 Open/Closed Circuit Connected
Disconnected Test Position
Breaker or Switch or CD2 CE2 Position CT2
OF2 Position Contacts Contacts
Position Contacts Contacts
EF24: Combined Connected and Closed Contact CD1 CE1 CT1
OF1
OF23 or EF23 or or
OF22 or EF22 CE6 CE9
Connected
Connected
OF21 or EF21 CE5 CE8 Position
Position Contacts
OF14 or EF14 CE4 CE7 Contacts
OF13 or EF13 or
OF12 or EF12 CD6
Disconnected
OF22 or EF22 CD5 Position
OF11 or EF11 CD4 Contacts
Z1
Z2
M6C 911 811 311 A2 can cause the shunt trip or shunt close to not work
Previous Circuit Breaker Next Circuit Breaker
Q1
Q3
V1
Q2
V2
V3
Z1
Z5
Z2
Z3
Z4
terminal C2 or A2.
+24 Vdc * Shield
+24 Vdc * Out -
Common Out +
S1 S2 Common
Trip Unit In -
Common
+24 Vdc
In +
Out +
Out -
In +
M2C M6C
In -
or
F2+
F1–
471
E1
E6
M3
E2
E3
E4
E5
M1
M2
T1
T2
T3
T4
24 V * MX1
T3
T1
T2
T4
com
OF
SDE Circuit Breaker XF
Communication com
* Must be two separate isolated 24 Vdc sources. PF Module (BCM)
Note: Fixed-monted circuit breaker does not have CH
cell switches (CE, CD, CT). Micro switches
connected to BCM
53
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
54
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
55
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
56
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
Figure 24: 800–1200 A Masterpact NT 3P Drawout— Table 41: 800–1200 A Masterpact NT Drawout—Pan
Door Cutout Dimensions Dimensions
in.
Dimensions:
mm
57
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
58
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
59
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
60
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
DRAWOUT
FIXED
in.
Dimensions:
mm
61
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
62
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
63
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
64
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
DRAWOUT
FIXED
in.
Dimensions:
mm
65
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
66
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
67
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
Figure 44: 800–1200 A Masterpact NT 4P Fixed— Figure 45: 800–1200 A Masterpact NT Fixed—Pan Dimensions
Door Cutout Dimensions
in.
Dimensions:
mm
68
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NT Dimensional Drawings
in.
Dimensions:
mm
69
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
70
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
in.
Dimensions:
mm
71
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
72
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
73
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
74
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
75
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
76
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
Figure 60: 800–3000 A and 3200 A (H1, H2, H3) Door Cutout
in.
Dimensions:
mm
77
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
78
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
79
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
80
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
81
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
82
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
Figure 71: 800–3200 A and 4000 A (W-Frame) Circuit Breaker Door Cutout
in.
Dimensions:
mm
in.
Dimensions:
mm
83
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
84
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
85
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
86
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
87
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
88
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
89
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
90
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
91
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
92
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Masterpact NW Dimensional Drawings
in.
Dimensions:
mm
in.
Dimensions:
mm
93
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Section 7—Selection
INTRODUCTION95
Overview of Selection Procedure 95
FACTORY-ASSEMBLED CIRCUIT BREAKERS AND SWITCHES 97
T-Frame Selection97
W-Frame Selection98
Y-Frame Selection 100
REQUEST FOR QUOTATION 101
94
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Introduction
1. Select the completely assembled circuit breaker (circuit breaker frame plus trip unit):
— The frame ampere rating required
— The interrupting rating required
— The sensor plug rating required
— The connections
2. Select the trip unit, rating plug, and trip unit options.
3. Select circuit breaker frame options, if required.
4. Select cradle options, if required.
95
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Model Number NT NW NW
Frame type T W Y (wide-construction)
Maximum frame rating (A) 1600 4000 6300
Construction
Drawout • • •
Fixed • • •
Termination
Rotatable rear terminals • • •
Front-connected terminals • • •
96
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
T-Frame Selection
97
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
W-Frame Selection
98
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
800 NW08HF 85 85 85 85
1000 NW10HF 85 85 85 85
1250 NW12HF 85 85 85 85
1600 NW16HF 85 85 85 85
2000 NW20HF 85 85 85 85
2500 NW25HF 85 85 85 85
3200 NW32HF 85 85 85 85
4000 NW40HF 85 85 85 85
1
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a
circuit breaker with an equal continuous current rating.
99
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Y-Frame Selection
5000 NW50HA 85 85 85 85
6300 NW63HA 85 85 85 85
1When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
100
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Choose one: External neutral sensor (CT) Wiring for ready-to-close contact (PF)
Mod. differential ground-fault (MDGF) Wiring for four additional form C auxiliary switches (push-in terminals) or
Source ground return (SGR) 2a+2b auxiliary switches (ring terminals) (OF)
Wiring for eight additional form C auxiliary switches (push-in terminals) (OF)
Micrologic® Trip Unit Accessories
Choose one: Programmable contact module (M2C)
Programmable contact module (M6C) Manufacturing Numbers Provided with Quotation
Modbus® circuit breaker com. module (BCM)
Circuit Breaker:
Modbus® cradle com. module (CCM)
Restraint interface module (RIM) Cradle:
External power supply (24 Vdc) input voltage
Number of power supplies/circuit breaker: 1 or 2
Battery backup quantity: 1 or 2
External voltage sensing
See Delivery Schedule on the next page
Automatic reset (RAR)
101
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Selection
Circuit Breaker: $
Cradle: $ Delivery (from receipt of order)
Total $
Delivery Schedule
Circuit breaker and cradle to be shipped together
Cradle to be shipped prior to circuit breaker
102
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
103
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000
8000
9000
8000
with Adjustable Ground-Fault Pickup and Delay
7000 7000
6000
5000
6000
5000
Characteristic Trip Curve No. 613-1
4000 4000
Ground-Fault I2t OFF and ON
3000 3000
In ≤ 400 A
2000 2000
1500 1500
1000 1000
900 900
800 800
700 700
600 600
500 500
400 400
300 300
200
GROUND-FAULT
200
The time-current curve information is to be used for
150 PICKUP
x In
150 application and coordination purposes only.
100
90
100
90 Curves apply from -30°C to +60°C (-22°F to +140°F)
80 80
70 70 ambient temperature.
60 60
50 50
40 40
30 30
15 15
10 0.4 10
9 9
8 8
7 7
6 6
TIME IN SECONDS
5 5
4 4
0.6 0.8 1.0
3 3
2 2
1.5 1.5
DELAY
SECONDS AT 1 x In
1 1
.9
0.1 .9
0.2
0.4
.8 .8
.7 0.3 .7
ON
0.4
0.3
.6 .6
ON
.5 .5
0.2
.4 .4
DELAY BANDS
I2t ON
0.1
.3 .3
ON
0.3 OFF
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03
(FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
104
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
Figure 92: Micrologic 6.0 A/P/H Trip Units: 400 A < In ≤ 1200 A
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000
7000
8000
7000 Ground-Fault I2t OFF and ON
6000 6000
5000 5000
400 A < In ≤ 1200 A
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800 The time-current curve information is to be used for
700 700
600 600 application and coordination purposes only.
500 500
150 150
100 100
90 90
80
GROUND-FAULT 80
70
PICKUP 70
x In
60 60
50 50
40 40
30
0.2 0.3 0.5 0.7 0.9 30
20 20
15 15
10 10
9 9
8 8
7 7
6
0.4 0.6 0.8 1.0 6
TIME IN SECONDS
5 5
0.4
4 4
ON
3 3
0.2
2 2
ON
1.5 1.5
DELAY
SECONDS AT 1 x In
1 1
.9 0.1 .9
.8 0.2 .8
.7 0.3 .7
0.4
.6 .6
.5 .5
0.3
DELAY BANDS
N
I2t ON
.3 .3
0.3 OFF
0.1
N O
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03 (FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
105
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
AMPERES x 103
Characteristic Trip Curve No. 613-3
.05
.06
.07
.08
.09
.15
1.5
10
.1
.2
.3
.4
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
3000 3000
2000 2000
1500 1500
400 400
ambient temperature.
300 300
200 200
150
GROUND-FAULT 150
PICKUP
1120 A
800 A
x In
100 100
90 90
80 80
70 70
960 A
60 60
50 50
640 A
40 40
30 30
20 20
880 A
15 15
10 10
9 9
8 8
7 7
1040 A
6 6
TIME IN SECONDS
5 5
720 A
4 4
3 3
2 2
1200 A
1.5 1.5
500 A
DELAY
SECONDS AT 1 x In
1 1
.9
0.1 .9
0.4
.8
0.2 .8
0.3
ON
.7 .7
0.2
0.4
.6 .6
ON
.5 .5
0.3
.4 .4
DELAY BANDS
I2t ON
.3 .3
0.1
0.3 OFF
NO
MAXIMUM
.2 .2
UNRESTRAINED
GROUND-FAULT 0.2 OFF
.15 DELAY .15
.1 0.1 OFF .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
GROUND-FAULT
.04 DELAY BANDS .04
I2t OFF
.03 (FIXED DELAY) .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.05
.06
.07
.08
.09
1.5
6
7
8
9
10
106
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
Figure 94: Micrologic 5.0/6.0 A/P/H Trip Units: Long-Time Pickup and Delay, Short-Time Pickup, and I2t OFF Delay
B48095-613-04.ep
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000 8000 Characteristic Trip Curve No. 613-4
7000 7000
6000 6000
2000 2000
The time-current curve information is to be used for
1500 1500
application and coordination purposes only.
1000 1000
900
800
900
800 Curves apply from -30°C to +60°C (-22°F to +140°F)
700 700
600 600 ambient temperature.
500
24 500
16
400 400
300 300
24
normal. The amount of time delay reduction is
15 15
5 5
4 4
2. The end of the curve is determined by the
3 3
interrupting rating of the circuit breaker.
2 2 3. With zone-selective interlocking ON, short-time
1.5 1.5 delay utilized, and no restraining signal, the
1
8
1
maximum unrestrained short-time delay time band
SHORT-TIME 10 SHORT-TIME
.9
.8 PICKUP 6 DELAY I2t OFF
.9
.8 applies regardless of the setting.
.7 x Ir 1.5 2 2.5 (FIXED-TIME DELAY) .7
SECONDS AT 10 x Ir
.6
.5
4 .6
.5
4. Total clearing times shown include the response
.4
3 5 0.4 OFF .4
times of the trip unit, the circuit breaker opening, and
.3 .3
the extinction of the current.
0.3 OFF
.2
MAXIMUM
.2
5. For a withstand circuit breaker, instantaneous can
UNRESTRAINED
.15
SHORT-TIME
DELAY
0.2 OFF
.15
be turned OFF. See trip curve 613-7 for
instantaneous trip curve. See trip curve 613-10 for
0.1 OFF
.1
.09
.1
.09 instantaneous override values.
.08 .08
.07
.06
.07
.06
6. Overload indicator illuminates at 100%.
.05 .05
.04 .04
.03 .03
0
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
107
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
Figure 95: Micrologic 5.0/6.0 A/P/H Trip Units: Short-Time Pickup and I2t ON Delay
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In) Micrologic 5.0/6.0 A/P/H Trip Units
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000
9000
10000
9000
Characteristic Trip Curve No. 613-5
8000 8000
7000
6000
7000
6000
Short-Time Pickup and I2t ON Delay
5000 5000
4000 4000
3000 3000
2000 2000
1500 1500
1000 1000
900 900
800 800 The time-current curve information is to be used for
700 700
600 600 application and coordination purposes only.
500 500
150 150
SHORT-TIME
100
90
PICKUP
x Ir
100
90 NOTE:
80 80
70
1.5 2 2.5 6 8 10 70
60 60 1. There is a thermal-imaging effect that can act to
50 50
shorten the long-time delay. The thermal-imaging
40 40
3 4 5 effect comes into play if a current above the long-time
30 30
delay pickup value exists for a time and then is cleared
20 20 by the tripping of a downstream device or the circuit
15 15 breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
10 10
9
8
9
8
amount of time delay reduction is inverse to the
7
6
7
6
amount of time that has elapsed since the previous
TIME IN SECONDS
0.4
4 4
between overloads to completely reset thermal-
3 3
imaging.
0.2
ON
1.5 1.5
0.3
ON
1 1
.9 .9
.8 .8 utilized, and no restraining signal, the maximum
.7 .7
.6 .6 unrestrained short-time delay time band applies
.5
0.4 ON
.5
regardless of the setting.
.4 .4
SHORT-TIME
.3
DELAY I2t ON .3
4. Total clearing times shown include the response times
SECONDS AT 10 x Ir 0.3 ON
MAXIMUM
of the trip unit, the circuit breaker opening, and the
.2
UNRESTRAINED
SHORT-TIME 0.2 ON
.2
extinction of current.
.15 DELAY .15
5. For withstand circuit breaker, instantaneous can be
.1
.09
0.1 ON .1
.09
turned OFF. See trip curve 613-7 for instantaneous trip
.08
.07
.08
.07
curve. See trip curve 613-10 for instantaneous
.06
.05
.06
.05
override values.
.04 .04 6. See trip curve 613-4 for long-time pickup and delay trip
.03 .03 curve.
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
108
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
Figure 96: Micrologic 5.0/6.0 Trip Units: Instantaneous Pickup, 2x to 15x and OFF
08/7,3/(62)6(16255$7,1*,Q
MICROLOGIC® 5.0/6.0 A/P/H TRIP UNIT
CHARACTERISTIC TRIP CURVE NO. 613-7
Instantaneous Pickup
2x–15x and OFF
The time-current curve information is to be used
for application and coordination purposes only.
Curves apply from -30° to +60°C ambient
temperature.
Notes:
1. The end of the curve is determined by the
interrupting rating of the circuit breaker.
2. Total clearing times shown include the
response times of the trip unit, the circuit
breaker opening, and the extinction of the
current.
3. The instantaneous region of the trip curve
shows maximum total clearing times. Actual
clearing times in this region can vary
depending on the circuit breaker mechanism
,167$17$1(286
design and other factors. The actual clearing
3,&.83
[,Q
time can be considerably faster than indicated.
Contact your local Sales Office for additional
information.
4. For a withstand circuit breaker, instantaneous
can be turned OFF. See 613-7 for
10 x
instantaneous trip curve. See 613-10 for
instantaneous override values.
5. See 613-4 and 613-5 for long-time pickup,
long-time delay, short-time pickup, and short-
time delay trip curves.
7,0(,16(&21'6
2x 3x 4x 6x 8x 12 x 15 x
&<&/(
&<&/(
08/7,3/(62)6(16255$7,1*,Q
109
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
100
1.5
10
15
20
30
40
50
60
70
80
90
.5
.6
.7
.8
.9
1
6
7
8
9
10000 10000
9000 9000
8000 8000 Characteristic Trip Curve No. 613-9
7000 7000
6000 6000
2000 2000
The time-current curve information is to be used for
1500 1500
application and coordination purposes only.
1000
1000
900 900 Curves apply from -30°C to +60°C (-22°F to +140°F)
800 800
700 700 ambient temperature.
600 600
24 500
500
16
400 400
NOTE:
300 300
50 8
60
50
breaker itself. A subsequent overload will cause the
40 4 40 circuit breaker to trip in a shorter time than normal. The
30
2 30 amount of time delay reduction is inverse to the
1
.5 amount of time that has elapsed since the previous
20 20
24
overload. Approximately twenty minutes is required
15 15
5 5
4 4
3. Total clearing times shown include the response times
3 3
of the trip unit, the circuit breaker opening, and the
2 2 extinction of current.
1.5 1.5
4. Overload indicator illuminates at 100%.
8
1 1
.9 SHORT-TIME 10 .9
.8 PICKUP 6 .8
.7 x Ir 1.5 2 2.5 .7
.6 .6
4
.5 .5
.4 3 5 .4
.3 .3
.2 .2
.15 .15
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
.04 .04
.03 .03
.02 .02
1 CYCLE
.015 .015
.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006
.005 .005
1
1.5
6
7
8
9
10
.5
.6
.7
.8
.9
15
20
30
40
50
60
70
80
90
100
110
© 2006–2008 Schneider Electric All Rights Reserved 04/2008
Masterpact® NT and NW Universal Power Circuit Breakers Certified to ABS-NVR
Trip Curves
Figure 98: Micrologic 2.0/5.0/6.0 A/P/H Trip Unit Instantaneous Override Values
111
04/2008 © 2006–2008 Schneider Electric All Rights Reserved
Schneider Electric USA
3700 Sixth St SW
Cedar Rapids, IA 52404 USA
1-888-Square D
1-888-778-2733 0613CT0601R4/08 © 2006–2008 Schneider Electric All Rights Reserved
www.us.SquareD.com Replaces 0613CT0601R1/07 Dated 11/2007
04/2008