Process Control
Process Control
Process Control
Process Control
Most industrial processes require that certain variables such as
temperature, flow, level or pressure, remain at or near some reference value
(setpoint). Closed-loop control is used to achieve this. The process controller
looks at a signal representing the process value, compares it to the desired
setpoint and acts on the process to minimize the difference (error).
The method used by the controller to correct the error is the control mode.
The four most popular control modes are on/off, proportional, integral
and derivative.
Control Modes
On /off control activates an output until the measured value reaches the
reference value. A common example is the household thermostat. No control
action takes place until the measured value deviates from the setpoint by a
minimum amount (deadband). The output then goes from full off to full on,
turning off again when the setpoint is reached. While simple and low cost,
this mode of control has a tendency to overshoot the desired value. A digital
panel meter with relay output and adjustable setpoint can be used for on-off
process control.
A more refined control method is proportional control. Here the difference
between the setpoint and measured value generates a continuous, linear
control output. The control gain K sets the system response as a function
of time:
Output(t) = K [Setpoint - Measured(t)] + Bias.
The bias term creates a non-zero output when the error term is driven to zero.
This allows bi-directional control. The proportional band is the span of the
measured variable that causes a full range output.
The higher the gain,
the more the output
will change for a given
change in
measurement or
setpoint. High K
(narrow band)
provides more precise
control, but can create
stability problems.
Low K (wide band)
controls over a wider
input span, but may
be slower to respond. In proportional control, if system loading requires a
shift in operating point, a
difference between the
measurement and set point
will exist at equilibrium. The
higher the system gain, the
lower the offset will be for a
given load change.
Controllers with reset
(integral) action will
automatically recenter the
proportional band around
the offset bias level. An integral mode controller responds to the integral of
the difference between the setpoint and measured value. The adjustable
parameter for integral control is the integral time T, or the reset rate 1/T.
The integral mode is sometimes used as a single mode of control but is more
181
WESCHLER INSTRUMENTS www.weschler.com 800-903-9870 fax: 800-903-9590 info@weschler.com