Split air conditioner

Wall mounted Type


Service manual
MUP-09-HI

AUS-07H53R010Px

MUP-12HI
AUS-09H53R010Px

AUS-09H53R150Px
AUS-12H53R130Px
AUS-12H53R150Px
(X=1,2,3,........)

CONTENTS
Contents

Safety precautions

Installation

Block diagram

11

Trouble shooting

12

Fault diagnosis by symptom

13

Control specification

17

To disassemble mechanical parts

23

Exploded views and parts list

27

Wiring diagrams

35
31

SAFETY PRECAUTIONS
The following safety precautions must be taken when using your air
conditioner.
1. Warning: Prior to repair, disconnect the power cord.
2. Use proper parts: use only exact replacement parts. (Also, we recommend replacing parts rather
than repairing them.)
3. Use the proper tools: use the proper tools and test equipment, and know how to use them. Using
defective tools or test equipment may cause problems later-intermittent contact, for example.
4. Power cord: prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in
malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance.
Procedure: prior to applying power, measure the resistance between the power cord and the ground
terminal. The resistance must be greater than 30 megohms.
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surrounding area.

INSTALLATION
Selecting area for installation
Select an area for installation that is suitable to the customers needs.

1 Location of indoor unit


Keep the air inlet and outlet at a far distance from the blockage.
Keep the height distance between the indoor and outdoor unit at most 5m.
Mount on the wall solid enough to bear the weight of the unit and not cause any shake.
Avoid direct sunshine.
A place easy for condensate drain and easy for connecting with the outdoor unit.
Keep a far distance away from the fluorescent lamp, it may influence the operation of remote controller.
Keep at least 1m away from the TV radio and other home appliances.

2 Location of outdoor unit


A place solid enough to bear the weight of the unit and not cause any shake.
Good ventilation, less dust, far from direct rain and sunshine.
A place where the air discharged out of the outdoor unit or the operation noise will not annoy your
neighbours.
No blockage near the outdoor unit.
Avoid places close to inflammable gas leakage.

Caution:
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including area
near machines). Salty area such as coastal areas, areas where sulfuric gas is present such as hot spring
areas. Contact your dealer for advice.

INSTALLATION
Installation diagram of indoor unit and outdoor unit
Confirm the installation position by the mark of the indoor mounting plate.

above

105m

155mm
above 250mm

above

Note Different models have different mounting plates, the


installing charts of this book are presented just for the purpose
of illustration, please take the real objects as reference.

Above 20mm

The copper pipe can be led


from back, right, underside,
or left-back side.

back
right

front

left
back
Underside Left-back

above 500mm

While installing the pipeline on the


thin armor plate or on the wall of
metal mesh, you should use the
wooden board to clamp between
the wall and the pipeline, or wrap
up the pipeline with 7-8 layers of
insulating plastic tape.

abov

mm
300
em
0vm
a1b0o

e 30

0mm

00m

ve 5

abo

Notice: do not elevate the


drain hose.

abo

ve 5

00m

Cover connecting pipe with


adiabatic material.

Sponge plastic adiabatic


material with the
thickness of 8mm.

INSTALLATION
1 Securing the mounting plate and drill on the wall
Note:Different models have different mounting plates, the installing charts of this book are presented
just for the purpose of illustration, please take the real objects as reference.
Secure the mounting plate
The mounting plate should be attached to the structural part of wall (post etc).

fasten string at the central hole

at least 250mm
155mm or more
from sidewall

105mm or more
from sidewall
mounting plate
Tapping screw
ST4 25(5)

plumb

The holes at solid arrow position must be secured to avoid the shake of mounting plate.
When the expansion bolts are used, two holes ( 11 20 or 11 26 ) that the distance
between them is 450mm should be adopted.

NOTICE:

Drill on the wall

Pipe hole
Center of hole( 65mm)

Center of hole( 65mm)


Operation

1.Confirm the position of the wall hole according to the chart (If it need to orientat a hole on the left
side of the mounting plate, please refer to the method of orientating the right wall hole in the above chart).
2.Use the aiguille to drill a hole with a diameter of 65mm .

INSTALLATION
2 Wiring
Open the front grille;
Remove the screw from electrical box cover, pull the
Screw
electrical box cover away from the unit and set aside.
Remove the screw from fastener, pull the fastener
away from the unit and set aside.
Connect the cable.
Indoor unit terminal
Replace the fastener and electrical box cover.

Diagram

Connecting cable

NOTE:
The appliance shall be installed in accordance with national wiring regulations.
The appliance must not be installed in the laundry.
The appliance must be installed 2.3m above the floor.
The appliance must be positioned so that the plug is accessible.
For some models whose cooling capacity are above 4600W (17000BTU/h),
an all-pole disconnection device which has at least 3mm separation distance in
all pole and a residual current device(RCD)with the rating of above 10mA shall
be incorporated in the fixed wiring according to the national rule.

3 Installation of the drain hose


Liquid pipe

NOTE:
The drain hose must be arranged beneath the copper pipe.
The drain hose must not be hunched or twisted.
While wrapping up the drain hose, do not pull it.
The drain hose through the room must be wrapped up by the
thermal insulation materials.
The copper pipe and the drain hose must be wrapped up by felt
strip. Adiabatic pad should be used at where the pipe contacts
the wall.

gaspipe

Drain hose
Adiabatic
underlay
felt

ROUTE OF PIPE
If pipe comes out of the right side of the indoor unit, cut part
1 of the unit;
If pipe comes out of the lower-right side of the indoor unit, cut
part 2 of the unit;
If pipe comes out of the left side of the indoor unit, cut part 3
of the unit.

REFIT OF DRAIN HOSE


If pipe comes out of the left side of the indoor unit, the drain hose
must be refitted, otherwise water leakage may occur.
Refit methods: Interchange the position of drain hose and drain
rubber plug.
Clearance is not allowed after refit, it would lead to water leakage.

drain hose

Drain rubber
plug

INSTALLATION
Arrangement of the drain hose
To drain the condensate water easily, the drain hose should be declined downwards.
The following 5 arrangement methods are incorrect.
Decline
downward

Decline
downward

Dip hose
into water

Standing water
air

Water
leak
(Fig. 1)

Water
leak
(Fig. 2)

50mm or less
above floor

Water
leak
(Fig. 5)

(Fig. 4)

(Fig. 3)

Drain hose

If you find the drain hose not long enough to connect with the indoor
unit, you can extend it with the hoses in the accessory box.
The drain hose through the room must be wrapped up with the special
adiabatic material.

4 Installation of the indoor unit

Hose(ID 15cm)
PVC hard

Indoor unit

Let pipe go through the wall hole and attach the indoor
unit to the mounting plate.(Press the rib of indoor unit
inside the hook of the mounting plate.)

the mounting plate


Bottom

the rib of indoor unit

5 Pipe Connection
The number of bent position of the pipe in the indoor unit should not exceed 10.
The number of bent position of the pipe in the indoor unit and the outdoor unit should not exceed 15.
The radius of bent position should be more than 10cm.
Please break the evaporator craft tube with pincers before connecting. After exhausting the inside air,
use the wrench to twist down the nut of connecting tube of the evaporator.
Put some seal oil to cover the joint and the flare.
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench.
Attention:
Do not exhaust the inside air just by loosing the nut since there is the air of certain pressure
inside the tube of indoor unit. Please do not make extra effort for fear of damaging the flare.
DIAMETER OF PIPE
6.35mm ( 1/4 )
9.52mm ( 3/8 )

TORQUE(N m)
13.7---17.6
34.3---41.2

12.7mm ( 1/2 )
15.88mm ( 5/8 )

49.0---56.4
73.0---78.0

Evaporator
craft tube

6 Wall sealing and Pipe fastening


Use putty to seal the wall hole.
Use clamp (pipe fastener) to secure the pipe at specified position.
get rid of unwanted part
clamp

seal with putty


secure the connecting
pipe with clamp

Indoor unit

screw

INSTALLATION
Installation diagram of indoor unit and outdoor unit

1 Wiring
Outdoor unit terminal

Outdoor unit terminal

Connecting
cable

Connecting
cable

or

Wiring For Above 6000W Model (Above 21000BTU/h Model)


1 Remove the self-tapping screws (2 pcs)
on the maintenance board and take out the
maintenance board.

The cable wire can be led from the back hole


of the piping hole or ejecting hole.
Please utilize outdoor pipe support when
the cable wire is led from the backside.

Terminal board
Fix the cable wire
with anchor cable
Maintenance
board
Piping cover
2 Loosen the self-tapping screws (2 pcs) on
the fixing clip to loosen the fixing clip.
3 Loosen the fixing screw of the wire terminal
board, pass the power wire and signal wire
through the fixing clip. Then firmly fix the
power wire and signal wire on the terminal
board with the fixing screw. (Earth wire
must be connected firmly.)

Outdoor pipe support


(Outdoor pipe support is not required
when leading the cable wire from other places).
4 Tighten the self-tapping screw on the fixing clip.
5 Install the maintenance board. After the pipes
and cable wire are installed, please seal the
sponge block as per drawing indication.

Maintenance
board

Back wiring

Piping cover
Right wiring
Piping cover Ejecting hole

Sponge

INSTALLATION
Notice:
2

If the signal wire has to be bought separately, choose electric wire above 0.75mm.
If the interconnection cord for power supply has to be replaced, please see the
following table for reference.

SPECS (Interconnection cord)

MODEL

1.0mm

2700W(10000BTU/h)
3000W(11000BTU/h) -4000W(15000BTU/h)
4500W(18000BTU/h) -8000W(28000BTU/h)

1.5mm
2.5mm

2
2
2

WARNING:
Please take the electric circuit diagram attached to the indoor/outdoor units as major
reference while installing.
The power wire and signal wire between the indoor/outdoor units must be connected
one by one as per corresponding number on the wiring terminal board.
The connecting cables must be clipped together.
Special cable must be used to connect indoor unit and outdoor unit. It should be ensured
that the terminals are not influenced by external force. Poor connection may cause fire.
The electric box cover must be mounted and secured in position, otherwise fire or electrical
shock may occur because of dust or moisture.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away
from the copper tube.
All the models shall be connected with the mains which has system impedance limitations.
While installing the unit, please see the following table for impedance information or
consult with the supply authority.
R410A
series

3500W (12000BTU/h)
5100W (18000BTU/h)
6800W (18000BTU/h)

0.219
0.186
0.124

INSTALLATION
2 Installation of the drain joint(only for heat pump type)
Insert the outdoor double-channel drain joint in one of the
bottom holes of the suitable size then connect drain hose
and joint together.

Bottom
Double-channel
drain joint

Drain hose

3 Joint of the connecting pipe


Put some seal oil to cover the joint and the flare.
Align the centre of joint in line with that of flare and tighten the nut of connecting pipe
with wrench. ( Adjust the torque by the same method of connecting pipe for indoor unit.)

4 Air exhausting
Screw down the cap of both gas shut-off valve and
liquid shut-off valve as well as the nut of service port.
Use Allen wrench to turn the valve cork of liquid side
at 90 counter-clockwise, and close it after 10 seconds.
Use soapy water to check the gas leakage especially
at all joint. If there is no gas leakage, please turn the
valve cork of liquid side at 90 counter-clockwise again.
Press the cork of service port at gas shut-off valve, 10
seconds later, when you see foggy gas discharged, that
means inner air is exhausted out.

liquid connecting pipe


liquid shut-off valve

allen wrench
gas connecting
pipe

gas shut-off
valve

valve nuts
service port
service port cap

Use Allen wrench to turn the valve cork of both liquid


shut-off valve and gas shut-off valve counter-clockwise
until they are completely open and then replace the
valve caps and tighten them.

5 Process of flared tube


Use the pipe cutter to cut off the broken part of flare.
Remove burrs at the cut of the flare.

Copper pipe

Insert a nut into the connecting pipe and do flaring


with specified flaring tools, reamers for example.
Remove burrs at the cut of the flare.

Outer diameter
6.35mm ( 1/4 )
9.52mm ( 3/8

12.7mm ( 1/2 )
15.88mm(5/8 )

90

Burr
A(mm)
2.0--2.5
3.0--3.5
3.5--4.0

4.0--4.5

Check the quality of flaring technique.

Oblique

Roughness

Reamer

Burr

INSTALLATION
6 Adding refrigerant
If the connecting pipe is longer than 7 metres, add refrigerant as needed. (Cool only type) added
amount A=(Lm-7m) 15g/m ; (Heat pump type)added amount A= (Lm-7m)

50g/m. ( A: amount

of added refrigerant, L: the length of connecting pipe)

The length of connecting pipe (m)

10

(Cool only type)added amount (g)

15

30

45

(Heat pump type)added amount (g)

50

100

150

Exhaust the air as the above-mentioned method.

Manifold gauge

Screw the gas shut-off valve to close, connect


Low pressure
valve

charging hose(low pressure) to the service valve


and then open gas shut-off valve again.
Set the unit to cool operation mode.

Pressure meter
High pressure
valve

Charging line

Connect the refrigerant bottle to the charging hose


and then convert it.
Fill in liquid refrigerant as the above table.

Service port

Stop operation of the air conditioner.


Disconnect the manifold gauge after turning off the
shut-off valve, and then open gas shut-off valve again.
Tighten nuts and caps of each valve.

7 Relocation of the air conditioner.


Refer to this procedure when the unit is relocated.
1. Carry out the pump down procedure.
2. Remove the power cord.
3. Disconnect the assembly cable from the indoor and outdoor units.
4. Remove the flare nut connecting the indoor unit and the pipe.
At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
5. Disconnect the pipe connected to the outdoor unit.
6. Make sure you do not bend the connection pipes in the middle and store together with the cables.
7. Move the indoor and outdoor units to a new location.
8. Remove the mounting plate for the indoor unit and move it to a new location.

10

INSTALLATION
8 Operation test
Before test operation, wiring safety inspection must be carried out carefully again.
1. Emergency switch operation: Every press of emergency switch, the
air conditioner runs as in the following order:
Cool only type: Cool

Shut off

Heat pump type: Cool

Heat

Shut off

2. Remote controller operation: If the indoor unit sounds like Di, Di when pressing I/O button,
that indicates the air conditioner is under the operation of remote controller. After that, press
every button to test their functions.
3.Check switch operation: Open the front grille and press the check button. Switch on the power
source and then the operation test is activated. If the indicator lamps light up at first and then
go out in succession or the LED window of the indoor unit illuminates at first and then goes out,
the system is under normal operation. If one of the indicator lamps is flashing at all times, or
failure codes are displayed on the LED window of the indoor unit, the system has something
wrong and please check malfunction immediately.

BLOCK DIAGRAM
Refrigerant Cycle Block Diagram
INDOOR UNIT

OUTDOOR UNIT
Capillary tube
Check valve
2-way valve

Capillary tube

Cross fan

Heat
exchanger
(Evaporator)

Heat
exchanger
(Condenser)

Propeller fan

Liquid side

Gas side
3-way valve

Accumulator
Compressor

11

4-way valve
Cooling
Heating
Gas leak check point

TROUBLE SHOOTING
Items to be checked first
1. Is the voltage of the power correct?
The input voltage shall be rating voltage 10%.
The air conditioner may not operate properly if the voltage is out of this range.
2. Is the link cable connecting the indoor unit and the outdoor unit linked properly?
Please refer to the wiring diagram
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
3. When a problem occurs due to the contents illustrated in the table below, it is symptom not related to the
malfunction of the air conditioner.
Operation of air conditioner

Explanation

In COOL operation mode, the compressor does not operate


at a room temperature higher than the setting temperature
that the indoor fan should operate.
In a HEAT operation mode, the compressor does not
operate at a room temperature lower than the setting
temperature that indoor fan should operate.

It happens after a delay of 3 minutes when the compressor is


reoperated. The same phenomenon occurs when a power is on.
As a phenomenon that the compressor is reoperated after a
delay of 3 minutes, the indoor fan is adjusted automatically with
reference to a temperature of the air blow.

Fan speed setting is not allowed in AUTO or DRY mode.

The speed of the indoor fan is set to low in DRY mode.


Fan speed of 3 steps is selected automatically in AUTO mode.

Compressor stops operation intermittently in DRY mode.

Compressor operation is automatically controlled in DRY mode


depending on the room temperature and humidity.

Compressor of the outdoor unit is operating although it is


turned off in HEAT mode.

When the unit is turned off while de-ice is activated, the


compressor continues operation for up to 10 minutes(maximum)
until the deice is completed.

Timer indicator lamp lights up and the air conditioner does


not operate.

Timer is being activated and the unit is in ready mode.


The unit operates normally if the timer operation is cancelled.

The compressor and indoor fan stop intermittently in HEAT


mode.

The compressor and indoor fan stop intermittently if room


temperature exceeds a setting temperature in order to protect
the compressor from overheated air in HEAT mode.

Indoor fan and outdoor fan stop intermittently in HEAT mode.

The compressor stops intermittently in COOL mode or DRY


mode, and fan speed of the indoor unit decreases.

The compressor operates in a reverse cycle to remove exterior


ice in HEAT mode, and indoor fan and outdoor fan do not
operate intermittently for within 20% of the total heat operation.
The compressor stops intermittently or the fan speed of the
indoor unit decreases to prevent inside/outside air frozen
depending on the inside/outside air temperature.

SELF DIAGNOSIS FUNCTION


Our company provides the end-users with thoughtful services by installing various diagnostic systems to
indicate the following irregular performances.

Check code

Diagnosis of malfunction

FAULT F6

PG motor faults

FAULT F7

Indoor TEMP sensor faults

FAULT F8

Indoor coil pipe TEMP sensor faults

FAULT F9

Outdoor coil pipe TEMP sensor faults

RUN indicator lamp

SLEEP indicator lamp

TIMER indicator lamp

Diagnosis of malfunction
Indoor coil pipe TEMP sensor faults
Indoor TEMP sensor faults
Outdoor coil pipe TEMP sensor faults
PG motor faults

Remark:

lamp ON

lamp OFF

12

lamp FLASH

FAULT DIAGNOSIS BY SYMPTOM


Fan motor or its capacitor faults.
Fan motor
error

Loose connection or badly contact.

No cooling

Control circuit error.


Voltage may appear a little lower or higher.
compressor
does not operate

Loose or wrong connection.


Compressor faults or jumps for overloading.

No cooling
effect at all

Control circuit error.


Leakage of
refrigerant

Recharge the refrigerant at leaking place.


The capillary, pipeline are blocked or the valve
is not open or the connecting tube is folded flat.

Block of the cooling


system

Some leakage in the valve.


Insufficient
refrigerant

Some cracks, welding failure in the system.


Extra fluorin is added during mounting.

Poor cooling
efficiency

No periodical cleaning.

Air filter is
blocked

Accumulated lampblack, dust or contaminated


ambient environment.
Mounting location is not suitable, such as near the wall.

Poor efficiency of
heat dissipating on
the outdoor unit

Air outlet is blocked or accumulated lampblack


or dust is attached to the vane.
The outdoor unit gets exposed to the sun for too
long period.

Too high ambient


temperature

Not for residential use.


Air conditioning burden
is not adequate for the
room

The doors and windows are not closed well;


too weak of input cooling power or too many
heat resources in the room.

Low airflow volume

Low fan motor frequency or capacitor is not


functional.
Low fan speed or the fan motor faults.

The four-way
valve error

Blockage in
the system

The distributing air of the four-way valve may have mixed


together; the valve core or solenoid valve faults.
The valve is not completely open; the capillary or
Pipeline is half blocked.
Connecting tube is folded flat.

13

FAULT DIAGNOSIS BY SYMPTOM


Fan motor or its capacitor faults.
Fan motor
error

Loose connection or badly contact.

No heating

Control circuit error.


Voltage may appear a little lower or higher.
compressor
does not operate

Loose or wrong connection.


Compressor faults or jumps for overloading.

No heating
effect at all

Control circuit error.


Leakage of
refrigerant

Recharge the refrigerant at leaking place.

Block of the cooling


system

The capillary, pipeline are blocked or the valve


is not open or the connecting tube is folded flat.

The four-way valve


or solenoid valve faults.

The four-way valve did not commutate or the


distributing air of the four-way valve may
have mixed together.
Some leakage in the valve.

Insufficient
refrigerant

Some cracks, welding failure in the system.


Extra fluorin is added during mounting.

Poor heating
efficiency

No periodical cleaning.

Air filter is
blocked

contaminated ambient environment.

Too low ambient


temperature

Below 0 .

Too thick frost


generated on the
condenser.

The condenser does not defrost, no smooth air


circulation.

Extra refrigerant or
mixing air in the system

Discharge the redundant refrigerator recharge


the refrigerant after vacuum extraction.

Air conditioning burden


is not adequate for the
room

The doors and windows are not closed well;


too weak of input cooling/heating power.

The condenser is too dirty

Accumulated lampblack or dust is attached


to the vane.
Not satisfy the conditions for electric heater
running.

The electric heater is


not working

Plug cords may be loose.


Low fan motor frequency or capacitor is not
functional.

Low airflow volume

Low fan speed or the fan motor faults.


The four-way
valve error

Blockage in
the system

The distributing air of the four-way valve may have mixed


together; the valve core or solenoid valve faults.
The valve is not completely open; the capillary or
Pipeline is half blocked.
Connecting tube is folded flat.

14

FAULT DIAGNOSIS BY SYMPTOM


Fixing bolts somewhere may loose or rub, some
spare parts may not match very well.

Collision sound
of the machine
Noisy

Flowing sound
of the liquid

Refrigerant circulation or pressure change of


refrigerant while switch on/off.

Sound of the
running fan motor

Vane imbalance or distortion, rupture; loose


screw of vane.

Noise from
indoor unit

Plastic pieces deform due to expansion when


hot and shrink when cold. Or some spare parts
may not match very well.

Sound of plastic
pieces rubbing or
deforming

Noise from
Outdoor unit

Collision sound
of the machine

Collision of the pipeline, fixing screws loose or


deform caused by rubbing.

Oscillation
sound

Inappropriate installation method; the unit


does not match with the installation kit very well
or the compressor quivers acutely.

Sound of running
fan motor

Vane imbalance or distortion.

Sound made by
cooling operation

Refrigerant circulation or vane distortion.

Something wrong with the compressor, such as


oil shortage, valve slice distortion.

Sound of running
compressor

The unit does not match with the installation kit


very well
Resonance sound
The whole unit resonates thedoor and window.

Noise from
the whole
unit

Collision sound of the


machine

Collision of the pipeline, fixing screws loose or


plastic pieces deform.

Sound made by
compressor or motor

The compressor or motor makes abnormal noise.

Flowing sound of
condensed water

Condensed water is attached to the vane.

Sound of running fan


motor

Vane imbalance or distortion.

15

FAULT DIAGNOSIS BY SYMPTOM


Switching on the air conditioner

Junction wire looses and collides with the outer


cover.

The current leakage switch


jumps to turn off

Degraded capability of wire insulation.


Insulation capability of
some components has
lowered.

Check the resistance


of every component
by multimeter

Water comes into the plug or electric components.

The fuse is blown


or air limit switch
jumps to turn off

Is the voltage
of power supply lower
than 15% of rated voltage
(220V)?

No

Yes

The voltage is low,


please add manostat.

Short circuit in the


electric wire or
connection wire.

Short circuit
somewhere.

Partially short circuit in


some components.

Yes

Check as the above


-mentioned method.

Fuse capacity
is adequate or not?
No

Replace with adequate


fuse.

Strong circuit breaks


the circulation.

Without any
response

Check whether
the receptacle has
power or not.

The transformer faults.

The main control board


faults.
Power supply error

16

CONTROL SPECIFICATION

ABBREVIATION
ST: Setting Temperature
PT: Indoor coil Pipe Temperature
RT: Room Temperature
OT: Outdoor coil pipe temperature
OFAN: Outdoor fan
IFAN: Indoor fan
COMP: Compressor

OPERATION OF MAIN BOARD


COOL MODE
The ST at cool mode is adjustable within16 -31 .
When RT ST, both the compressor and the outdoor fan start;
When RT<ST-1 , the compressor stops and 18 seconds later, the outdoor fan will stop.
But the indoor fan keeps running at predetermined speed.
Once turning on the unit while set at cool mode, the indoor fan immediately runs at
predetermined speed; if all the conditions meet with the requirement of compressor
operation, both the outdoor fan and compressor start running. If not, either the outdoor
fan or compressor could start.
The four-way valve keeps being off all the time at cool mode.

Condensate dew prevention


If the horizontal air flow louver is set at low angle on COOL mode, after a while, it will auto swing to
its maximum angel for system protection. 3 minutes later, the horizontal air flow louver will resume
to its original position.

Anti-ice function
When PT=2 , the compressor does not stop and indoor fan runs at high speed.
When PT -1
high speed.

for 1 minute, the compressor and outdoor fan stop and indoor fan runs at

When PT 8 for 5 minutes, anti-ice protection deactivates, both the compressor and the
outdoor fan start operation.

8
2
-1
5 mins

OFAN

ON

ON
OFF

COMP

ON

3 mins

ON

OFF
High speed
IFAN

Set speed

Set speed

17

CONTROL SPECIFICATION
HEAT MODE
If the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will
take approximately 3 minutes for the compressor to start.
The ST at heat mode is adjustable within16 -31 .
When RT ST, the compressor stops; when RT<ST-1 , the compressor starts.
Once turning on the unit while set at heat mode, if all the conditions meet with the
requirement of compressor operation, the four-way valve gets charged and 8 seconds later,
the compressor and outdoor fan start running.

Strong-wing prevention :
A.PT<27,the indoor fan stops running, the swing louver cannot be controlled by the remote
controller.
B.34>PT 27,the indoor fan runs at low speed, the sweep louver erects.
C.PT

34,the indoor fan and the swing louver can be controlled normally.

Heat overload protection:


For 7000BTU/h Model, when PT 47 , the outdoor fan stops; when PT 42 , the outdoor
fan starts; when PT 60 , the compressor stops.
For 9000BTU/h Model, when PT 50 , the outdoor fan stops; when PT 47 , the outdoor
fan starts; when PT 63 , the compressor stops.
For 9000 BTU/h Model, when PT 55 , the outdoor fan stops; when Pt 50 , the outdoor
fan starts; when PT 63 , the compressor stops.

Deice control:
Conditions for activating deice:
a. The working hours of compressor accumulates to be 40 minutes.
b. When OT -4 for 1 minute.
Conditions for terminating deice:
a. When OT 15 for 1 minute.
b. Over 10 minutes of deicing operation.

Electric-heat control:
Conditions for initiating electric-heat function:
a. RT 23 ; b. RT+3
ST; c. The indoor fan runs;
d. Turn on the electric-heat key; e. PT<50
Conditions for terminating electric-heat function:
a. PT 50 ; b. RT 26 ; c. The indoor fan stops running;
d. Turn off the electric-heat key; e. Mode change.
Conditions for terminating electric-heat function:
a. PT 50 ; b. RT 26 ; c. The indoor fan stops running;
d. Turn off the electric-heat key; e. Mode change.
15
OT

-4
COMP

ON
OFF

OFAN

ON
OFF

4-way
valve

ON
OFF
30S

30S

15S

TIME
10 minutes at most

18

15S

CONTROL SPECIFICATION
DRY MODE
In this mode, the air conditioner automatically sets the room temperature and this temperature
is incontrollable by remote controller. The initial ST =RT-2 .
Control during dry mode:
a. When RT<15 , dry mode is not available; when RT 15 , the compressor intermittently
runs under the influence of TS and RT.
b. When RT 23 , if RT ST, the compressor runs intermittently as this:
Run for 8 minutes
Stop for 3 minutes
If RT<ST, the compressor runs intermittently as this:
Stop for 4 minutes
Run for 1 minute

c. When RT<23 , if RT ST, the compressor runs intermittently as this:


Run for 2 minutes
Stop for 3 minutes
If RT<ST, the compressor runs intermittently as this:
Stop for 4 minutes
Run for 1 minute

d. In this mode, the indoor fan keeps running at low speed with the same pace as the compressor,
and this speed can not be controlled by remote controller.

AUTO MODE
In this mode, the air conditioner can automatically adjust the room temperature to decide the most
suitable temperature. At the start of operation, the unit will automatically select the operation mode
according to the room temperature. The following table shows the conditions which are set at start up.
Room
Temperature (RT)
RT 26
26
RT 25
25
RT 23
RT 23

Heat pump type

Cool only type


Mode
Cool
Dry

Initial Setting Temperature


24
RT-2
RT-2
21

Mode
Cool
Dry
Heat

Initial Setting Temperature


24
RT-2
RT-2
26

Auto mode entering


a. Once some operation mode is determined, it can not be changed even if the RT has altered.
b. You can change the operation mode by remote controller.
If restart within 2 hours, the unit will resume the same operation mode as before.
If restart after 2 hours, the unit will select the operation mode according to the initial room temperature.
At auto mode the ST can only be set + or - 2

of the RT.

19

CONTROL SPECIFICATION
FAN MODE
In this mode, the outdoor unit does not operate. The indoor fan alone operates.
Press UP & DOWN SWING button or LEFT & RIGHT SWING button to change air flow direction.
Press FAN SPEED button to change the fan speed of indoor unit.

LIGHT-WAVE MODE (only applied to light-wave series)


Every press of LIGHT-WAVE button, the air conditioner will cycle in the order of enter/quit light-wave
mode. Once entering the light-wave mode, the light-wave icon will light up on display panel of the
indoor unit and the air conditioner will judge whether to connect the light-wave tube by ambient
temperature.

TURBO function (only applied to turbo series)


This function will make the air conditioner heat or cool quickly and during this period, the noise of the
air conditioner will increase. Turbo function can be only started up in heat or cool mode(turbo heating
or turbo cooling) otherwise, it can not be started up. When the air conditioner is in cool or heat mode,
press turbo button to initiate turbo function, the remote controller displays TURBO and the icon of
fan speed is
,meanwhile the air conditioner cannot be controlled by the remote controller. Press
turbo button again or start up sleep mode or transit modes to exit turbo function. After exiting turbo
function the fan runs at low speed.

FRESH AIR function (only applied to fresh air series)


When the air conditioner is on, press fresh air button to initiate or stop fresh air function. While this function
is initiated the remote controller displays FRESH AIR ,meanwhile the fan starts to run, the letter
FRESH AIR extinguishes and the fan stops if fresh air function stops.

CLEAN function (only applied to clean series)


When the air conditioner is on, press CLEAN/PLASMA button for 3 seconds to initiate or stop clean function.
While this function is initiated the remote controller displays CLEAN and it will extinguish if clean function
stops. Please
note that after clean function starts up, the evaporator will only clean automatically on the
condition that the air conditioner is turned off normally.Moreover, after the evaporator is checked dirty by the
system, the LED of indoor unit will display CLEAN to remind you of starting up the clean function.

AIR QUALITY CHECKING function (only applied to air quality checking series)
When the air conditioner is on, air quality checking function starts up automatically, at the same time the air
quality indicator light on the indoor unit will flash once, which shows that the air conditioner starts up air
quality checking function. After the air quality checking function is initiated, if the air quality is good the
indicator light extinguishes; if the air quality is bad the indicator light will flash 5 times then lighten. Air
quality is showed through the lighteness of the indicator light, the lighter the indicator the worse the air
quality. When
the indicator light is lighten, fresh air function is supposed to be started up. After the air is
renewed, the system will stop or continue fresh air function according to the air quality. You can also stop
fresh air function as you like. When the air conditioner is turned off, the indicator light will flash once to
show the air quality checking function is in gear. And every time starting up inoizer, aux-heat, light-wave,
plasma,clean and turbo function the indicator light will flash once.

20

CONTROL SPECIFICATION
SLEEP mode
Normal sleep
When the air conditioner is in cooling and dry mode, the indoor fan runs at low speed After one hour of
operation the set temperature will increase by 1 .One hour later, the set temperature will increase by
1 once more. The unit will then continue operating at 2 above the set temperature.
When the air conditioner is in heating mode , the indoor fan runs at low speed. After one hour of
operation the set temperature will decrease by 2 . One hour later, the set temperature will decrease
by 2 once more. The unit will then continue operating at 4 below the set temperature.
Sleep mode 1
When the air conditioner is in cooling and dry mode and 23
st 16 ,during the 3 hours after sleep
mode 1 start up ,the set temperature will increase by 1 every hour .The unit will continue operating
at 3 above the set temperature. 8 hours later, the set temperature will decrease 2 .The unit will then
continue operating at this temperature.
When 24
st 27 , during the 2 hours after sleep mode 1 start up, the set temperature will increase
by 1 every hour .The unit will continue operating at 2 above the set temperature.8 hours later, the set
temperature will decrease 2 ,the unit will continue operating at this temperature.
When 28
st 31 ,the unit will operate at the set temperature all along.
When the air conditioner is in heat mode and18
st 16 , the unit will operate at the set temperature
all along.
When 19
st 25 , during the 2 hours after sleep mode 1 start up, the set temperature will decrease
by 1 every hour. The unit will continue operating at 2 below the set temperature.8 hours later, the
set temperature will increase 2 , the unit will continue operating at this temperature .
When 26
st 31 , during the 3 hours after sleep mode 1 start up, the set temperature will decrease
by 1 every hour. The unit will continue operating at 3 below the set temperature.8 hours later, the
set temperature will increase 2 .The unit will then continue operating at this temperature.
Sleep mode 2
When the air conditioner is in cooling and dry mode and 23
st 16 , during the 3 hours after sleep
mode 2 start up ,the set temperature will increase by 1 every hour .The unit will continue operating
at 3 above the set temperature.7 hours later, the set temperature will decrease 1 . The unit will
then continue operating at this temperature.
When 24
st 27 , during the 2 hours after sleep mode 2 start up, the set temperature will increase
by 1 every hour .The unit will continue operating at 2 above the set temperature.7 hours later, the
set temperature will decrease 1 ,the unit will continue operating at this temperature .
When 28
st 31 ,the unit will operate at the set temperature all along.
When the air conditioner is in heat mode and18
st 16 , the unit will operate at the set temperature
all along.
When 19
st 25 , during the 2 hours after sleep mode 2 start up ,the set temperature will decrease
by 1 every hour .The unit will continue operating at 2 below the set temperature.7 hours later, the
set temperature will increase 1 , the unit will continue operating at this temperature .
When 26
st 31 , during the 3 hours after sleep mode 2 start up, the set temperature will decrease
by 1 every hour. The unit will continue operating at 3 below the set temperature. 7 hours later, the
set temperature will increase 1 .The unit will then continue operating at this temperature.

21

CONTROL SPECIFICATION
Sleep mode 3
When the air conditioner is in cooling and dry mode and 23
st 16 , during the 3 hours after sleep
mode 3 start up, the set temperature will increase by 1 every hour .The unit will continue operating
at 3 above the set temperature.
When 24
st 27 , during the 2 hours after sleep mode 3 start up, the set temperature will increase
by 1 every hour .The unit will continue operating at 2 above the set temperature.
When 28
st 31 ,the unit will operate at the set temperature all along.
When the air conditioner is in heat mode and18
st 16 , the unit will operate at the set temperature
all along.
When 19
st 25 , during the 2 hours after sleep mode 3 start up ,the set temperature will decrease
by 1 every hour. The unit will continue operating at 2 below the set temperature.
When 26
st 31 ,during the 3 hours after sleep mode 3start up, the set temperature will decrease
by 1 every hour. The unit will continue operating at 3 below the set temperature.

PLASMA function (only applied to plasma series)


When the air conditioner is on, press CLEAN/PLASMA button to start or stop plasma function.
The LED of the remote controller displays

while it is initiated and extinguishes while it stops.

INOIZER function(only applied to inoizer series)


Press inoizer button to start or stop inoizer function when the air conditioner is on or set timer.
The LED of the remote controller displays

while it is initiated and extinguishes while it stops.

This function can only be stopped by pressing inoizer button or turning off the air conditioner.

22

TO DISASSEMBLE MECHANICAL PARTS


Stop operation of the air conditioner and remove the power cord before repairing the unit.
The following pictures taking P1 as an example are presented just for the purpose of illustration.

Indoor unit
No

Parts

Front grille

Procedure

Remark

1.Stop the air conditioner


operation and block the
main power.
2.Contract the second finger
to the left ,and right handle
and pull to open the inlet
grille.

3.Draw away signal line.

4.Take the left and right filter


out.

5. Loosen two fixing screw of


front grille.

6.Put hands at the two ruts


of the body, then pull the
front panel out .

23

TO DISASSEMBLE MECHANICAL PARTS


No

Parts

Electrical
parts

Procedure

Remark

1.Loosen the earth screw in


evaporator.

2.Loosen the stepping motor


line, and pull softly the indoor
pipe temperature sensor out
from the pipe casing.

3.Push the hook outside to take


the electrical box out easily.

4.Separate the electrical box


from the indoor unit.

Assy tray
drain

1.Push the left and right hooks


to make the assy pulled out.

24

TO DISASSEMBLE MECHANICAL PARTS


No

Parts

Procedure

Remark

2.Separete the assy tray drain


from the body.

1.Push the left hook and


separate the left part out of
evaporator.

2.Push the right hook and


separate the right part out
of evaporator.
4

Evaporator

3.Separate the evaporator


from the indoor unit.

Fan motor and 1.Separate the fan motor


cross fan
from the fan.

25

TO DISASSEMBLE MECHANICAL PARTS


Outdoor unit
No

Parts

Procedure

Remark

Cabinet

1.Turn off the unit and remove


the power cable.

2.Remove the upper cabinet,


the front cabinet and back
cabinet.
2

Fan motor &


propeller fan

1.Remove the nut flange.


(Turn to the right to remove
as it a left turned screw )
2.separate the propeller fan
from fan motor.
3.Loosen the fixed screw of
fan motor,separate the fan
motor from outdoor unit

Ass'y control 1.Loosen the fixing screw of


out
the base-electrical control .

2.separate the connector.

3.Separate the ass' y control


out from the outdoor unit.

26

Exploded Views and Parts List


Indoor unit

27

Exploded Views and Parts List


Indoor unit
No. English Part Name
1
2
3

Electrical control box with air


sensitive display (optional)
Air
sensitive
display
panel(optional)
Air
sensitive
display
piece(optional)

Quantity No. English Part Name Quantity


1

28 Temperature sensor

29 Temperature sensor

30 Terminal block

Display electrical control box

31 Spring piece

LED

32 Grounded terminal

Display piece

33

Connecting wire for LED

34

Connecting wire

35

9 Cover for front panel


10 Stepping motor
11 Ionizer(optional)

1
1
1

36
37
38

12 Water collecting tray for P1

39

13
14
15
16

Drain cap
Drain hose
Connecting pole
Air leading vane

1
1
2
10

40
41
42
43

17 Air leading plectrum

44

18
19
20
21
22
23

1
2
1
2
2
2

45
46

24
25
26
27

Swing louver for P1


Air filter supporter
P1 front panel
Screw cover for B3
Air filter
Supporter for front panel
Front
panel
for
P
series(optional)
Decorating board for front
panel of P series
Power supply cord
Power supply cord clip

1
1
1
1

28

Electrical control box


for P1
Electrical supporter
Rubber
shock
absorption base
Fan motor
Mounting plate
Bottom enclosure
Air
sensitive
detecting
assembly(optional)
Evaporator
Indoor unit fan
Oil bearing
Rubber bear support
Cover of electrical
control box for P1
Transformer
Main control board

1
1
1
1
1
1
1
1
1
1
1
1
1
1

Exploded Views and Parts List


Outdoor unit

AUS-09H53R150Px
AUS-12H53R150Px
MUP-09-HI AND MUP-12-HI

29

Exploded Views and Parts List


Outdoor unit
No.

MUP-09-HI AND MUP-12-HI


AUS-09H53R150Px
AUS-12H53R150Px

English Part Name

Quantity

No.

English Part Name

Quantity

Air outlet grille

26

Right handle

Front panel

27

Outdoor fan motor supporter

Outdoor unit fan

Partition

Valve board

Compressor screw

Power supply cord fixs

Power supply cord clip

Capacitor for compressor

10

Electrical install board

11

Right side board

12

Top cover

13

fan motor capacitor

14

Outdoor unit terminal block

15

High pressure valve

16

Capillary assembly

17

Low pressure valve

18

Four way valve

19

Compressor

20

Bottom board

21

Condenser

22

Uphold board

23

Capacitor fixing clip

24

Fan screw nut M6

25

Fan screw nut M8

32
30

Wiring Diagrams
Indoor unit

AUS-07H53R010Px
AUS-12H53R150Px
MUP-09-HI AND MUP-12-HI
MUP-09-HI AND AUS-12H53R130Px
MUP-12-HI
AUS-09H53R010Px
AUS-09H53R150Px

FL
IFAN

Outdoor unit

AUS-07H53R010Px

AUS-09H53R010Px

31

Wiring Diagrams
Outdoor unit

AUS-09H53R150Px
AUS-12H53R130Px
MUP-09-HI AND MUP-12-HI
AUS-12H53R150Px

32