BENTOFLEX ST 108 PL
DESCRIPTION
Components
1. Reset button
2. Control box
3. Ignition transformer
4. Ignition cables
5. Nozzle assembly
6. Nozzle
7. Brake plate
8. Blast tube
9. Ignition electrodes
10. Connecting pipe
11. Air damper
12. Solenoid valve
13. Pump
14. Drive coupling
TECHNICAL DATA
ST 108 PL 6-7-19-10
Dimensions
162
239
89
56
188
145
275
Length of burner
tube
Incl. flange A
Measure B
Incl. flange B
Measure B
Incl. flange C
Measure B
Incl. flange D
Measure B
PL
80
45
58
66
65
PL
127
92
125
113
112
Burner tube
PL
Oil capacity
Outputy
Recommended
Nozzle
Recommended
Pump pressure
kg/h
kW
Mcal/h
Angle
Type
Bar
1,5-3,3
18-39
15-34
80
H, S
10
The net calorific value of 11,86 kWh/kg for light oil has been used.
Recommended nozzle
Because of different boiler types
existing on the market, with varying
combustion chamber designs, it is
Burner head
3,5-4,5
2,5-3,1
(- 0,5) + 0,5
7,0-8,0
171 225 02 07-01
TECHNICAL DATA
Dimensions
Flange A
Flange C
89,7
90
25
10,3
10
130-150
125
Flange B
Flange D
89,5
12
3
0,
90
12
136-150
125-150
GENERAL INSTRUCTIONS
General rules
The installation of an oil burner
should be carried out in accordance
with local regulations. The installer of
the burner must therefore be aware
of all regulations relating to oil and
combustion.
Only oil suitable for the burner should
be used and then in combination with
a suitable oil filter before the oil pump
of the burner.
If the burner is replacing an existing
burner make sure that the oil filter is
replaced or cleaned. The installation
must only be undertaken by
experienced personnel. Care should
be taken by the installer to ensure that
no electrical cables or fuel/gas pipes
are trapped or damaged during
installation or service/maintenance.
Installation instructions
General installation instructions
accompany the burner and should be
left in a prominent place adjacent to
the burner.
Adjustment of burner
The burner is from the factory pre-set
to an average value that must then be
adjusted to the boiler in question.
All burner adjustments must be made in
accordance with boiler manufacturers
instructions.These must include the
checking of flue gas temperatures,
average water temperature and CO2
or O2 concentration.
To adjust the combustion device,
start by increasing the air volume
somewhat.
When the burner starts it is burning
with excess air and smoke number
0. Reduce the air volume until soot
occurs and increase again to reach
a combustion free of soot.
By this procedure an optimum
adjustment is obtained. If larger
nozzles are used the preadjustment of
the air volume must be increased.
Condensation in chimney
A modern burner works with less
excess air and often also with smaller
nozzles than older models. This
increases the efficiency but also the risk
of condensation in the chimney. The risk
increases if the area of the chimney flue
is too large. The temperature of the flue
gases should exceed 60C measured
0,5 metres from the chimney top.
Adjustment of burner
To obtain a correct adjustment a
flue gas analysis and a temperature
measurement must be carried out.
Otherwise there is a risk that a bad
adjustment may cause a formation of
soot, bad efficiency or condensate in
the chimney.
Maintenance
The boiler/burner should be examined
regularly for any signs of malfunction
or oil leakage.
Warning: Before doing any service switch off power at the main switch and cut off the oil supply
ELECTRIC EQUIPMENT
OIL BURNER CONTROL: LOA21... / LOA24...
List of components
A1 Oil burner control
A2 Twin thermostat
F1 Fuse, max. 10A
H1 Alarm lamp
H2 Signal lamp (optional)
M1 Burner motor
P1 Time meter (optional)
R1 Photoresistor
S3 Main switch
T1 Ignition transformer
Y1 Solenoid valve
X1 Plug-in contact, burner
X2 Plug-in contact, boiler
Wiring diagram
(1)(2)
X1
X2
1(2)
171 415 20 07-01
ELECTRIC EQUIPMENT
Function
1. Switch on operating switch and twin thermostat
The burner motor starts, an ignition spark is formed, the prepurge goes
on till the prepurge period expires and the solenoid valve opens (2).
2. Solenoid valve opens
Oil mist is formed and ignited. The photocell indicates a flame.
(1) The ignition spark goes out 15 s. after flame indication (LOA24.171...).
(2) The ignition spark goes out 2 s. after flame indication when the ignition
transformer is connected to terminal 7 (LOA24.173...).
3. The safety time expires
a. If no flame is established before this time limit the control cuts out.
b. If for some reasons the flame disappears after this time limit, the
burner will make an attempt to re-start.
3-4. Operating position
If the burner operation is interrupted by means of the main switch or the
thermostat, a new start takes place when the conditions in accordance
with point 1 are fulfilled.
The oil burner control cuts out
A red lamp in the control is lit. Press the reset button and the burner
re-starts.
Post-ignition
(2) If a post-igniton of 15 s. is wanted, move the ignition transformer
from terminal 7 to terminal 6 (LOA24.173...).
Technical data
Pre-ignition time:
Pre-purge time:
(1) Post-ignition time:
(2) Post-ignition time:
Safety lock-out time:
Reset time after lockout:
Reaction time on flame failure:
Ambient temperature:
Min. current with flame established:
Max. photo current at start:
Enclosure:
(Under voltage proof only LOA24...)
13 s
13 s
15 s
2s
10 s
50 s
max. 1 s
from - 20 to +60C
65 A
5 A
IP 40
2(2)
171 415 20 07-01
1,3-12,0 mm2/s
7-15 bar
-10 to +70C
Purging
On 1-pipe systems it is necessary to
purge the pump. On 2-pipe systems
purging is automatic through the
return line.
Components
1 Nozzle port G1/8"
2. Pressure gauge port
3. Pressure adjustment, 4mm allen key
4. Cartridge filter
5. Vacuum gauge port G1/8"
6. Return line G"
7. Suction line G"
8. Return plug
1-pipe system
Height Pipe diameter
H
4 mm 5 mm 6 mm
m m m m
4,0
51
100
100
3,5
45
100
100
3,0
38
94
100
2,5
32
78
100
2,0
26
62
100
1,5
19
47
97
1,0
13
31
65
0,5
6
16
32
1-pipe system
Two-pipe system
H
eight Pipe diameter
H
6 mm 8 mm 10 mm
m m m m
4,0
33
100
100
3,5
31
98
100
3,0
29
91
100
2,5
27
85
100
2,0
25
79
100
1,5
23
72
100
1,0
21
66
100
0,5
19
60
100
Two-pipe system
Height Pipe diameter
H
6 mm 8 mm 10 mm
m m m m
0
17
53
100
-0,5
15
47
100
-1,0
13
41
99
-1,5
11
34
84
-2,0
9
28
68
-2,5
7
22
53
-3,0
5
15
37
-3,5
3
9
22
4,0
1
3
6
H
C
S
D
P1
A
R
oil than the gear set can supply
under existing circum-stances, the
oil pressure falls below the set value
and the valve closes against the
return side (R) by means of the
diaphragm (D) and goes into starting
position.
This can be remedied by:
- Reducing the pump pressure.
- Reducing the oil quantity supplied
by using a smaller nozzle.
- Using a pump with a larger capacity.
NC
NOZZLE TABLE
8
kg/h
kW
9
Mcal/h kg/h
kW
10
Mcal/h kg/h
kW
11
Mcal/h kg/h
kW
Mcal/h
0,40
1,33
16
13
1,41
17
14
1,49
18
15
1,56
18
16
0,50
1,66
20
17
1,76
21
18
1,86
22
19
1,95
23
20
0,60
2,00
24
20
2,12
25
22
2,23
26
23
2,34
28
24
0,65
2,16
26
22
2,29
27
23
2,42
29
25
2,54
30
26
0,75
2,49
29
25
2,65
31
27
2,79
33
28
2,93
35
30
0,85
2,83
33
29
3,00
36
31
3,16
37
32
3,32
39
34
1,00
3,33
39
34
3,53
42
36
3,72
44
38
3,90
46
40
1,10
3,66
43
37
3,88
46
39
4,09
48
42
4,29
51
44
1,20
3,99
47
41
4,24
50
43
4,47
53
46
4,68
55
48
1,25
4,16
49
42
4,40
52
45
4,65
55
47
4,88
58
50
1,35
4,49
53
46
4,76
56
48
5,02
59
51
5,27
62
54
1,50
4,98
59
51
5,29
63
54
5,58
66
57
5,85
69
60
1,65
5,49
65
56
5,82
69
59
6,14
73
63
6,44
76
66
1,75
5,82
69
59
6,18
73
63
6,51
77
66
6,83
81
70
2,00
6,65
79
68
7,06
84
72
7,45
88
76
7,81
93
80
2,25
7,49
89
76
7,94
94
81
8,38
99
85
8,78
104
89
2,50
8,32
99
85
8,82
105
90
9,31
110
95
9,76
116
99
2,75
9,15
108
93
9,71
115
99
10,24
121
104
10,73
127
109
3,00
9,98
118
102
10,59
126
108
11,16
132
114
11,71
139
119
3,50
11,65
138
119
12,35
146
126
13,03
154
133
13,66
162
139
4,00
13,31
158
136
14,12
167
144
14,89
176
152
15,62
185
159
4,50
14,97
177
153
15,88
188
162
16,75
198
171
17,57
208
179
5,00
16,64
197
170
17,65
209
180
18,62
221
190
19,52
231
199
5,50
18,30
217
187
19,42
230
198
20,48
243
209
21,47
255
219
6,00
19,97
237
204
21,18
251
216
22,34
265
228
23,42
278
239
6,50
21,63
256
220
22,94
272
234
24,20
287
247
25,37
301
259
7,00
23,29
276
237
24,71
293
252
26,06
309
266
27,33
324
279
7,50
24,96
296
254
26,47
314
270
27,92
331
285
29,28
347
298
8,00
26,62
316
271
28,24
335
288
29,79
353
304
31,23
370
318
8,50
28,28
335
288
30,00
356
306
31,65
375
323
33,18
393
338
9,00
29,95
355
305
31,77
377
324
33,59
398
342
35,14
417
358
The table applies to oil with a viscosity of 4,4 mm2/s (cSt) with density 830 kg/m3.
Burner with preheater
Consider that on preheating the oil quantity is reduced by 5-20% depending on.
- Rise in temperature at the nozzle
- Design of nozzle
- Capacity (high capacity - small difference)
1(2)
171 505 44 07-01
NOZZLE TABLE
12
kg/h
kW
13
Mcal/h kg/h
kW
14
Mcal/h kg/h
kW
15
Mcal/h kg/h
kW
Mcal/h
0,40
1,63
19
17
1,70
20
17
1,76
21
18
1,82
21
18
0,50
2,04
24
21
2,12
25
22
2,20
26
22
2,28
27
23
0,60
2,45
29
25
2,55
30
26
2,64
31
27
2,73
32
28
0,65
2,65
31
27
2,75
33
28
2,86
34
29
2,96
35
30
0,75
3,08
36
31
3,18
38
32
3,30
39
34
3,42
40
35
0,85
3,47
41
35
3,61
43
37
3,74
44
38
3,87
46
39
1,00
4,08
48
42
4,24
50
43
4,40
52
45
4,56
54
46
1,10
4,48
53
46
4,67
55
48
4,84
57
49
5,01
59
51
1,20
4,89
58
50
5,09
60
52
5,29
63
54
5,47
65
56
1,25
5,10
60
52
5,30
63
54
5,51
65
56
5,70
68
58
1,35
5,50
65
56
5,73
68
58
5,95
70
61
6,15
73
63
1,50
6,11
72
62
6,36
75
65
6,60
78
67
6,83
81
70
1,65
6,73
80
69
7,00
83
71
7,27
86
74
7,52
89
77
1,75
7,14
85
73
7,42
88
76
7,71
91
79
7,97
94
81
2,00
8,18
97
83
8,49
101
86
8,81
104
90
9,12
108
93
2,25
9,18
109
94
9,55
113
97
9,91
117
101
10,26
122
105
2,50
10,19
121
104
10,61
126
108
11,01
130
112
11,39
135
116
2,75
11,21
133
114
11,67
138
119
12,11
144
123
12,53
148
128
3,00
12,23
145
125
12,73
151
130
13,21
157
135
13,67
162
139
3,50
14,27
169
145
14,85
176
151
15,42
183
157
15,95
189
163
4,00
16,31
193
166
16,97
201
173
17,62
209
180
18,23
216
186
4,50
18,35
217
187
19,10
226
195
19,82
235
202
20,51
243
209
5,00
20,39
242
208
21,22
251
216
22,03
261
225
22,79
270
232
5,50
22,43
266
229
23,34
277
238
24,23
287
247
25,07
297
256
6,00
24,47
290
249
25,46
302
260
26,43
313
269
27,49
326
280
6,50
26,51
314
270
27,58
327
281
28,63
339
292
29,63
351
302
7,00
28,55
338
291
29,70
352
303
30,84
366
314
31,91
378
325
7,50
30,59
363
312
31,83
377
324
33,04
392
337
34,19
405
349
8,00
32,63
387
333
33,95
403
346
35,25
418
359
36,47
432
372
8,50
34,66
411
353
36,07
428
368
37,45
444
382
38,74
459
395
9,00
36,71
435
374
38,19
453
389
39,65
470
404
41,02
486
418
The table applies to oil with a viscosity of 4,4 mm2/s (cSt) with density 830 kg/m3.
Burner with preheater
Consider that on preheating the oil quantity is reduced by 5-20% depending on.
- Rise in temperature at the nozzle
- Design of nozzle
- Capacity (high capacity - small difference)
2(2)
171 505 44 07-01
FAULT LOCATION
Burner fails to start
Remedies
Situation
Possible causes
Motor runs
Flame instability
Burner pre-purges
Excess air
Flame occurs
Burner locks out
Motor runs
Burner pre-purges
False light
No flame occurs
Burner locks out
No spark
No oil
Adjust thermostat
Check by replacement
Motor runs
Rectify condition
No spark
Excessive draught
Replace nozzle
Delayed ignition
Frskran om verensstmmelse
Declaration of conformity
Konformittserklrung
Dclaration de conformit
Brnnare, Burner, lbrenner, Brleur
Certifikat TV Sddeutschland
Certifikat nr.
Typ, Type:
08128915006
BF 1
0111110535004
B1
0207110535005
B2
02119815001 ST 97, ST 108, ST 120,
ST 133, ST 146
02119815002
B 9, B 10, B 11
Certifikat nr.
02119815003
02119815004
040588622001
040588622002
13129815007
Typ, Type:
B 20, B 30, B 40, B 45
B 50, B 60, B 70, B 80
B 55
B 65
B 45 MF, B 45-2 MF
Enertech AB frskrar under eget ansvar att ovannmnda produkter r i verensstmmelse med fljande standarder eller andra
regelgivande dokument och uppfyller tillmpliga delar i EU direktiv.
Enertech AB declares under sole responsibility that the above mentioned product is in conformity with the following standards or other
normative documents and follows the provisions of applicable parts in the following EU Directives.
Enertech AB erklrt in eigener Verantwortung, dass obenstehende Produkte mit folgenden Normen oder anderen normativen
Dokumenten und anwendbare Teile in EU-Direktiven in bereinstimmung stehen
Enertech AB dclare sous sa seule responsabilit que les produits dsigns ci-dessus sont conformes aux normes et aux documents
normatifs suivants et satisfont aux critres applicables des directives CE suivantes:
Dokument:
EN 267
Genom att brnnaren uppfyller ovannmnda standarder och direktiv erhller brnnaren CE - mrkningen.
In that the burner conforms to the above mentioned standards it is awarded the CE mark.
Indem der Brenner die obengenannten Normen und Richtlinien erfllt, erhlt der Brenner die CE-Kennzeichnung.
Du fait de leur conformit aux directives mentionnes ci-dessus, les brleurs Bentone bnficient du marquage CE.
Hkan Lennartsson
Starting precautions
Make sure that the oil tank is not empty
Make sure that the valves on oil and water supply pipes
areopen.
Make sure that the boiler flue damper is open.
Make sure that the boiler thermostat is set at the correct
temperature.
Switch on the current. Most relay systems have a
delayed action so that the burner will not start for
perhaps 20 seconds.
With heavy oil the delay will be longer as the burner
will notstart until the oil in the preheater reaches the
requiredtemperature.
If the burner will not start