ETPG-275.pdf 250 KVA Perkins PDF
ETPG-275.pdf 250 KVA Perkins PDF
ETPG-275.pdf 250 KVA Perkins PDF
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
Generating Rates
PRIME
STANDBY
kVA
250
275
kW
200
220
POWER RATING
POWER
Rated Speed
r.p.m
1500
Standard Voltage
400
Available Voltages
Cos Phi
0.8
Ambient conditions of reference: 1000 mbar, 25C, 30% relative humidity. Power according to ISO 3046
normative.
P.R.P. Prime Power - ISO 8528 : prime power is the maximum power available during a variable power
sequence, which may be run for an unlimited number of hours per year,between stated maintenance intervals.
The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10%
overload available forgoverning purposes only.
Standby Power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time
(500h), within the following limits of maximum operating time: 100% load 25h per year 90% load 200h per
year. No overload available. Applicable in case of failure of the main in areas of reliable electrical network.
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
PRP
STANDBY
217
239
kW
Manufacturer
Perkins
Model
1306C-E87TAG6
mm
16.9:1
Cooling system
Water-cooled
Engine Speed/Frequency
Coolant Capacity
rpm/Hz 1500/50HZ
37.2
L
Starting System
Electric 24 volt DC
Displacement
8.7
26.4
24VDC
Governing Type
Type
Air Filter
Type
Fuel Consumption
Electronic
Dry
Load
100%
75%
50%
25%
L/h
45.0
36.0
24.0
13.8
ENGINE--Industrial 4 stroke cooled diesel engine complete with air,fuel and oil filters,electric
starting and charging equipment,engine protection against low water level.
COOLING--Radiator and colling fan complete with protection guards,designed to cool engine at
specified output in air temperatures upto 45 ,radiators suitable for higher temperatures are
available.Low water level protection fitted as standard.
ELECTRICAL SYSTEM--24V upto.Axial type starter motor,battery charging alternator,high capacity
lead acid battery,and battery tray mounted on the generator base frame,and heavy duty
interconnecting cable with terminations.
EXHAUST SYSTEM--Heavy duty industrial exhauset silencer with flexible piping.
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
LEROY SOMER
STAMFORD
LSA46.2L6
UCI274K
Model
Exciter System
Poles
Self-excited, brushless
Num
Cooling Fan
Bearing
Single,double shielded
Windings
100% copper
Connection Type
Reconnectable
Insulation Type
Class
Class H
Pitch
2/3
Amortisseur Winding
Full
Voltage Regulator
A.V.R. (Electronic)
1%
Underspeed Protection
Standard
Overexcitation Protection
IP23
<50
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
Main Features:
Automatic mains failure
Engine control,Generator protection
Built in alarms and warnings
Remote Start operation available
Fuel pump control
Mains simulation
Block heater control
Field adjustable parameters
Free MS-Windows Remote monitoring
LED displays
Configurable analogue inputs
I/O expansion capability
Protection Circuits
Instruments
WARNING
ENGINE
Engine speed
Oil pressure
SHUT DOWNS
Coolant temperature
Fail to start
Run time
Emergency stop
Battery volts
TOR
Voltage (L-N)
Current (L1-L2-L3)
Frequency
Mains
Electrical trip
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
General Features:
Composed of Perkins diesel engine and Stamford or Leroy somer alternator
Oil and fuel filter fitted,water separator
Lube-oil drain valve fitted
Electric Starter Charge motor 24 VD.C
Water-cooled
8-hours operation base tank
Auto start
Optional soundproof and weatherproof canopy
3 pole MCCB Delixi breaker
Operation & Maintenance manual
Special Integrated Steel Base tank and sprayed overall in gloss enamel paint
Voltage Regulation:
Voltage regulation maintanined within 0.5%
Between 0.8 and 1.0 lagging and unity
From no load to full load
At speed droop variation upto 4.5%
Frequency Undulation:
load from 0-100%,frequency undulation within 0.25%
No load wire volts max undulation ration\ within 1.8%
Three Phrase balanced load in the order of 5%
Effect factor of Telecom
TIF better than 50
THF to IEC60034 Part 40 better than 2%
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
POWERED BY PERKINS
DIESEL GENERATOR SET
Model: ETPG275
INDUSTRIAL RANGE
Powered by Perkins
Quality Standards
ISO9001:2000,ISO14000,ISO3046
ISO8528 BS4999
BS5514,AS1359,ICE34
CE Compliance