Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Lightning & Surge Protection: /... Class I+II Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Watchful Eye Solutions, Inc.

WTH-80, WTH-100 /... Class I+II Series

Lightning & Surge Protection

www.watchfuleyesolutions.com

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

WTH-100/G/1P-255 (N-PE Only)

Uc

WTH-80 Series

WTH-100 Series

50kA

Imax

100kA

Iimp

12.5kA

Up

1.2kV

Ures

0.7kV

WTH-100/G/1P-255

WTH-80
Requirement Class to IEC61643-1

255VAC

In

WTH-100
Class I+II
C, B & A

IEEE Category Rating

L-N, L-PE, N-PE

Protection Modes
Nominal Discharge Current (In @8/20s)

40kA

50kA

Max. Discharge Current (Imax @8/20s)

80kA

100kA

Pulsed Current (Iimp @10/350s)

10kA

Follow Current (If)


Short Circuit Current Ratings (SCCR)

Surge Protective Device


for Low Voltage Power Supply System

12.5kA

Different types for your choosing according to


different voltages
(110V, 120/208V, 220/380V, 277/480V, 347/600V)

NO
20kA rms

Response Time (tA)


Leakage Current (at 75%U1mA)

< 25ns
<20A

In accordance with: IEC 61643-1 - Class I+II and


UL1449 Type 4 Location

Thermal Protection
Back-up Fuse (if mains > 125A)

YES
125A gL

Location of use: main sub-distribution boards,


branch sub-distribution boards

- 40 to 176F (-40 to 80C)


0% to 95% noncondensing

Temperature Range
Relative Humidity
Maximum Operating Altitude

The convenient plug-in module, and separate


base design

10,000 feet (3000m)


35mm (solid) / 25mm (stranded)

Terminal Cross Section


Stripping Length Contacts
Terminal Screw Torque

Internal thermal disconnect devices help ensure


safe or at end-of-life

0.6inches (15mm)

Combinations: 1P, 1P+NPE, 2P, 3P, 3P+NPE, 4P

Max. 3.5Nm

Protection Rating (IP Code)

Remote Contact: optional

IP 20
>5000 events
35mm top-hat rail

Surge Life at 3kA (8/20s)


Din Rail EN60715
Housing Material

Thermoplastic; extinguishing degree UL 94 V-0


10

10
2

F1

L1 F3

L2
L3
N
PE

PEN
F2
5

F2
S
P
D

S
P
D

S
P
D

S
P
D

S
P
D

S
P
D

S
P
D

S
P
D

S
P
D

5
6

80/100-2

Key
1. Origin of the installation
2. Distribution board
3. Distribution outlet
4. Main earthing terminal or bar
5. Surge protective device, class I or II tested
6. Earthing connection (earthing conductor) of the
surge protective device
7. Fixed equipment to be protected
8. Surge protective device, class II tested
9. Surge protective device, class II or class III tested
10. Decoupling element or line length
F1, F2, F3 overcurrent protective disconnectors
NOTE Refer to IEC 61643-12 for further information.

IEC62305-4
Installation example of test class I, class II and class III SPDs

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

Type:

Up

Ures

WTH-80/B+C/...75 Series

75VAC

1.3kV

0.6kV

WTH-80/B+C/...115 Series

115VAC

1.5kV

0.7kV

WTH-80/B+C/...150 Series

150VAC

1.6kV

0.8kV

WTH-80/B+C/...275 Series

275VAC

1.8kV

1.0kV

WTH-80/B+C/...320 Series

320VAC

2.0kV

1.1kV

WTH-80/B+C/...385 Series

385VAC

2.1kV

1.2kV

WTH-80/B+C/...420 Series

420VAC

2.2kV

1.4kV

WTH-80/B+C/...550 Series

550VAC

2.7kV

1.8kV

WTH-80/B+C/...690 Series

690VAC

3.0kV

2.1kV

WTH-100/B+C/...75 Series

75VAC

1.4kV

0.6kV

WTH-100/B+C/...115 Series

115VAC

1.6kV

0.7kV

WTH-100/B+C/...150 Series

150VAC

1.7kV

0.8kV

WTH-100/B+C/...275 Series

275VAC

1.9kV

1.0kV

WTH-100/B+C/...320 Series

320VAC

2.1kV

1.1kV

WTH-100/B+C/...385 Series

385VAC

2.2kV

1.2kV

WTH-100/B+C/...420 Series

420VAC

2.3kV

1.4kV

WTH-100/B+C/...550 Series

550VAC

2.8kV

1.8kV

WTH-100/B+C/...690 Series

690VAC

3.1kV

2.1kV

Uc (MCOV)

How to name our products

WTH - 80 / B+C / R / 1P - 385


Watchfuleye

Remote contacts

Imax

Class 1+II / Type 1+2

Uc~: 385V

Combination

Features of Class I + II :

Power Supply System

Uc(MCOV), L-PE Mode, Uc>1.15Un

110V, 120/208

150VAC

220/380

275VAC, 320VAC, 385VAC

230/400V

275VAC, 320VAC, 385VAC , 420VAC

240/415V

320VAC, 385VAC , 420VAC

277/480V

320VAC, 385VAC , 420VAC

347/600V

550VAC, 690VAC

The impulse current and residual voltage curve in In=-40kA


(WTH-80/B+C/1P-420(L-PE))

Have high capability of Class I lightning and surge protection,


and capability of Class II (equivalent to the parameters of
WTH-40 ) fine protection with low residual voltage as well,
applying to Class I and Class II lightning and surge protection
in multiple areas. If you are not sure which module to choose
for protecting your area, Class I + II is the best solution.

Un: Normal operating voltage rating


Uc (MCOV - UL): Max. continuous operating voltage
Up: Voltage protection level (at In)
Ures: Residual voltage at 6kV 1.2/50s & 3kA 8/20s
Frequency: 50Hz to 60Hz
Note: Uc>1.15Un
The relationship between two parameters Uc and Up of a SPD is proportional.
If Uc is small, the value of Up is also small; SPDs with smaller Up can provide
better surge protection.
Whether to choose smaller Uc depends on the voltage stability of the grid. If
you choose SPDs with smaller Uc for the grid with instable voltage, the SPDs
will frequently work while the grid voltage fluctuates, resulting in shortening
SPDs product life.
If you choose larger Uc, and the value of Up is accordingly large, the surge
protective efficiency will not be so fine.
If you are unsure of the voltage stability of the grid, it is suggested to calculate
Uc using the following formula: 2 Un<Uc< 3 Un

The impulse current and residual voltage curve in In=-40kA


(WTH-80/B+C/1P-690(L-PE))

Watchful Eye Solutions, Inc.

80/100-3

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

Application
Customized and designed by professional and experienced
engineers according to your systems
Different specifications for your choices (plastic shell and
metal shell box; single-phase, three-phase power supply
system)
Suitable for 110V, 120/208V, 220/380V, 277/480V, 347/600V
AC voltage systems
Able to assemble fuses, circuit breakers, lightning counter
and monitoring, etc. in accordance with the requirements
of your surge protection systems
Realize remote intelligent monitoring through wireless,
wired network or cloud service

Bus Bar
Insert

m
35m
r a il

3.5Nm

WTH-2P/100
(1P+NPE, 2P Mode)

WTH-3P/100
(2P+NPE, 3P Mode)

WTH-4P/100
(3P+NPE, 4P Mode)

Bus bar

Single modules can be combined with a bus bar in multiple combination methods

PULL

Insert

Remote Contacts
3

1: COM(Common)
2: NC(Normally Close)
3: NO(Normally Open)

Type: WTH-80/B+C/ R /1P-385


WTH-80/B+C/R

Remote contacts
Remote Contacts
Contact Ratings
Terminal Cross Section
Stripping Length Contacts
Remote Terminal Torque

80/100-4

Surge Arrester

L/N (L)

Uc~ : 385V
In : 40kA
Imax : 80kA
Up : <2.1kV
IEC61643-1 T1

T2

Ro H S

PE (N)

green: ok red: replace

AC:125V/1A
Max. 1.5mm
0.25inches (6-7mm)
0.25Nm

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

F1

F1

L/N

L/N
F2

N
F2

Back-up fuse

Thermal disconnect devices

Remote Contact

Protective Element:
High Energy GDT

Protective Element:
High Energy MOV

WTH-80, WTH100 Series

WTH-80, WTH-100 Series

Selection of back-up fuse

WTH-100/G/1P-255

N-PE Only

Selection of back-up circuit-breaker

F1125A gL

F2 = 125A gL

F163A

F2 = 63A

F1125A gL

F2

F163A

F2

Dimensions

advice :
min. recommended
cross section 10mm

Back-up circuit-breaker

Two details strengthening the protection


36mm
36mm distance between two
terminals
Increase creepage distance

90

35.8max

99

Make the connection more secured


More important for the application
with UC higher than 550V

Indication of two levels of


lightning and surge protection
The capability of displaying 50 percent of
surge protection capacity: under normal
circumstances, with two MOVs' protection
at the same time, the module can realize
Class I lightning protection; in case that
one of the indicator windows indicates
red, there's still 50% of surge protection
capacity to meet Class II lightning/surge
protection requirements, and the module
shall be replaced timely at this point.

or

Fault Indication
green : OK

replace

35mm ra

il

red : fault (replace)

Pull out upward

WatchfulSystem
Eye Solutions, Inc.
Surge Protection for AC Power Supply

80/100-5

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

Lightning and Surge Protection


for 2 Wire + Ground System
1

N
G(PE)

Single Phase
2 Wire + Ground

F1
L
N
PE

L
N
PE

F1
L
N

L
N
PE
F2

F2

PE

PE

WTH-80/B+C/...2P, WTH-100/B+C/...2P Combination

WTH-80/B+C/...1P+NPE, WTH-100/B+C/1P+NPE... Combination

F1
L/N

L/N

PE

PE

PE

N
PE

F2

PE

WTH-80/B+C/...1P, WTH-100/B+C/...1P Series

80/100-6

PE

WTH-100/G/1P-255

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

Lightning and Surge Protection


for 3 Wire + Ground System
2

L1

L2
L3
G(PE)

3 Phase Delta
3 Wire + Ground

F1
L1

L1

L2
L3
PEN

L2
L3
PEN
F2

PE

WTH-80/B+C/...3P, WTH-100/B+C/...3P Combination

E
F1

F1
L/N

L/N

PE

PE
F2

L1

L1

L2
L3
PEN

L2
L3
PEN
F2

PE
PE
WTH-80/B+C/...1P, WTH-100/B+C/...1P Series

WTH-80/B+C/...3P, WTH-100/B+C/...3P Combination

Watchful Eye Solutions, Inc.

80/100-7

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

Lightning and Surge Protection


for 4 Wire + Ground System
3

L1
L2
N

3 Phase Star
4 Wire + Ground

L3
G(PE)

F1
L1

L1

L2
L3
N
PE

L2
L3
N
PE

F1
L1
L2
L3
N

L1
L2
L3
N
PE
F2

F2

PE

PE
WTH-80/B+C/...4P, WTH-100/B+C/...4P Combination

WTH-80/B+C/...3P+NPE, WTH-100/B+C/...3P+NPE Combination

F1

F1

L/N

L/N

PE

PE

PE

N
PE

F2

PE

WTH-80/B+C/...1P, WTH-100/B+C/...1P Series

80/100-8

PE

WTH-100/G/1P-255

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

Lightning and Surge Protection


for 3 Wire + Ground System
4

L1
N

Split Phase
3 Wire + Ground

L2
G(PE)

F1

F1
L/N

L/N

PE

PE
F2

L1

L1

L2
L3
PEN

L2
L3
PEN
F2

PE
PE
WTH-80/B+C/...1P, WTH-100/B+C/...1P Series

WTH-80/B+C/...3P, WTH-100/B+C/...3P Combination

Watchful Eye offers complete and reliable technical solutions for AC power supply systems, protecting
the electrical facilities throughout buildings against lightning and surge, providing a guarantee for the
security of your systems and avoid unnecessary losses.

Watchful Eye Solutions, Inc.

80/100-9

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

Ordering Code
Type:

Ordering code

Type:

Ordering code

US 120 241

WTH-80/B+C/R/1P-75

WTH-80/B + C/1P-115

US 120 242

WTH-80/B+C/R/1P-115

US 120 252

WTH-80/B + C/1P-150

US 120 243

WTH-80/B+C/R/1P-150

US 120 253

WTH-80/ B+ C/1P-275

US 120 244

WTH-80/B+C/R/1P-275

US 120 254
US 120 255

WTH-80/B + C/1P-75

US 120 251

US 120 245

WTH-80/B+C/R/1P-320

WTH-80/ B+ C/1P-385

US 120 246

WTH-80/B+C/R/1P-385

US 120 256

WTH-80/ B+ C/1P-420

US 120 247

WTH-80/B+C/R/1P-420

US 120 257

WTH-80/ B+ C/1P-550

US 120 248

WTH-80/B+C/R/1P-550

US 120 258

WTH-80/ B+ C/1P-690

US 120 249

WTH-80/B+C/R/1P-690

US 120 259

WTH-100/B + C/1P-75

US 120 261

WTH-100/B+C/R/1P-75

US 120 271

WTH-100/B + C/1P-115

US 120 262

WTH-100/B+C/R/1P-115

US 120 272

WTH-100/B + C/1P-150

US 120 263

WTH-100/B+C/R/1P-150

US 120 273

WTH-100/ B+ C/1P-275

US 120 264

WTH-100/B+C/R/1P-275

US 120 274

WTH-100/ B+ C/1P-320

US 120 265

WTH-100/B+C/R/1P-320

US 120 275

WTH-100/ B+ C/1P-385

US 120 266

WTH-100/B+C/R/1P-385

US 120 276

WTH-100/ B+ C/1P-420

US 120 267

WTH-100/B+C/R/1P-420

US 120 277

WTH-100/ B+ C/1P-550

US 120 268

WTH-100/B+C/R/1P-550

US 120 278

WTH-100/ B+ C/1P-690

US 120 269

WTH-100/B+C/R/1P-690

US 120 279

WTH-100/G/1P-255

US 120 240

WTH-80/ B+ C/1P-320

WTH-2P /10 0

US 129 004

WTH-3P/100

US 129 005

WTH-4P/100

US 129 006

80/100-10

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

Lightning and Surge Protection


for AC Power Supply System
A

Utility Service

Class I Surge Arresters

Origin of the installation

Electric Equipment

Class II Surge Arresters

Distribution board

Class III Surge Arresters

Distribution outlet

AC

F
E
C

B C

G
H

C D
AC

IEEE 62.41
CATEGORY C: outdoor overhead lines, service entrance (most severe)
CATEGORY B: major feeder, short branch circuits, service panel (indoor)
CATEGORY A: long branch circuits, receptacles (indoor) (least severe)

Watchful Eye Solutions, Inc.

80/100-11

The Guardian that Protects Your AC Power Supply System against Surge and Lightning

UL Listed

(http://www.ul.com/database)
http://www.ul.com/database

http://www.ul.com/database

Search results
You may choose to Refine Your Search.

watchful eye

Search:
watchful eye

Company Name

Category Name

WATCHFUL EYE SOLUTIONS INC

Surge- protective

WATCHFUL EYE SOLUTIONS INC

Surge- protective

Model number information is not published for all product


number, please contact Customer Service for further assi

VZCA2. E345944
Surge- protective Devices - Component
Page Bottom

Surge- protective Devices - Component


See General Information for Surge- protective Devices - Component
WATCHFUL EYE SOLUTIONS INC

E345944

24E Hudson View Dr


Beacon, NY 12508 USA
Effective May 3, 2010

Cat No.

SPD
Type

Volts
( V)

AC/ DC/
DC PV

PH

AMPS
( A)

AMB
( C)

MODE

VPR
( Vpk)

MLV
( Vpk)

MCOV
( V)

Vn
( Vdc)

In
( kA)

SCCR
( kA)

NOTES

WTH50/ B+ C/ 1P- 385

4CA

277

AC

n/a

65

Ld- Ld

1830

385

n/a

20

n/a

WTH50/ B+ C/ R/ 1P385

4CA

277

AC

n/a

65

Ld- Ld

1830

385

n/a

20

n/a

WTH65/ B+ C/ 1P- 385

4CA

277

AC

n/a

65

Ld- Ld

1830

385

n/a

20

n/a

WTH65/ B+ C/ R/ 1P385

4CA

277

AC

n/a

65

Ld- Ld

1830

385

n/a

20

n/a

AC

n/a

65

Ld- Ld

1620

385

n/a

20

n/a

Din Rail Moudle, Series WTH- 385


WTH100/ B+ C/ 1P385

80/100-12

4CA

277

Surge Protection for AC Power Supply System

www.watchfuleyesolutions.com

Lightning and Surge Protection


for AC Power Supply System
A

Class I Surge Arresters ( voltage switching type )

Class II Surge Arresters

Class I Surge Arresters ( voltage limiting type )

Class III Surge Arresters

Iimp(10/350 s )
Uoc(1.2/50s+8/20s)

Imax
A

400kA

WTH-500/G Series(Iimp:50kA)

200kA

WTH-300/G Series(Iimp:25kA)
WTH-165/B Series(Iimp:17.5kA)

B 165kA

WTH-120/B Series(Iimp:15kA)

B 120kA

20kA

10kA

WTH-20/D Series(Uoc:20kV)
WTH-10/AC Series(Uoc:15kV)

kA

WTH-40/C Series(with the most widely application)

kA

40kA

60kA

80kA

100kA

200kA

50

50kA

kA

40

65kA

kA

30

WTH-80/B+C Series(Iimp:10kA)
WTH-65/B+C Series(Iimp:7.5kA)
WTH-50/B+C Series(Iimp:5kA)

kA

80kA

25

20

WTH-100/B+C Series(Iimp:12.5kA)

100kA

5k
10 A
kA

In(8/20 s )

IEC61643-1
5 Standard ratings
5.1 Preferred values of impulse current for class I tests Iimp
5.2 Preferred values of nominal discharge current for class I I tests In
5.3 Preferred values of open-circuit voltage for class III tests Uoc

Watchful Eye Solutions, Inc.

80/100-13

Watchfuleye is specialized in a complete range of lightning and surge protective devices, with
wide applications in low voltage DC & AC power supply system, data and control system,
intelligent monitoring system and new energy industry like solar and wind power system, etc.
Our company also offers reliable custom technical solutions in lightning & surge protection for
global customers.
Headquatered in New York, watchful Eye has a network of sales to serve our customers world
wide. with high quality products and optimal service, Watchful Eye can meet your strict technical
standards and unique requirements.

Watchful Eye

The Guardian that Protects


Your System against Surge and Lightning

Watchful Eye Solutions, Inc.

www.watchfuleyesolutions.com

You might also like