Energy End-Use Patterns in Full-Service Hotels: A Case Study
Energy End-Use Patterns in Full-Service Hotels: A Case Study
Energy End-Use Patterns in Full-Service Hotels: A Case Study
Marylynn Placet, Srinivas Katipamula, Bing Liu, James Dirks, and Yulong Xie
Pacific Northwest National Laboratory
Gregory Sullivan, Efficiency Solutions
Jim Walent, BF Saul, Inc.
Rebecca Williamson, InterContinental Hotel Group
ABSTRACT
The U.S. Department of Energy (DOE) recently initiated a program Commercial
Building Partnerships (CBP) to work with private-sector companies in the design of highlyefficient retrofit and new construction projects. Pacific Northwest National Laboratory (PNNL)
is conducting a project with a major hotel company to retrofit a full-service, large hotel with the
goal of reducing energy consumption by at least 30%. The first step of the project was an
intensive metering and monitoring effort aimed at understanding energy end use patterns in the
hotel. About 10% of the guest rooms (32), as well as circuits for most of the end uses in public
spaces (lighting, elevators, air handlers and other HVAC system components, and various
equipment), were equipped with meters. Data are being collected at 1- or 5-minute intervals and
downloaded on a monthly basis for analysis.
This paper presents results from the first four months of the monitoring effort, which
revealed energy end-use consumption patterns, variability of guest room energy use, daily load
curves, monthly variations, and other aspects of hotel energy use. Metered end-use data for
hotels at this level of detail are not available from any currently-available public sources. This
study presents unique information and insight into energy end-use patterns in the lodging sector
of commercial buildings and can also serve as a case study of a complex sub-metering project.
3-310
most of the packaged terminal heat pumps (PTHP) serving the guest rooms are 7-years old or
more (though they are gradually being replaced). There was no energy benchmarking or energy
audit completed prior to commencement of this project.
Figure 1. Aerial Photo of the Hotel
The first step of the project was to measure the baseline energy use and conduct a
detailed study of the end-use energy consumption patterns in the hotel. Some information on
energy end-use in hotels is available from sources such as the Commercial Building Energy
Consumption Survey conducted by the Energy Information Administration (EIA 2005), Energy
Star (EPA, 2010) and the California Commercial End-Use Study (CEC 2006). However, these
sources are primarily aimed at benchmarking and are typically based on whole-building energy
consumption data or modeled/estimated energy loads by end use. One published study
monitored lighting in hotel guest rooms (Page and Siminovitch, 1999). The metering effort
described here was designed to provide a detailed and accurate picture of energy consumption at
this particular property to support building energy simulation modeling and the development and
analysis of energy efficiency measures, leading to a 30% or more improvement in energy
efficiency. However, the end-use consumption data reported in this paper are also generally
useful for describing end-use patterns in the large hotel sector, because the guest room
equipment and various other features of the hotel are typical of large hotels in the United States.
The property is a full-service hotel with sit-down restaurant, coffee shop, on-site laundry,
offices, and conference/banquet rooms, making it a challenging project. Hotels have a wide
diversity of energy uses, with spaces that may or may not be occupied on any given day, and
guest rooms that are occupied by different guests with varying habits. As a result, the metering
data collection for this project has been considerably more extensive and complicated compared
to other projects in the CBP Program.
Initial analysis of the 2009 electricity interval data from the utility (Dominion Power)
shows a relatively flat daily load curve in all seasons across all days of the week (Figure 2). The
lack of variation between weekdays and weekends is not surprising, given the hotel has a very
high occupancy rate and serves both tourists (including weekend stays) and business guests
3-311
(typically during the week). From these data, it appears that this hotel has almost 400 kW of
base load. The peak cooling load is about 200 kW (see Figure 2, August) and the hotel has
overall higher electricity use in the winter due to use of electric resistance heat1 in the packaged
terminal heat pumps (PTHPs) serving the guest rooms and the duct heaters serving common
spaces.
Figure 2. Daily Electricity Consumption (kW) based on Utility Interval Data in Selected
Months
In addition, the hotel uses natural gas for service water heating (a significant hotel load),
as well as kitchen appliances and laundry equipment. Table 1 shows the monthly energy
consumption for both electricity and natural gas in the year of 2009. At the site, electricity
During the metering period, many of the PTHPs were heating in resistance mode due to a software control issue.
3-312
consists of 73% of the total energy consumption. Converting to source energy use, electricity
consists of 89% of total Btus. The metering and monitoring effort was aimed at breaking down
these totals by end use.
The effort to understand the breakdown of energy by end use load involved: (1)
extensively metering various circuits and pieces of equipment in the hotel, (2) estimating loads
using information about equipment capacity and use, and (3) building energy simulation
modeling and calibration using EnergyPlus. This paper will discuss items (1) and (2); the energy
simulation modeling is underway and will be described in a future paper.
Table 1. Monthly Energy Consumption, 2009
January
February
394,642
March
342,010
April
258,781
May
273,499
June
318,592
July
350,831
August
391,549
September
276,165
October
280,615
November
316,914
December
506,513
4,274,106
Month
Total
1.35
4,876
0.49
1.17
6,103
0.61
0.88
5,441
0.54
0.93
5,390
0.54
1.09
4,773
0.48
1.20
4,313
0.43
1.34
3,829
0.38
0.94
3,360
0.34
0.96
4,447
0.44
1.08
3,995
0.40
1.73
4,016
0.40
14.58
54,661
5.46
3-313
rooftop unit (to provide outdoor ventilation air to guest floor hallways), the three points (preheat, re-heat, and fan motor) for the nine air handing units (AHUs), and various kitchen, laundry,
and other equipment circuits. For the lighting, we metered circuits serving various common
areas and conference/ballrooms with a combination of Hobo data loggers and current
transformers. In total, the metering devices include 96 watthour meters, 158 plug power meters,
91 temperature measurement devices, 32 relative humidity measurements, 109 current
measurement devices, and 64 lighting level measurements for a total of 550 measurement
devices. The installation was complete and tested on September 25, 2009. Data has been
downloaded on a monthly basis.
Metering Results: End Use Loads
Figure 3 shows daily consumption for October 2009 for guest rooms [chart (a)], hotel
heating, ventilation, and air conditioning (HVAC) systems [chart (b)], and other loads [chart (c)].
The charts also show average daily outdoor air temperature. Note that, for the purpose of
developing an estimate of total load in the hotel, the data for the 32 guest rooms and guest
hallway equipment (ice makers and vending machine) were scaled using guest occupancy rates
in the 32 rooms versus the hotel as a whole. The PTHP load in Figure 3 (a) is highly correlated
with average outside air temperature (R-squared is 92%). As currently configured, the balance
point for the guest rooms is approximately 55F; i.e., at 55F, the minimum PTHP consumption
occurs. Temperatures lower 55 result in significant heating loads, and at temperatures greater
than 55F, PTHP consumption increases due to cooling. The HVAC loads shown in Figure 3 (b)
for the common areas in the hotel, including duct heaters, air handling units (AHU), and rooftop
units (RTU), also indicate a high correlation between average outside air temperature and heating
and cooling consumption. Here the balance temperature appears to be closer to 60F, as the
majority of the HVAC in this portion of the building is running continuously with 100% outside
air. The other loads shown in Figure 3(c) are not correlated with outdoor temperature. Figure
4 shows monthly energy consumption by end use for the four metered months.
3-314
Figure 3. Daily Metered End Use Loads versus Outdoor Temperature (T out) in October
(a) Guest Room Loads
Guest Room Daily Energy Use and T out
5,000
80
4,500
70
4,000
60
3,500
50
3,000
2,500
40
2,000
30
PTHP
Refrig
Lights/TV/Other
T out (Avg)
1,500
20
1,000
10
500
0
0
1
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Day of Month
Figure 3 (continued). Daily Metered End Use Loads versus Outdoor Temperature (T out)
in October
(b) HVAC Loads in Common Spaces
Hotel HVAC Daily Energy Use and T out
80
2,500
60
50
1,500
40
1,000
30
20
70
2,000
AHU/Ventillation
Resistance Heat
Chiller/AC
RTU
T out (Avg)
500
10
0
1
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Day of Month
3-315
700
60
500
50
400
40
300
30
200
20
100
70
600
Lights
Kitchen
Vending/Ice
Laundry
Elevator
T out (Avg)
10
0
1
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Day of Month
3-316
Figure 4. Monthly Electricity End-Use for the Four Metered Months (Combined)
Distribution of End Use Energy (ave. kWh/day) Based on Metered Data
(Oct 2009 - Jan 2010)
Vending/Ice 218 Laundry 44
Elevator 141
Kitchen 233
Lights 467
RTU 11
Chiller/AC 240
PTHP 4,016
AHU/Ventillation 653
Refrig 196
Lights/TV/Other 193
3-317
Figure 6. Comparison of Loess Fits for New and Old PTHP Units
3-318
Independently, the unmetered loads do not show a strong correlation with either
occupancy or outdoor air temperature. Through regression analysis, we correlated both the
utility-supplied and project-monitored data with outside air temperature. The premise behind
this analysis is that if one data set has an appreciably different relationship to outdoor air
temperature, the resulting regression lines will not be parallel. As shown in Figure 8 the lines
are, by-and-large, parallel. This consistency highlights the relative constant nature of the
difference indicating this difference is not weather variant and is likely driven by miscellaneous
base loads.
Figure 7. Whole-Building Utility Data Versus Sum of Metered Data for December
Utility - Metered Data Comparison
December 2009
25,000
20,000
Utility Data
15,000
Meter Data
10,000
5,000
1 2 3 4 5 6 7 8 9 10111213141516171819202122232425262728293031
3-319
Figure 8. Regression of Utility and Metered Data with Outdoor Air Temperature
The estimation of unmetered loads began with a thorough review of audit notes, various
equipment lists, and installed metering points. Once all major loads were identified, they were
reconciled as being metered or not; those not metered were listed for inclusion in the estimation
exercise. The five main categories of unmetered loads are as follows:
Pumping. Includes all domestic cold water pumps, chilled water and condenser water
pumps, domestic hot water recirculation pumps, and the pool pump. Chiller, condenser
water, and pool pump energy use were scaled based on metered equipment run times;
domestic water pumps were calculated based on schedule.
HVAC. Includes unmetered exhaust fans and a variety of electric space heaters. It is
likely that this group has additional, yet-to-be discovered, electrical heating loads possibly including other space heat and pre/reheat coils. (Note: the pool is unheated.)
Lighting. Includes all unmetered lighting loads categorized using a detailed lighting
audit.
Kitchen. Unmetered kitchen energy use was derived based on an audit done by PNNLs
kitchen subcontractor. To prevent double counting, these values were input and then
reduced by the metered kitchen loads.
Miscellaneous Equipment. Includes miscellaneous appliance and equipment at the onsite Starbucks, the restaurant bar, the back office, and in the engineering areas.
Once identified, these loads were researched for rated energy use and schedule to
estimate whole building impact. The results of this effort are shown in Figure 9.
3-320
Note that, in this figure, the top series represents the total unmetered load, and the series
below are cumulative, such that they build up the estimated unaccounted load. The remaining
unaccounted-for load increases with time, indicating a potential for missing heating/ventilation
loads, as the outdoor temperature was generally decreasing over the analysis period.
Given the magnitude and complexity of energy use in this hotel, unaccounted-for electric
loads are expected. The above analysis reduced the average aggregate unaccounted-for loads
from 37.9% to 16.4%. The resulting breakdown of energy use is shown in Figure 10. (Note:
average over the four months was 13,285 kWh/day.) Further analysis is being conducted to
reduce the percentage of unaccounted-for energy use.
The penthouse where gas is used in three boilers and one water heater to generate
domestic hot water.
The laundry area where gas is used in two water heaters to generate hot water for clothes
washers, in three clothes dryers, and in one ironer (known in industry as a flat iron).
The kitchen where gas is used in a variety of cooking and warming equipment.
The challenge of this activity was disaggregating the various gas using devices listed
above and developing these into relative shares of the whole-building use. While end-use
metering of each device was desirable, the cost, complexity, and relative intrusiveness of gas
metering made this impractical.
3-321
Gas is metered at the building service entrance via a utility-owned rotary style gas meter.
Gas bills from this meter were reviewed. In November 2009, the utility meter was retrofit with a
pulse output device with full safety isolation. These pulses were now collected by a data logger
at 5-minute interval and downloaded on monthly basis.
Figure 10. Metered plus Estimated Electricity End-Use for October through January
Distribution of End Use Energy (ave. kWh/day) Based on Metered and
Estimated Un-Metered (Oct 2009 - Jan 2010)
Unaccounted For 2,124
Misc. 437
PTHP 4,016
Elevator 141
Laundry 44
Vending/Ice 218
Kitchen 997
Refrig 196
Lights/TV/Other 193
Lights 959
AHU/Ventilation 907
RTU 11
Chiller/AC 240
Resistance Heat 2,804
To estimate gas use for the domestic hot water and laundry systems, a number of proxy
measurement techniques were employed.
Predominantly, these relied on temperature
measurements of products-of-combustion either in exhaust stacks (boilers, water heaters, iron) or
combustion chambers (clothes dryers). In addition, flow (via a non-intrusive ultrasonic flow
meter) and temperature measurements were made in the Penthouse to assess gas used in
domestic hot water generation.
By its nature, proxy metering does not measure the variable of interest, rather a surrogate
for that variable. As such, the potential for inaccuracy can be significant. To minimize these
potential inaccuracies and to improve confidence in the result, secondary measurements or
calculations are always recommended. For this activity, all proxy measurements were verified
with secondary calculations typically based on manufacturer-provided energy-use intensities.
Gas use for the kitchen was calculated by a team from the Halton Inc. Figure 11 presents
the proxy measurement results by major end-use. Service hot water accounts for 51% of the gas
use, with kitchen and laundry accounting for about 25% each.
3-322
A comparison was completed whereby the sum of the parts gas use (i.e., domestic hot
water, laundry, and kitchen) was compared to the whole (i.e., the average annual daily gas
use). The result was that the former was calculated to be 6.3% greater than the latter. This
difference is well within the expected accuracy of a proxy analysis.
Figure 11. Average Daily Natural Gas Use by End Use
Conclusions
The work to date in this project, i.e., to measure, monitor, and estimate end-use energy
consumption in a 1970-era full-service hotel in the Middle Atlantic region, was a challenging
undertaking and provided a rich source of information about the major energy end uses in hotels.
A few major conclusions from the study include:
Heating of the guest rooms and the public areas is by far the largest consumer of
electricity, accounting for almost 60% of total electricity consumption, in the autumn and
winter months in this large hotel in the Washington, D.C. area, and would likely the
dominant seasonal load in any hotel in a similar climate zone. For new construction
projects, more efficient approaches for heating the guest rooms, instead of PTHPs, should
be evaluated. In a retrofit situation like the project described here, replacement of PTHPs
with the most efficient products available on the market is warranted and is likely to have
a significant impact on total energy use. The fact that the PTHPs were not operating
properly in this hotel and the energy management system is not fully functional probably
resulted in a somewhat higher heating load than would be seen in newer hotels with fully
functional energy management systems. For heating of public spaces, alternatives to
electric resistance heat and better control systems will be examined in the next phase of
this project.
3-323
Not surprisingly, energy consumption in both PTHPs and the other HVAC equipment in
the hotel is correlated with outside temperature. This study shows that the correlation is
very strong.
The rest of the loads in this hotel (and most hotels) are diverse, making the development
of an energy efficiency improvement strategy complicated. The kitchen consumes about
8% of the electricity and a quarter of the natural gas, hence about 10% of total energy use
in the winter (the percentage would be higher in the summer). Unlike office buildings or
some other commercial building types, lighting loads in a large hotel account for a fairly
modest percentage of electricity consumption (about 7% in the winter and a somewhat
higher percentage in the summer). Water heating consumes somewhat less than lighting
at about 6%.
Despite a rigorous metering campaign and subsequent analysis using calculations and
proxy measures, we could account for only 84% of the electricity load in this hotel. This
underscores the need for better understanding of miscellaneous electricity loads in
commercial buildings, including hotels. This issue will be further studied in subsequent
work.
References
CEC. 2006. California Energy End-Use Survey Consultant Report. CEC-400-2006-005.
California Energy Commission, Sacramento, CA.
DOE. 2010. Commercial Building Partnerships Program, U.S. Department of Energy,
Washington,
DC.
Last
accessed
on
May
11,
2010
at
http://www1.eere.energy.gov/buildings/commercial_initiative/building_partnerships.html
EIA. 2005. Commercial Buildings Energy Consumption Survey 2003. Energy Information
Administration, U.S. Department of Energy, Washington, D.C. Last accessed in May 11,
2010 at http://www.eia.doe.gov/emeu/cbecs/contents.html.
EPA 2010. ENERGY STAR for Hospitality and Entertainment. U.S. Environmental
Protection Agency, Washington, DC.
Last accessed on May 11, 2010 at
http://www.energystar.gov/index.cfm?c=business.bus_hospitality_entertainment
Page and Siminovitch. 1999. Lighting Energy Savings Opportunities in Hotel Guestrooms.
LBNL-44448. Lawrence Berkeley National Laboratory, Berkeley, CA. Last accessed on
May 11, 2010: http://gaia.lbl.gov/btech/pubs/pubs.php?code=Lighting%20Systems
3-324