Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Esp Troubleshooting Guide PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 65

ESP

Controls &
Electrical Systems

Troubleshooting
Guide

1998 NWL
312 Rising Sun Road
Bordentown, NJ 08505 USA
609-298-7300
All rights reserved under
Pan-American Copyright Conventions.
Published in the United States by
NWL
Bordentown, NJ
Unauthorized reproduction of this book
is forbidden by law.
Library of Congress Catalog Card Number
98-091393

DISCLAIMER: The information in this booklet is for


reference only. Neither NWL, nor any of its divisions,
makes warranties, expressed or implied, concerning the
application or use of this information.

Contents
Introduction
Section I
Concepts and Terminology:
Power Sources for
Electrostatic Precipitators
Abstract
Overview
The Current Limiting Reactor
(CLR)
The Transformer Rectifier (T/R)
The T/R Controller

1
2
2
5
9
23

Section II
Troubleshooting Tips
The Lamp TestA Simple
Means for Testing T/Rs
What Meter Readings Can Tell
You When Troubleshooting
Transformer Rectifiers (T/Rs)
Recommended Practice:
Oil Integrity Testing
Mineral Oil Filtering
Procedure for Transformer
Rectifier (T/R) Sets

33
34

40
43

47

Contents (continued)

Section III
Equipment Troubleshooting
Electrical Systems (overall)
T/R Set
T/R Controller
Rapper Controller
Meter Readings Low
Back Corona
Opacity Spikes

51
52
54
56
58
60
62
63

Section IV
Index
Glossary of Air Pollution
Control and ESP
Terminology
Clean Air Act Amendments
Conversion Factors Metric
Equivalents
Altitude-Pressure Temperature
Density Table of Air
Title III
Hazardous Air Pollutants

iv

65

66
108
109
111
113

ESP Troubleshooting Guide

Introduction
A Portable Informational
Resource on ESP Controls
and Electrical Systems
Competitive pressures on the utility industry mandate doing more with lessfewer (and younger)
maintenance personnel, tighter budgets and less time
to effect solutions to electrostatic precipitator control
system problems. Yet, in the utility industry, pollution control remains as critical as ever. While there
are a number of good resources available on the theory and operation of electrostatic precipitators
(ESPs)The Art of Electrostatic Precipitation, first
published November 1, 1979, immediately comes to
mindthere has not been a good book that provides
helpful diagnostic sequences one can use to deal
with day-to-day ESP electrical control problems.
Until now.
Welcome to NWLs ESP Controls & Electrical
Systems Troubleshooting Guide. Organized into four
sections, this handbook is designed to give maintenance essential, critical troubleshooting information
in an easy to read and understand format. Toward
that end it contains:
Quick overviews of key terms and concepts

along with descriptions of two critical components: the Current Limiting Reactor (CLR) and
Transformer Rectifier (T/R).
Practical, easy to use troubleshooting tips.
Equipment diagnostic decision trees for determining the cause of malfunctions among such
equipment as T/R Sets, T/R Controllers, and
Rapper Controllers and poor electrical performance indicated by low meter readings, back
corona and opacity spikes.
The troubleshooting decision trees follow a simple yes-no question format to make getting to the
root causes of problems quickly. In short, whether
you are new to the field or an old hand, the Troubleshooting Guide offers a wealth of information
right at your fingertipsincluding a helpful index.
The index contains important ESP terminology,
glossary of air-pollution control terms, listing of
Clean Air Act Amendments as well as useful metric
and altitude-pressure temperature density tables,
along with a listing of Title III hazardous air
pollutants.
As you can well imagine, it would be impossible
to cover every imaginable potential problem within
the confines of a short pocket book such as this one.
As a result, we have only focused on those our
experience shows to be most common and critical.
Please feel free to call our technical staff if you
have troubleshooting issues not covered in the confines of this guidewhether the equipment was
made by NWL or not. If required, we can also offer
expert field-service diagnostics, repair and replacement equipment.

Having designed and built more than 10,000 T/Rs


over the past ten years, NWL can provide both field
service and shop repair of almost any ESP T/R. Our
repair groupwith dedicated facilities and inventoryis extraordinarily responsive to equipmentrepair needs, providing one-to-four week turnaround
on most repairs.
Preventive maintenance is, of course, the most
cost-effective way to deal with problemsbefore
they occur. In fact, many T/R failures are often
caused by process and system changes that can only
be truly evaluated on-site. Our trained technicians
and engineers may also be called upon to evaluate
T/R and control-system performance under actual
operating conditions.
Finally, if you have questions you would like
answered in future editions of this Guide, please
contact us. We stand ready to help meet your pollution control equipment diagnostic and preventive
maintenance needs.

vi

Introduction

ESP Troubleshooting Guide

vii

SECTION I

CONCEPTS AND
TERMINOLOGY:

Power Sources
For Electrostatic
Precipitators
Abstract
Overview
The Current Limiting Reactor
(CLR)
The Transformer Rectifier
(T/R)
The T/R Controller

viii

ESP Troubleshooting Guide

Abstract
The purpose of this section is to provide a summary
of technical terms and concepts that are generally
employed in the field of commercial electrostatic
precipitation. The descriptions provided are limited
to the components and concepts associated with
providing electrical energy to the precipitator. This
system of components shall be referred to as the
ESP Power Supply.

the Voltage Control System which is a major subassembly of the control cabinet. The term Automatic
Voltage Controller or AVC is commonly used when
referring to the control electronics of the system.
To ESP Discharge
Electrode Field

Line in Typical
480 VAC 1 Phase

Overview
The purpose of the power supply for an electrostatic
precipitator (ESP) is to provide a source of high
voltage for the discharge electrodes of the system.
The power supply must accept incoming voltage
that is available from the plant; typically 380VAC to
690VAC single phase and output voltage levels
from 45KVDC to over 100 KVDC. The amount of
electrical current delivered by the power supply is a
function of the size and load of the ESP field. Current levels from 500 maDC to 1500 maDC are typical for industrial applications.
The dynamic nature of the ESP load imposes
severe stress on the power supply system due to the
requisite sparking and arcing that occurs within the
ESP field. The power supply must be capable of
sensing these disruptions and then be capable of
altering its output to clear these disruptions while
maximizing the efficiency of the ESP field.
The four major components of the system
include: the Control Cabinet, the Current Limiting
Reactor (CLR), the Transformer Rectifier (T/R) and

ESP Troubleshooting Guide

Current Limiting
Reactor (CLR)

Transformer
Rectifier (TR)

Control Cabinet
Voltage Control System

Figure 1 ESP power supply main components

The control cabinet accepts a line feed that is typically 480AVC and provides an output that is a
phase angle controlled power source for the system.
Phase angle control is established through the use of
silicon controlled rectifiers (SCRs). The level of
power delivered to the system is a complex function
of set points and feedback signals.
The major components of a typical control cabinet include the Automatic Voltage Control System,
the SCR system, panel meters, illuminated indicators and a circuit breaker.
The current limiting reactor is an iron core inductor that serves to limit current surges in the system
and to provide wave shaping of the T/R primary
current. The electrical rating and physical size for
the CLR varies widely for different size systems and

Concepts and Terminology

varied applications. For smaller systems, the CLR


may be either mounted inside the control cabinet, in
an attached enclosure to the T/R, or inside the T/R
oil tank. Large systems usually include a separate
stand-alone enclosure for the CLR.
The Transformer Rectifier accepts a phase angle
control feed signal typically up to 575VAC and
delivers a high voltage Direct Current (DC) voltage
to the ESP. Average output voltages for T/Rs range
from 55KVDC to over 100KVDC. T/Rs are oil
filled assemblies that house a step-up transformer
and a high voltage rectifier system. In addition, the
T/R provides feedback signals to the control electronics (AVC) to permit spark detection, waveform
analysis and metering for operator readout. The T/R
assemblies are usually mounted on the top of the
ESP and use pipe and guard systems for distributing
the high voltage power to the emitter electrodes.
The Automatic Voltage Controller (AVC) mounts
inside or on the door of the control cabinet. Modern
AVCs are microprocessor based systems available
from a variety of vendors. The AVC accepts feedback signals from the T/R as well as feedback signals from components in the control cabinet. The
primary output signal of the AVC is a signal that is
used to control the firing angle for the SCRs within
the control cabinet. The AVC continuously adjusts
the firing angle to achieve the desired performance
for the ESP field. Modern AVCs are usually
equipped with digital readout, keypad operator entry
system and a communication link for remote control
and monitoring.

The Current Limiting


Reactor (CLR)

Concepts and Terminology

ESP Troubleshooting Guide

A. Physical Location
The Current Limiting Reactor (CLR) is a large
inductor that is used in the primary circuit of the
T/R. The purpose of the CLR is to limit the maximum current in the T/R primary and to provide a
means of shaping the wave form of the Power Supply output. The CLR can be physically located
inside the T/R tank, inside the T/R junction box or
in a separate free standing enclosure. The choices
for locating the CLR are primarily economically driven for systems below 200 amps. At currents above
200 amps, the heat generated by the CLR usually
makes the choice of a separate enclosure mandatory.

B. Inductance
The unit of measure for reactors is the henry. The
ability of a reactor to impede the flow of AC current
is termed inductance. The inductance of CLRs is
usually from 5 to 20 millihenries (.005H to .020H).
The CLR value that is required is based upon the
total system impedance that is desired for the power
supply. This system impedance limits the maximum
amount of current that can flow in the primary circuit and is usually specified as percent impedance.
A value of from 30% to 50% is usually employed.
The impedance of the reactor can be calculated by:
Zclr = L x (2 x x f) = L x 377
where Zclr = impedance in ohms
L = inductance in henries
= 3.1415

f
= frequency in hertz
The percent impedance that the CLR provides is
calculated by:
%Z = L x 377 x I x 100
V
where
%Z = percent impedance
L = inductance in henries
I = rated primary current
V = system voltage (typically 480 or
575 VAC)
The same formula can be used for calculating the
inductance required for a desired % impedance by:
L =
V x %Z
I x 377 x 100
The system impedance also includes the reactance of the transformer which is typically 5% to
10%. A system impedance of 50% limits the maximum AC current to twice the rated current. At 33%
the limit is three times the rated current. When specifying the CLR, the inductance in henries, the primary rated current, and the anticipated spark rate
must be given. Since the ESP will periodically
spark, the actual average current that the CLR will
need to withstand is greater than the T/R rated
current.

C. Limiting Peak Current


The term Current Limiting Reactor is somewhat
misleading. Although a system impedance of 50%
will limit AC current to twice its rating, this is of
limited value in light of the fact that neither the

ESP Troubleshooting Guide

CLR nor the T/R can withstand such current for any
length of time before failing. The current limiting
characteristic of the CLR that is most important is
the ability to limit the rate of rise of current over a
half line cycle (8.3 milliseconds). When a severe arc
occurs in the ESP, the voltage at the point of the arc
drops to near zero. The amount of current that will
flow through the arc is limited by impedance of the
various feed components, including the transformer,
CLR as well as the inductance of the ACR and HV
buss work.
In addition, the peak current through the arc is
increased by the capacitive discharge of the ESP. As
the current through the arc increases, the CLR will
be subject to the full line voltage. A 50% impedance
system will limit the peak current through the primary to about two times the rated current. In addition, the rate of rise in current through the primary
circuit and the SCR controller will be limited to
remain within the rating of the SCR devices.
The peak current that accompanies arcs imposes
a severe stress on the CLR. The CLR must be capable of withstanding repeated arcing with the resultant two times rated current without adverse effect.
To accomplish this, both conductor size and core
size must preclude magnetic saturation during peak
current conditions. If the core of the CLR were to
saturate, then the inductance would diminish to near
zero and the CLR would cease to contribute to limiting fault currents.

Concepts and Terminology

D. CLR Wave Shaping


The second function of the CLR is to smooth out
the pulsating waveform to the ESP. The full wave
rectified signal that is supplied to the ESP is actually
a pulse train at 120 pulses per second. If the system
was permitted to run at full conduction, then the
output signal would tend to be a sinusoidal. In reality, however, the waveform of the primary current as
well as the secondary voltage (KV) is affected by
the conduction angle of the controller, the system
inductance, the capacitance of the ESP and the secondary current level.
The wave shape of the T/R primary current is
affected by the amount of reactance in the primary
circuit. This wave shaping results in several benefits
to the overall system. These benefits become particularly important for systems that are running at conduction angles of 90 degrees or less (50% conduction or less). As the inductance of the primary
circuit is increased, the percent conductance at a
particular load level can be significantly increased.
The benefit that is realized is the ability to increase
the average current to the ESP before sparking
occurs. In many instances, this increased current
level results in better collection efficiency for the
ESP.

ESP Troubleshooting Guide

The Transformer
Rectifier (T/R)
The T/R is a critical component of the ESP power
supply. The purpose of the T/R is to accept an AC
power feed from the SCR/CLR control system and
convert the 0 to 480VAC (nominal) signal to the
required level of high voltage. Transformer Rectifiers are oil filled tanks with a low voltage junction
box and one or two high voltage bushings. Single
bushing T/Rs are referred to as full wave units and
dual busing T/Rs are referred to as double half wave
units.
Figures 2 and 3 show the electrical configuration
of a full wave and a double half wave unit. T/Rs are
usually mounted on the roof of the ESP. Large ESPs
may require 50 or more T/Rs. The electrical components of a T/R include the high voltage transformer,
the diode assembly, the air core reactor (ACR), the
feedback voltage divider and a ground switch which
may be integral with the T/R or mounted in the bus
duct.
A critical component of the T/R, that is not
shown in the electrical drawing, is the dielectric
fluid that fills the T/R tank. This fluid provides a
means for electrically insulating the internal components as well as a means for dissipating internally
generated heat.

Concepts and Terminology

External
Bushing

Diode
Bridge

Power
Feed

Air Core
Reactor
Voltage
Divider

mA
Feedback
KV
Feedback

mA
Resistor

Low Voltage
Junction Box

Figure 2 Electrical drawing single bushing full wave transformer


Bushing 1

Bushing 2

Air Core
Reactor 1

Power
Feed

Diode
Bridge

Air Core
Reactor 2
Voltage
Divider 1

Voltage
Divider
2

mA 1
Feedback
mA 2
Feedback
KV 1
Feedback

mA
Resistor
mA
Resistor

KV 2
Feedback
Low Voltage
Junction Box

Oil Filled Tank

Figure 3 Electrical drawing dual bushing (double half wave) transformer


rectifier (TR)

A. T/R Dielectric Fluids

the fractional distillation of crude petroleum. Mineral oil is the most commonly used dielectric fluid for
T/Rs.
2. Silicone Oil: a linear polymer liquid termed polydimethyl siloxane or PDMS. This fluid has a higher
fire point than mineral oil. Silicone fluid is normally
used for indoor applications or when decreased
flammability is deemed necessary. Silicone fluid
costs considerably more than does mineral oil. Silicone fluid is slightly more viscous than mineral oil
for temperatures above 10 degrees Celsius and
sometimes requires additional measures be taken to
facilitate heat transfer (additional radiator or bigger
tank). Usually, however, this is not a critical parameter if tank size is conservatively designed.
3. High Molecular Weight Hydrocarbon: This
dielectric fluid is a less costly alternative to silicone
fluid for installations needing reduced flammability.
HTH fluid is a petroleum based product. Since HTH
is significantly more viscous than both silicone and
mineral oil at temperatures below 100 degrees Celsius, heat transfer characteristics at lower temperatures require extra consideration in the T/R tank and
radiator sizing. The use of this dielectric could be a
problem when used in a cold environment where
T/Rs are allowed to cool off. This problem is overcome by gradually bringing the T/Rs up to full
power to allow the fluid to heat up.

Three types of fluid are presently used for T/R


dielectric fluid.
1. Petroleum Based Oil: also known as transformer oil or mineral oil. This oil is obtained from

B. The Transformer

10

Concepts and Terminology

ESP Troubleshooting Guide

The step-up transformer is the major component of


the T/R system. Transformers designed for ESP

11

applications employ design techniques specifically


developed for this use. ESP transformer coils must
be capable of withstanding repeated sparking and
arcing of the load. Disruptions such as these, along
with occasional shorted fields, cause current surges
well above the system ratings. These surges cause
the windings of the transformer to exert considerable physical force on the system insulation and
support mechanism. If not properly accounted for,
these forces will eventually cause premature
destruction of the insulation and system failure. The
transformer design must integrate the many specified requirements of the system. Included are
1. Turns ratio of the transformer (A 400 VAC to
40 KVAC transformer requires a ratio of 400
to 40,000 or 1 to 100).
2. The peak secondary voltage to determine the
internal insulation and clearances.
3. The average/peak secondary current required.
4. The voltage and current form factors as
determined by the impedance of the load.
These form factors define the relationship
between the average and RMS values of the
output waveforms. There is a separate form
factor for the load voltage and load current.
These form factors are used to size the transformer to provide the desired average output
voltage and current for a specific load
impedance.
5. The maximum temperature rise allowed as
determined by the ambient air temperature
extremes.
6. The maximum available primary voltage as

12

ESP Troubleshooting Guide

determined by the feed voltage and the primary reactance of the system.
7. The KVA rating of the system to determine
conductor sizes as will as core size.
The transformer is typically the most reliable
component in the system. Failures of transformers,
however, do occur and can often be placed in two
general categories. The first is degenerative failure
that is caused by the long term breakdown of a component part. If the transformer is used within its
rated parameters, then degenerative failure is most
likely due to a defect of material or workmanship.
the second failure category is overstress failure.
Overstress failure is caused by subjecting the transformer to either excessive voltage or excessive current. Overstress failure is usually the case for transformers that fail between five and twenty years of
operation.
Degenerative Failure
Of the components and materials used on T/Rs, the
layer insulation on the transformer winding determines the life expectancy of the system. Modern
designs use Kraft insulation. The life expectancy of
the insulation is a function of stress level (voltage
across the insulation) and temperature of the insulation material. The operating temperature of the insulation is usually assumed to be 10 (C) higher than
the overall temperature rise of the winding. The 10
margin is based upon the assumption that heat transfer between the coils and the oil can never be
absolutely uniform. The expected life of the insula-

Concepts and Terminology

13

tion for modern designs is 34 years if the unit is


continuously subjected to rated current and rated
voltage (REF ANSI C57.91.1981). Degenerative
insulation failure after less than 15 years, although
possible is statistically very unlikely, unless there
are other contributing factors.
Degenerative insulation failure can be caused by
abrasion caused by excessive vibration and physical
movement of the transformer windings. Vibration is
induced by the 60 cycle AC current while coil movement is induced by current surges. ESPs by nature
present a harsh load for transformers due to the
sparks and arcs that are expected. T/Rs designed for
such applications must therefore employ extraordinary measures to tolerate such conditions. If such
measures are not employed or improperly employed,
then the abrasion of the coils will occur.
Stress Failure
Stress failure of the T/R occurs when the unit is
subjected to either overvoltage or overcurrent conditions. Operators should be suspicious of overstress
failure mode if a T/R failure was preceeded by some
change that effected operating levels. Common
causes for such changes include change in the fuel
in use and change out of the T/R controller. But a
change in fuel and the resultant change in ESP operating conditions should not cause overstress of the
T/Rs. The task of operating the T/R within their
design limits is accomplished by the T/R controller.
The controller should limit both the KV level and
the current level as well as the spark rate to safe
limits. The potential for problems with overstress of

14

ESP Troubleshooting Guide

the T/R become greater when controls are not properly calibrated and/or if the system feedback does
not include the KV signal.

C. The Diode Assembly


1. Function in T/R
The diode assembly of the T/R converts the high
voltage AC output of the transformer to a DC signal. The diodes are configured as a full wave bridge
with the positive output of the bridge connected to
earth ground. The negative output is routed through
an air core reactor and then to the high voltage
bushing. The diode assembly is made up of a series
string of many diode junctions. This series string of
diodes should be capable of blocking at least twice
the peak output voltage of the T/R. A typical 45 KV
T/R will have a peak output voltage in excess of 75
KV. The diode assembly must, therefore, have an
effective PIV (peak inverse voltage) of at least 150
KV.
The use of a series string of diodes to obtain high
blocking voltage requires that special measures be
employed to assure proper voltage sharing. Improper voltage sharing is caused by variation of the
reverse leakage of individual diode junctions. This
variation results in an uneven distribution of the PIV
among the diodes. The wide tolerance that is characteristic of standard silicon diodes will cause the
devices with the lowest leakage to accept a disproportionate share of the total voltage. If this phenomenon is permitted to occur, then the diodes will fail
in a domino fashion.

Concepts and Terminology

15

2. Types Used
Prior to 1980, T/R manufacturers employed the use
of RC (Resistor-Capacitor) compensation to address
the voltage sharing problem. This approach provided
a means of using standard 1000 volt diodes in a
string with each diode connected in parallel with a
resistor and capacitor. The resistor serves to limit the
DC reverse voltage to be shared, while the capacitor
distributes high frequency AC voltages caused by
sparking and/or ringing of the ESP system.
Since 1980, several T/R manufacturers have
employed controlled avalanche diodes and eliminated the need for the RC compensation. These
diodes are now available with ratings exceeding
10,000 volts PIV for each device. Avalanche diodes
are screened to insure closely matched reverse leakage characteristics. Because of this, they can be
relied upon to properly share the total reverse voltage without the need for parallel RC compensators.
T/R bridge assemblies that use such diodes can
usually be assembled on a single circuit board that
is mounted in the T/R tank. The RC compensated
technology required large assemblies that are populated with many small circuit boards to make up the
diode bridge network. Such assemblies consume
considerable space in the tank, are prone to mechanical failure and are difficult to replace in the event
of failure.

occur if the power supply is allowed to exceed its


rated current output for an extended period of time.
Since most T/Rs in service have a source impedance
of about 50%, the T/R can actually deliver twice its
rated current.
In cases of disruptions such as severe arcs or
shorted output, the system relies upon the controller
to maintain the output current to a safe level. When
such disruptions occur, the current may instantly
rise to twice rating but must be quickly reduced by
the controller to preclude damage to the T/R. If an
overcurrent condition is permitted to continue,
excessive heat is generated by the diodes. As the
diode junctions heat to beyond their rated temperature, the bridge will fail.

3. Failure Modes
The two common causes for diode failure are excessive electrical stress due to either overcurrent or to
overvoltage. Diode failure from overcurrent may

Heat Related Failures. In many cases of T/R overcurrent, the heat generated by the diodes cause the
diode junctions to exceed their maximum operating
temperature. When this occurs the diodes will fail.
Occasionally the heat generated will be sufficient to
cause the solder that fastens the diodes to the PC
board to melt away. As the solder melts and is displaced with dielectric fluid, arcing occurs between
the diode lead and the PC board. This arcing results
in the breakdown of the dielectric fluid. Carbon and
cyanide gas are two of the resultant components of
this breakdown. If the internal arcing continues,
then the generated carbon will eventually be attracted to the transformer windings and cause failure of
the transformer. If excessive cyanide gas is generated, then the air space between the tank lid and the
oil will become explosive.

16

Concepts and Terminology

ESP Troubleshooting Guide

17

In some cases of overcurrent the diode junction


fails to an open condition prior to melting the solder. In such cases, the open circuit diode will be
subjected to the entire output voltage of the T/R.
This voltage is sufficient to permit arcing around the
failed diode creating carbon and cyanide. In addition, the remaining diodes will be subject to excessive voltage and in turn fail. In some cases this
process may take place within a few minutes after
which the T/R will cease to perform. Such rapid
failure modes are less catastrophic because the oil is
usually not severely contaminated and the T/R can
be repaired on-site. If the failure, however, takes
days, then the oil will be severely contaminated and
the T/R will require major rebuild in order to be put
back in service.
Voltage Related Failures. The second cause of failure of the diode bridge is an overvoltage condition.
The diode bridge must be rated for a PIV of at least
twice the peak output voltage of the T/R. Intuitively
it could be assumed that such a condition could not
occur. There are, however, two ways that T/Rs are
subject to overvoltage. The most common cause of
overvoltage is a malfunctioning or misused controller. A less common cause of overvoltage is voltage ringing of the T/R and the ESP.
The provision for KV limitation of the T/R output
is a standard feature of most controllers. To accomplish this, a KV feedback is needed. This feedback
signal is sometimes either not available because of a
lack of voltage dividers in the T/R system or
because of a feedback failure. Some controllers use

18

ESP Troubleshooting Guide

the primary voltage in conjunction with the turns


ratio to calculate the KV value. This calculated
value, however, can never be truly accurate because
of the unknown load characteristics of the ESP.
When T/Rs are specified, the primary voltage rating is usually 10% to 20% lower than the actual
feed voltage. This primary voltage rating (usually
400 VAC for a 480 VAC feed) is specified so that
full KV output can be supported under full current
conditions. A 480 VAC system with 50% impedance
can only deliver about 400 VAC to the transformer
primary under full current conditions because of the
voltage drop in the reactor (CLR). If, however, the
T/R is under no load conditions (i.e. open circuited),
then entire feed voltage of 480 VAC can be
impressed upon the primary. This 20% overvoltage
on the primary results in a similar overvoltage on
the secondary. In addition, under open circuit conditions the output bushing will charge to the peak
voltage of the secondary voltage waveform. A 55
KV, T/R will charge to approximately 92 KV.
Bridge failure under such conditions depends upon
the bridge rating. Its ability to survive such stress
depends upon the amount of safety factor designed
into the T/R.
High Voltage Ringing. The second cause of
overvoltage condition is ringing of the secondary
circuit. This phenomenon is fairly unusual but does
occur under some conditions. Ringing is a term that
denotes resonant oscillation of the secondary circuit.
An important element of the T/R secondary circuit
is the ESP box itself. A resonant circuit is created

Concepts and Terminology

19

whenever a capacitor and an inductor are connected


together. The plates and wires of an ESP have both a
resistive and a capacitive component. Prior to the
onset of corona, the ESP is essentially a capacitive
load to the T/R. As corona current increases, the
resistive component of the ESP increases.
Ringing or resonant oscillation is more likely
to occur when sparking occurs under light load conditions. Under such conditions, a tank circuit is
made up of the ESP acting as a capacitor and a combination of the transformer, the ACR and the high
voltage bus work as an inductor. Oscillation will
occur at the resonant frequency of this system which
is typically a few KHz.
The existence of ringing can be observed through
use of an oscilloscope on the secondary feedback.
Ringing can be detected by monitoring KV feedback using an ESP spark as a scope trigger. If a
problem exists, then a damped oscillation at 15
KHz will be observed with peak voltages in excess
of T/R ratings.

D. The Voltage Divider

ing to obtain KV feedback.


The voltage divider is a resistor network connected to the high voltage bushing. This divider is made
up of a series string of many resistors. Divider values of 50 megohm, 80 megohm and 120 megohm
are typically used. The high resistance is used to
create a current source that is typically a 01 milliamp that is proportionate to the full scale voltage
of the T/R. A 50 meg divider provides 01 ma feedback signal that corresponds to 050 KV output.
The output of the voltage divider could be used to
directly drive a 1 ma meter with an appropriate
scale or it could be converted to a voltage signal. A
10 K ohm resistor is commonly used to provide a
010 volt feedback signal. This approach permits
the physical location of the resistor to be close to
the T/R and reduce the possibility of high voltage
signals in the control area. Many of the modern digital controllers use a 05V or 010V signal for KV
feedback for metering and for spark detection. This
low voltage feedback can be used to drive an analog
voltmeter with an appropriate scale that is wired in
parallel with controller.

1. Function: The voltage divider provides a means


for supplying a low voltage feedback signal that is
proportionate to the KV output of the T/R. This signal is used for both metering and for control purposes. Most modern T/Rs include a voltage divider that
is mounted under fluid within the T/R tank. Many of
the older systems, however, did not use KV feedback as a control or metering parameter. In many
such installations, external voltage dividers may be
mounted outside the T/R near the high voltage bush-

2. External Dividers: The external voltage divider


network is usually mounted in a protective insulating tube of PVC or fiberglass. The divider must be
capable of dissipating the heat that is caused by the
maximum voltage (KV) output of the T/R. For a 50
meg divider, the power at 50KV is 50 watts. The
physical configuration of the external divider must
provide a means of dissipating this energy (heat) at
a rate sufficient to maintain the resistor temperature

20

Concepts and Terminology

ESP Troubleshooting Guide

21

within its rated maximum.


Voltage dividers are simple devices and are easily
maintained. Failure of the divider is often caused by
mechanical or thermal stress. The testing and
replacement of dividers is usually a task well within
the skills of plant personnel. The testing of dividers
for proper resistance could be accomplished through
the use of a general purpose digital meter although
the use of a Megger is preferred. If a general purpose multimeter is used, then the divider should be
disconnected from the T/R; connections should be
made through use of high voltage clip leads. Any
stray charge or capacitance that may exist will affect
readings in the 50 meg+ range.

E. The Air Core Reactor (ACR)


1. Function: The Air Core Reactor (ACR) provides
a means for protecting the diode bridge from high
voltage transients that occur within the ESP.
ACRs used in modern T/Rs are rated from 20 to 50
millihenries. As the ESP sparks and arcs, the full
ESP voltage will be impressed across the ACR.
ACR design must provide sufficient layer insulation
and clearance to accommodate such voltage. Typical
failure mode for ACRs is a sparkover of the layer
insulation. Since the ACR is physically much smaller than the transformer secondary coil, it is subject
to extreme voltage stress. In the event of any contamination of the dielectric fluid, the ACR is often the
first component to fail.

of T/Rs results in severe stress of ACRs. The Double Half Wave system provides a means of exciting
two isolated electrode fields from one T/R. Each
field is energized by half of the DC output to provide a 60 Hz pulse train, with 8.3 milliseconds on
and 8.3 milliseconds off. While seldom used today,
this configuration was often employed during the
late 1960s. During that period, several installations
achieved increased efficiency through the use of the
pulsing effect of the split output.
In addition, this approach provided the benefit of
isolating a faulty field through the use of the HV
switch that is provided. Potential problems for the
power supply of the DHW include: unbalanced load
for the transformer, complex spark reaction for the
controller and capacitor dumping and ringing
through the ACR. The ACR problem occurs when
one of the fields sparks and discharges both fields
through the ACRs and the switch. Many installations that featured the DHW configuration now connect the two bushings together to avoid excessive
stress of the T/R components.

The T/R Controller

2. Double Halfwave: The Double Half Wave use

The purpose of the T/R controller is to accept the


incoming line voltage from the power source (typically 480 VAC) and provide a variable voltage to
the T/R set. Modern day controllers utilize fast acting Silicon Controlled Rectifiers (SCRs) to phase
angle control the primary voltage. Older controllers
utilized much slower saturable core reactors to vary
the voltage. The exact voltage that the controller

22

Concepts and Terminology

ESP Troubleshooting Guide

23

will output to the T/R is a function of a number of


variables that are dependent upon the precipitator
load and the T/R set being used. The controller will
try to maintain the highest possible voltage on the
precipitator field for varying load conditions. The
highest possible voltage is typically the sparkover
voltage of the field. The controller must also protect
the T/R set from sparks or arcs that occur in the
field. It must also make sure that the system is not
operating at any current or voltage levels that
exceed the design ratings of the T/R set.
Modern controllers utilize microprocessor circuits
to analyze feedbacks and operating setpoints to
determine the proper output levels. These microprocessors also provide data acquisition, graphical
trending of metering values, graphical V-I curve of
the precipitator field and an assortment of other features. Most control enclosures contain the following
major components.

shunt trip circuit breaker instead of a contactor.

C. SCR Assembly
The SCR assembly is the main device used to regulate the primary voltage to the T/R set. The assembly is made up of two SCRs connected in a reverse
polarity parallel configuration.

Input Voltage

Output Voltage

SCR Assembly

The contactor is the main device for energizing and


de-energizing the primary power to the T/R set. The
control circuits open the contactor to remove power
if an system alarm occurs. Some controllers use a

One SCR controls the positive half cycles while the


other controls the negative. The SCRs are protected
from dv/dt damage by a resistor capacitor snubber
network and a metal oxide varistor. They are also
fused to protect against overcurrent conditions.
The SCR will turn on when two conditions are
simultaneously met. The SCR must be forward
biased and the gate must be given a trigger signal.
By varying the time delay between when these two
conditions occur, the amount of time that the SCR is
on will also vary. The amount of time that an SCR
is on is called the conduction time. It is more commonly referred to as the conduction angle and

24

Concepts and Terminology

A. Circuit Breaker
The circuit breaker is used to protect the system
from short circuits that occur primarily on the 480
VAC line. It also acts as a lockable disconnect
device for removing power from the controller for
maintenance purposes.

B. Contactor

ESP Troubleshooting Guide

25

expressed in terms of degrees. Zero degrees conduction means that the SCR is not gated on, and 180
degrees conduction means the SCR is fully gated
on.

D. Metering Circuits
Most control enclosures also contain analog meters
in addition to the digital metering displays of the
microprocessor circuits. The analog meters provide
a better visual trend of the readings under sparking
conditions of the precipitator.

E. Alarm Circuits
Alarm circuits are used to monitor the system and
de-energize the T/R set if certain conditions occur.
The common alarm conditions are:
OvercurrentProtects the T/R and controller
from operating at current levels above the T/R ratings.
Undervoltage DCThis occurs if the output
voltage of the T/R remains low (typically under 10
KVDC) for more than a short period of time (typically 30 seconds). Undervoltage alarms usually indicate a shorted field, a shorted T/R, or a malfunction
in the controller.
Overvoltage DCThis occurs if the output voltage of the T/R set goes above the rating of the set.
This alarm usually indicates a problem with the
power system or an open circuit in the precipitator
field.
SCR UnbalanceIf both SCRs are not operating at the same conduction angle, a DC voltage will
be fed to the T/R primary. This can cause the T/R

26

ESP Troubleshooting Guide

core to saturate and draw a large amount of DC current. This type of alarm usually indicates a problem
with the SCRs or the triggering of the SCRs.
T/R OvertemperatureThis monitors the temperature switch on the T/R set. If the oil gets too hot
(typically 95 C) the unit will shutdown. This alarm
indicates that the system may be operating at too
high a current, or that there is a problem in the T/R
set.
T/R Liquid LevelThis monitors the level
switch on the T/R set. If the dielectric fluid gets too
low, the unit will shutdown. This alarm usually indicates a lead in the T/R set. Not all T/Rs have this
feature.
SCR OvertemperatureThis monitors the temperature switch on the SCR heatsink. If the heatsink
gets too hot, it indicates either a problem with the
SCRs, or the ventilation system in the enclosure.
Not all SCR assemblies have this feature.

F. Limit Circuits
There are certain conditions that occur within the
system that require some type of corrective action,
but not necessarily turning the T/R off. With limit
circuits, the conduction angle of the SCRs will automatically change to try to correct the condition. The
most common limit circuits are:
Current LimitIf the current starts to exceed a
preset level, the controller will reduce the conduction angle of the SCRs to whatever is required to
maintain that level. Because of this, a T/R set can
operate a shorted precipitator field and never exceed

Concepts and Terminology

27

G. Process Control
The controller must perform certain process control
also. The efficiency of the precipitator is directly
related to the voltage applied to it. The higher the
average voltage on the fields, the better they will
perform. The controller must find the optimum voltage to operate at. The highest voltage that can be
applied to any field is the voltage at which that field
sparks. The controller will continually increase the
output of the T/R until one of the following conditions occurs:
a. A spark or arc occurs
b. Current limit is reached
c. Voltage limit is reached
d. Maximum conduction angle is reached
By continually searching for the highest possible
operating voltage, the controller is able to optimize
the collection process for any load variations.

H. Spark/Arc Response
The controllers search for the maximum voltage

28

ESP Troubleshooting Guide

that can be applied to a field, actually causes the


field to spark. The controller must also protect the
system from the effects of this sparking. There are
two different types of sparkovers that occur, a spark
and an arc. The controller should recognize when
each type occurs and respond accordingly.
SparkA spark is a relatively small discharge
within the precipitator that self-extinguishes with no
increase in the base waveform current.
Since the spark is gone by next half cycle, the
controller really doesnt have to protect against any
large fault currents. But if it takes no control action,

another spark will occur on the next half cycle. Each


time a spark occurs the electrostatic field is discharged. If the field is rapidly sparking in this manner, it will never reach its optimum voltage. The

100%
AC SW Voltage

the current rating of the T/R.


Voltage LimitIf the output voltage starts to
exceed a preset level, the controller will reduce the
conduction angle of the SCRs to whatever is
required to maintain that level. This is used to protect a T/R set from operating at too high a KVDC
output.
Conduction Angle LimitThis is used to place
the unit in manual operation or to limit the conduction angle from exceeding a certain value.

SB - 10%
RAMP
= 1 Sec.

SB = 15%
RAMP
= 1 Sec.

10

Time Seconds

Concepts and Terminology

29

are off is called the quench time. A fast ramp


then quickly increases the voltage to the spark setback level where the slow ramp then increases it
back to the arc over voltage.

I. Intermittent Energization
This mode allows the primary voltage to the T/R to
be pulsed a variable number of half cycles on and a
variable number of full cycles off. This pulsing may
be helpful for back corona conditions or for power
savings.

Primary Current

proper control response is to reduce the conduction


angle of the SCRs a small amount on the next half
cycle. This setback will reduce the KVDC in the
precipitator so as to stop another spark from occurring. A slow ramp then increases the voltage back
to the original sparkover point.
ArcAn arc is a large disruptive discharge within the precipitator that will not self-extinguish. During an arc large levels of fault current continually
flow. The level of that current is determined by the
system impedance but is usually high enough to
damage the SCRs or the T/R rectifiers.

To stop this from happening the controller turns


the SCRs off during the next half cycle. They will
stay off for a certain duration of time. This reduces
the KVDC to zero allowing the arc to extinguish or
quench itself. The period of time that the SCRs
Slow Ramp =
1 Second

AC SW Voltage

100%

SB = 25%
Quench =
1 Cycle

Fast Ramp =
5 Cycles

5
Time (Seconds)

30

ESP Troubleshooting Guide

Care must be taken that the off time is always


configured in full cycles of voltage. If half cycles are
used the voltage being applied to the transformer
when it turns on would be the same polarity as the
voltage that was applied when it turned off. This
could possibly cause the transformer core to saturate.

J. Back Corona
Back corona is a condition that occurs primarily
with high resistivity ash loads and is usually associated with low sulfur coals. The resistivity of the ash
determines the voltage drop across the dust layer on

Concepts and Terminology

31

the collecting and electrode surfaces. If the resistivity of the dust is high enough, the voltages will be
high enough to cause a back corona to be generated
in the dust layer. This back corona generates positive ions that neutralize the negative charge from the
electrodes. The loss of the space charge also causes
a loss in the precipitator efficiency. Back corona can
be diagnosed by performing a V-I curve. If the curve
goes vertical, meaning small changes in KV cause
large changes in mADC, back corona is present. If
the curve bends backwards, meaning the KV actually decreases and the MADC increases, there is a
severe back corona condition present.

SECTION II

Troubleshooting
Tips
The Lamp TestA Simple
Means for Testing T/Rs
What Meter Readings Can Tell
You When Troubleshooting
Transformer Rectifiers (T/Rs)

Recommended
Practice:
Oil Integrity Testing
Mineral Oil Filtering Procedure for
Transformer Rectifier (T/R) Sets

32

ESP Troubleshooting Guide

33

TROUBLESHOOTING TIP

The Lamp Test


A Simple Means For
Testing T/Rs
Often, the functional health of a T/R needs to be
determined. The T/R Lamp Test can be performed
on T/Rs that are already installed as well as on T/Rs
that are disconnected.
When testing an installed T/R, the T/R Lamp Test
can be performed either at the T/R location or at the
Controller location. While the Lamp Test should by
no means be considered a complete T/R test, it does
provide a means of ruling out many common failure
modes. In addition, the test provides a high confidence
level that the T/R system is safe to energize with a
fully powered control system (typical 480 VAC).
But before you proceed with this test, several
warnings are in order:
1. The tests described results in high-voltage output on the T/R high-voltage bushing as well as
the possibility of high voltage on feedback
connection points.
2. This test should ONLY be performed by persons familiar with high-voltage systems.

Connected to 120VAC power source available


as a standard wall plug
A recommended lamp size of 60 to 100 watts will
limit the maximum current draw to about 1 ampere
under a short circuit condition. The test operator can
draw various conclusions by simply observing the
brightness of the light bulb. In addition, if the test
operator has the skill to use other instruments such
as a volt/ammeter and/or an oscilloscope, significant
additional information can be assessed as well.
The basic indicator of the lamp test is the observation of a dull glow of the light bulb. In general,
this will indicate that the T/R is in operable condition (a bright illumination or no illumination indicates an abnormal condition). If an abnormal condition is suspected then this hookup can provide a
configuration for further testing.

Test rig assembly

The lamp test uses an ordinary incandescent light


bulb to permit low level energization of a T/R. This
technique can provide excellent information about
the units functionality. The test setup consists of:
A light bulb that is wired in series with the T/R
primary winding

1. Connect a wire of desired length between the


hot side of the wall plug and one terminal (or
wire) of the lamp socket (the hot side is normally the smaller prong).
2. Connect a wire to the return side of the wall
plug long enough to reach the test connection
point. The loose end of this wire should be suitably dressed (lug or clip) to hook up to the T/R
connection point. This is the Return Wire.
3. Connect a wire to the second terminal or wire
of the lamp socket long enough to reach the connection point (same as wire in step 2). This is the
Hot wire.
4. Install the light bulb.

34

Troubleshooting Tips

Summary

ESP Troubleshooting Guide

35

Current Limiting Reactor

4.

T/R Set
Transformer

5. Verify proper connections by connecting the


Hot wire to a ground point, plugging in the
wall plug and observing the lamp illuminating
brightly.

Configuration for Installed T/R


1. The hookup to the system may be either at the
T/R junction box or at the controller output
terminals. In all cases the circuit breaker feed to
the T/R must be opened.
2. The High Voltage connection (bushing) to the
ESP field may be open or connected at the
operators option. Upon conducting the test,
High Voltage in excess of 20,000 volts will be
present on the T/R output. All interlocks and
safety precautions for the ESP and High Voltage
duct work MUST BE OBSERVED!
If the ESP field is connected, then a shorted
field will give the same results as will a shorted
secondary in the T/R.
3. If the hookup is at the Controller output then
the CLR will also be in the primary circuit.
The impedance of the CLR will have negligible

36

ESP Troubleshooting Guide

5.

6.

7.

impact on the test indications since the current


draw is so low.
If the system is equipped with a KV feedback
capability the operator must be mindful of the
high voltage that will be present on the high voltage bushing as well as on the KV feedback system. Verify that the KV feedback signal has an
appropriate resistance path to ground. This path
may be through the KV indicator meter or
through an external resistor. IF THE KV FEEDBACK WIRE IS OPEN CIRCUIT TO GROUND
THEN HIGH VOLTAGE WILL BE PRESENT
ON THIS WIRE! IF THERE IS ANY DOUBT
OF THIS THEN CONNECT THE KV FEEDBACK TERMINAL TO GROUND!
Connect the test fixture Hot wire (the wire
from the lamp) to the hot side (the terminal that
connects the SCRs to the CLR and then to the
T/R). If the connection is to be made at the T/R
junction box then the hot side of the system is
the connection point between the T/R and the
CLR.
Connect the test fixture Return Wire (the
wire from the plug) to the Return Side of the
system under test.
Plug the fixture into a wall socket and observe
the lamp. A dull glow indicates a basically
Healthy System; a bright illumination or no
illumination indicates trouble. The choice of lamp
size, either 60 or 100 watt, should be a function
of the T/R size. For units under 700 ma the
smaller lamp is more effective.

Troubleshooting Tips

37

Interpreting the results


VERY DULL GLOW
Normal indications from a very dull glow:
The T/R does not have any shorted turns in
either the Primary or Secondary windings.
There are no direct shorts in the hot side feed
to the T/R nor shorts to ground in the
transformer winding.
There are no shorts to ground in the CLR if
connected during test.
The T/R Rectifier bridge does not have a
shorted leg.
The output, High Voltage feed system and ESP
field (if connected) are not shorted to ground.

functionality. If you would like more information


on this and other tests you can use in T/R troubleshootinglet us know on the reply card
attached to this issue. Or better still, call 1-800PICK NWLand talk with one of our service
people who have long-term experience in performing on-site ESP equipment diagnostics.

BRIGHTER THAN DULL GLOW


A brighter than dull glow indicates potential for:
Shorted turns in transformer
Shorted High Voltage bushing or ESP field or HV
duct
Shorted rectifier bridge
Short in primary voltage feed system
NO GLOW
No glow from the bulb indicates an open circuit on
the 480 VAC system. The open circuit may be in the
interconnection wiring, in the CLR (if present), or in
the T/R primary winding or connections.

This T/R Lamp Test is an abbreviated version


of but one test that can be used to determine T/R

38

ESP Troubleshooting Guide

Troubleshooting Tips

39

TROUBLESHOOTING TIP

What Meter Readings Can Tell


You When Troubleshooting
Transformer Rectifiers (T/Rs)
You pass by them dozens of times in the course of a
work weekmeters. Theyre designed to give you
information about the performance of specific components of your clean-air system.
Analyzed collectively, however, they can also
help perform an important diagnostic function. The
following are four problems indicated by T/R
metersalong with tests you may want to perform
in resolving those problems.

VAC

AAC

KDVC

AAC

KDVC

mADC

Problem: Short CircuitDC Side


Tests
1. Run T/R set with HV bushing disconnected from
the precipitator.
a. If no current flows the short is in the precipitator.
b. If current still flows the short is in the T/R set.
2. If precipitator is shorted, check electrodes and
insulators for shorts.
3. If T/R is shorted, check HV bushing and external
switch (if applicable) for shorts.

mADC

Probable Cause: No power to T/R set


Tests
1. Check if controller is responding to sparking. If it
is, use a scope to verify that sparks/arcs are
occurring. Run T/R with precipitator disconnected to verify that T/R is not sparking internally.
2. Check for open SCR fuses.
3. Verify that SCRs are firing.
4. Check for open CLR.
5. Check for proper operation of controller power
components.
a. circuit breaker
b. contactor

40

VAC

ESP Troubleshooting Guide

VAC

AAC

KDVC

mADC

Problem: Short Circuit T/R set


Tests
1. Megger diodes for shorts.
2. Run T/R without diodes. If AAC still high, transformer is bad.

Troubleshooting Tips

41

RECOMMENDED PRACTICE

Oil Integrity Testing


VAC

AAC

KDVC

mADC

Problem: Open circuit


Tests
1. Run T/R set with HV bushing grounded externally.
a. If current flows, precipitator field is open.
b. If no current flows, T/R is open.
2. If precipitator is open, check all HV connections
to electrodes.
3. If T/R is open, megger unit. Check for open
diodes or connections in T/R tank.

To insure continued performance of your power supplies, the following ASTM tests should be performed
annually on dielectric fluid sample extractions.
Test 1
Neutralization Number (D664)The neutralization number for service-aged transformers is, in
general, a measure of the acidic constituents of the
oil. It may be pertinent, if compared to the value of
the new product, in detecting contamination of the
oil from substances which have come in contact
with the oil. It may also be important in revealing a
tendency toward chemical change or deterioration of
the oil and its additives. It may be used as a general
guide for determining when oil should be replaced
or reclaimed, provided suitable rejection limits have
been established and confirmation is received from
other tests.
Test 2
Dielectric Breakdown Voltage (D877)The
dielectric breakdown voltage of an insulating liquid
is of importance as a measure of its ability to withstand electric stress without failure. It is the voltage
at which breakdown occurs between two electrodes
under prescribed test conditions. It serves primarily
to indicate the presence of contaminating agents
such as water, dirt or conducting particles in the liquid, one or more of which may be present when low
dielectric values are found by test. However, a high

42

ESP Troubleshooting Guide

Troubleshooting Tips

43

dielectric breakdown voltage does not indicate the


absence of all contaminants.
Test 3
Interfacial Tension (D971)The interfacial tension
between an electrical insulating oil and water is a
measure of the molecular attractive force between
their unlike molecules at the interface. It is
expressed in dynes per centimeter (millinewtons per
meter). This test provides a means of detecting soluble polar contaminants and products of deterioration. Soluble contamination or oil-deterioration
products generally decrease the interfacial tension
value.
Test 4
Power Factor (D924)Power factor is the
ratio of the power dissipated in the oil in watts to
the product of the effective voltage and current in
voltamperes, when tested with a sinusoidal field
under prescribed conditions. A high value is an indication of the presence of contaminants or deterioration products such as oxidation products, metal
soaps, charged colloids, etc.
Test 5
Color (D1500)The color of an insulating oil
is determined by means of transmitted light and is
expressed by a numerical value based on comparison with a series of color standards. A rapidly
increasing or high color number is an indication of
oil deterioration or contamination or both.

44

ESP Troubleshooting Guide

Test 6
Water in Insulating Oil, Karl Fisher Method
(D1533)Water contamination of insulating oil
may be present in several forms. The presence of
free water may be disclosed by visual examination
in the form of separated droplets or as a cloud dispersed throughout the oil. This type of water invariably results in decreased dielectric strength, which
may be restored by filtration or other suitable
means. Water in solution cannot be detected visually and is normally determined by either physical or
chemical means.
ASTM methods cited are suitable for the determination of water in insulating oil and, depending
upon conditions of sample handling and method of
analysis, can be used to estimate total water as well
as soluble water content of oil. The unit of measure
of the water is in soluble water content of oil in
parts per million. These tests are significant in that
they will show the presence of water which may not
be evident from electrical tests.
The following typical control limits for oil are
used for evaluating the conditions of dielectric fluid:
Neutralization Number
ASTM D664 .4 mg XOH/gram Maximum
Dielectric Breakdown
ASTM D877 22 KV Minimum
Interfacial Tension
ASTM D971 18 dynes/DM Minimum
Power Factor
ASTM D924 1.0% (Doble limit)

Troubleshooting Tips

45

Color
ASTM D1500 4.0 Maximum
Moisture Content
ASTM D1533 55 ppm Maximum

RECOMMENDED PRACTICE

Mineral Oil Filtering


Procedure for Transformer
Rectifier (T/R) Sets
One of the best ways to insure continued operation
of your T/R set is to insure the proper condition of
the mineral oil in it. The mineral oil provides not
only a cooling medium but a dielectric medium to
handle the voltage stress within the unit. Its not
uncommon that as the operational age of the unit
increases, the dielectric strength of the oil will
decrease. One of the ways to remove any contamination, and restore the dielectric strength, is to filter
the mineral oil. Although the filtering process
described below will not remove moisture or degasify the oil, it is very effective for particulate removal.

Equipment Required
Filtering should be done with a two-stage filter. The
first stage should use a cellulose cartridge designed
to remove particles 25 microns or larger. The second
stage filter should be designed for removal of particles .5 microns or larger. A pump will also be
required to circulate the mineral oil through the filters. The pump should be suitable for use with mineral oil. The flow rate of the pump should not exceed
the maximum allowable flow through the filters.

Equipment Hookup
The hookup of the equipment is relatively simple.
First you should de-energize the T/R set and properly ground the precipitator field for personnel safety.

46

ESP Troubleshooting Guide

Troubleshooting Tips

47

Next attach the intake side of the pump to the drain


valve located at the bottom of the T/R set. The outlet of the pump will be run through the filter.
Remove the T/R set access cover and place the filter
outlet hose in a horizontal position just below the oil
level. This horizontal position will help eliminate
the formation of air bubbles as the oil is returned to
the T/R set. Once the hose is in position reinstall the
access cover as tightly as possible to reduce any further contamination.

Filtering the Oil


Once the equipment is properly connected the pump
should be run for about 8 hours to remove the contaminants from the fluid. It may be necessary to have
some additional fluid available to prime the pump or
serve as make up for the oil in the filtering system.
It is very important that the high voltage coils are
not exposed to air during the filtering process.
Exposure of the coils to air may result in a failure
upon re-energization of the T/R set. After the filtering is complete, remove the access cover and visually inspect the mineral oil. If particles can still be
seen, continue filtering until all of the particles have
been removed. Once completed, test the oils dielectric strength. The minimum level should be 28 KV
using ASTM test method D877.

Let stand for 23 hours, then check for any decrease


in the pressure level. The pressure test is performed
to insure that the T/R is properly sealed and will not
breathe. After the pressure test is completed, bleed
off excess nitrogen to .5 psi. The process of applying the nitrogen blanket then bleeding off excess
pressure can be repeated several times. This will
essentially purge the top air space of any moisture.

Routine Maintenance
The T/R set mineral oil should be tested on a annual
basis to insure proper dielectric strength. Additional
tests as can also be performed on the oil. They
include neutralization number, interfacial tension,
power factor, color, and moisture content.

Pressure Test
Once the filtering equipment has been disconnected,
reinstall the T/R access cover. Next, pressurize the
top air space above the oil with dry nitrogen to 4 psi.

48

ESP Troubleshooting Guide

Troubleshooting Tips

49

SECTION III

EQUIPMENT
TROUBLESHOOTING

NWL
Equipment
The following decision trees will
help you conduct more thorough
troubleshooting for the following:
Electrical Systems (overall)
T/R Set
T/R Controller
Rapper Controller
Meter Readings Low
Back Corona
Opacity Spikes

50

ESP Troubleshooting Guide

51

ELECTRICAL SYSTEMS

Is Opacity
High?
yes

Are All
Fields
Energized?

yes

Are
Meters
Reading
Low?

no

yes
no

Go to Meters
Reading Low
Section

Is
Problem in
T/R Set?
yes

Go to T/R
Section

52

no

Are
Rappers
Operating?

yes

Are
There
Opacity
Spikes?

no

Go to
Rapper
Controller
Section

no

Is
There
Back
Corona?

yes

yes

Go to
Opacity
Spikes
Section

Go to
Back
Corona
Section

Is
Problem in
Controller?
yes

Go to
Controller
Section

ESP Troubleshooting Guide

Equipment Troubleshooting

53

T/R SET

Is T/R open circuited?


Are there high voltage
and low current levels?

Is T/R short circuited?


Are there high Currents,
low voltage levels?

no

yes

yes

yes
yes

Open in
precip.

no

no

1. Meggar diodes.
2. Run T/R with no
diodes.

Open in
T/R.
Disconnect T/R from
field. Is there still
current flowing?

Are meter readings normal, but


no KVDC?

no

Are meter readings normal, but


no MADC?

yes

Is there MADC current?

Ground HV bushing.
Does current flow?

no

no

1. Megger
divider.
2. Check low
end resistor.
3. Check for
shorted surge
arrestor.
4. Check for
open or shorted
feed back wiring.
5. Check for
defective
meters.

no

No meter
movements.

yes

yes

1. Check MADC
shunt.
2. Check
shorted surge
arrestor.
3. Check open
or shorted feedback wiring.
4. Check for
defective meter.

Go to controller
section.

yes
1. Check for
open jumpers
in penthouse
section.

1. Megger T/R.
2. Check for
open connections in T/R
tank.

1. Check H.V.
bushing.
2. Check ground
switch for shorts.

1. Check for shorted


electrodes in precip.
2. Check hopper level.

54

ESP Troubleshooting Guide

Equipment Troubleshooting

55

T/R CONTROLLER

Is there control?
no

yes

Does display light up?


no
Is there 120
VAC on J1 pin 1
& 2 of power
supply?

no
no

Are there
any active
alarms?

Apply
120
VAC.

yes
Is there +5VDC
on regulator on
control module?

Does contactor energize?

Replace
control
module.

yes

yes

Clear
alarms.

no

Replace
cable.

Is there
120 VAC
on TB1-11
(enable
line)?

no

Apply
120 VAC.

Is there 120
VAC on
TB1-15
(contactor)?

yes
Replace display module. Does problem
continue?
yes
Contact NWL.

Is spark indicator showing


spark or arcs?

Is SCR fuse
open?

yes

no Apply
120 VAC.

Using an oscilloscope, are


there firing pulses coming from
control module?

Replace
fuse.

no

Replace
control
module.

no

Replace
trigger
board.

yes

Is there
120 VAC
on TB116?

no

Replace
control
module.

yes

yes
Is the contactor coil
good?

Using an oscilloscope, are there


gate pulses at
the SCRs?

Unplug
SCRs from
trigger
board. Does
output go
full on?

Verify if
sparks or arcs
yes are real using yes
an oscilloGo to
scope. Are
Meters
they real?
Reading
Low
no
section.
Lower spark/
arc sensitivity.

yes

yes
Clear memorydoes
problem continue?

Is there output?

no

yes
Is there +5VDC
on regulator on
display cable of
display module?

yes

no

no
no

yes

yes Replace
SCRs.

no

Reconnect
SCRs trigger board
and
unplug
trigger
board from
control
module.
Does output go full
on?

yes Replace
trigger
board.

no
Replace
control
module.

Replace SCRs.
no

Replace
contactor.

yes
Contact NWL.

56

ESP Troubleshooting Guide

Equipment Troubleshooting

57

RAPPER CONTROLLER
yes

Does display light


up?
no
Is there 120 VAC
on J2-1, J2-2 of
power supply?

no

Is the voltage
on J1-3 and
J1-4 of the
power supply
above
4.8VDC?

no

Does clearing the memory solve the


problem?

yes
Is there 5 VDC
output to J2-11 to
J2-12 of the
CPU/crate
controller?

no

Replace
CPU/
crate
controller
D20624.

yes
Is there 5 VDC
output at the end
of the 25 pin cable
that connects to
display?

no

yes
Does clearing the memory solve the problem?

Replace
cable.

no

Does
replacing
power
supply
solve
problem?

yes

Replace
power
supply.

no
Does replacing the
CPU/crate
controller
solve the
problem?

Are all of the


rappers firing?

Are two or more


yes rappers on a single
output card firing?

Pull cards
from cage
one at a
time to see
if one card
is loading
the 5VDC
down.

no
Are all
ground
connections
secure?
yes

Check the coil


resistance of
rappers in
questions. Are
they correct?

Replace output
card and recalibrate A/D, does
problem go
away?

yes

Contact NWL.
Replace
fuses.

Contact NWL.

Does replacing the power


module solve
the problem?

Put a rapper in repeat


mode and calibrate.

no

Replace
yes that output card.

Does replacing
CPU/crate
controller solve
problem?
no

yes
Are all of the
rappers on the
same output
card?

Replace
yes output
card.

no
no

no
Does replacing the display solve the problem?

Repeat above
procedure
after adding
the output card
in the next slot.
Does the fuse
blow?

Go to
fuse
blowing
section.

yes
no

Adjust
the A/D
gain pot.

no

yes

no

no

yes
Remove all
output cards,
except in slot1.
Energize a
rapper in slot 1
and see if fuse
blows.

no

no

Is the A/D calibration correct?

yes

Replace CPU
card, does problem go away?

yes

Is power module in question


being selected
to fire? Is LED
flashing?

Are fuses blowing


on power module?

Is the A/D calibration correct for the


power module?

no

Are all the rappers in question fired from


the same
power module?

Are fuses on
power module
open?

no

yes

no

yes
Check
circuit
breaker,
check
fuses.

yes
Is there 5VDC
output from the
power supply; J13 to J1-4 and
approx. 13VDC on
J1-2 to J1-4?

no

Is there garbage
on the display?

yes

Replace output card and


recalibrate
A/D on power
module.

Contact NWL

no

Does replacing CPU/


crate controller solve
the problem?

Contact NWL.

no
Contact NWL.

58

ESP Troubleshooting Guide

Equipment Troubleshooting

59

METER READINGS LOW

no

Is controller indicating
sparks?
yes

Is the controller indicating


a current or voltage limit?
yes

Use a scope to verify if


sparks/arcs are really
occurring. Are they?

no

Readjust the
spark/arc
sensitivity pots.

Using external meters,


make sure the digital
meters are calibrated.
Are they?

no

Calibrate the
meters.

yes
yes

Energize the T/R in manual mode with the precip.


disconnected from the HV
bushing. Can higher voltage level be reacted?
no

yes

Something in
the precip. is
limiting the
voltage. Check
clearances,
electrode, alignment, hopper
levels, insulators, etc.

The limiting conditions


really exist. Probably due
to the load in the precip.

Is controller still indicating


spark/arcs are occurring?
yes

Something internal to the


T/R set is sparking or
arcing, contact NWL.

60

ESP Troubleshooting Guide

Equipment Troubleshooting

61

BACK CORONA

Do a VI curve. Does back


corona exist?
yes

Place controllers in back


corona mode. Does opacity improve?
no

Place the controller in


intermittent energization
mode. Does opacity
improve?

OPACITY SPIKES

Do the spikes occur on a


periodic basis?
yes

Is the timing the same as


the timing of any of the
rapping groups?
yes

Does lowering the intensity of that rapping group


stop the spikes?

yes

Does opacity
in the rip rap
mode at the
original intensity stop the
spikes?

no
no

Is sodium or sulfur
injection system
operating properly?
no

Does increasing the ACG


time stop the spikes?
no

Contact NWL.

Fix injection systems.

62

ESP Troubleshooting Guide

Equipment Troubleshooting

63

SECTION IV

Index
Glossary of Air Pollution
Control and ESP Terminology
Clean Air Act Amendments
Conversion Factors Metric
Equivalents
Altitude-Pressure
Temperature Density Table
of Air
Title III Hazardous
Air Pollutants

64

ESP Troubleshooting Guide

65

Glossary of
Air-Pollution Control
and ESP Terminology

collect gaseous pollutants. Used both for measurement and control.

The terminology for electrostatic precipitators has


been standardized by the Institute of Clean Air
Companies, Inc. (ICAC). The terms most used are
defined below.

AdsorptionThe adhesion of a substance to the


surface of a solid or liquid.

Abrasion-FlexWhere cloth has abraded in a


creased area by excessive bending.
AbsorberA kind of scrubber.
Absorptionthe penetration of a substance into or
through another; distinct from adsorption.
ACFMActual Cubic Feet per Minute of gas volume at the actual condition temperature, pressure
and composition. See gas flow rate.
Acid Deposition(Acid Rain) A complex chemical
and atmospheric phenomenon that occurs when
emissions of sulfur and nitrogen compounds and
other substances are transformed by chemical
processes in the atmosphere, often far from the original sources, and then deposited on earth in either a
wet or dry form. The wet forms, popularly called
acid rain, can fall as rain, snow or fog. The dry
forms are acidic gases or particulates.

AerosolParticle of solid or liquid matter that can


remain suspended in the air because of its small
size. Particulates under 1 micron in diameter are
generally called aerosols.
Air Changes per Hour (ACH)The movement of
a volume of air in a given period of time; if a building has one air change per hour, it means that all of
the air in the building will be replaced in a one-hour
period.
Air ContaminantAn impurity emitted to the outside air. It can be solid (dust, particulate matter), liquid (vapor/mist), or gas (carbon monoxide, sulfur
dioxide).
Air Core Reactor (ACR)Protects the T/R diode
bridge from high voltage transients that occur within
the ESP.
Air HorsepowerThe theoretical horse power
required to drive a fan if there are no losses in the
fan, that is, if its efficiency is 100%.

AdsorbentIn addition to the adjectival meaning,


the term describes any of several substances that

Air LeakageUnwanted air intruding into an


exhaust system (holes in ducts, missing and ineffective seals, etc.).

66

Index

ESP Troubleshooting Guide

67

Air MonitoringThe continuous sampling for and


measuring of pollutants present in the atmosphere.
Air Quality CriteriaAs the Federal government
uses the term, the varying amounts of pollution and
lengths of exposure at which specific adverse effects
to health and welfare take place.
Air Quality StandardsThe approximate concentration level of a selected pollutant that is permitted
in the atmosphere to minimize detrimental effects.

Antisneakage bafflesInternal baffle elements


within the precipitator to prevent the gas from
bypassing the active field or causing hopper reentrainment.
APCAir Pollution Control.
ArcA discharge of substantial magnitude of the
high voltage system to the grounded system, of relativity long duration and not tending to be immediately self-extinguishing.

Air Pollutionthe presence in the atmosphere of


gases, fumes or particulate matter, alone or in combination with each other, in sufficient concentration
to disturb the ecological balance; cause objectionable effects, especially sensory offenses; cause
transient or chronic illnesses; or impair or destroy
property.

Area SourceAny small source of nonnatural air


pollution which is not large enough to be classified
as a major source or point source.

Air, StandardDry air at 70 and 29.92 inches


(Hg) barometer. This is substantially equivalent to
0.075 lb/ft3.

Aspect RatioThe ratio obtained by dividing


effective length of the precipitator by the effective
height.

Air ToxicsAny air pollutant for which a national


ambient air quality standard (NAAQS) does not
exist (i.e., excluding ozone, carbon monoxide, PM10, sulfur dioxide, nitrogen oxides) that may reasonably be anticipated to cause cancer, developmental
effects, reproductive dysfunctions, neurological disorders, heritable gene mutations or other serious or
irreversible chronic or acute health effects in
humans.

ASTMAmerican Society of Testing Materials.

68

Index

ESP Troubleshooting Guide

AromaticsA type of hydrocarbon, such as benzene or toluene, added to gasoline in order to


increase octane. Some aromatics are toxic.

Attainment AreaAn area considered to have air


quality as good as or better than the National Ambient Air Quality Standards as defined by the Clean
Air Act. An area may be an attainment area for one
pollutant and a nonattainment area for others.
AttritionWearing or grinding down by friction.

69

One of the three basic contributing processes of air


pollution, the others being vaporization and combustion.
Automatic Power SupplyAutomatic regulation
of high voltage power for changes in precipitator
operating conditions utilizing feedback signal(s).
Sometimes referred to as AVC (automatic voltage
control).
Auxiliary Control EquipmentElectrical components required to protect, monitor and control the
operation of precipitator rappers, heaters and other
associated equipment.
BACM(Best Available Control Measure) A term
used in the CAAA referring to the best measures
(according to EPA guidance) for controlling emissions.
BACT(Best Available Control Technology) An
emission limitation based on the maximum degree
of emission reduction achievable. Under Title I of
the CAAA, EPA will establish BACT standards for
serious, severe and extreme nonattainment areas.
Back CoronaA phenomenon that occurs when
the gas within a high resistivity dust layer becomes
ionized, which causes heavy positive ion backflow,
which neutralizes negative ion current and reduces
voltage levels.

or liquid entering the filter media and not being discharged by the cleaning mechanism. Once enough
material has built up, air flow is severely restricted
and the bags have to be cleaned or replaced.
Blow-pipeSee manifold.
Blue SmokeA descriptive term for the gaseous
hydrocarbons that escape from hot asphalt and other
sources of VOC.
Bolted PlateA cover provided with sufficient
bolts to insure tight closure where occasional accessibility is required.
Brake HorsepowerThe horsepower actually
required to drive a fan. This includes the energy
losses in the fan and can be determined only by
actual tests of the fan (this does not include the
drive losses between motor and fan).
BridgeMaterial building across an opening (such
as a screw conveyer) and blocking off that opening.
Bus SectionThe smallest portion of the precipitator which can be independently de-energized (by
subdivision of the high voltage system and arrangement of support insulators).
CAAAClean Air Act Amendments of 1990.

Blind(Blinding) Blockage of bag by dust, fume

CableOil filled cable or dry cable for transmitting


high voltages.

70

Index

ESP Troubleshooting Guide

71

Capture VelocityThe air velocity at any point in


front of a hood or at a hood opening necessary to
overcome opposing air currents and to capture the
contaminated air at the point by causing it to flow
into the hood.
Carbon MonoxideA colorless, odorless gas
which is toxic because of its tendency to reduce the
oxygen-carrying capacity of the blood.
Carrying VelocityThe gas velocity that is necessary to keep the dust airborne. Usually 3500 to 4599
ft/min in ductwork depending upon the nature of the
dust.
CAS (Chemical Abstracts Service)Registry
Number is a numeric designation assigned by the
American Chemical Societys Chemical Abstracts
Service which uniquely identifies a specific chemical compound.
CasingEnveloping structure to enclose the internal components of the precipitator. Rectangular or
cylindrical configuration are used. The casing
includes the gas tight roof, side walls, and end walls
and hoppers and/or bottoms. A gastight dividing
wall is used to separate chambers. A nongastight
load bearing wall is used to separate bus sections.
The casing is sometimes called the housing or shell.
Cell (In width)A cell is an arrangement of bus
sections parallel to gas flow. NOTE: Number of
cells wide times number of fields deep equals the

72

ESP Troubleshooting Guide

total number of bus sections.


CellplateSee tubesheet.
CFMCubic Feet (of any gaseous matter) per
Minute. See gas flow rate.
ChamberA gastight longitudinal subdivision of a
precipitator. A precipitator with a single gastight
dividing wall is referred to as a two chamber precipitator. NOTE: Very wide precipitator chambers are
frequently equipped with nongastight load bearing
walls for structural considerations. These precipitators by definition are single chamber precipitators.
Clean Coal TechnologyAny technology not in
widespread use as of the date of enactment of the
Clean Air Act Amendments which will achieve significant reductions.
Clean FuelBlends and/or substitutes for gasoline
fuels. These include compressed natural gas,
methanol, ethanol and others.
COHAbbreviation for coefficient of haze, unit of
measurement of visibility interference.
Coke OvenAn industrial process which converts
coal into coke, which is one of the basic materials
used in blast furnaces for the conversion of iron ore
into iron.
Collecting Surface AreaThe total flat projected

Index

73

area of collecting surface exposed to the active electrical field (effective length x effective height x 2 x
number of gas passages).
Collecting Surface RapperA device for imparting vibration or shock to the collecting surface to
dislodge the deposited particles or dust.

ter such as carbon oxides, nitrogen, oxygen and


water vapor resulting from the combustion of fossil
fuels. 2) In the context of emission control, the
gaseous products resulting from the burning of any
kind of material containing carbon in a free or combined state. Also referred to as combustion contaminants.

Collecting SurfacesThe individual elements


which make up the collecting system and which collectively provide the total surface area of the precipitator for the deposition of dust particles.

ConcentrationThe amount of dust in gas. Usually expressed in terms of grains per ft3, lbs per 1000
lbs of gas, parts per million or milligrams per cubic
meter.

Collecting SystemThe grounded portion of the


precipitator to which the charged dust particles are
driven and to which they adhere.

ConductionThe transfer of heat by physical contact between substances.

Collection efficiencyThe weight of dust collected


per unit time divided by the weight of dust entering
the precipitator during the same unit time expressed
in percentage. The computation is as follows:
Efficiency = (Dust in) - (Dust out) x 100
(Dust In)
Combustionthe production of heat and light energy through a chemical process, usually oxidation.
One of the three basic contributing processes of air
pollution, the others being attrition and vaporization.
Combustion AirAmount of air necessary to burn
the available fuel.

Control DamperA device installed in a duct to


regulate the gas flow by degree of closure. Examples: Butterfly or Multilouver.
Conversion FactorsSee page 109 and 110.
ConvectionThe transfer of heat through a liquid
or gas by the actual movement of the molecules.
Corona Power (KW)The product of secondary
current and secondary voltage. Power density is
generally expressed in terms of: (1) watts per square
foot of collecting surface, or (2) watts per 1000
ACFM of gas flow.

Combustion Products1) Primarily gaseous mat-

Current DensityThe amount of secondary current per unit of precipitator collecting surface. Com-

74

Index

ESP Troubleshooting Guide

75

mon units are ma/ft.2 and mA/cm2.


Current Limiting Reactor (CLR)An impedance
device used to protect T/R diode bridge by limiting
the current flow during an arc or spark. It also provides a means of wave shaping that voltage to provide higher average valves.
CTG (Control Techniques Guideline)Guidance
documents issued by EPA which define Reasonably
Available Control Technology (RACT) to be
applied to existing facilities that emit certain threshold quantities of air pollutants; they contain information both on the economic and technological feasibility of available techniques.
Delta P (AP)Change in pressure, or pressure
drop, that occurs across a piece of control equipment.
DNAPLSDense nonaqueous phased liquids.
Density FactorThe ratio of actual air density to
density of standard air. The product of the density
factor and the density of standard air (0.075 lbs/ft3)
will give the actual air density in pounds per cubic
foot.

humidity and pressure as the temperature is reduced.


For flue gaining water vapor and SO it is the set of
conditions at which liquid sulfuric acid begins to
condense as the temperature is reduced.)
Dielectric FluidA substance used to keep the
transformer operating at moderate temperature levels, and as a dielectric where space is concerned.
Diode AssemblyConverts high voltage AC output
of the transformer to a DC signal.
Discharge ElectrodeThe part which is installed
in the high voltage system to perform the function
of ionizing the gas and creating the electrical field.
Typical configurations are
Rigid (RF)
Weighted Wire (W/W)
Rigid Discharge Electrode (RDE)
Discharge Electrode RapperA device for
imparting vibration or shock to the discharge electrodes in order to dislodge dust accumulation.
DoorsA hinged or detached cover provided with a
hand operated fastening device where accessibility
is required.

Dew Pointthe temperature at which the equilibrium vapor pressure of a liquid is equal to the existing
partial pressure of the respective vapor. (For air containing water vapor, it is the temperature at which
liquid water begins to condense for a given state of

Dry Bulb TemperatureThe actual temperature of


a gas, taken with a conventional thermometer.

76

Index

ESP Troubleshooting Guide

DSCFMTDry Standard Cubic Feet per Minute.


See gas flow rate.

77

DustA dispersion aerosol formed by the grinding


or atomizing of a solid, or the transfer of a powder
into a state of suspension through the action of air
currents or by vibration.
Dust Collector EfficiencySee collection
efficiency.
Dust or Mist ConcentrationThe weight of dust
or mist contained in a unit of gas, e.g. pounds per
thousand: pounds of gas, grains per standard dry
cubic foot (the temperature and pressure of the gas
must be specified if given as volume).
Early Reduction/Early ComplianceA provision
in the CAAA which provides incentives to a company for complying with new standards before they
are required to by law.
Effective Cross-Sectional AreaEffective width
times effective height.
Effective HeightTotal height of collecting surface
measured from top to bottom.
Effective LengthTotal length of collecting surface measured in the direction of gas flow. Length
between fields is to be excluded.
Effective Stack HeightThe height at which a
plume becomes essentially level. It is the actual
stack height plus the plume rise.

78

ESP Troubleshooting Guide

Effective WidthTotal number of gas passages


multiplied by spacing dimension of the collecting
surfaces.
EffluentA discharge or emission of a fluid (liquid
or gaseous).
Electrostatic AttractionMutual attraction, caused
by static electricity, by which particles tend to draw
together or adhere.
Electrostatic PrecipitatorA kind of precipitator
that first charges particulate (ESP), allowing electrostatic forces to attract particles to a collection point.
EmissionRelease of pollutants into the air from a
source.
Emission Control EquipmentMachinery used to
remove air contaminants from the discharge of
industrial exhaust streams.
Emission FactorThe statistical average of the
amount of a specific pollutant emitted from each
type of polluting source in relation to a unit quantity
of material handled, processed or burned. Eg. the
emission factor of oxides in nitrogen in fuel oil
combustion is 119 lbs per 1,000 gallons of fuel oil
used. By using the emission factor of a pollutant
and specific data regarding quantities of material
used by a given source, it is possible to compute
emissions for that sourceinformation necessary
for an emission inventory.

Index

79

Emission InventoryA list of primary air pollutants emitted into a given communitys atmosphere,
in amounts (commonly tons) per day, by type of
source. The emission inventory is basic to the establishment of emission standards. Also see emission
factor.
Emission StandardThe maximum amount of a
pollutant that is permitted to be discharged from a
single polluting source: e.g., the number of pounds
of fly ash per cubic foot of gas that may be emitted
from a coal-fired boiler. Rule or measurement established to regulate or control the amount of a given
pollutant that may be discharged to the outdoor
atmosphere from its source.

the exhaust stack, usually measured in ACFM.


Federal Implementation Plan (FIP)Under current law, a Federally implemented plan to achieve
attainment of an air quality standard, used when a
State is unable to develop an adequate plan. Under
the Senate bill, a plan containing control measures
developed and promulgated by EPA in order to fill
gaps in a State Implementation Plan (SIP).
Field (in depth)A field is an arrangement of bus
sections perpendicular to gas flow that is energized
by one or more high voltage power supplies.
FinesFine particulate; aerosol.

EPAEnvironmental Protection Agency.

FlexingBending, or contracting and expanding.

EvaporationThe physical transformation of a liquid to a gas at any temperature below its boiling
point.

Fly AshThe particulate impurities resulting from


the burning of coal and other material.

Excess AirAir in excess of the amount necessary


to combust all the available fuel.
Exhaust GasThe gases emitting from an industrial process, generally a combustion process.
Exhaust Stack TemperatureThe temperature of
the exhaust gas, measured in the discharge stack.

FogThe condensation of water vapor in air. Also


see smog.
Forced Draft BurnerA burner which has its secondary air supplied under pressure. This is normally
done by surrounding the dryer opening by a plenum
or windbox and supplying the air with a low pressure fan.

Exhaust VolumeThe amount of exhaust gas (air,


products of combustion and water vapor) leaving

Fossil FuelsCoal, oil and natural gas; so-called


because they are the remains of ancient plant and
animal life.

80

Index

ESP Troubleshooting Guide

81

Fugitive EmissionsEmissions not caught by a


capture system.
Fumesolid particulates generated by condensation
from the gaseous state, generally after volatilization
from molten metal, and often accompanied by a
chemical reaction, such as oxidation. Fumes flocculate and sometimes coalesce.
GACT(Generally Available Control Technology)
Methods, practices and techniques which are commercially available and appropriate considering economic impacts and the technical capabilities of the
firms to operate and maintain the emissions control
systems. Under Title III of the CAAA, EPA will
establish either GACT or MACT standards for each
source of HAPs.
Gas Distribution DevicesInternal elements in the
transition or ductwork to produce the desired velocity contour at the inlet and outlet of the precipitator.
Example: turning vanes or perforated plates.
Gas Distribution Plate RapperA device used to
prevent dust buildup on perforated plates.
GasesNormally, formless fluids which occupy the
space of their enclosure and which can be changed
to a liquid or solid state only by the combined effect
of increased pressure and decreased temperature.
Gases diffuse.

The volume of process gas at any point of the plant


exhaust system measured in terms of minutes. There
are several units of measurement:
ACFMThe actual gas flow measured (Actual
Cubic Feet per Minute)
SCFMThe gas flow volume reduced to 70F
(standard temperature) by calculation (Standard
Cubic Feet per Minute)
DSCFMThe gas flow reduced to 70
(standard temperature) and without volume of
steam or water vapor contained in the exhaust gas
(Dry Standard Cubic Feet per Minute)
Gas PassageFormed by two adjacent rows of collecting surfaces; measured from collecting surface
centerline to collecting surface centerline.
GrainA dust weight unit commonly used in air
pollution control. Equal to one seven thousandth of
a pound. One grain = 1/7000 lb.
Grain LoadingThe rate at which particles are
emitted from a pollution source. Measurement is
made by the number of grains per cubic foot of gas
emitted.
HalonsA family of compounds containing
bromine, fluorine, iodine and chlorine used in fighting fires, that breakdown in the atmosphere depleting stratospheric ozone.

Gas Flow Rate, Cubic Feet per Minute (CFM)

HAPs (Hazardous Air Pollutants)Any of the


189 chemicals listed under Title III of the CAAA.

82

Index

ESP Troubleshooting Guide

83

All HAP sources will have to comply with GACT or


MACT standards.

3. Silicon Controlled Rectifier (SCR)


Electronic switch for voltage regulation

HCFCsChlorofluorocarbons that have been


chemically altered by the addition of hydrogen, and
which are significantly less damaging to stratospheric ozone than other CFCs.

High Voltage StructureThe structural elements


necessary to support the discharge electrodes in
their relation to the collecting surface by means of
high voltage insulators.

HEPA Filter (High Efficiency Particulate Air Filter)Capable of removing at least 99.97% by
count of a standard 0.3 micron challenge particulate
(DOP test).

High Voltage SystemsAll parts of the precipitator


which are maintained at a high electrical potential.

High Voltage ConductorsConductor to transmit


the high voltage from the transformer rectifier to the
precipitator high voltage system.
High Voltage Power SupplyThe supply unit to
produce the high voltage required for precipitation,
consisting of a transformer rectifier combination and
associated controls. Numerous bus sections can be
independently energized by one power supply.
High Voltage Power Supply Control
EquipmentElectrical components required to
protect, monitor and regulate the power supplied to
the precipitator high voltage system. Regulation of
the primary voltage of the high voltage transformer
rectifier is accomplished by one of the following
devices:
1. Saturable Core ReactorA variable
impedance device
2. Variable Auto-Transformer control

84

ESP Troubleshooting Guide

High Voltage SystemSupport InsulatorA


device to physically support and electrically isolate
the high voltage system from ground.
Hi-Volume SamplerAlso called a Hi-Vol. A
device used in the measurement and analysis of suspended particulate pollution.
HONHazardous Organic NESHAPs.
Hopper CapacityTotal volumetric capacity of
hoppers measured from a plane 10" below high voltage system or plates, whichever is lower.
Humidity, AbsoluteThe weight of water vapor
per unit volume, pounds per cubic foot or grams per
cubic centimeter.
Humidity, RelativeThe ratio of the actual partial
pressure of water vapor in a space to the saturated
pressure of pure water vapor in a space to the saturated pressure of pure water at the same temperature.

Index

85

H.V. BusA conductor enclosed within a grounded


duct.

Isolation DamperA device installed in a duct to


isolate a precipitator chamber from process gas.

HydrocarbonAny of the vast family of compounds containing carbon and hydrogen in various
combinations: found especially in fossil fuels. Some
of the hydrocarbon compounds are major air pollutants; they may be carcinogenic or active participants in the photochemical smog process.

InversionAn atmospheric condition caused by a


layer of warm air preventing the rise of cooling air
trapped beneath it. This prevents the rise of pollutants that might otherwise be dispersed and results
in a concentration of the air pollution.

Inch of WaterA unit of pressure equal to the


pressure exerted by a column of water one inch high
at a standard temperature. (407" WC = 14.7 PSI)
Inches WG (Inches of Water Gauge)See inch of
water.
IncineratorA device which burns household,
industrial, pathological or hazardous solid, liquid or
gaseous wastes under controlled conditions.
Inclined ManometerA testing instrument using a
liquid column, set at an incline to increase reading
accuracy, to measure pressure. Normally used to
read velocity pressure.
InsulationAny method which will retard the flow
of heat through a wall.
Insulator CompartmentEnclosure for the insulator(s) supporting the high voltage system (may contain one or more insulators, but not enclosing the
roof as a whole).

86

ESP Troubleshooting Guide

Impedance Devices
1. Linear inductor or current limiting reactor
required to work with SCR-type controllers
2. A transformer with a specially designed high
impedance core and coils
3. Saturable core reactor
4. Resistors
LAER (Lowest Achievable Emission Rate)The
rate of emissions which reflects either the most
stringent emission limit contained in the implementation plan of any state (unless it is proved that such
limitations are not achievable) or the most stringent
emission limit achieved in practice, whichever is
most stringent.
Liquid FlowrateThe amount of water or scrubbing liquid introduced into a wet collector.
Low NOx BurnersOne of several combustion
technologies used to reduce emission of NOx.
Lower Explosive LimitThe lower limit of flammability or explosibility of a gas or vapor at ordi-

Index

87

nary ambient temperature expressed in percent of a


gas or a vapor in air by volume.

fall. The difference in the level of the water columns


is equivalent to the pressure differential.

Lower Weather EnclosureA nongastight enclosure at base of precipitator to protect hoppers from
wind and/or detrimental weather conditions.

Manual Power SupplyManual regulation of high


voltage power based on precipitator operating conditions as observed by plant operators.

MACT (Maximum Achievable Control Technology)the standard with which sources of HAPs will
have to comply; the CAAA defines MACT as the
maximum degree of reduction in emissions...
achievable for new or existing sources... taking into
account the cost of achieving such reductions.
MACT standards for existing sources must be at
least as stringent as the average level of control
achieved at the best controlled 12 percent of facilities, and MACT for new sources will have to be
even stricter.

Mechanical CollectorDevices that are functionally dependent on the laws of mechanics governing
the motion of bodies in space. Can be operated dry
or wet. When operated wet, devices are generally
called scrubbers. Examples of mechanical collectors
are cyclones, settling chambers and various types of
impingement collectors.

Major SourceA stationary source which emits a


large amount of pollution. In nonattainment areas,
under Title I of the CAAA, a major source is one
which emits more than 100, 50, 25 or 10 tons per
year depending on whether the area is classified as
Marginal or Moderate, Serious, Severe or Extreme,
respectively. For hazardous air pollutants, under
Title III of the CAAA, a major source is one which
can emit more than 10 TPY of any one HAP or 25
TPY of total HAPs.

MegaA prefix meaning 1 million.


MicroA prefix meaning 1/1,000,000 abbreviated
by the Greek letter u.
MicrometerSee micron.
MicronSymbol um; a unit of length equal to one
millionth of a meter. An average human hair is 70
microns in diameter. In general, particles down to 10
microns can be seen without the aid of magnification.

ManometerA u-shaped device for measuring the


static pressure at a point relative to some other
point; the pressure difference causes water to rise or

Migration VelocityA parameter in the DeutchAnderson equation used to determine the required
size of an electrostatic precipitator to meet specified
design conditions. Other terminology used: W-value
and precipitation rate. Values are generally stated in
terms of ft/min or cm/sec.

88

Index

ESP Troubleshooting Guide

89

MilliA prefix meaning 1/1,000.


MistSuspended liquid droplets generated by condensation from the gaseous to the liquid state or by
breaking up a liquid into a dispersed state, such as
by splashing, foaming and atomizing.
ModelingAn investigative technique using computer mathematical or physical representation of a
system that accounts for all or some of its known
properties.
Montreal ProtocolAn international environmental agreement to control chemicals that deplete the
ozone layer. The protocol, which was renegotiated
in June 1990, calls for a phaseout of CFCs, halons
and carbon tetrachloride by the year 2000, a phaseout of chloroform by 2005, and provides financial
assistance to help developing countries make the
transition from ozone-depleting substances.
MSDS (Material Safety Data Sheet)Compilation of data and information on individual hazardous
chemicals produced by the manufacturers and
importers of that chemical, as required by OSHAs
Hazard Communication Standard, 29 CFR
1910.1200.

New SourceA stationary source, the construction


or reconstruction of which is commenced after the
proposal date of the standard. Also NSPS (New
Source Performance Standard).
NIOSH (National Institute for Occupational
Safety and Health)Created by the Occupational
Safety and Health Act of 1970. NIOSH is part of the
Centers for Disease Control under the Department
of Health and Human Services. Its mandate includes
conduction research in developing criteria and/or
recommendations to be used in setting occupational
exposure standards, identifying and evaluating
workplace hazards, measurement techniques and
control technologies, and providing professional
education as well as health and safety information.
Nonattainment AreaAn area which has not
achieved air quality as good as the National Ambient Air Quality Standards as defined by the CAAA.

NEDSNational Emission Data System.

NOx (Nitrogen Oxides)Chemical compounds


containing nitrogen and oxygen; react with volatile
organic compounds, in the presence of heat and sunlight, to form ozone. They are also a major precursor to acid rain. Nationwide, approximately 45% of
NOx emissions come from mobile sources, 35%
from electric utilities and 15% from industrial fuel
combustion.

NESHAPNational Emissions Standards for Hazardous Air Pollutants.

OCIS (OSHA Computerized Information System)A comprehensive data base that contains

90

Index

ESP Troubleshooting Guide

91

information and data on standards interpretation,


chemical information, hazardous waste activity
5(a)(1) citations, a health hazard evaluation index,
training materials and other information compiled
by OSHA on subjects related to occupational safety
and health.
OpacityRefers to the amount of light that can
pass through; normally refers to the degree of visibility of an exhaust plume. Normal measurement
technique used is by EPA method 9.
OzoneA compound consisting of three oxygen
atoms, that is the primary constituent of smog. It is
formed through chemical reactions in the atmosphere involving volatile organic compounds, nitrogen oxides and sunlight. Ozone can initiate damage
to the lungs as well as damage to trees, crops and
materials. There is a natural layer of ozone in the
upper atmosphere which shields the earth from
harmful ultraviolet radiation.
ParticulateA particle of solid or liquid matter.
Particulate MatterAny solid or liquid material in
the atmosphere.
PEL (Permissible Exposure Limits)Limits
developed by OSHA to indicate the maximum airborne concentration of a contaminant to which an
employee may be exposed.

over the precipitator to contain the high voltage


insulators.
PermitAn authorization, license or equivalent
control document issued by EPA or an approved
state agency to implement the requirements of an
environmental regulation; e.g., a permit to operate a
facility that may generate harmful emissions.
Photochemical ProcessThe chemical changes
brought about by the radiant energy of the sun acting upon various polluting substances. The products
are known as photochemical smog.
Pitot TubeA specially constructed probe for taking velocity pressure readings in a duct.
PlenumPressure equalizing chamber.
Plenum PulseType of pulsing collector where
entire sections of the clean air plenum are isolated
and pulsed with either compressed air or air from a
high pressure blower.
PM10A new standard for measuring the amount of
solid or liquid matter suspended in the atmosphere
(particulate matter). Refers to the amount of particulate matter under 10 micrometers in diameter.
The smaller PM10 particles penetrate to the deeper
portions of the lung, affecting sensitive population
groups such as children and people with respiratory
diseases.

PenthouseA weatherproof, gastight enclosure

92

ESP Troubleshooting Guide

Index

93

Point SourceA stationary location or facility


from which pollutants are emitted. Also, any single
identifiable source of pollution.
PolymerizedA chemical reaction in which two
ore more small molecules combine to form larger
molecules that contain repeating structural units of
the original molecules.

Precipitator VoltageThe average DC voltage


between the high voltage system and grounded side
of the precipitator.
Effective cross section is construed to be the
effective field height x width of gas passage x number of passages.

Pounds per 100 Pounds of GasA common quantitative definition of pollution concentration.

Pressure, AtmosphericThe pressure due to the


weight of the atmosphere. It is the pressure indicated by a barometer; standard atmospheric pressure is
29.92 inches of mercury.

PPM (Parts per Million)The number of parts of


a given pollutant in a million parts of air. Units are
expressed by weight or volume.

Pressure DropThe differential pressure between


two points in a system. The resistance to flow
between the two points.

Precipitator CurrentThe rectified or unidirectional average current to the precipitator measured


by a milliammeter in the ground leg of the rectifier.

Pressure, StaticThe potential pressure exerted in


all directions by fluid at rest. For a fluid in motion it
is measured in a direction normal (90) to the direction of flow. Usually expressed in inches water
gauge when dealing with air.

PrecipitatorsAny number of devices using


mechanical, electrical or chemical means to collect
particulates. Used for measurement, analysis or control. See electrostatic precipitator.
Precipitator Gas VelocityA figure obtained by
dividing the volume rate of gas flow through the
precipitator by the effective cross sectional area of
the precipitator. Gas velocity is generally expressed
in terms of ft./sec. and is computed as follows:
Velocity = Gas Volume (CFM)
Effective cross section area ft2

94

ESP Troubleshooting Guide

Pressure, VelocityThe kinetic pressure in the


directional flow necessary to cause a fluid at rest to
flow at a given velocity. Usually expressed in inches
water gauge.
Prevention of Significant Deterioration (PSD)
EPA program in which state and/or federal permits
are required that are intended to restrict emissions
for new or modified sources in places where air
quality is already better than required to meet primary and secondary ambient air quality standards.

Index

95

Primary CollectorA dry or wet collector which


is followed by a secondary collector with greater filtering efficiency.
Primary CurrentCurrent in the transformer primary as measured by an AC ammeter.
Primary VoltageThe voltage as indicated by
AC voltmeter across the primary windings of the
transformer.
Process WeightThe weight per hour that is run
through the process. Commonly used in APC codes
to determine the maximum allowable pollution
exhausted.
PromulgateTo make a new law known and put it
into effect. The EPA promulgates a rule when it
issues the final version in the Federal Register.
PSI (Pounds per Square Inch)A measure of
pressure. 1 psi equals 27.7" water gauge.
PSIA (Pounds per Square Inch Absolute)The
absolute pressure without reference to another point.
Atmospheric pressure is 14.7 PSIA.
PSIG (Pounds per Square Inch Gauge)The
pressure relative to atmospheric. For instance, 10
PSIG equals 24.7 PSIA. This is the common pressure term.

Measures)A broadly defined term referring to


technologies and other measures that can be used to
control pollution; includes Reasonably Available
Control Technology and other measures. In the case
of PM10, it refers to approaches for controlling small
or dispersed source categories such as road dust,
wood stoves and open burning.
RACT (Reasonably Available Control Technology)An emission limitation on existing sources in
nonattainment areas, defined by EPA in a Control
Techniques Guideline (CTG) and adopted and
implemented by states. Under Title I of the CAAA,
EPA will establish RACT standards for marginal,
moderate and serious nonattainment areas.
RadionuclideRadioactive element which can be
man-made or naturally occurring. They can have a
long life as pollutants, and are believed to have
potentially mutagenic effects on the human body.
RadonA colorless, naturally occurring, radioactive, inert gaseous element formed by radioactive
decay of radium atoms in soil or rocks.
Rapper InsulatorA device to electrically isolate
discharge electrode rappers yet transmit mechanically, forces necessary to create vibration or shock in
the high voltage system.

RACM (Reasonably Available Control

ReentrainmentThe phenomenon whereby dust is


collected from the air stream and then is returned to
the air stream. Occurs when dust is pulsed from a bag

96

Index

ESP Troubleshooting Guide

97

and then caught up by an upward moving air stream.


REL (Recommended Exposure Limits)Issued
by NOISH to aid in controlling hazards in the workplace. These limits are generally expressed as 8- or
10-hour TWAs for a 40-hour work week and/or ceiling levels with time limits ranging from instantaneous to 120 minutes.

cent black; a Ringelman No. 5, to 100 percent. They


are used for measuring the opacity of smoke arising
from stacks and other sources, by matching with the
actual effluent, the various numbers, or densities,
indicated by the charts. Ringelman numbers were
sometimes used in setting emission standards.

RepoweringThe replacement of an existing coalfired boiler with one or more clean coal technologies, in order to achieve significantly greater emission reduction relative to the performance of
technology in widespread use as of the enactment of
the Clean Air Act Amendments.

RTECS (Registry of Toxic Effects of Chemical


Substances)A data base that lists an identification
number, synonyms, Department of Transportation
(DOT) hazard label information, EPA Toxic Substances Control Act (TSCA) information, OSHA
and Mine Safety and Health Administration
(MSHA) air exposure limits, and animal and human
toxicologic data.

Residual RiskThe quantity of health risk remaining after application of the MACT (Maximum
Achievable Control Technology).

SanctionsActions taken against a state or local


government for failure to plan or to implement a
SIP, e.g., a ban on construction of new sources.

ResistanceIn air flow, it is caused by friction of


the air against any surface, or by changing the
momentum of the gas.

Safety Grounding DeviceA device for physically


grounding the high voltage system prior to personnel entering the precipitator. (The most common
type consists of a conductor, one end of which is
grounded to the casing, the other end attached to the
high voltage system using an insulated operating
lever.)

RingelmanA measure of the opacity caused by


pollution from a stack. Grades opacity from 0 to 5,
where 0 is an invisible discharge and 5 is totally
opaque.
Ringleman ChartActually, a series of charts,
numbered from 0 to 5, that simulate various smoke
densities, by presenting different percentages of
black. A Ringelman No. 1 is equivalent to 20 per-

98

ESP Troubleshooting Guide

SCFM (Standard Cubic Feet per Minute)The


volume that a gas would occupy at standard temperature and pressure conditions (70 F and 14.7
PSIA). See gas flow rate.

Index

99

ScrubberA device that uses a liquid spray to


remove aerosol and gaseous pollutants from an air
stream. The gases are removed either by absorption
or chemical reaction. Solid and liquid particulates
are removed through contact with the spray. Scrubbers are used for both the measurement and control
of pollution.

taken by the State and its subdivisions to implement


their responsibilities under the Clean Air Act.

Scrubber, GasAny device in which a contaminant, solid or gaseous, is removed from a gas stream
by liquid droplets. (Types include spray towers,
packed towers, cyclone scrubbers, jet scrubbers, orifice scrubbers, venturi scrubbers, impingement
scrubbers and mechanical scrubbers).

SmokeCarbon or soot particles, less than 0.1


micrometers in size which result from the incomplete combustion of carbonaceous materials such as
coal, oil, tar and tobacco.

Secondary CollectorA dust collector which is


preceded by primary collector(s). The secondary filter normally has a higher filtering efficiency.
Settling ChamberA dry collection device which
removes particulate matter from the gas stream by
slowing down the exhaust gas velocity.
Silicon RectifierA rectifier consisting of silicon
diodes immersed in mineral oil or silicone oil.
Single PrecipitatorAn arrangement of collecting
surfaces and discharge electrodes contained within
one independent casing.

SmogThe irritating haze resulting from the suns


effect on certain pollutants in the air, notably those
from automobile exhaust; see photochemical
process. Also a mixture of fog and smoke.

SO2Sulfur dioxide is an invisible, nonflammable


acidic gas, formed during combustion of fuel containing sulfur.
SO3Sulfur trioxide oxidized from SO2; combines
with atmospheric moisture to form sulfuric acid mist
(H2SO4).
SootVery finely divided carbon particles clustered
together in long chains.
SourceAny place or object from which pollutants
are released.
SparkA discharge from the high voltage system
to the ground system, self-extinguishing and of
short duration.

SIP (State Implementation Plan)Documents prepared by states, and submitted to EPA for approval,
which identifies actions and programs to be under-

Specific Collecting Area (SCA)A figure obtained


by dividing total effective collecting surface of the

100

Index

ESP Troubleshooting Guide

101

precipitator by gas volume, expressed in thousands


of actual cubic feet per minute.

air in excess of the stoichiometric ratio is usually provided to encourage complete combustion of the fuel.

StackA smokestack; a vertical pipe or flue


designed to exhaust gases.

Sulfur Dioxide (SO2)A heavy, pungent, colorless


air pollutant formed primarily by the combustion of
fossil fuels. It is a respiratory irritant, especially for
asthmatics, and is the major precursor to the formation of acid rain.

Stage II ControlsSystems placed on service station gasoline pumps to control and capture gasoline
vapors during an automobile refueling.
Static Pressure (Cold)The pressure caused by
the resistance to air flow through the system if the
gas were at standard conditions or colder, if this is a
possibility.
Static Pressure (Hot)The pressure caused by the
resistance to air flow through the system at actual
conditions. Measured in inches of water (WG).
Streamline FlowFluid flow in which the velocity
pressure and fluid density of a given particle
remains constant with time.
STEL (Short Term Exposure Limit)The
employees 15 minute time weighted average exposure which cannot be exceeded at any time. STEL is
set by OSHA for each pollutant and expressed in
terms of ppm or mg/m3.

Sulfur OxidesPungent, colorless gases formed


primarily by the combustion of fossil fuels; considered major air pollutants, sulfur oxides may damage
the respiratory tract as well as vegetation.
System Gas VolumeAll gases flowing through
the exhaust gas system (including excess air, scavenger air, leakage air).
Tape SamplerA device used in the measurement
of both gases and fine particulates. It allows air sampling to be made automatically at predetermined
times.
Threshold Limit Values (TLV)Represents the air
concentrations of chemical substances to which it is
believed that workers may be exposed daily without
adverse effect.

Stoichiometric AirThe exact quantity of air


required to combine with the given fuel so that the
ensuing combustion reaction is perfect and no free
oxygen or unburned constituents remain. In reality,

TLV (Threshold Limit Value)A registered


trademark for an exposure limit developed by the
American Conference of Governmental Industrial
Hygienists (ACGIH). A listing of TLVs may be
found in the ACGIHs Documentation of the

102

Index

ESP Troubleshooting Guide

103

Threshold Limit Values and Biological Exposure


Indices for 1988-1989.
TPYTons per year.
Transformer RectifierA unit comprised of a
transformer for stepping up normal service voltages
to voltages in the kilovolt range, and a rectifier operating at high voltage to convert AC to unidirectional
current.
TransitionAn aerodynamically designed inlet or
outlet duct connection to the precipitator. Transitions are normally included as part of the precipitator, sometimes referred to as inlet/outlet nozzles.
Transportation Control Measures (TCMs)Steps
taken by a locality to adjust traffic patterns (e.g., bus
lanes, right turn on red) or reduce vehicle use
(ridesharing, high-occupancy vehicle lanes) to
reduce vehicular emissions of air pollutants.
TraverseA method of sampling points in a duct
where pressure readings will be taken to determine
velocity. A traverse divides the duct into equal,
evenly distributed areas that are each tested, compensating for errors caused by uneven gas flow in
the duct.

TSCA (Toxic Substances Control Act)Administered by the Environmental Protection Agency


(EPA), was passed by Congress to protect human
health and the environment by requiring testing and
necessary use restrictions to regulate the commerce
of certain chemical substances.
TSD (Facility)Treatment, Storage and Disposal.
Turbulent FlowFluid flow in which the velocity
of a given particle changes constantly both in magnitude and directionhere, uneven gas flow in the
exhaust system is caused by obstructions and
changes in direction.
Turning VanesVanes in ductwork or transition to
guide the gas and dust flow through the ductwork in
order to minimize pressure drop and to control the
velocity and dust concentration contours.
TWA (Time Weighted Average)Employees
average airborne exposure which can not be exceeded in any 8-hour work shift. TWA is set by OSHA
and expressed in mg/m3.
Upper Weather EnclosureA nongastight enclosure on the roof of the precipitator to shelter equipment (T/R sets, rappers, purge air fans, etc.) and
maintenance personnel.

Treatment TimeA figure, in seconds, obtained by


dividing the effective length, in feet, of a precipitator by the precipitator gas velocity figure calculated
above.

VaporizationThe change of a substance from the


liquid to a gaseous state. One of the three basic contributing processes of air pollution: the others being

104

Index

ESP Troubleshooting Guide

105

attrition and combustion.


VaporsThe gaseous form of substances which are
normally in the solid or liquid state and which can
be changed to these states, either by increasing the
pressure or decreasing the temperature alone. Vapors
diffuse.
VariancePermission granted for a limited time,
under stated conditions, for a person or company to
operate outside the limits prescribed in a regulation.
Usually granted to allow time for engineering and
fabrication of abatement equipment to bring the
operation into compliance.
VelometerA simple instrument for determining
the velocity of gas in a duct. Its operation is similar
to an inclined manometer, except that it automatically converts the reading to velocity.
VenturiDevice used to increase the efficiency of
a compressed air pulse. Designed with converging
circular sides to a throat and then diverging sides.
Designed such that when a pulse is introduced at the
top, a negative pressure zone is created outside the
top, and secondary air is induced into the venturi,
compounding the pulse strength.
Venturi ScrubberA wet type dust collector that
can obtain very high efficiency, but requires large
horsepower to do so. The gas and dust particles are
accelerated in a throat, where finely atomized water
is introduced and water/dust collisions take place.

106

ESP Troubleshooting Guide

VOCs (Volatile Organic Compounds)A group


of chemicals that react in the atmosphere with nitrogen oxides in the presence of heat and sunlight to
form ozone; does not include methane and other
compounds determined by EPA to have negligible
photochemical reactivity. Examples of VOCs
include gasoline fumes and oil-based paints.
Voltage DividerA means for supplying a low
voltage feedback signal that is proportional to the
KV output of the T/R.
Water GaugeInches water is a pressure term
defined as a pressure equal to that exerted by a column of water of the same height. 27.7" WG equals
1 PSI.
Wet Bulb TemperatureThe temperature of a gas
stream taken with a wetted thermometer. It is
approximately equal to the adiabatic saturation temperature of the gas.
Wet CollectorDust collector which uses water to
remove particulate matter from the exhaust gas (wet
washers, venturis, wet fans).
WrapperUsed in electrostatic precipitators, the
light gauge steel or aluminum covering put over
insulation.

Index

107

CLEAN AIR ACT


AMENDMENTS

CONVERSION FACTORS
METRIC EQUIVALENTS

1990

Length

Title I:

Nonattainment: Ambient Air Quality

Title II:

Motor Vehicles

cm = 0.3937 in
meter = 3.2808 ft
meter = 1.0936 yd

Title III:

Hazardous Air Pollutants

Volume

Title IV:

Acid Rain

cm3 = 0.0610 in3


m3 = 35.3145 ft3
m3 = 1.3079 yd3

Title V:

Permits

Title VI:

Stratospheric Ozone

in = 2.5400 cm
ft = 0.3048 m
yd = 0.9144 km

in3 = 16.3872 cm3


ft3 = 0.0283 m3
yd3 = 0.7647 m3

Capacity
Title VII: Enforcement
Title VIII: Miscellaneous

liter = 2.2046 lb of
pure water at 4C
liter = 61.0250 in3
liter = 0.0353 ft3

liter = 0.2642 gal (US)


in3 = 0.0164 liter
ft3 = 28.3162 liter
gal (US) = 3.7853 liter

Weight
gram = 15.4324 grains
gram = 0.0353 oz
kg = 2.2046 lb

grain = 1/7000 lb
grain = 0.0648 g
oz = 28.3495 g
lb = 0.4536 kg

Concentration
grain/ft3 = 2288.1 mg/m3
lb/acre = 0.11208 g/m2
lb/1000 ft3 = 16,017 mg/m3
lb/1000 ft2 = 4.8807 g/m2
ton/sq mile = 0.35026 g/m2
grain/ft2 = 0.69725 g/m2

108

ESP Troubleshooting Guide

Index

109

Heat & Energy Units


1 boiler HP = 33,475 Btu/hr
1 ton (refrig) = 12,000 Btu/hr
Btu = 0.2520 kg-cal

ALTITUDE-PRESSURE
TEMPERATURE DENSITY
TABLE OF AIR
Altitude
(feet)

1 kw-hr=
1000 whr
1.3410 hp-hr
3413 Btu

1 hp-hr=
0.7457 kw-hr
1,980,000 ft-lb
2545 Btu

1 lb water evaporated from and at 212 F

Temperature Equivalents
Fahrenheit, F = Ranking - 460 = (Cx9/5)+32
Celsius, C = Kelvin - 273 = 5/9 = (F-32)x5/9

Pressure Equivalents
1 atmosphere =
14.696 lb/in2 = 2116.3 lb/ft2
33.96 ft of water = 407.52 in water
29.92 in mercury = 760 mm mercury
1.01296 bar
1 in water =
0.0361 lb/in2 = 5.196 lb/ft2
0.0735 in mercury = 1.876 mm mercury
0.002456 atmosphere = 0.08333 ft water
1 bar =
0.9872 atmosphere
14.5 lb/in2

110

ESP Troubleshooting Guide

0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
11000
12000
13000
14000
15000
20000

Index

Pressure

Temperature

Density

(In Hg Abs)

(Degrees F)

(lbs/ft3)

29.92
29.38
28.85
28.33
27.82
27.31
26.81
26.33
25.84
25.37
24.89
24.43
23.98
23.53
23.09
22.65
22.12
21.80
21.38
20.98
20.57
19.75
19.03
18.29
17.57
16.88
13.70

70.0
68.1
66.1
64.2
62.3
60.4
58.4
56.5
54.6
52.6
50.7
48.8
46.9
45.0
43.0
41.0
39.0
37.1
35.2
33.3
31.3
28.5
23.6
19.7
15.8
12.0
-12.6

.0750
.0740
.0730
.0719
.0709
.0698
.0687
.0676
.0666
.0657
.0648
.0638
.0628
.0619
.0610
.0600
.0590
.0581
.0573
.0564
.0555
.0538
.0521
.0505
.0488
.0473
.0405

111

Altitude-Pressure Temperature Density Table


of Air (continued)

TITLE III
Hazardous Air Pollutants

Altitude

CAS No.
75070
60355
75058
96862
53963
107028
79061
79107
107131
107051
92671
62533
90040
1332214
71432

(feet)

25000
30000
35000
40000
45000
50000

Pressure

Temperature

Density

(In Hg Abs)

(Degrees F)

(lbs/ft3)

11.10
8.88
7.03
5.54
4.36
3.43

-30.1
-47.5
-65.6
-69.8
-69.8
-69.8

.0337
.0281
.0233
.0185
.0145
.0114

92875
98077
100447
92524
117817
542881
75252
106990
156627
105602
133062
63252

112

ESP Troubleshooting Guide

Index

Chemical Name
Acetaldehyde
Acetamide
Acetonitrile
Acetophenone
2-Acetylaminofluorene
Acrolein
Acrylamide
Acrylic acid
Acrylonitrile
Allyl chloride
4-Aminodiphenyl
Aniline
o-Anisidline
Asbestos
Benzene
(including gasoline)
Benzidine
Benzotrichloride
Benzyl chloride
Biphenyl
Bls (2-ethylhexyl)phthalate
(DEHP)
Bls(chiromethyl)ether
Bromoform
1,3-Butadiene
Calcium cyanamide
Caprolactarn
Captan
Carbaryl

Category
OV
OV
OV
OV
OV
OV
OV
OV
OV
HV
OV
OV
OV
N
OV
OV
HV
HV
OV
OV
HV
HV
OV
OV
OV
OV

113

Hazardous Air Pollutants (continued)


CAS No.
75150
56235
463581
120809
133904
57749
7782505
79118
532274
108907
510156
67663
107302
126998
1319773
95487
108394
106445
98828
94757
3547044
334883
132649
96128
84742
106467
91941
111444

114

Chemical Name
Carbon disulfide
Carbon tetrachloride
Carbonyl sulfide
Catechol
Chloramben
Chlordane
Chlorine
Chloroscetic acid
2-Chloroacetophenone
Chlorobenzene
Chlorobenzilate
Chloroform
Chloromethyl methyl ether
Chloroprene
Cresols/Cresylic acid
(isomers/mixer)
o-Cresol
m-Cresol
p-Cresol
Cumene
2,4-D, Salts and Esters
DDE
Diazomethane
Dibenzofurans
1,2-Dibromo-3-chloropropane
Dibutylphthalate
1,4-Dichlorobenzene(p)
3,3-Dichlorobenzidene
Dichloroethyl ether
(Bls(2-chloroethyl) ether)

Hazardous Air Pollutants (continued)


Category
OV
HV
OV
OV
HV
HV
N
HV
HV
HV
HV
HV
HV
HV
OV
OV
OV
OV
OV
HV
OV
OV
HV
OV
HV
HV
HV

ESP Troubleshooting Guide

CAS No.
542756
62737
111422
121697
64675
119904
60117
119937
79447
68112
57147
131113
77781
534521
51285
121142
123911
122667
106898
106887
140885
104414
51796
75003
106934

Index

Chemical Name
1,3-Dichloropropolene
Dichlorovos
Diethanolamine
N,N-Diethyl anilline
(N,N-Dimethylaniline)
Dimethyl sulfate
3,3-Dimethoxybenzidine
Dimethyl aminoazobenzene
3,3'-Dimethyl benzidine
Dimethyl Carbamoyl chloride
Dimethyl formamide
1,1-Dimethyl hydrazine
Dimethyl phthalate
Dimethyl sulfate
4,6-Dinitro-o-cresol, and Salts
2,4-Dinitrophenol
2,4-Dinitrotoluene
1,4-Dioxane
(1,4-Diethyleneoxide)
1,2-Diphenythydrazine
Ephichlorohydrin
(1-Chloro-2,3-epoxypropane)
1,2-Epoxybutane
Ethyl acrylate
Ethyl benzene
Ethyl carbonate (urethane)
Ethyl chloride (chloroethane)
Ethylene dibromide
(dibromoethane)

Category
HV
HV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
HV
OV
OV
OV
OV
HV
HV

115

Hazardous Air Pollutants (continued)

Hazardous Air Pollutants (continued)

CAS No. Chemical Name


Category
107062
Ethylene dichloride
HV
(1,2-dichloroethane)
107211
Ethylene glycol
OV
151564
Ethylene imine (Aziridine)
OV
75218
Ethylene oxide
OV
96457
Ethylene thlourea
OV
75343
Ethylene dichloride
OV
(1,1-Dichloroethane)
50000
Formaldehyde
OV
76448
Heptachlor
HV
118741
Hexachlorobenzene
HV
87683
Hexachlorobutadlene
HV
77474
Hexachlorocyclopentadlene HV
67721
Hexachloroethane
HV
822060
Hexamethylene-1,6-diisocyanate
680319
Hexamethylphosphoramide
OV
100543
Hexane
OV
302012
Hydrazine
N
7647010 Hydrochloric acid
A
7664393 Hydrogen fluoride
A
(Hydrofluoric acid)
123319
Hydroquinone
OV
78591
Isophorone
58899
Lindane (all isomers)
HV
108316
Maleic anhydride
OV
67561
Methanol
OV
72435
Methoxychlor
HV
74839
Methyl bromide (Bromethane) HV
74873
Methyl chloride
HV
(Chloromethane)

CAS No. Chemical Name


71556
Methyl chloroform
(1,1,1-Trichloroethane)
74884
Methyl iodide (Iodomethane)
108101
Methyl isobutyl ketone
(Hexone)
624839
Methyl isocyanate
80626
Methyl methacrylate
1634044 Methyl tert butyl ether
101144
4,4'-Methylene bis
(2-chloroardiline)
75092
Methylene chloride
(Dichloromethane)
101688
Methylene diphenyl
diisocyanate (MDI)
107779
4,4'-Methylenedlaniline
91203
Naphthalene
98953
Nitrobenzene
92933
4-Nitrobiphenyl
100027
4-Nitrophenol
79469
2-Nitropropane
684935
N-Nitroso-N-methylurea
62759
N-Nitrosodimethylamine
59892
N-Nitrosomorpholine
56382
Parathion
82688
Pentachloronitrobenzene
87865
Pentachlorophenol
108952
Phenol
106503
P-Phenylenediamine
75445
Phosgene
7803512 Phosphine

116

Index

ESP Troubleshooting Guide

Category
HV
HV
OV
OV
OV
OV
HV
HV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
OV
HV
OV
OV
HV

117

Hazardous Air Pollutants (continued)

Hazardous Air Pollutants (continued)

CAS No.
7723140
85449
1336363

CAS No.
95954
88062
121448
1582098
540841
108054
593602
75014
75354
1330207
95476
108383
106423
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1120714
57578
123386
114261
78875
75569
75558
91225
106514
100425
96093
1746016
79345
127184
7550450
106883
95807
584849
95534
8001352
120821
79005
79016

118

Chemical Name
Category
Phosphorus
N
Phthalic anhydride
OV
Polychlorinated biphenyls
HV
(Alodors)
1,3-Propane sultone
OV
beta-Propiolactone
OV
Proplonaldehyde
OV
Propoxur (Baygon)
OV
Propylene dichloride
HV
(1,2-Dichloropropane)
OV
Propylene oxide
OV
1,2-Propylenimine
OV
(2-methyl aziridine)
Quinoline
OV
Quinone
OV
Styrene
OV
Styrene oxide
OV
2,3,7,8-Tetrachlorodibenzo-p-dioxin
1,1,2,2-Tetracholoethane
HV
Tetrachloroethylene
HV
(Perchloroethylene)
Titanium tetrachloride
M
Toulene
OV
2,4-Toulene diamine
OV
2,4-Toulene diisocyanate
OV
o-Toluidine
OV
Toxaphene
HV
1,2,4-Trichlorobenzene
HV
1,1,2-Trichloroethane
HV
Trichloroethylene
HV

ESP Troubleshooting Guide

Index

Chemical Name
Category
2,4,5-Trichlorophenol
HV
2,4,6-Trichlorophenol
HV
Triethylamine
Trifluralin
OV
2,2,4-Trimethylpentane
Vinyl acetate
OV
Vinyl bromide
HV
Vinyl chloride
HV
Vinylidene chloride
HV
Xylenes (isomers/mixture)
OV
o-Xylenes
OV
m-Xylenes
OV
p-Xylenes
OV
Antimony Compounds
M
Arsenic Compounds
N
Beryllium Compounds
M
Cadmium Compounds
M
Chromium Compounds
M
Cobalt Compounds
M
Coke Oven Emissions
Cyanide Compounds1
Glycol Ethers2
OV
Lead Compounds
M
Manganese Compounds
M
Mercury Compounds
M
Fine Mineral Fibers3
Nickel Compounds
M
4
Polycylic Organic Matter
O
Radionuclides (including Radon)5
Selenium Compounds
N

119

Hazardous Air Pollutants (continued)


V=Volatile
N=Nonmetallic Inorganics
O=Organic
M=Metals and Metal Compounds
A=Acids, Bases and Salts
NOTE: For all listings above which contain the
word compounds and for glycol ethers, the following applies: Unless otherwise specified, these
listings are defined as including any unique chemical substance that contains the named chemical (i.e.,
antimony, arsenic, etc.) as part of that chemicals
infrastructure.
1

120

X'CN where X=H' or any other group where a formal dissociation may occur. For example KCN or
Ca(CN)2.
Includes mono- and di- ethers of ethylene glycol,
diethylene glycol and triethylene glycol R(OCH2CH)n - OR' where
n= 1, 2 or 3
R= alkyl or aryl groups
R'= R, H or groups which, when removed, yield glycol ethers with the structure: R-(OCH2CH)n - OH.
Polymers are excluded from the glycol category.
Includes mineral fiber emissions from facilities manufacturing or processing glass, rock or slag fibers (or
other mineral derived fibers) of average diameter 1
micrometer or less.
Includes organic compounds with more than one
benzene ring, and which have a boiling point greater
than or equal to 100 C.
A type of atom which spontaneously undergoes
radioactive decay.

ESP Troubleshooting Guide

Index

121

You might also like