EE Project Mapua
EE Project Mapua
EE Project Mapua
CITY HEIGHTS
THE SITE
TO PUROK MALAKAS
TO SORIANO SUBD.
BLK. 8
VICINITY MAP
NOT TO SCALE
PROJECT: PROPOSED RESIDENTIAL
BUILDING
LOCATION: #010 SEBASTIAN ST.,
PARADISE SUBD., G.S.C.
OWNER:
CONTENTS:
SHEET NO.
VICINITY MAP
E-2
3.5
4.5
4.5
1.5
1.5
10.5
.8
5.5
4.5
14
FLOOR PLAN
SCALE 1:75
PROJECT: PROPOSED RESIDENTIAL
BUILDING
LOCATION: #010 SEBASTIAN ST.,
PARADISE SUBD., G.S.C.
CONTENTS:
SHEET NO.
FLOOR PLAN
E-3
2
G
H
L
M
G
J
L
H IJ
E FG
K
M
E
N
P
O
Q
A
B
C
O
B
AE
BCD
A
D
A
LIGHTING LAYOUT
SCALE 1:100
PROJECT: PROPOSED RESIDENTIAL
BUILDING
LOCATION: #010 SEBASTIAN ST.,
PARADISE SUBD., G.S.C.
OWNER:
CONTENTS:
SHEET NO.
LIGHTING LAYOUT
E-5
12
11
8
10
13
POWER LAYOUT
SCALE 1:100
PROJECT: PROPOSED RESIDENTIAL
BUILDING
LOCATION: #010 SEBASTIAN ST.,
PARADISE SUBD., G.S.C.
OWNER:
CONTENTS:
SHEET NO.
POWER LAYOUT
E-6
LEGEND:
300 W CHANDELIER
CONVENIENCE OUTLET
40 W FLUORESCENT LIGHT
PANEL BOARD
20 W FLUORESCENT LIGHT
CIRCUIT HOMERUN
LIVE LINE
20 W PIN LIGHT
4 kW MICROWAVE
5 kW ELECTRIC RANGE
6 kW WASHING MACHINE
3 kW WATER HEATER
1.5 hp WATER PUMP
2 hp AIR CONDITIONING UNIT (ACU)
PROJECT: PROPOSED RESIDENTIAL
BUILDING
LOCATION: #010 SEBASTIAN ST.,
PARADISE SUBD., G.S.C.
OWNER:
MARK RANDOLPH T. ARNAEZ
ELECTRICAL ENGR.:
ENGR. JHAYSON ALLEN S. TAN
CONTENTS:
SHEET NO.
LEGEND
E-4
GENERAL NOTES/SPECIFICATION:
ALL WORK SHALL CONFORM WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE RULES
AND REGULATION OF THE ENFORCING AUTHORITY AND THE LOCAL LIGHTS AND POWER COMPANY.
ALL MATERIALS TO BE USED SHALL BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE AS
SPECIFIED ON PLANS.
SERVICE ENTRANCE SHALL BE 2 80 mm THW CU. WIRE WITH 1 14 mm GROUND CU. WIRE IN
50 mm RIGID METALLIC CONDUIT (RMC).
WIRING SHALL BE CONCEALED USING A RIGID METALLIC CONDUIT (RMC).
ALL WORKS SHALL BE UNDER THE DIRECT SUPERVISION OF THE DULY LISENCED ELECTRICAL ENGINEER
OR MASTER ELECTRICIAN.
OWNER:
MARK RANDOLPH T. ARNAEZ
ELECTRICAL ENGR.:
ENGR. JHAYSON ALLEN S. TAN
CONTENTS:
SHEET NO.
GENERAL NOTES/
E-1
SPECIFICATION
LOAD SCHEDULE:
Circuit #
Wires
Ground Wire
Conduit
Description
Lighting Outlets
Voltage Current
230 V
1.97 A
15 AT
2 - 2.0 mm
-----
15 mm
Lighting Outlets
230 V
2.09 A
480 W
15 AT
2 - 2.0 mm
-----
15 mm
6 Convenience Outlets
230 V
4.70 A
1080 W
20 AT
2 - 3.5 mm
1 - 3.5 mm
15 mm
7 Convenience Outlets
230 V
5.48 A
1260 W
20 AT
2 - 3.5 mm
1 - 3.5 mm
15 mm
7 Convenience Outlets
230 V
5.48 A
1260 W
20 AT
2 - 3.5 mm
1 - 3.5 mm
15 mm
4 kW Microwave
230 V
17.39 A
4000 W
30 AT
2 - 5.5 mm
1 - 5.5 mm
15 mm
5 kW Electric Range
230 V
17.39 A
4000 W
30 AT
2 - 5.5 mm
1 - 5.5 mm
15 mm
6 kW Washing Machine
230 V
26.09 A
6000 W
70 AT
2 - 22 mm
1 - 8.0 mm
25 mm
3 kW Water Heater
230 V
13.04 A
3000 W
20 AT
2 - 3.5 mm
1 - 3.5 mm
15 mm
10
3 kW Water Heater
230 V
13.04 A
3000 W
20 AT
2 - 3.5 mm
1 - 3.5 mm
15 mm
11
230 V
10.00 A
2300 W
30 AT
2 - 5.5 mm
1 - 5.5 mm
15 mm
12
230 V
12.00 A
2760 W
30 AT
2 - 5.5 mm
1 - 5.5 mm
15 mm
13
230 V
12.00 A
2760 W
30 AT
2 - 5.5 mm
1 - 5.5 mm
15 mm
IT = 140.67 A
IW = 147.19 A
USE 50 mm RMC
OWNER:
MARK RANDOLPH T. ARNAEZ
ELECTRICAL ENGR.:
ENGR. JHAYSON ALLEN S. TAN
CONTENTS:
SHEET NO.
LOAD SCHEDULE
E-7
DESIGN ANALYSIS:
LIGHTING CIRCUIT: 24 x FLOOR AREA = 24 x 138 m2 = 3312 W
SMALL APPLIANCE CIRCUIT:
1500 W
LAUNDRY CIRCUIT:
1500 W
BATHROOM CIRCUIT:
1500 W
7812 W
IT = 141.32 A
- 3000 W
4812 W
x 0.35
IW = 147.84 A
1684.2 W
+ 3000 W
4684.2 W
4 kW MICROWAVE:
4000 W
5 kW ELECTRIC RANGE:
4000 W
6 kW WASHING MACHINE:
6000 W
2 - 3 kW WATER HEATER:
6000 W
2300 W
5520 W
ICB = 186.97 A
USE 175 AT Moulded Case Circuit Breaker (MCCB)
USE 2 80 mm THW CU. WIRE
USE 1 14 mm GROUND CU. WIRE
USE 50 mm RMC
27820 W
TOTAL POWER = 27820 W + 4684.2 W = 32504.2 W
IT = 32504.2 W / 230 V
IT = 141.32 A
OWNER:
CONTENTS:
SHEET NO.
DESIGN ANALYSIS
E-8
15 AT
20 AT
20 AT
20 AT
30 AT
30 AT
70 AT
20 AT
30 AT
10
30 AT
30 AT
1
3
5
11
13
2
4
6
12
30 AT
OWNER:
MARK RANDOLPH T. ARNAEZ
ELECTRICAL ENGR.:
ENGR. JHAYSON ALLEN S. TAN
CONTENTS:
SHEET NO.
RISER DIAGRAM/
E-9
PANEL BOARD