Tan Delta-F
Tan Delta-F
Tan Delta-F
Tan Test
Purpose
PLTU Kendari 3
1 x 10 MW
Turbin Room
Location
1. NAME PLATE
Brand
Type
QF-12-2
12000
14118
6300
3000
Frequency (Hz)
50
212
1294
Power Factor
0.85 Lagging
Product No.
12301
155
Connected
130
2. Result
Phase
Voltage Injected
(V)
Dissipation
Factor (%)
Capacitance
(pF)
Dissipation
Factor (%)
Capacitance
(pF)
Dissipation
Factor (%)
Capacitance
(pF)
1260
3.6585
95,512.743
3.6453
96,199.243
3.6321
96,885.743
2520
3.7849
95,696.161
3.7402
96,374.867
3.6954
97,053.573
3780
3.9585
95,914.753
3.8875
96,574.497
3.8165
97,234.241
5040
4.2201
96,254.764
4.1233
96,867.621
4.0265
97,480.456
6300
4.5580
96,735.111
4.4403
97,295.742
4.3226
97,856.374
5041
4.2666
96,277.595
4.1693
96,894.586
4.0719
97,511.578
3781
3.9744
95,921.089
3.9112
96,592.166
3.8480
97,263.244
2521
3.7996
95,699.201
3.7734
96,405.727
3.7472
97,112.253
1261
3.6911
95,526.091
3.6661
96,242.881
3.6410
96,959.669
27.10.2016
Date
Tested by,
Alexander Panel
Date
Prepared by,
PT.Hutama Karya
Date
Witnessed by,
RECONSULT
Date
Witnessed by,
PLN PUSERTIF
Date
Approved by