Bus Bar Protection
Bus Bar Protection
Bus Bar Protection
At a glance:
Bus arrangements
Bus components
Bus protection techniques
CT Saturation
Application Considerations:
High impedance bus differential relaying
Low impedance bus differential relaying
Advantages:
This bus bar arrangement enjoys less cost of installation
Less maintenance
simple operation
Disadvantages:
when Bus bar is under maintenance total supply and all
feeders should be disconnected
Least flexibility and reliability.
Fault on the bus bar all the feeders connected to the
bus bars should be disconnected.
Advantages:
Any circuit can be taken out of circuit for maintenance.
Flexibility in connecting the feeder circuit to either of
the bus-bars.
Disadvantages:
Most expensive.
Loose circuits connected to bus-bar when fault occurs
on the bus-bar.
Advantages:
Low initial cost
Any breaker can be taken of circuit for maintenance
Disadvantages:
Requires one extra breaker for bus tie
Switching is somewhat complicated when breaker is
under maintenance
Advantages:
Most flexible operation possible.
High reliability.
Bus failure will not remove any circuit from service.
Disadvantages:
High cost.
Relaying is somewhat complicated since the
middle breaker must responsible for both the
circuits on either direction and should operate.
Advantages:
Low cost
Flexible operation for breaker maintenance
Any breaker can be taken out of service without
interrupting load
Power can be fed from both the direction
Disadvantages:
Fault occur during maintenance will break the ring
Relaying is complex
Breaker failure during fault will trip one additional circuit.
Fandamentals
of
Bus bar protection
So, it is clear that under normal condition there is no current flows through
the bus-bar protection tripping relay. This relay is generally referred as Relay
87.
Essentially all the CTs used for differential bus-bar protection are of same
current ratio.
Hence, the summation of all secondary currents must also be equal to zero.
Now, say fault is occurred at any of the feeders, outside the protected zone. In
that case, the faulty current will pass through primary of the CT of that feeder.
This fault current is contributed by all other feeders connected to the bus. So,
contributed part of fault current flows through the corresponding CT of
respective feeder. Hence at that faulty condition, if we apply KCL at node K, we
will still get, iR = 0.
At this condition, also the faulty current is contributed by all feeders connected to the
bus. Hence, at this condition, sum of all contributed fault current is equal to total
faulty current.
Now, at faulty path there is no CT.
Here, bus section A or zone A is bounded by CT1, CT2 and CT3 where CT1 and
CT2 are feeder CTs and CT3 is bus CT.
Similarly bus section B or zone B is bounded by CT4, CT5 and CT6 where CT4 is
bus CT, CT5 and CT6 are feeder CT.
Bus components
BUS 1
ISOLATOR 1
+
BUS 2
ISO 1
7B
7A
ISOLATOR 1 OPEN
F1a
F1c
F1b
ISO 2
CB 1
ISO 3
BYPASS
ISOLATOR 1
BUS 1
+
7B
7A
ISOLATOR 1 CLOSED
F1a
F1c
F1b
Current Transformers
BUS 1
BUS 2
ISO 1
ISO 2
Protection Requirements
High bus fault currents due to large number of circuits
connected:
CT saturation often becomes a problem as CTs may not be sufficiently
rated for worst fault condition case
large dynamic forces associated with bus faults require fast clearing
times in order to reduce equipment damage
Interlocking Schemes
BLOCK
50
50
50
50
50
50
51
Linear Couplers
40 V
10 V
10 V
0V
20 V
External
Fault
If = 8000 A
2000 A
2000 A
0A
4000 A
0V
59
Linear Couplers
Esec= Iprim*Xm - secondary voltage on relay terminals
IR= Iprim*Xm /(ZR+
ZC) minimum operating current
where,
Iprim primary current in each circuit
Xm liner coupler mutual reactance (5V per 1000Amps => 0.005
@ 60Hz )
ZR relay tap impedance
ZC sum of all linear coupler self impedances
If = 8000 A
Internal Bus
Fault
40 V
0V
0A
10 V
2000 A
10 V
2000 A
0V
0A
20 V
4000 A
59
Linear Couplers
59
Accuracy dependent on
secondary circuit resistance
Usually requires larger CT cables
to reduce errors higher cost
Important Notations
: per unit method current base
: per unit method power base
: per unit method voltage base
: per unit method admittance base
: per unit method impedance base
-Percentage Impedance
- Per unit Impedance
- Actual Impedance
-Per unit base Impedance
Three Phase
Dividing a system element by its per-unit base value gives the per-unit
value of the element
Some times per-unit values are available for a given base kV, but the
problem being solved is using a different base. In this instance it is possible
to convert the unit
Source Impedance
Generator
Transformer
Impedance
where V is in kV
as 20 MVA and
the Line-Neutral voltage on the secondary of the transformer is 0.4/3 = 0.230 kV, giving:
Where Zpu, is the total impedance between the source and the fault.
Fault flow through parallel branches is given by the ratio of impedances. As illustrated this can enable
fault flows to be found through each branch.
Having calculated the fault flow in each branch, it is then relatively simple to find the
current distribution using :
where
Sequence Network
Electrical power and voltage are generally taken as base quantities. In
three phase system, three phase power in MVA or KVA is taken as base
power and line to line voltage in KV is taken as base voltage. The base
impedance of the system can be calculated from these base power and
base voltage, as follows,
Per unit is an impedance value of any system is nothing but the radio of
actual impedance of the system to the base impedance value.
Sequence Impedance
Positive Sequence Impedance
The impedance offered by the system to the flow of positive sequence
current is called positive sequence impedance .
Negative Sequence Impedance
The impedance offered by the system to the flow of negative sequence
current is called negative sequence impedance .
Zero Sequence Impedance
The impedance offered by the system to the flow of zero sequence current
is known as zero sequence impedance .
In previous fault calculation, Z1, Z2 and Z0 are positive, negative and zero
sequence impedance respectively. The sequence impedance varies with
the type of power system components under consideration
In static and balanced power system components like transformer and lines, the
sequence impedance offered by the system are the same for positive and negative
sequence currents. In other words, the positive sequence impedance and
negative sequence impedance are same for transformers and power lines.
But in case of rotating machines the positive and negative sequence impedance
are different.
The assignment of zero sequence impedance values is a more complex one. This is
because the three zero sequence current at any point in a electrical power system,
being in phase, do not sum to zero but must return through the neutral and /or
earth. In three phase transformer and machine fluxes due to zero sequence
components do not sum to zero in the yoke or field system. The impedance very
widely depending upon the physical arrangement of the magnetic circuits and
winding.
The reactance of transmission lines of zero sequence currents can be about 3 to 5 times the
positive sequence current, the lighter value being for lines without earth wires. This is because
the spacing between the go and return(i.e. neutral and/or earth) is so much greater than for
positive and negative sequence currents which return (balance) within the three phase
conductor groups.
The zero sequence reactance of a machine is compounded of leakage and winding reactance,
and a small component due to winding balance (depends on winding tritch).
The zero sequence reactance of transformers depends both on winding connections and upon
construction of core.
Percentage Impedance
The percentage impedance of a transformer is the volt drop on
full load due to the winding resistance and leakage reactance
expressed as a percentage of the rated voltage.
It is also the percentage of the normal terminal voltage required
to circulate fullfull-load current under short circuit conditions.
The impedance is measured by means of a short circuit
test. With one winding shorted, a voltage at the rated frequency
is applied to the other winding sufficient to circulate full load
current.
Thanks
For Your Attention