Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
100% found this document useful (1 vote)
180 views

Transformer Protection Guide

Protection of power equipment aims to prevent hazards like fires or explosions from overloads, short circuits, and earth faults. Relay protection systems continuously monitor the power system state using current and voltage transformers and detect abnormal situations. Relays are set to operate after a time delay to limit disturbances and maintain selectivity. Protection zones are formed by relays and circuit breakers to isolate faults and maintain redundancy. Relay types include overcurrent, differential, directional, and impedance relays. Transformer, generator, line, and motor protection systems use various relay schemes tailored to the equipment for safety and reliability.

Uploaded by

kponram
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
180 views

Transformer Protection Guide

Protection of power equipment aims to prevent hazards like fires or explosions from overloads, short circuits, and earth faults. Relay protection systems continuously monitor the power system state using current and voltage transformers and detect abnormal situations. Relays are set to operate after a time delay to limit disturbances and maintain selectivity. Protection zones are formed by relays and circuit breakers to isolate faults and maintain redundancy. Relay types include overcurrent, differential, directional, and impedance relays. Transformer, generator, line, and motor protection systems use various relay schemes tailored to the equipment for safety and reliability.

Uploaded by

kponram
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

Protection of power equipment

· overload protection
- over heating causes hazard of fire or explosion
- not used, if outage would be more dangerous; alarm needed anyway
- overload protection can be integrated with short circuit protection

· short circuit protection


- aim is to prevent excess heating of components
- other hazard: sag of conductors, broken conductor

· earth fault protection


- single phase to earth fault
- into earthed equipment
- into other system parts or objects
- generally should be noticed up to Rf = 500 W
- automatic tripping versus alarm only
· protection against hazard voltages
- public safety of people
- risks of fire
- risk of explosion
- importance depends on circumstances
- e.q. extremely hazardous or hazardous conditions
Protective relays

· measure continuously power system state


- usually connected by measurement transformers
- CT & VT (current & voltage transformer)

· detect abnormal situations


- short circuit, earth fault, overload, over voltage, under voltage
- relay operates when set values are exceeded

· objective is to prevent or limit large disturbances


- alarm levels
- try to limit the affected area (selectivity)

· operate after the set time delay


- total fault time: relay delay + CB operation time (~ 100 ms)
Principles of relay protection
· Selectivity: minimum outage coverage

· Speed and sensitivity


- in order to minimize the damages
- in order to maintain transmission stability
· Redundancy
- adjacent relays partly overlapping
- always some back-up protection
- no blind spots
· Reliable and simple Selectivity
· Testing must be possible
- on site · Relay detects the fault within protection zone
- during operation · Relay does not trip, if
· Reasonable investment costs - there is no fault
- fault is outside the protection zone
· Absolute selectivity
- relay trips only for faults within protection zone
· Time grading
· Current grading
Protection zones
· formed by relays and circuit breakers
· lines, transformers, generators, motors

Back-up protection
· works in case of primary protection fails
· important especially in transmission systems
· large machines and transformers

Main tasks of relay protection

· indicate faults
· limit affected area
· limit consequences
Types of relays
Over current relays :
t t t

I I I
instantaneous definite time inverse time

Differential relays :
transformer
Id
cable
I1 I2

Id
Id
I
I = (I1+I2)/2
Id = I2 - I1
Relay types

Directional relays : Impedance relays :


Zj = line impedance
X

I
I R
Rf
U
U
I
j

I sin j
MV-line short circuit protection
Re-closing (RC) :

fault RC RC

t1 0,5 s t2 ~ 1-2 min = Dt t3

Equivalent fault duration:


t ekv = (t1 + t 2 )e - Dt / t + t 3
t is the conductor cooling time constant

Maximum allowed fault duration is tmax

t max = I1s
2 2
Ik
Ik = actual fault current (max)
I1s = 1s thermal rated current

It must be tekv £ tmax


t1+t2 £ tmax
Overcurrent protection of a MV line
The relay settings include :
I> delayed tripping current setting
t> delayed tripping time setting
I>> fast tripping current setting
t>> fast tripping time setting
tn re-closing time settings

Conditions for settings :


I> >> ILOAD
I> << Ik,min (2-phase short circuit)
t> : tekv < tmax (thermal limiting current)

The time setting t> must be clearly higher than the time delay
of the relay downstream, but clearly lower than the setting of the
back-up protection upstream.

Fast tripping takes care of strong faults close to the substation.


Often re-closings are blocked in this case.

Minimum time grading : mechanical relays 0.5 s ;


static relays 0.3 s´; numeric relays 0.15 s
Earth fault protection of a MV-line

1) Zero sequence over current relay


- works in unearthed systems
- the fault current must be clearly higher than the
capacitive charge current in the sound line case.

I0>
C0j åC
i
0i >> C 0j
i¹ j
If = 3wC0e·E

2) Zero sequence directional relay in reactive current connection

- works in unearthed systems


U0
condition :
I0
j I0 sin j > Ias
I0
I0
j0 = 90°
U0
Earth fault protection in compensated neutral systems

3) Zero sequence directional relay in active current connection

- works properly in coil earthed systems


U0
j I0 condition:
I0 I0 cos j > Ias
I0
U0
Relay protection in transmission systems

400 kV line protection

Distance relay
· both short circuit and earth fault protection
· back-up protection for other network parts
· pilot wire systems

Differential relay
· only short lines (cables)
Distance relays

· Not-switching
- very fast
- 6 measurement units
- phase-phase
- phase-earth
- works in 20 ms

· Switching
- pick-up unit
- measurement unit
- short circuit / earth fault connection
- works in 30…70 ms
Protection zones of a distance relay

D A B C

1
2
3
4

Example:
Zone 1: reach 85 % of line A-B, operation time < 100 ms
Zone 2: reach 120 % of line A-B, time delay 400 ms
Zone 3: reach120 % of line A-C, time delay 1 s
Zone 4: reach forward A-C, time delay 4 s

X Line impedance

Load current

R
Rf
Zones of protection

A B C

A B C

The effect of side-feeds:


z=0,85(a+kb)
z=0,85a

a b
IA+IB
A B C
IA + IB
k = IA IB
IA ~ ~
The power swing must not trip the relay

Example: switching state change

Power Impedance
Power swing blocking relay

X Impedance during
a power swing

Blocking relay operation area

R
Impedance relay operation area

- If power swing relay picks-up, it will block the distance relay after time delay Dt

- Dt is taken big enough that blocking has not time to operate during
faults, but short enough that it works during power swings before the
relay trips.
Transformer protection

· protection for short circuits inside and downstream

· primary partly protected by the feeding line relay

· short circuit protection by over current relay


- small primary transformers
- fast tripping for primary faults
- delayed tripping for downstream faults

· the use of differential relays


- compensation of the transforming ratio
- blocking for inrush currents
- 100 Hz component
- the effect of on-load tap-changer must be considered

· Buchholz-relay or gas relay

- between tank and expansion chamber


- overload and arc produces gas
- first alarm, then trip
- strong faults: fast trip
Transformer protection

Buchholz-relay
- detection of insulation faults
- operation time 100…300 ms
- steps for alarm and trip
- gas analysis Þ fault type !

Parts of a gas relay


1 body
2 cover
3 window for inspection
4 alarm float
5 trip float
6 tube for alarm contact
7 tube for trip contact
8 connection wires
9 connection screws
10 valve for gas sample
Transformer overload protection :
· temperature measurement of top-oil
· modeling circuit for winding

Earth fault protection :


· zero sequence over current relay

In the case of large transformers :


· earth fault protection
· oil level indication
· flow relay for on-load tap-changer

Factors affecting the protection solutions:


· importance of the transformer
· type of neutral earthing
· type of network
- radial, or looped
Differential relay in transformer protection
Iv = (I1 +I2) / 2 & Id = I1 - I2

p = basic setting = Id1/In


s = pick-up ratio = Id2/Iv

Id/In

Iv
1
Id2
Id1

0 1 2 3
Iv/In

Id

I1 I2
Factors affecting the setting of a differential relay

· saturation of current transformers


· transformer magnetizing inrush current
· errors of current transformers (< 13%)
· steps of on-load tap-changer (< 15%)

L1

L2

L3

An example of the inrush current


123kV CB

Example of the
Art fault
24kV CB
Alarm

transformer Short circuit &


protection Earth fault Back-up

Short circuit

Earth fault
(110 / 20 kV primary
transformer) Tap changer
Flow relay
Gas relay

Oil level
Oil temperature

Winding temp model

Short circuit
Back-up

Short circuit

Busbar protection

Earth fault

Earth fault

Busbar voltage
monitoring
Generator protection

· investment costs
· operation costs
- faults
- maintenance
- preventive maintenance
- outage costs
- these all depend on the protection

Faults of generators in Finland in the years 1970-1983


year -70 -71 -72 -73 -74 -75 -76 -77 -78 -79 -80 -81 -82 -83
generators pcs 89 95 102 104 106 109 111 118 118 118 118 119 120 120
faults pcs 1 6 4 2 0 5 3 5 6 4 4 9 9 5
fault costs 3,8 0,9 0,6 7,9 0 1,7 8,0 3,5 4,8 5,2 7,5 2,5 3,4 2,1
Mmk / case
average outage 60 57 65 225 0 77 140 43 60 52 25 110 70 60
time (days)
Generator protection

· Basic protection relays


- over current
- stator earth fault protection
- disconnection and synchronizing relays
· protection of the turbine
· magnetizing control and stopping logic
· winding cooling system
· fire protection (CO2)
· bearing lubrication and cooling
An example
voltage rise

inter-turn faults

rotor earth fault

1 = alarm
2 = generator CB
3 = magnetizing CB
4 = turbine trip

reverse power

over load

load unsymmetry

over current

stator earth fault

You might also like