T O R S I O N A L V I B R AT I O N S
p ( d iq + q id )
3
Tem = (7)
2
p = no of generator pole pairs
The equation of mechanical motion is
J d
Tdrive = Tem + (8)
p dt
Tdrive = driving turbine torque
J = moment of inertia
The equations (1) to (8) are used to drive final dynamical model
to find various generator parameters during sudden fault
conditions.
The standard flux equations are as
d = Ld id + Lmd (i fd + iD ) (9)
q = Lqiq + LmqiQ (10)
0 = L0i0 (11)
fd = Lfd i fd + Lmd (id + iD ) (12)
D = LDiD + Lmd (id + i fd ) (13)
Q = LQiQ + Lmqiq (14)
where
m denotes mutual induc tan ce and denotes leakage induc tan ce.
imd = id + i fd + iD , imq = iq + iQ (15)
Ld = L + Lmd , Lq = L + Lmq
L fd = L fd + Lmd , LD = LD + Lmd , (16)
LQ = LQ + Lmq
Also
d
= (17)
dt
Ld 1 = Ld cos , Ld 2 = Ld sin
Lq1 = Lq cos , Lq 2 = Lq sin
(21)
Lmd 1 = Lmd cos , Lmd 2 = Lmd sin
Lmq1 = Lmq cos , Lmq 2 = Lmq sin
From rotor voltage equations flux term is removed by replacing with equation (12), (13) and
(14) di di diD
Lmd d
+ L fd fd
+ Lmd = R fd i fd + u fd (22)
dt dt dt
did di di
Lmd + Lmd fd + LD D = RD iD (23)
dt dt dt
diq diQ
Lmq + LQ = RQ iQ (24)
dt dt
Continued
Now put the values of flux given by equation (9) and (10) and after simplifying eqn.(7) gives
3
Tem = p ( Lmd imd iq + Lmq id imq ) ____(25)
2
LINE TO GROUND SHORT CIRCUIT
Let phase A be faulted phase.
The boundary condition s in this case.
u A = 0, (26)
iB = iC = 0. (27)
Voltage across phase A is given as:
d A
u A = R iA +
dt
from (26)
d A
R iA + =0 (28)
dt
Also from converse Park-Gorev transformation (19), we get:
Differentiating (29) w.r.t time and considering (9),(10,(11), (17) and (28) , we get
d d d q d 0
cos + sin + = RiA d sin + q cos (30)
dt dt dt
1
3 L0
L
d 1 iA R iA
id L i
Lq 2 d2 d
d iq Lq1 iq
dt i =
L
i
(31)
Lmd 1 fd md 2 fd
iD L iD
i
Lmd 1 Q iQ
Lmq1
L
mq 2
Also from (18), (26) and (27), we get
2 did 2 diA
id = i A co s
= cos + iA sin
3 dt 3 dt
(3 2 ) (33)
2 diq 2 diA
iq = i A sin = sin iA cos
3 dt 3 dt
di fd diD
L fd LD = R fd i fd + RD iD + u fd (34)
dt dt
Also from (15) and (32) and Eqn (25)
T
2
3 (Ld 1 Lq1 ) sin iA
i
Tem = P Lmd 2 fd i (35)
iD A
Lmd 2
Lmq1 iQ
LINE TO LINE SHORT CIRCUIT
Suppose Phase B and Phase C is short circuited
u B = uC (36)
iA = 0
(37)
iB = iC
d B d C
u B = R iB + , uC = R iC + (38)
dt dt
d
( B C ) + R (iB iC ) = 0 (39)
dt
d
( B C ) + 2 R iB = 0 (40)
dt
From (19)
Differentiating (41) w.r.t time and taking in to acccount (17), (36) and (40) ,
we get
d d d q 2
sin cos = RiB + d cos + q sin (42)
dt dt 3
T
2
Further from (9) and (10), we get 3R
Ld 1
T iB
Ld 2 id i
L i d
d L
q1 q q 2
iq
Lmd 2 . i fd = (43)
dt i fd
Lmd 2 iD Lmd 1 iD
Lmq1 iQ
L iQ
md 1
L
mq 2
Torque Calculation:
Apply boundary conditions to current equations and using Park-Transform (18), we get
2 did 2 diB
id = iB sin = sin + iB cos
3 dt 3 dt
(44) (45)
2 diq 2 diB
iq = iB cos = cos + iB sin
3 dt 3 dt
T
2(Ld 1 Lq1 ) sin iB
i
3Lmd 1
Tem = p fd i (46)
3Lmd 1 iD B
3Lmq 2 iQ
THREE PHASE SHORT CIRCUIT
Boundary conditions are as
iA + iB + iC
iA + iB + iC = 0 i0 = = 0 (47)
3
u A = u B = uC = 0
From (18), we get ud = uq = 0 (48)
did di fd di
Ld + Lmd + Lmd D = Rid + ( Lq iq + Lmq iQ ) (49)
dt dt dt
diq diQ
Lq + Lmq = Riq ( Ld id + Lmd i fd + Lmd iD ) (50)
dt dt
The stator phase currents are calculated using (19) and (47)
iA = id cos + iq sin
iB =
1
2
( )
id + 3iq cos
1
2
( )
3id + iq sin (51)
1
( )
iC = id + 3iq cos +
2
1
2
( )
3id iq sin
DYNAMIC SIMULATION
The general dynamic model for Line to Ground fault and Line to Line fault is shown below. The below
mentioned six coupled equations can be solved in MATLAB using Adams predictor corrector scheme
with startup by Runge-Kutta method.
i phase i phase u fd
i
d i fd 0
+X =
fd
L
dt iD iD 0
Q
i Q 0
i
d
P
= Tem (52)
dt J
d
=
dt
For Line to ground fault use equations (34), (23), (24), (31), (17) and (25) processed using (32),(33)
0 Lfd LD 0
c L cos L L 0
md md D
L= c Lmq sin 0 0 LQ
L
+ c L cos cos + c L sin sin L cos L cos L sin
0
3 d q md md mq
0 R fd RD 0
c L sin 0 RD 0
X =
md
c Lmq cos 0 0 RQ
G Lmd sin Lmd sin Lmq cos
where
G = c ( Ld Lq ) cos sin + ( Ld Lq ) sin cos + R
2
c=
3
For Line to Line fault use equations (34), (23), (24), (43), (17) and (25) processed using (44),(45)
0 L fd LD 0
c Lmd sin Lmd LD 0
L=
c Lmq cos 0 0 LQ
c Ld sin sin + c Lq cos cos Lmd sin Lmd sin Lmq cos
0 R fd RD 0
c L cos 0 RD 0
X =
md
c Lmq sin 0 0 RQ
G Lmd cos Lmd cos Lmq sin
where
G = c ( Ld + Lq ) cos sin + ( Ld + Lq ) sin cos + c R
2
c=
3
For Three Phase fault
The below mentioned seven coupled equations again can be solved in MATLAB using Adams
predictor corrector scheme with startup by Runge-Kutta method.
id id 0
i i
d q q 0
L i fd + X i fd = u fd
dt
iD iD 0
iQ iQ 0
d P
= Tem
dt J
d
=
dt
Use equations (49), (50), (22), (23), (24), (25) and (17)
where
Ld 0 Lmd Lmd 0
0 Lq 0 0 L m q
L = Lmd 0 L fd Lmd 0
Lmd 0 Lmd LD 0
0 Lmq 0 0 L Q
R Lq 0 0 Lmq
L R Lmd Lmd 0
d
X = 0 0 R fd 0 0
0 0 0 RD 0
0 0 0 0 RQ
VALIDATION OF PREDICTOR CORRECTOR
FORMULATION IN MATLAB
Validation for linear equation
from ref. [1] x + 1.5 x = 7.5 + 4.5 cos(t ) + 3sin(5t ), x (t = 0) = 0
S S Rao, fifth edition chapter 4
x1 = x2
Validation for nonlinear equation from ref. [2]
x2 = 200 x1 10 x2 50 x1 x1 x1
S S Rao, second edition, chapter 13, pp 643
x1 (0) = 7.5
x2 (0) = 0
Time Adams P-C Scheme Ref. [2] Adams P-C Scheme Ref. [2]
(x1) (x1) (x2) (x2)
0 7.500000000000000 7.50000 0 0
0.0025 7.430295407266823 7.43030 -55.2857313413170 -55.2857
0.0050 7.227114553836680 7.22711 -106.3502008584617 -106.35
0.0075 6.903976272629309 6.90398 -150.9436182706467 -150.944
0.0100 6.478992587482140 6.47900 -187.6677677688700 -187.662
0.0125 5.972579126001135 5.97268 -216.0208293218877 -216.014
0.0150 5.405450100088078 5.40567 -236.3178352751917 -236.317
0.0175 4.796747326300100 4.79708 -249.4562148819691 -249.463
0.0200 4.162906242365495 4.16331 -256.6594832884100 -256.674
0.0225 3.517126088700053 3.51755 -259.2491802493062 -259.270
RESULTS