G U LF G R ILL Ese O.

VARIABLE
AIR VOLUME
VAD90 VARIABLE AIR VOLUME
SINGLE DUCT BY-PASS VAV

The GGC Model VAD90, by-pass VAV, provides The model is compatible with reverse or direct
pressure dependent and independent variable air acting electric/electronic thermostats. Zone
volumes to individual zones while by-passing the thermostats directly control the by-pass damper
unneeded air to the ceiling plenum for recirculation. assuring that the required amount of air needed is
delivered to the zone.
Although zone air volume in small buildings may
vary greatly, the cost of fan controls many times Down stream ductwork pressure losses can be
cannot be justified. Zone variable air volumes are matched by adjusting an integral by-pass type
realized with the by-pass unit while the supply fan balancing damper.
delivers a constant CFM.

Other Features Include:

Airflow capacities from full shut-off zone to Balancing damper in by-pass is standard.
2,500CFM.
Averaging airflow sensor for the type pressure
Electronic, electric or manual damper control. independent at the inlet is standard.

Low pressure drop. Optional hanger brackets.

Low sound levels. Optional control enclosure for electric control.

Thermally and acoustically insulated casing. Optional internal foil coated insulation (for
applications of hospitals and laboratories etc.)
Open-end discharge provided with slip and
drive connection for easy installation. Optional heating/cooling change over sensor.

../ Optional multi-discharge adaptors has Wiring diagrams will be furnished for all types of
round/oval outlet connections with integral VAV's.
balancing damper.

24-1
VADBO-C VARIABLE AIR VOLUME
STANDARD CONSTRUCTION FEATURE
SINGLE DUCT BY - PASS VAV WITHOUT HEATER

RELIEF AIR
BALANCING DAMPER o x 4" LONG SPIGOT

H
CONTROL ENCLOSURE
(OPTIONAL)

ACCESS DOOR E x F (BY-PASS OPENING)


(OPTIONAL)

PRODUCT DESCRIPTION

The complete casing with by-pass damper The VAV damper blade and control shaft (3/8"-0)
section is made up of 22 gauge zinc coated mill are extruded aluminum mechanically keyed
galvanized steel. together as a single piece.

1" thick fiberglass 24 kglme densities Operation of blade by maintenance free nylon
comfortably acting as acoustic attenuator and bearings for smooth and noiseless operation
thermal resistant barrier insulate the casing. and the damper closing against a gasket seal.

VAD90 02C 04C 06C 08C 10C 12C 14C


CFM RANGE 125-250 250-475 350-725 475-1000 700-1450 1000-1950 1250-2500

DIMENSIONS LISTED IN INCHES - BASIC ASSEMBLY


UNIT DISCHARGE LENGTH COLLAR EQUIVALENT BY-PASS OPENING
H
MODEL A B C DIA-0-D OVAL SIZE-O E F
VAD90-02C 12 10 24 6 N/A 12 4 14
VAD90-04C 12 10 24 8 N/A 12 4 14
VAD90-06C 12 10 24 9* 77/8x97/16 12 4 14
VAD90-08C 17 10 30 10* 7 718 x 11 1/32 17 4 14
VAD90-10C 17 10 30 12* 7718 x 14 3/16 17 4 14
VAD90-12C 27 10 36 14* 7718 x 175/16 27 41/2 14 1/2
VAD90-14C 34 10 36 16* 7718 x 20 1/2 34 41/2 14 1/2
AE : Air Flow Enter, AD: Air Flow Discharge.
"Provided with flat oval collar. All other collars are round.
Oval Size - 0: H x W - height x width of oval collar.
N/A: Not Available.

24-2
VAD90-CH VARIABLE AIR VOLUME
STANDARD CONSTRUCTION FEATURE
SINGLE DUCT BY - PASS VAV WITH HEATER

J .....
D x 4" LONG SPIGOT

CONTROL ENCLOSURE
(OPTIONAL) '" .....

,,
'"
'"
,.. '" .....
..... .....

HEATER CONTROL '" '" , <,

ENCLOSURE (: <, H
..
I ....
I
I

6"

RELIEF AIR
'--- BALANCING DAMPER

PRODUCT DESCRIPTION

The complete casing with by-pass damper The VAV damper blade and control shaft (3/8"-0)
section is made up of 22 gauge zinc coated mill are extruded aluminum mechanically keyed
galvanized steel. together as a single piece.

1" thick fiberglass 24 kg/me densities Operation of blade by maintenance free nylon
comfortably acting as acoustic attenuator and bearings for smooth and noiseless operation
thermal resistant barrier insulate the casing. and the damper closing against a gasket seal.

VAD90 02CH 04CH 06CH 08CH 10CH 12CH 14CH


CFM RANGE 125-250 250-475 350-725 475-1000 700-1450 1000-1950 1250-2500

DIMENSIONS LISTED IN INCHES - BASIC ASSEMBLY


UNIT DISCHARGE LENGTH COLLAR EQUIVALENT HEATING COIL
H G
MODEL A B C DIA-0-D OVAL SIZE-O MxN
VAD90-02CH 12 10 24 6 N/A 11 x 8 14 4
VAD90-04CH 12 10 24 8 N/A 11 x 8 14 4
VAD90-06CH 12 10 24 9* 77/8 x 97/16 11 x 8 14 4
VAD90-08CH 17 10 30 10* 7 7/8 x 11 1/32 16 x 8 14 4
VAD90-10CH 17 10 30 12* 77/8 x 14 3/16 16 x 8 14 4
VAD90-12CH 27 10 36 14* 77/8 x 175/16 26 x 8 14 1/2 4 1/2
VAD90-14CH 34 10 36 16* 77/8 x 20 1/2 33 x 8 141/2 4 1/2
-' AE Air Flow Enter, AD: Air Flow Discharge.
*Provided with flat oval collar. All other collars are round.
Oval Size - 0: H x W - height x width of oval collar.
N/A: Not Available.

24-3
I.r' ~~
VARIABLE AIR VOLUME r.R;1
PERFORMANCE DATA ~
SINGLE DUCT BY - PASS VAV WITH AND WITHOUT HEATER~

SOUND POWER LEVEL DATA FOR UNIT MODELS WITH AND WITHOUT HEATER

STATIC
AIR FLOW SOUND POWER LEVEL (dB) OCTAVE BAND
PRESSURE
CFM IN.W.G. 125 250 500 1000 2000 4000 8000
UNIT MODEL VAD90-02C & CH
125 0.025 - - - - - - -
175 0.041 - - - - - - -
200 0.055 - - - - - - -
UNIT MODEL VAD90-04C & CH
250 0.032 - - - - - - -
300 0.052 - - - - - - -
375 0.065 46 44 40 36 32 25 20
UNIT MODEL VAD90-06C & CH
425 0.035 - - - - - - -
500 0.050 45 42 38 33 30 26 20
600 0.070 48 45 42 38 32 28 22
UNIT MODEL VAD90-08C & CH
650 0.045 - - - - - - -
800 0.070 52 50 45 40 36 34 30
900 0.090 55 54 50 45 39 36 28
UNIT MODEL VAD90-10C & CH
800 0.045 48 46 42 38 35 30 26
1000 0.072 50 49 47 42 40 38 32
1200 0.096 55 52 50 49 45 41 36
UNIT MODEL VAD90-12C & CH
1250 0.045 50 48 45 42 39 35 30
1500 0.062 52 50 44 46 42 40 33
1750 0.080 58 55 54 52 49 45 40
UNIT MODEL VAD90-14C & CH
1600 0.058 52 49 48 44 40 36 31
2000 0.085 55 53 50 48 45 42 40
2500 0.120 60 58 57 55 52 49 44

NOTES:
Static pressure is minimum pressure drop through the unit for given airflow.

- Denotes unit within 5 dB of background in test room for sound power level.

NC ratings are for terminal units without additional attenuation in low velocity duct.

GGC recommends that a balancing damper be installed three (3) feet upstream from inlet of the terminal unit to
avoid excessive pressure where required. r
Full shut off can be attempt by all units except for units with pressure independent controls "range" is needed.

Add heater pressure drop with above static pressure for units with heater from our Air Velocity-Vs-Pressure
drop graph (see page 22-09).

24-4
EP50-DI VARIABLE AIR VOLUME
STANDARD CONSTRUCTION FEATURE
EXTENDED PLENUM (MULTI-DISCHARGE ADAPTOR)

/ AIR IN THROUGH VAV


~

J----AIR OUTLET SPIGOT


D X REQUIRED LENGTH

B ~ L-- BALANCING DAMPER

IA , (NOT FOR TIGHT SHUTOFF)

STD. TYPE OUTLET ARRANGEMENT


TYPE H - SHOWN
A - 1" MIN. GAP TO THE EDGE OF CASING
B-2" MIN. GAP BETWEEN THE OUTLETS

PRODUCT DESCRIPTION

Sturdy 22 gauges galvanized steel construction Outlet configurations as shown for both
with roundloval outlets. standard and extended plenum outlets.

Convenient slip and drive connection on inlet. Optional insulation of 1" thick 24 kq/rnt' density
fiberglass material.

Manual locking and balancing damper on each Optional hanger brackets.


outlet (does not provide complete shut-off)

STANDARD OUTLET DIMENSIONS ( INCHES)


NOMINAL SIZE ROUND 0 OVAL SIZE - H X W NOMINAL SIZE ROUND 0 OVAL SIZE - H X W
5 4 7/8 3718 X 5 7/16 14 N/A 7 718 X 17 5/16
6 5 7/8 3718 X 7 1/32 16 N/A 7718 X 207/16
7 6 7/8 5718 X 7 7/16 18 N/A 7718 X 239/16
8 7 7/8 N/A 20 N/A 7718 X 26 3/4
9 N/A 7718 X 97/16 22 N/A 7718 X 29 7/8
10 N/A 7718 X 11 1/32 24 N/A 7718 X 33 1/32
12 N/A 7718 X 143/16 26 N/A 7718 X 36 3/16

N/A: Not Available Size.


Round 5: Outlet Diameter.
HxW: Height x Width of Oval Collar.

24-5
VARIABLE AIR VOLUME
CONFIGURATIONS FOR OUTLETS

CONFIGURATIONS FOR STANDARD TYPE OUTLET ARRANGEMENTS (PLAN VIEW)

AIR FLOW AIR FLOW

88888888008
8G88GG
CONFIGURATIONS FOR EXTENDED TYPE PLENUM OUTLET ARRANGEMENTS (PLAN VIEW)

AIR FLOW 0 AIR FLOW

NX

B88SB
SELECTION OF CONFIGURATION FOR STANDARD OUTLET ARRANGEMENT I EXTENDED
PLENUM (MULTI-DISCHARGE ADAPTOR)

Select the dimension for required diameter (round collar) or equivalent dimension of oval collar from the
standard dimension outlet table.

Add 2" to the diameter of round outlet orto the width of oval outlet.

Compute the number of outlets required on one surface by further a gap of 2" in between the collars.

The result must be less than or equal to the available unit length for side outlets orwidth for end outlets.

Available unit length without extended plenum is found by subtracting 12" from standard unit length and
available unitwidth is full unit width.

Also the outlet diameter of round collar or height of oval collar should be 2" less than the total unit height.
If side outlets chosen exceeds the above dimensions allowed then an extended plenum (multi discharge
adaptor) is required.

Extended plenums (multi discharge adaptors) are available from 12" increment to a maximum of 48".

If unit has optional control panel, side outlets on unit control panel side are not allowed without multi discharge
adaptor i.e. extended plenum.

24-6
VARIABLE AIR VOLUME
STANDARD CONSTRUCTION FEATURE
ELECTRIC HEATER

PRODUCT DESCRIPTION

The GGC Electric Coil is available on single duct Heater frames and boxes are constructed of 20
terminal units. Electric coils meet all applicable gauges G.I. Steel. Factory pre-wiring of
requirements of National Electric Code (NEC) and components eliminates costly field installation. A
are UL listed. specified wiring diagram is furnished for every
heater.

Other Features Include:


Automatic reset primary thermal cutout. Airflow proving switch with total pressure pick
up probe.
Replaceable secondary thermal cutout.
Control transformer in heaters for electric or
Low-pressure drop/sound levels. electronic control options.

Powerterminal blocks. Ground connectorforearth.

Control line terminal blocks. Disconnect switch/fusing and mercury


contractors as required /optional.
De-energizing magnetic contactors as required.

Airflow interlock switch.

Coils are provided with S and Drive connections


on the inlet and flange connection on the
discharge .
./

80-20 Nickel-Chromium wire.

24-7
VARIABLE AIR VOLUME
PERFORMANCE SELECTION DATA
ELECTRIC HEATER

KW Required to Match Heat Loss (0) KW = _O----'-(B_t_u/_h-'---)_


3413

Sensible Heat Load a (Btu/h) = 1.08x CFM x Temp. Rise

CFM x Air Temperature Rise


Load Requirement KW=
3160

Kw x 3160
Temperature Rise T.R. = Cubic Feet Per Min.

(Volts) 2
Ohm's Law Watts = Resistance
= Volts x Amps

Watts
Line Current, 1 Phase Amps = Volts

Watts
Line Current, 3 Phase Amps = 1.73x Volts

__ K_WI_ft_.2_ X (velocity in FPM\ 2


Pressure Drop
760 500 ~

Maximum Discharge Air


Temperature

Duct Width (in) x Duct Height (in)


KW Per Square Foot
144

Note: Maximum heater discharge temperature should not exceed 1250 Fto avoid nuisance tripping.

24-8
VARIABLE AIR VOLUME
ELECTRIC COIL PERFORMANCE DATA
ELECTRIC HEATER

Since an electric duct heater has a constant BTU And has to be compared with the minimum airflow
output as long as the heater is energized, a velocity through the electric heater based on
minimum air velocity must be maintained through discharge duct area (Ft.2). The minimum uniform
the heater. Proper airflow will prevent over- airflow in a duct heater is directly related to the inlet
temperature causing nuisance tripping and will air temperature and consideration must be given to
maintain element life expectancy. The velocity of both the airflow across the heater and the inlet air
airflow in the duct is determined by the formula: temperature.

Divide the total watts by square footage of duct


VELOCITY =CFM DUCT AREA (Fe) area to calculate the watts per sq. foot of that duct
area. Use the chart to determine the minimum FPM
based on inlet entering air temperature.

24
\..!) (2)
22 ~
/ I I
20
18
I v -

t-= 16
/ V I
"/ I
.-
./
LL

d
en
14
~
.",..
V ....V
12 "..,.,. ,.". i-"""
<,
/ ~
s~ 108 ./ Vy "..,.,. i.--""
io"""
/1/ ~ I
6
4
2
~
"..,.,.
.,.,--" , .X"
1/
~
...,.
~V
~ ~ - ...V

0
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

Air Velocity (FPM)


I 1 - Below 70F inlet air 2 -70F to 90F in-'-le-t-a-ir-3---91--=o-F-to-1-1-0-=oF:-Ci-'-nl-et-a""-ir-r

0.18

o
:::J:N
"
c:
0.16

0.14
.----'/
1/
~ -
b.
o
0.12 V .........
~ ~
0)
C 0.1
.J'
~
.-'~
V
V ....--- ....---
~
,~ ~
-
C1l
~ 0.08
....---
IJI

e
IJI

a...
0.06
....1...-::
/
~
,~-
~ ~
~
....--- - --- /

CJ 0.04
.... ......:~
j,....o-' -"....
C'a
en 0.02
I
~
o ~ I I I I I
o 200 400 600 800 1000 1200 1400 1600 1800 2000 2200

Air Velocity (FPM)


1,2,3 and 4 are the number of rows for heater coils