MJT314
MJT314
MJT314
nt
e 3
ga
ici
Ele
nte
Easy to Use
Applications
Distribution feeders
Transmission lines
AC machines
Capacitor banks
Transformers
Used in Compact MV Switch Boards with CB Numerical Overcurrent &
Where Auxillary Voltage is not available or guaranteed Earthfault Protection - MJT 314 (B&C)
Common Features for MJT 314 Wiring Diagrams
(B&C)
Protection
IDMTL / DTL phase fault overcurrent ( 50 / 51 )
IDMTL / DTL earth fault overcurrent ( 50N /51N)
Dual DC transient free highsets for phase fault & earth fault
True RMS measurement
Six characteristics
Control
The relay has the following output contacts
MJT 314 B
Normally Open 1 N/O
Capacitor Charged Outputs 1 N/O
MJT 314 C Typical Wiring Diagram for MJT314 C
Capacitor Charged Outputs 1 N/O
Indication
Technical Information Green LED Protection healthy
CT Input Rating 1A & 5A Orange LED Starter
Frequency 50Hz Red LED Trip
Auxiliary Supply Red LED (3mm) Submenu
Self Powered from CT input 16x2 Alphanumeric LCD display for settings, metering and fault
Protection Settings data
Burden
Phase Fault 0.5xIn to 2xIn 0.01 In AC Current Input
Earth Fault 0.2xIn to 0.8xIn 0.01 In 5 A Rating #15 VA
Highset1 Phase Fault 4xIn to 20xIn 0.5 In, off 1 A Rating #3 VA
Auxiliary input
Highset1 Earth Fault 0.5xIn to 12xIn 0.5 In, off
Quiescent (typical) 5 W (DC)
Highset2 Phase Fault 4xIn to 20xIn 0.5 In, off 12VA (AC)
Highset2 Earth Fault 0.5xIn to 12xIn 0.5 In, off Environmental
Temperature IEC 60068-2-1/2
P/F Time Multiplier 0.025 to 1.6 0.001 Operating range -10 C to +55C
E/F Time Multiplier 0.025 to 1.6 0.001 Storage range -25 C to +70C
Humidity IEC 60068-2-3
P/F DTL 0 Secs to 20 Secs 0.01 Secs
4 days at 40C and 93%RH
E/F DTL 0 Secs to 20 Secs 0.01 Secs Transient Overvoltage IEC 60255-5
P/F Highset1 DTL 0 Secs to 20 Secs 0.01 Secs 5KV, 1.2/50Fs, 0.5J between all terminals and earth or between
any two terminals without damage or flashover
E/F Highset1 DTL 0 Secs to 20 Secs 0.01 Secs
Insulation IEC 60255-5
Highset2 Instantaneous 2.0 KVrms for 1 min between all terminals and earth
Reset Time 0 to 60 Secs 1 sec 2.0 KVrms for 1 min between independent circuits
1.0 KVrms for 1 min across normally open contacts
High frequency Disturbance IEC 60255-22-1 Class III
Inverse Characteristics
Operating time can be calculated as follows: 2.5 KV Common (Longitudinal) mode #3%
1.0 KV Series (Transverse) mode #3%
Electrostatic Discharge IEC 60255-22 -2 Class III
6 KV Contact Discharge #5%
8 KV Air Discharge #5%
Radio Frequency Interference IEC 60255-22-3 Class III
where 20 MHz to 1000 MHz, 10V/m #3%
I=fault current Fast Transient
Is=current setting
2 KV, 5/50 ns, 2.5 kHz repetitive IEC 60255-22-4 Class III #3%
Tm=time multiplier
Vibration (Sinusoidal) IEC 60255-21-1 Class I
Si3 - k =0.14, a= 0.02 Shock and Bump IEC 60255-21-2 Class I
SI1 - k =0.0613, a= 0.02 Mechanical Classification
VI - k =13.5, a= 1.0 Durability in excess of 106 operations
EI - k =80.0, a= 2.0
LTI - k =120.0, a= 1.0
Contact Rating
Carry continuously 5A AC rms or DC
Make & Carry 20A for 0.2sec
Break Resistive 75W DC
Inductive 50W DC
@L/R#40msec
with a maximum of 300V DC
Resistive 1250 VA AC
Inductive 250 VA @ PF #0.4
Cutout Details
SIZE 6 CASE
A B C
155 151 130.5
Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm
Ordering Information
Battery source
MJT 314 B or MJT 314 C
CT Rating 1 Amp or 5 Amps
Qualification
ISO 9001-2008
The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly
from that described and illustrated in the publication.