MJT314

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Eff

nt
e 3

ga

ici
Ele

nte
Easy to Use

Numerical Self Powered Genesis Range


Overcurrent & Earthfault MJT 314 B&C
Protection

Description Key Features of MJT 314 B


The MJT 314 B (Self powered numerical overcurrent protection) (Self Powered Numerical Over Current Protection)
& MJT 314 C (Self powered with series trip numerical overcurrent
protection) relay combines the power and flexibility of Charged capacitor output is available to actuate low energy
microprocessor technology with decades of experience in the magnetic actuator in the Breaker(12-24V DC output-
field of protection. A wide range of protection elements and 0.25 joules)
characteristics are supplemented by advance features such as
In absence of low energy magnetic actuator, the breaker
metering, fault recorder and communication.
can be tripped using power from external power pack. For
the same one N/O contact is available in the relay
MJT 314 (B&C) offers inverse time and definite time over current
protection for phase fault and earth fault with communication.

Design Key Features of MJT 314 C


(Self Powered with Series Trip Numerical Over Current
The MJT Protection unit consists of the following modules within
Protection)
its dimensions.
Input Module This relay comes with two boxes, One with main Relay and
Power Supply and Output Relay module other with series Trip element .
Measuring Module & communication interface
Front Fascia Output of the main relay has been modified suitably to
Status input module energize, special B33 type of series trip element three
The four modules viz. Input, Power supply, Measuring and status numbers(coils are connected in series). The break contacts
input modules are plugged into the Front fascia which houses of this will be used to divert the C.T current to the series
switches, LEDs and LCD display for the human machine trip coils of the breaker.
interface. All PCB s are well protected from one another and from
external environment with best shielding for better
electromagnetic compatibility and housed in the enclosed
chassis, which is withdrawable from the outer case.

The draw-out case is provided with the required CT shorting


contacts.

Applications
Distribution feeders
Transmission lines
AC machines
Capacitor banks
Transformers
Used in Compact MV Switch Boards with CB Numerical Overcurrent &
Where Auxillary Voltage is not available or guaranteed Earthfault Protection - MJT 314 (B&C)
Common Features for MJT 314 Wiring Diagrams
(B&C)

Two group settings


Storage of two fault records
Internal real time clock
Suitable for flashing faults
Gets power from the C.T input itself. (No auxiliary D.C
supply necessary)
The current measurement on relay is available when current
flows more than 400mA on all the three phases
The Back light of the LCD will glow when current flows
more than 750mA
To set the relay or read the fault records (in absence of
current input ) a separate battery box with inbuilt battery
charger is available, external to the relay. (order to be placed
separately for this)
Wide range of current settings
Self diagnostics feature
Currents-Ir,Iy,Ib,Ie
Typical Wiring Diagram for MJT314 B
Readable human machine interface with Backlit LCD
display
LED indications
Push buttons for viewing/editing the settings and resetting
Data communication using IEC 60870-5-103 Protocol
RS485 communication electrical terminals at rear

Protection
IDMTL / DTL phase fault overcurrent ( 50 / 51 )
IDMTL / DTL earth fault overcurrent ( 50N /51N)
Dual DC transient free highsets for phase fault & earth fault
True RMS measurement
Six characteristics

Control
The relay has the following output contacts
MJT 314 B
Normally Open 1 N/O
Capacitor Charged Outputs 1 N/O
MJT 314 C Typical Wiring Diagram for MJT314 C
Capacitor Charged Outputs 1 N/O
Indication
Technical Information Green LED Protection healthy
CT Input Rating 1A & 5A Orange LED Starter
Frequency 50Hz Red LED Trip
Auxiliary Supply Red LED (3mm) Submenu
Self Powered from CT input 16x2 Alphanumeric LCD display for settings, metering and fault
Protection Settings data
Burden
Phase Fault 0.5xIn to 2xIn 0.01 In AC Current Input
Earth Fault 0.2xIn to 0.8xIn 0.01 In 5 A Rating #15 VA
Highset1 Phase Fault 4xIn to 20xIn 0.5 In, off 1 A Rating #3 VA
Auxiliary input
Highset1 Earth Fault 0.5xIn to 12xIn 0.5 In, off
Quiescent (typical) 5 W (DC)
Highset2 Phase Fault 4xIn to 20xIn 0.5 In, off 12VA (AC)
Highset2 Earth Fault 0.5xIn to 12xIn 0.5 In, off Environmental
Temperature IEC 60068-2-1/2
P/F Time Multiplier 0.025 to 1.6 0.001 Operating range -10 C to +55C
E/F Time Multiplier 0.025 to 1.6 0.001 Storage range -25 C to +70C
Humidity IEC 60068-2-3
P/F DTL 0 Secs to 20 Secs 0.01 Secs
4 days at 40C and 93%RH
E/F DTL 0 Secs to 20 Secs 0.01 Secs Transient Overvoltage IEC 60255-5
P/F Highset1 DTL 0 Secs to 20 Secs 0.01 Secs 5KV, 1.2/50Fs, 0.5J between all terminals and earth or between
any two terminals without damage or flashover
E/F Highset1 DTL 0 Secs to 20 Secs 0.01 Secs
Insulation IEC 60255-5
Highset2 Instantaneous 2.0 KVrms for 1 min between all terminals and earth
Reset Time 0 to 60 Secs 1 sec 2.0 KVrms for 1 min between independent circuits
1.0 KVrms for 1 min across normally open contacts
High frequency Disturbance IEC 60255-22-1 Class III
Inverse Characteristics
Operating time can be calculated as follows: 2.5 KV Common (Longitudinal) mode #3%
1.0 KV Series (Transverse) mode #3%
Electrostatic Discharge IEC 60255-22 -2 Class III
6 KV Contact Discharge #5%
8 KV Air Discharge #5%
Radio Frequency Interference IEC 60255-22-3 Class III
where 20 MHz to 1000 MHz, 10V/m #3%
I=fault current Fast Transient
Is=current setting
2 KV, 5/50 ns, 2.5 kHz repetitive IEC 60255-22-4 Class III #3%
Tm=time multiplier
Vibration (Sinusoidal) IEC 60255-21-1 Class I
Si3 - k =0.14, a= 0.02 Shock and Bump IEC 60255-21-2 Class I
SI1 - k =0.0613, a= 0.02 Mechanical Classification
VI - k =13.5, a= 1.0 Durability in excess of 106 operations
EI - k =80.0, a= 2.0
LTI - k =120.0, a= 1.0
Contact Rating
Carry continuously 5A AC rms or DC
Make & Carry 20A for 0.2sec
Break Resistive 75W DC
Inductive 50W DC
@L/R#40msec
with a maximum of 300V DC
Resistive 1250 VA AC
Inductive 250 VA @ PF #0.4
Cutout Details

MODULAR CASES: SIZES 6

SIZE 6 CASE
A B C
155 151 130.5

Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 200mm

Ordering Information
Battery source
MJT 314 B or MJT 314 C
CT Rating 1 Amp or 5 Amps

Qualification
ISO 9001-2008

The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly
from that described and illustrated in the publication.

ERL Group Corporate Office


#389, Rasukumaki, Hulimavu, Begur Hobli, Bannerghatta Road, Bangalore 560 076, India
Tel: +91 80 6717 7000 / 7001 Fax: +91 80 6717 7002 Email: cenmarket@easunreyrolle.net

Global Marketing Offices


Germany, Canada, Hong Kong, Thailand, South Africa, UAE, Brazil, Peru & USA

FACT/MJT314 B&C /01-11/REV 3.0.


Global Manufacturing Centers
India, Canada & Germany

Global Technology Centers


India, Canada & Germany

Marketing Offices in India


Bangalore Chennai Kolkata
Tel: +91 80 6717 7000/01 Bhopal Tel: +91 44 2434 6425/7608 Tel: +91 33 2284 8320
Fax: +91 80 6717 7002 Fax: +91 755 2684221 Fax: +91 44 2434 6435 Fax: +91 33 2284 8326
Email: cenmarket@easunreyrolle.net Email: bhopal@easunreyrolle.net Email: chennai@easunreyrolle.net Email: kolkata@easunreyrolle.net

Mumbai Noida
Tel: +91 22 2285 5415/ 2202 2270
Fax: +91 22 2285 5703
Email: mumbai@easunreyrolle.net
Tel: +91 120 2405 741/42/43
Fax: +91 120 2405 744
Email: noida@easunreyrolle.net
Secunderabad
Telfax: +91 40 2781 7847
Email: hyderabad@easunreyrolle.net ERL
www.easunreyrolle.com

You might also like