C Aj 1609
C Aj 1609
C Aj 1609
F Rating 2 Hr
T Rating 0 Hr
1. Floor or Wall Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or
normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of
any UL Classified Concrete Blocks*.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for
names of manufacturers.
2. Nonmetallic Sleeve Nom 6 in. (152 mm) diam (or smaller) Sch 40 polyvinyl chloride
(PVC) pipe cast or grouted into floor or wall assembly, flush with floor or wall surfaces.
A. Steel Pipe Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier)
steel pipe.
B. Iron Pipe Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing
or steel conduit.
D. Copper Tubing Nom 3 in. (76 mm) diam (or smaller) Type L (or heavier)
copper tubing.
E. Copper Pipe Nom 3 in. (76 mm) diam (or smaller) Regular (or heavier) copper
pipe
A. Packing Material Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3)
mineral wool batt insulation firmly packed into sleeved opening as a permanent form.
Packing material to be recessed from top end of sleeve for floors or from both ends of
sleeve for walls as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* Sealant Min 1/2 in. (13 mm) thickness of
fill material applied within the annulus, flush with the top end of the sleeve for floors
or with both ends of the sleeve for walls. Min 1/2 in. (13 mm) thick bead of sealant to
be installed around pipe at interface with sleeve at point contact installations.