ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 1
Indication Processing
Single Point Information
Double Point Information
Bit-String Information
Measurement Processing
Analogue Measured Information
Digital Measured Information
Step Position Information
Integrated Total Information
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 2
SCADA Basic Functions, Monitoring Direction
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 3
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 4
SCADA Functions, General Functionality 23BE23
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 5
Local Blocking
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 6
SCADA Functions, General Functionality 23BE23
Digital Filter
1
input channel
0
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 8
SCADA Functions, General Functionality 23BE23
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 9
Qualifier
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 11
state plant
SPI states plant
auxiliary contacts
DPI
auxiliary contact
1 OFF 1
0 0
ON 1
0
0 1 0 10 00 01 11
OFF ON OFF OFF ON faulty
position
OFF
ON
DPI 8 DPI 7 DPI 6 DPI 5 DPI 4 DPI 3 DPI 2 DPI 1 DPI number within board
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 12
SCADA Functions, Double Point Information
ON Intermediate
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 13
OFF Indeterminate
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 14
SCADA Functions, Double Point Information
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 15
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 16
SCADA Functions, Double Point Information
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 17
DPI DPI
1
ON
0 abnormal state change
1
ON ->intermediate-> ON
OFF
0
DPI DPI
1
ON
0 abnormal state change
1 time out
OFF
0
DPI
Midposition Suppression Disabled
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 18
SCADA Functions, Double Point Information
Supervision time
1
ON
0 Normal signal state change
OFF 1
ON -> OFF
0
DPI
1
ON
0 abnormal state change
1 ON ->intermediate -> ON
OFF
0
DPI
1
DPI
ON
0
abnormal state change
1
time out
OFF
0
Chattering suppression
Purpose: Reduction of transmission load by oscillation suppression
Example: Auxiliary contact of flap in front of transformer cooling fan
Activation: Individually per single / double indication
Configuration parameter: Maximum chatter frequency .
number of changes
MAX CHA FREQ = [ Hz ]
second
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 20
SCADA Functions, Single/Double Point Information
Chattering suppression
Tosc is the monitoring period:
2 000
T osc = [ milliseconds ]
MAX CHA FREQ
Example:
At 1 Hz the monitored period is 2 seconds
2 000
T osc = = 2 second
1 Hz
1
indication
0
60 sec
chatter counter reset time
register
3
2
1
0
Tosc Tosc Tosc time
ABB PSN
RTU560 Training Status: Status:
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 22 Invalid Valid
SCADA Basic Functions, Monitoring Direction
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 23
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 25
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 26
SCADA Functions, Digital Measured Information
Maximum Value:
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 27
DMI 8 S 7 6 5 4 3 2 1
Process Input PV 0V 0V 0V 0V 0V 0V PV
= NO = NO 1 0 0 0 0 0 0 1
= YES = NO 1 1 1 1 1 1 1 0
= NO = YES 0 0 0 0 0 0 0 1
= YES = YES 0 1 1 1 1 1 1 0
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 29
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 30
SCADA Functions, Digital Measured Information
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 31
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 32
SCADA Functions, Bit String Information
BSI08 and BSI16 are supported by the Binary Input Board 23BE23
BSI32 are accepted only from a subdevice communication interface
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 33
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 34
SCADA Functions, Integrated Total Information
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 36
SCADA Functions, Integrated Total Information
... time
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 37
time
Period Period
End of End of
Wrap Around Period Period
reading reading
Counter
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 38
SCADA Functions, Integrated Total Information
Reduction Factor
The function Reduction Factor is normally used only in conjunction
with the function Programmable Logic Controller (PLC). If the
Reduction Factor is set (for example to 2), each second pulse of
the counter input will be transmitted to the communication unit,
independent of the cyclic reading (IR, EPR).
Note: This function will result in a very high load on the Bus !
IT = invalid time
no valid system-time, e.g. after start-up
RTU not synchronized
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 40
SCADA Basic Functions, Monitoring Direction
Functions on 23BE23
General Functionality
Single Point Information (SPI)
Double Point Information (DPI)
Digital Measured Information (DMI)
Step Position Information (STI)
Bit-String Information (BSI)
Integrated Total Information (ITI)
Functions on 23AE23
Analogue Measured Information (AMI)
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 41
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 42
SCADA Functions, Analogue Measured Information
+ 4096
e.g. -20..+20
3000
2000
is converted
-20 -15 -10 -5 5 10 15 20
-100 25 50 75 100 [%]
-3000
- 4096
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 43
Unipolar
Normalized AMI value
Overflow OV (IEC)
Over range OR (DNP3)
1.000
0.800
0.600
0.400
0.200 Input signal
invalid IV 0 %
100%
On-Line=0 e.g. 0 V e.g. 10 V
-0,25 %
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 44
SCADA Functions, Analogue Measured Information
Normalized AMI value
Bipolar
+ 1.000
Overflow OV
Over range OR
input signal
-20 -15 -10 -5 5 10 15 20 [e.g. mA] e.g. from
-100 -75 -50 -25 25 50 75 100 [%] measurement
transducer
overflow OV
Over range OR
ABB PSN - 1.000
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 45
Adjust
Live Zero
-1.000
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 46
SCADA Functions, Analogue Measured Information
Normalized AMI value
Conversion Factor
+1.000
Overflow OV
Over range
Overflow OV
Over range
ABB PSN
RTU560 Training
- 1.000
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 47
60 threshold value
new value
40
New value transmission to CCI
20
time
Periodic
update
cycle
ABB PSN (UC)
RTU560 Training
1 ... 60 s
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 48
SCADA Functions, Analogue Measured Information
Integrated 60
new value
new value
transmission
transmission
Threshold 40
Supervision
20
deltas (differences) to last reported value
0
time
scan cycle
e.g.580 ms
at 50 Hz
Threshold Difference-
Register exceed threshold exceed threshold
[% of input signal]
+ 10
+ threshold
0
- threshold time
-10
example = threshold = 10 % of input signal
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 50
SCADA Functions, Analogue Measured Information
+2.5
zero value
zone +0.05
0
min=0.1% -0.05 time
max=5.0%
-2.5
scan cycle
23AE23
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 52
SCADA Functions, Analogue Measured Information
Switching Detection
Smoothing
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 54
SCADA Functions, Analogue Measured Information
Smoothing
The smoothing is calculated as follows:
MW MWls
MW ns = + MWls
K
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 55
45,00
Smoothing
K= 2
40,00
= 4
35,00
= 8
= 16
30,00
25,00
20,00
15,00
10,00
5,00
0,00
0 5 10 15 20 25 30 35 40 45
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 56
SCADA Basic Functions, Monitoring Direction
ABB PSN
RTU560 Training
08_RTU560_SCADA-Functions_MonitorDir_E, R 1.10 57