REHVA Guidebook n 17
The major focus of the book is on the current state-of-the art equipment
and systems. Practical guidance is offered for the selection, installation and
operation of equipment, as well as information on the future design trends.
Rev
Rehva , Olli
Seppanen,, Nejc Brelic,
Pecs Univ, HUN,
Alex van den Borre
Rev Zoltan Magyar
Rev
Rev
ESSO, F
Herv Lamy
Reviewers: Ahmet Arisoy (Turkey), Derrick Braham (UK), Vincenc Butala, (Slovenia), Gianfranco Rizzo
(Italy), Christian Feldmann (France), Risto Kosonen (Finland)
Acknowledgements Mika Vuolle (EQUA), Niels Bidstrup (Grundfos), Sandrine Marinhas and Sylvain
Courtney (Eurovent Certification), Petra Vladykova (Swegon), Philippe Rivire (Mines ParisTech) for all their
valuable contributions to the guidebook. Verity and Derrick Braham for proof-reading.
Layout and typesetting: Jarkko Narvanne (Finland)
7% Educational 14 %
Sport facilities 57 %
17% 23%
Hot water
Other
Heating
Lighting
Non-residential floor space for the Other
European countries with industrial buildings
excluded (source: BPIE).
End use energy splits in British office
buildings in 2006
Building related cost 10 % Salary and employee related cost 80% Miscellaneous cost 10%
Energy 0.30.6%
Electricity Heating
0.20.4% 0.10.2%
46 % 150 000
100 000
Typical split of life-cycle costs for AHUs
in office buildings (Source: Eurovent) 50 000
0
AHU AHU AHU AHU AHU
3.2 m/s 2.6 m/s 2.3 m/s 1.9 m/s 1.5 m/s
197 220
200
156
125
100 69
0 40% 49%
10% 19%
20% 29%
30% 39%
50% 59%
0
HRW 6
HRW 8
HRW 1
HRW 2
HRW 3
HRW 4
HRW 5
HRW 7
Exhaust Supply
air air
Recommendations in a nutshell:
DCV systems can be successfully applied for indoor air quality control in a number of different types of buildings.
The most suitable is application in premises with varying occupancy density.
The controlling sensor must be located in a place where it best represents and responds to the measured indicator.
For best performance a DCV system should be designed, installed, commissioned and operated under a constant and
complete commissioning process.
Airflow rate
Hygienic airflow rate
C A V s ystem
Number of people -
Airflow rate
DC V s ystem
O ccupancy
8 9 10 11 12 13 14 15 16
Time of day
50%
300 2
EER Max
250 1,5
1 75%
Cooling 1129 1224
200 874
779 892
475
0,5 125 111 40 1 Number
150 872 of units
0
100 EER 17,5 50 100 200 350 500 700 900 1200 1500
point Cooling capacity [kW]
50 35C
0
Air-cooled chillers EER distribution in Eurovent
10 6 2 2 6 10 14 18 22 26 30 34 38 database from year 2010 (Rivire, 2011).
Outdoor temperature (C)
2500
Energy (kWh/year)
2000
1500
1000
Energy consumption of four different circulation pumps
500
(ST a standard single-speed pump; IM a single-
speed pump with improved hydraulic efficiency; VS-AC
0
a variable speed pump with an asynchronous motor 25% 50% 75% 100% Total
and a variable frequency drive; VS-EC a variable Flow
speed pump with EC motor) ST IM VS-AC VS-EC