EVENT ANALYSIS REPORT
UNIT NO : 6 ITPS: Chandrapur Super Thermal Power Station Unit Capacity: 500 MW
1. *HO Code: Station Code: CSTPS U6 Time- Date- No. of days from last
T11 2A15-16 00:45 Hrs 22lL2l20Ls SynC.:- 9.1
Last Overhaul (COH) synchronisation Date 221071201s t52,9 Days 0.42 Years
2. operating conditions at the time of Event ,r
Load MW Coal Cycles in seruice Oil Suppoft
345 A,C,D, E, F,H AB
3.NatureofEvent:UnittrippedonCondensorPressureve
Pumps failure. (Electrical Problem)
5 A) Obseruations :-
Unit was running with 345 MW load. All running CCW pumps tripped due to failure of DC supply & closure of
Butterfly valve of running CCW pumps. Condenser pressure increased & unit tripped on Condenser pressure very
High. CCW DC supply cable checked from both end, found open.
5 B) Remedial Action/work done l-
DC supply source extended from HT switchgear control supply fuse board & supply normalised (BFV Dc control
supply normalised)